Getz Bldg 17 2023.pdf
PDF 234 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Form for a fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The inspection was conducted on May 15, 2023 by Getz Fire Equipment. The form provides detailed results of the visual and functional testing performed on various fire alarm system components, including manual pull stations, notification appliances, and control equipment. All tested components passed inspection. The document also includes information on the fire alarm control panel, battery readings, and any identified deficiencies (none reported).
The related federal contract opportunity is a solicitation (W50S7U-24-B-0001) issued by the Department of the Army National Guard for the 183 CES Repair Base Fire Alarm System project. The solicitation includes a Performance Work Statement (PWS) and other supporting documents. Interested parties are required to attend a site visit as part of the bid submission process.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P17 - Pass
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 7 7 0 7 0 7
Water Flow Alarm 1 1 0 1 0 1
Tamper Switch 3 3 0 3 0 3
Smoke Detector 1 1 0 1 0 1
Monitor Module 5 5 0 5 0 5
Speaker Strobe 10 10 0 10 0 10
Control Module 1 1 0 1 0 1
Remote Relay 3 3 0 3 0 3
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-17 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Monaco Model Number MAAP-X
Date Last Serviced 2020-12-17
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location RP1
Disconnecting Means Location 53 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 7 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator N/A N/A N/A
Power Extender Panels N/A N/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
3 Sheet Metal 2 Manual Pull Station Yes Yes Pass
4 Metals Tech 2W Manual Pull Station Yes Yes Pass
5 Metals Tech 2 S Manual Pull Station Yes Yes Pass
6 A.G.E 1 East Manual Pull Station Yes Yes Pass
7 A.G.E 1 East Manual Pull Station Yes Yes Pass
9 Paint Booth Fan Remote Relay Yes Yes Pass
10 Paint Booth Fan Remote Relay Yes Yes Pass
11 Sheet Metal 2 NW Shower
Monitor Module Yes Yes Pass
12 Metal Tech 2 West Shower
Monitor Module Yes Yes Pass
13 Waterflow Outdoor
HS
Control Module Yes Yes Pass
14 Sprinkler WF Water Flow Alarm Yes Yes Pass
15 Sprinkler Tamper Tamper Switch Yes Yes Pass
16 Sprinkler PIV Tamper Switch Yes Yes Pass
17 Sheet Metal 2 E Shower
Monitor Module Yes Yes Pass
18 A.G.E 1 Shower Monitor Module Yes Yes Pass
19 Sprinkler Sheet Metal 2
Tamper Switch Yes Yes Pass
20 HVAC Shutdown Remote Relay Yes Yes Pass
21 Sheet Metal 2 SW Shower
Monitor Module Yes Yes Pass
22 FACU Corridor Smoke Detector Yes Yes Pass
1 NE Exit Manual Pull Station Yes Yes Pass
2 Exit STN Manual Pull Station Yes Yes Pass
Break Room Speaker Strobe Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
Hall By RR Speaker Strobe Yes Yes Pass
Womens RR Speaker Strobe Yes Yes Pass
Main Hanger NW Speaker Strobe Yes Yes Pass
Main Hanger NE Speaker Strobe Yes Yes Pass
Main Hanger SW Speaker Strobe Yes Yes Pass
Main Hanger SE Speaker Strobe Yes Yes Pass
Sprinkler Room East Speaker Strobe Yes Yes Pass
Sprinklr Room West Speaker Strobe Yes Yes Pass
A.G.E Room Speaker Strobe Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Monaco
Model: MAAP-X
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
6-2021 Yes Yes 12/33 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/33
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P17
None
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com