Gtez Bldg 46 2023.pdf

PDF 355 KB Posted

Attached to
183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Inspection and Testing Form for a fire alarm system at the Department of Military Affairs in Springfield, Illinois. The inspection was conducted on May 16, 2023 by Scott Calhoon of Getz Fire Equipment. The form details the results of the annual NFPA 72 inspection, including the status of various fire alarm system components such as manual pull stations, heat detectors, and photo detectors. Two deficiencies were noted: the need to replace batteries in the 4099 NAC (12AH) panel in the Boiler Room, and a failed photo detector in Hall 141 North.

The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineer Squadron (183 CES). The solicitation, numbered W50S7U-24-B-0001, was issued by the Department of the Army National Guard. The Performance Work Statement (PWS) and other relevant documents are attached. A site visit is required as part of the bidding process, and the details for the site visit are provided in the solicitation.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P46 - Fail

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 8 8 0 8 0 8

Heat Detector 51 51 0 51 0 51

Duct Detector 3 3 0 3 0 3

Photo Detector 15 14 1 15 0 15

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name P-25 Reference Number P-46

Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4010

Software Revision 3.03 Date Last Serviced 2020-12-17

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location RIPA

Disconnecting Means Location 1 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 18 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels Yes Yes Pass

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

AHU 1 RETURN Duct Detector Yes Yes Pass

AHI 1 SUPPLY EAST Duct Detector Yes Yes Pass

AHU 1 SUPPLY

WEST

Duct Detector Yes Yes Pass

ELECTRONICS

MANAGEMENT

OFFICE

Heat Detector Yes Yes Pass

LOGISTICS OFFICE Heat Detector Yes Yes Pass

MENS SHOWER Heat Detector Yes Yes Pass

NORTHEAST EXIT

FOYER

Heat Detector Yes Yes Pass

ROOM 1 Heat Detector Yes Yes Pass

ROOM 10 Heat Detector Yes Yes Pass

ROOM 11 Heat Detector Yes Yes Pass

ROOM 14 Heat Detector Yes Yes Pass

ROOM 15 Heat Detector Yes Yes Pass

ROOM 17 NORTH Heat Detector Yes Yes Pass

ROOM 17 SOUTH Heat Detector Yes Yes Pass

ROOM 2 Heat Detector Yes Yes Pass

ROOM 23 Heat Detector Yes Yes Pass

ROOM 25 Heat Detector Yes Yes Pass

ROOM 26 Heat Detector Yes Yes Pass

ROOM 28 Heat Detector Yes Yes Pass

ROOM 3 Heat Detector Yes Yes Pass

ROOM 30 Heat Detector Yes Yes Pass

ROOM 31 Heat Detector Yes Yes Pass

ROOM 32 Heat Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

ROOM 33 Heat Detector Yes Yes Pass

ROOM 34 EAST Heat Detector Yes Yes Pass

ROOM 34 NORTH Heat Detector Yes Yes Pass

ROOM 34 WEST Heat Detector Yes Yes Pass

ROOM 38 Heat Detector Yes Yes Pass

ROOM 39 Heat Detector Yes Yes Pass

ROOM 4 Heat Detector Yes Yes Pass

ROOM 40 Heat Detector Yes Yes Pass

ROOM 41 Heat Detector Yes Yes Pass

ROOM 42 EAST Heat Detector Yes Yes Pass

ROOM 42 NORTH Heat Detector Yes Yes Pass

ROOM 42 SOUTH Heat Detector Yes Yes Pass

ROOM 42 WEST Heat Detector Yes Yes Pass

ROOM 43 Heat Detector Yes Yes Pass

ROOM 46 Heat Detector Yes Yes Pass

ROOM 47 Heat Detector Yes Yes Pass

ROOM 48 Heat Detector Yes Yes Pass

ROOM 50 Heat Detector Yes Yes Pass

ROOM 51 Heat Detector Yes Yes Pass

ROOM 52 Heat Detector Yes Yes Pass

ROOM 53 Heat Detector Yes Yes Pass

ROOM 6 Heat Detector Yes Yes Pass

ROOM 7 Heat Detector Yes Yes Pass

ROOM 8 Heat Detector Yes Yes Pass

ROOM 9 Heat Detector Yes Yes Pass

SOUTHEAST EXIT

FOYER

Heat Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

SOUTHWEST EXIT

FOYER

Heat Detector Yes Yes Pass

WEST EXIT FOYER Heat Detector Yes Yes Pass

WEST HALL

JANITOR CLOSET

Heat Detector Yes Yes Pass

WEST HALL

TELEPHONE ROOM

Heat Detector Yes Yes Pass

WOMENS SHOWER Heat Detector Yes Yes Pass

130 NORTHEAST

EXIT

Manual Pull Station Yes Yes Pass

COLD STORAGE

EAST

Manual Pull Station Yes Yes Pass

COLD STORAGE

WEST

Manual Pull Station Yes Yes Pass

NORTHWEST EXIT Manual Pull Station Yes Yes Pass

SOUTHEAST EXIT Manual Pull Station Yes Yes Pass

SIP TRAINING

ROOM

Manual Pull Station Yes Yes Pass

SOUTHWEST EXIT Manual Pull Station Yes Yes Pass

UPSTAIRS

FURNACE ROOM

Manual Pull Station Yes Yes Pass

HALL 101 CENTER

BY 540

Photo Detector Yes Yes Pass

HALL 101 EAST BY

Photo Detector Yes Yes Pass

HALL 101 EAST

CENTER BY 266

Photo Detector Yes Yes Pass

HALL 101 WEST BY

Photo Detector Yes Yes Pass

HALL 101 WEST

CENTER

Photo Detector Yes Yes Pass

HALL 137 BY 159 Photo Detector Yes Yes Pass

HALL 141 NORTH

BY 207

Photo Detector Yes Yes Fail

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

HALL 141 NORTH

CENTER

Photo Detector Yes Yes Pass

HALL 188 NORTH Photo Detector Yes Yes Pass

HALL 188 NORTH

CENTER

Photo Detector Yes Yes Pass

HALL 188 SOUTH

CENTER

Photo Detector Yes Yes Pass

HALL 188 SOUTH

BY 100

Photo Detector Yes Yes Pass

HALL BY ROOM 239 Photo Detector Yes Yes Pass

WEST HALL 141

SOUTH

Photo Detector Yes Yes Pass

WEST HALL 141

SOUTH CENTER

Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4010

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2020 Yes Yes 12/18 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/18

Comments

Location: Boiler Room

Manufacturer: Simplex

Model: 4099 NAC (12AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 26.3 26.4

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2017 Yes Yes 12/12 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/12

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P46

Deficiency #1

System Name: ES FA - FIRE ALARM P46 4099 NAC (12AH) - Boiler Room Battery Pass/Fail: Fail Secondary Battery Pass/Fail:

Notes: Batteries need replaced

Deficiency #2

System Name: ES FA - FIRE ALARM P46 Model: PSD Photo Detector - HALL 141 NORTH BY 207 -

Status: Fail

Notes: Failed inspection

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com