183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Annual NFPA 72 Fire Alarm Inspection Report for the Department of Military Affairs building located at 3101 David Jones Parkway in Springfield, Illinois. The report details the testing and inspection of various fire alarm system components, including manual pull stations, water flow alarms, tamper switches, horn strobes, and photo detectors. All tested devices passed inspection. The report also includes details on the fire alarm control panel, including the manufacturer, model, software revision, power supply, and battery backup capacity. No deficiencies were noted.

The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineer Squadron (183 CES) facility. The U.S. Department of the Army National Guard has issued Solicitation #W50S7U-24-B-0001 for this work. The solicitation includes a Performance Work Statement (PWS) and other documents. A site visit is required, with details provided in the solicitation.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P26 - Pass

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 10 10 0 10 0 10

Water Flow Alarm 2 2 0 2 0 2

Tamper Switch 4 4 0 4 0 4

Horn Strobe 22 22 0 22 0 22

Photo Detector 2 2 0 2 0 2

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-26 Type Transmission Reverse Polarity

System Type

Control Unit Manufacturer Notifier Model Number NFW-100X

Software Revision 1.01 Date Last Serviced 2020-12-18

Last Date and Software or Configuration was Revised

2020-10-17

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location EM3718

Disconnecting Means Location 12 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 12 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels Yes Yes Pass

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

17 SPRINKLER Tamper Switch Yes Yes Pass

2 NORTHEAST EXIT Manual Pull Station Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

5 SOUTHEAST

ENTRANCE

Manual Pull Station Yes Yes Pass

3 MECH. ROOM Manual Pull Station Yes Yes Pass

OUTSIDE Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

1 SOUTHWEST EXIT Manual Pull Station Yes Yes Pass

10 ABOVE FACP Photo Detector Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

MECH ROOM Horn Strobe Yes Yes Pass

RESTROOM Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

4 SOUTHEAST

ENTRANCE

Manual Pull Station Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

RESTROOM Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

16 SPRINKLER Water Flow Alarm Yes Yes Pass

20 SPRINKLER Tamper Switch Yes Yes Pass

20 SPRINKLER Tamper Switch Yes Yes Pass

17 SPRINKLER Tamper Switch Yes Yes Pass

1 SOUTHWEST EXIT Manual Pull Station Yes Yes Pass

3 MECH. ROOM Manual Pull Station Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

WAREHOUSE Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

16 SPRINKLER Water Flow Alarm Yes Yes Pass

OUTSIDE Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

2 NORTHEAST EXIT Manual Pull Station Yes Yes Pass

4 SOUTHEAST

ENTRANCE

Manual Pull Station Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

5 SOUTHEAST

ENTRANCE

Manual Pull Station Yes Yes Pass

MECH ROOM Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

10 ABOVE FACP Photo Detector Yes Yes Pass

RESTROOM Horn Strobe Yes Yes Pass

WAREHOUSE Horn Strobe Yes Yes Pass

RESTROOM Horn Strobe Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Notifier

Model: NFW-100

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2021 Yes Yes 12/12 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/12

Comments

Location: Boiler room

Manufacturer: Notifier

Model: NX100

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Boiler room

Manufacturer: Potter

Model: PSN-106

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2021 Yes Yes 12/7 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/7

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P26

None

Report of Inspection / Test Annual NFPA 72

2023-05-17 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

File details come from the government source that posted it. Updated .