Gtez Bldg 46 2023.pdf
PDF 355 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Form for a fire alarm system at the Department of Military Affairs in Springfield, Illinois. The inspection was conducted on May 16, 2023 by Scott Calhoon of Getz Fire Equipment. The form details the results of the annual NFPA 72 inspection, including the status of various fire alarm system components such as manual pull stations, heat detectors, and photo detectors. Two deficiencies were noted: the need to replace batteries in the 4099 NAC (12AH) panel in the Boiler Room, and a failed photo detector in Hall 141 North.
The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineer Squadron (183 CES). The solicitation, numbered W50S7U-24-B-0001, was issued by the Department of the Army National Guard. The Performance Work Statement (PWS) and other relevant documents are attached. A site visit is required as part of the bidding process, and the details for the site visit are provided in the solicitation.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P46 - Fail
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 8 8 0 8 0 8
Heat Detector 51 51 0 51 0 51
Duct Detector 3 3 0 3 0 3
Photo Detector 15 14 1 15 0 15
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name P-25 Reference Number P-46
Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4010
Software Revision 3.03 Date Last Serviced 2020-12-17
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location RIPA
Disconnecting Means Location 1 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 18 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels Yes Yes Pass
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
AHU 1 RETURN Duct Detector Yes Yes Pass
AHI 1 SUPPLY EAST Duct Detector Yes Yes Pass
AHU 1 SUPPLY
WEST
Duct Detector Yes Yes Pass
ELECTRONICS
MANAGEMENT
OFFICE
Heat Detector Yes Yes Pass
LOGISTICS OFFICE Heat Detector Yes Yes Pass
MENS SHOWER Heat Detector Yes Yes Pass
NORTHEAST EXIT
FOYER
Heat Detector Yes Yes Pass
ROOM 1 Heat Detector Yes Yes Pass
ROOM 10 Heat Detector Yes Yes Pass
ROOM 11 Heat Detector Yes Yes Pass
ROOM 14 Heat Detector Yes Yes Pass
ROOM 15 Heat Detector Yes Yes Pass
ROOM 17 NORTH Heat Detector Yes Yes Pass
ROOM 17 SOUTH Heat Detector Yes Yes Pass
ROOM 2 Heat Detector Yes Yes Pass
ROOM 23 Heat Detector Yes Yes Pass
ROOM 25 Heat Detector Yes Yes Pass
ROOM 26 Heat Detector Yes Yes Pass
ROOM 28 Heat Detector Yes Yes Pass
ROOM 3 Heat Detector Yes Yes Pass
ROOM 30 Heat Detector Yes Yes Pass
ROOM 31 Heat Detector Yes Yes Pass
ROOM 32 Heat Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
ROOM 33 Heat Detector Yes Yes Pass
ROOM 34 EAST Heat Detector Yes Yes Pass
ROOM 34 NORTH Heat Detector Yes Yes Pass
ROOM 34 WEST Heat Detector Yes Yes Pass
ROOM 38 Heat Detector Yes Yes Pass
ROOM 39 Heat Detector Yes Yes Pass
ROOM 4 Heat Detector Yes Yes Pass
ROOM 40 Heat Detector Yes Yes Pass
ROOM 41 Heat Detector Yes Yes Pass
ROOM 42 EAST Heat Detector Yes Yes Pass
ROOM 42 NORTH Heat Detector Yes Yes Pass
ROOM 42 SOUTH Heat Detector Yes Yes Pass
ROOM 42 WEST Heat Detector Yes Yes Pass
ROOM 43 Heat Detector Yes Yes Pass
ROOM 46 Heat Detector Yes Yes Pass
ROOM 47 Heat Detector Yes Yes Pass
ROOM 48 Heat Detector Yes Yes Pass
ROOM 50 Heat Detector Yes Yes Pass
ROOM 51 Heat Detector Yes Yes Pass
ROOM 52 Heat Detector Yes Yes Pass
ROOM 53 Heat Detector Yes Yes Pass
ROOM 6 Heat Detector Yes Yes Pass
ROOM 7 Heat Detector Yes Yes Pass
ROOM 8 Heat Detector Yes Yes Pass
ROOM 9 Heat Detector Yes Yes Pass
SOUTHEAST EXIT
FOYER
Heat Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
SOUTHWEST EXIT
FOYER
Heat Detector Yes Yes Pass
WEST EXIT FOYER Heat Detector Yes Yes Pass
WEST HALL
JANITOR CLOSET
Heat Detector Yes Yes Pass
WEST HALL
TELEPHONE ROOM
Heat Detector Yes Yes Pass
WOMENS SHOWER Heat Detector Yes Yes Pass
130 NORTHEAST
EXIT
Manual Pull Station Yes Yes Pass
COLD STORAGE
EAST
Manual Pull Station Yes Yes Pass
COLD STORAGE
WEST
Manual Pull Station Yes Yes Pass
NORTHWEST EXIT Manual Pull Station Yes Yes Pass
SOUTHEAST EXIT Manual Pull Station Yes Yes Pass
SIP TRAINING
ROOM
Manual Pull Station Yes Yes Pass
SOUTHWEST EXIT Manual Pull Station Yes Yes Pass
UPSTAIRS
FURNACE ROOM
Manual Pull Station Yes Yes Pass
HALL 101 CENTER
BY 540
Photo Detector Yes Yes Pass
HALL 101 EAST BY
Photo Detector Yes Yes Pass
HALL 101 EAST
CENTER BY 266
Photo Detector Yes Yes Pass
HALL 101 WEST BY
Photo Detector Yes Yes Pass
HALL 101 WEST
CENTER
Photo Detector Yes Yes Pass
HALL 137 BY 159 Photo Detector Yes Yes Pass
HALL 141 NORTH
BY 207
Photo Detector Yes Yes Fail
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
HALL 141 NORTH
CENTER
Photo Detector Yes Yes Pass
HALL 188 NORTH Photo Detector Yes Yes Pass
HALL 188 NORTH
CENTER
Photo Detector Yes Yes Pass
HALL 188 SOUTH
CENTER
Photo Detector Yes Yes Pass
HALL 188 SOUTH
BY 100
Photo Detector Yes Yes Pass
HALL BY ROOM 239 Photo Detector Yes Yes Pass
WEST HALL 141
SOUTH
Photo Detector Yes Yes Pass
WEST HALL 141
SOUTH CENTER
Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4010
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
5-2020 Yes Yes 12/18 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/18
Comments
Location: Boiler Room
Manufacturer: Simplex
Model: 4099 NAC (12AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 26.3 26.4
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
5-2017 Yes Yes 12/12 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/12
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P46
Deficiency #1
System Name: ES FA - FIRE ALARM P46 4099 NAC (12AH) - Boiler Room Battery Pass/Fail: Fail Secondary Battery Pass/Fail:
Notes: Batteries need replaced
Deficiency #2
System Name: ES FA - FIRE ALARM P46 Model: PSD Photo Detector - HALL 141 NORTH BY 207 -
Status: Fail
Notes: Failed inspection
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
File details come from the government source that posted it. Updated .