Getz Bldg 36 2023.pdf
PDF 320 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Annual NFPA 72 Inspection and Testing Report for a fire alarm system at a Department of Military Affairs facility. The report details the inspection and testing results for various fire alarm system components, including manual pull stations, photo detectors, high-sensitivity smoke detectors, and duct detectors. The inspection identified two deficiencies: a battery fault in the M1-1 NAC panel and a battery fault in the 4099 NAC panel in the boiler room. The report provides detailed information on the fire alarm control panels, power supplies, and battery readings.
The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineer Squadron (183 CES) facility. The solicitation number is W50S7U-24-B-0001, and the agency is the Department of the Army National Guard. The solicitation includes a Performance Work Statement (PWS), fire panel images, and an SF1705 form for a site visit. Interested bidders are advised to thoroughly review the solicitation and other provided documents and comply with the solicitation requirements.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P36 - Fail
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 20 20 0 20 0 20
Duct Detector 3 3 0 3 0 3
HSSD 4 4 0 4 0 4
Photo Detector 32 32 0 32 0 32
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-36 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4100ES
Software Revision 2.1 Date Last Serviced 2020-12-19
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location PLC
Secondary Standby Sealed Lead-Acid Storage Battery: Amp Hour Rating 33
Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels Yes Yes Failed M1-1 NAC panel is showing a battery fault
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
MAIN ENTRY Manual Pull Station Yes Yes Pass
FACP ROOM Manual Pull Station Yes Yes Pass
AHU ROOM Manual Pull Station Yes Yes Pass
EXIT BY 187C Manual Pull Station Yes Yes Pass
187C WORKSHOP Manual Pull Station Yes Yes Pass
187C WORKSHOP
EXIT
Manual Pull Station Yes Yes Pass
ROOM 172 EXIT
EAST
Manual Pull Station Yes Yes Pass
ROOM 172 ENTRY
WEST
Manual Pull Station Yes Yes Pass
ROOM 172 SOUTH
EXIT
Manual Pull Station Yes Yes Pass
ROOM 172 NORTH
EXIT
Manual Pull Station Yes Yes Pass
171 EXIT BY
RESTROOM
Manual Pull Station Yes Yes Pass
EXIT BY 170 Manual Pull Station Yes Yes Pass
EXIT BY 156 Manual Pull Station Yes Yes Pass
EXIT BY 152 Manual Pull Station Yes Yes Pass
ROOM 148 EAST Manual Pull Station Yes Yes Pass
ROOM 148 WEST Manual Pull Station Yes Yes Pass
ROOM 146 Manual Pull Station Yes Yes Pass
EXIT BY ROOM 117 Manual Pull Station Yes Yes Pass
ROOM 125 Manual Pull Station Yes Yes Pass
EXIT BY ROOM 103 Manual Pull Station Yes Yes Pass
ENTRY 187C Photo Detector Yes Yes Pass
ENTRY 179 Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
ENTRY TO 171 Photo Detector Yes Yes Pass
ROOM 171 Photo Detector Yes Yes Pass
ROOM 172 EAST Photo Detector Yes Yes Pass
ROOM 172 WEST Photo Detector Yes Yes Pass
171 BY RESTROOM Photo Detector Yes Yes Pass
HALL BY ROOM 170 Photo Detector Yes Yes Pass
ROOM 180 WEST Photo Detector Yes Yes Pass
ROOM 180 EAST Photo Detector Yes Yes Pass
ROOM 167 Photo Detector Yes Yes Pass
BY ROOM 168A Photo Detector Yes Yes Pass
HALL BY 180 Photo Detector Yes Yes Pass
HALL BY 108 Photo Detector Yes Yes Pass
HALL BY 112 Photo Detector Yes Yes Pass
HALL BY 156 Photo Detector Yes Yes Pass
HALL BY 152 Photo Detector Yes Yes Pass
ROOM 149 Photo Detector Yes Yes Pass
ROOM 148 EAST Photo Detector Yes Yes Pass
BY ROOM 147 Photo Detector Yes Yes Pass
ROOM 146 Photo Detector Yes Yes Pass
HALL BY 142 Photo Detector Yes Yes Pass
HALL BY 128 Photo Detector Yes Yes Pass
HALL BY 149 Photo Detector Yes Yes Pass
HALL BY 132 Photo Detector Yes Yes Pass
HALL BY 122 Photo Detector Yes Yes Pass
HALL BY 121 Photo Detector Yes Yes Pass
HALL BY 117 Photo Detector Yes Yes Pass
ROOM 125 Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
ROOM 159 Photo Detector Yes Yes Pass
HALL BY 103 Photo Detector Yes Yes Pass
ROOM 103 Photo Detector Yes Yes Pass
ROOM 134 HSSD Yes Yes Pass
ROOM 127 HSSD Yes Yes Pass
CSS ROOM 106 HSSD Yes Yes Pass
ROOM 144 HSSD Yes Yes Pass
ROOM 144 Duct Detector Yes Yes Pass
ROOM 162 Duct Detector Yes Yes Pass
ROOM 162 Duct Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4100ES
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 26.2 26.4
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Yes Yes 12/55 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/55
Comments
Location: Boiler Room
Manufacturer: Simplex
Model: 4099 NAC (7AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Yes Yes 12/7 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/7
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Boiler Room
Manufacturer: Simplex
Model: 4099 NAC (7AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Yes Yes 12/7 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/7
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P36
Deficiency #1
Power Extender Panels: Failed Model: 4100ES
Notes: M1-1 NAC panel is showing a battery fault
Deficiency #2
System Name: ES FA - FIRE ALARM P36 4099 NAC (7AH) - Boiler Room Battery Pass/Fail: Fail Secondary Battery Pass/Fail:
Notes: Control is showing a battery fault for this NAC
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com