Getz Bldg 17 2023.pdf

PDF 234 KB Posted

Attached to
183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Inspection and Testing Form for a fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The inspection was conducted on May 15, 2023 by Getz Fire Equipment. The form provides detailed results of the visual and functional testing performed on various fire alarm system components, including manual pull stations, notification appliances, and control equipment. All tested components passed inspection. The document also includes information on the fire alarm control panel, battery readings, and any identified deficiencies (none reported).

The related federal contract opportunity is a solicitation (W50S7U-24-B-0001) issued by the Department of the Army National Guard for the 183 CES Repair Base Fire Alarm System project. The solicitation includes a Performance Work Statement (PWS) and other supporting documents. Interested parties are required to attend a site visit as part of the bid submission process.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P17 - Pass

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 7 7 0 7 0 7

Water Flow Alarm 1 1 0 1 0 1

Tamper Switch 3 3 0 3 0 3

Smoke Detector 1 1 0 1 0 1

Monitor Module 5 5 0 5 0 5

Speaker Strobe 10 10 0 10 0 10

Control Module 1 1 0 1 0 1

Remote Relay 3 3 0 3 0 3

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-17 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Monaco Model Number MAAP-X

Date Last Serviced 2020-12-17

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location RP1

Disconnecting Means Location 53 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 7 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator N/A N/A N/A

Power Extender Panels N/A N/A N/A

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

3 Sheet Metal 2 Manual Pull Station Yes Yes Pass

4 Metals Tech 2W Manual Pull Station Yes Yes Pass

5 Metals Tech 2 S Manual Pull Station Yes Yes Pass

6 A.G.E 1 East Manual Pull Station Yes Yes Pass

7 A.G.E 1 East Manual Pull Station Yes Yes Pass

9 Paint Booth Fan Remote Relay Yes Yes Pass

10 Paint Booth Fan Remote Relay Yes Yes Pass

11 Sheet Metal 2 NW Shower

Monitor Module Yes Yes Pass

12 Metal Tech 2 West Shower

Monitor Module Yes Yes Pass

13 Waterflow Outdoor

HS

Control Module Yes Yes Pass

14 Sprinkler WF Water Flow Alarm Yes Yes Pass

15 Sprinkler Tamper Tamper Switch Yes Yes Pass

16 Sprinkler PIV Tamper Switch Yes Yes Pass

17 Sheet Metal 2 E Shower

Monitor Module Yes Yes Pass

18 A.G.E 1 Shower Monitor Module Yes Yes Pass

19 Sprinkler Sheet Metal 2

Tamper Switch Yes Yes Pass

20 HVAC Shutdown Remote Relay Yes Yes Pass

21 Sheet Metal 2 SW Shower

Monitor Module Yes Yes Pass

22 FACU Corridor Smoke Detector Yes Yes Pass

1 NE Exit Manual Pull Station Yes Yes Pass

2 Exit STN Manual Pull Station Yes Yes Pass

Break Room Speaker Strobe Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

Hall By RR Speaker Strobe Yes Yes Pass

Womens RR Speaker Strobe Yes Yes Pass

Main Hanger NW Speaker Strobe Yes Yes Pass

Main Hanger NE Speaker Strobe Yes Yes Pass

Main Hanger SW Speaker Strobe Yes Yes Pass

Main Hanger SE Speaker Strobe Yes Yes Pass

Sprinkler Room East Speaker Strobe Yes Yes Pass

Sprinklr Room West Speaker Strobe Yes Yes Pass

A.G.E Room Speaker Strobe Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Monaco

Model: MAAP-X

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

6-2021 Yes Yes 12/33 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/33

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P17

None

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com