183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Annual NFPA 72 Inspection and Testing Report for a fire alarm system at a Department of Military Affairs facility. The report details the inspection and testing results for various fire alarm system components, including manual pull stations, photo detectors, high-sensitivity smoke detectors, and duct detectors. The inspection identified two deficiencies: a battery fault in the M1-1 NAC panel and a battery fault in the 4099 NAC panel in the boiler room. The report provides detailed information on the fire alarm control panels, power supplies, and battery readings.

The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineer Squadron (183 CES) facility. The solicitation number is W50S7U-24-B-0001, and the agency is the Department of the Army National Guard. The solicitation includes a Performance Work Statement (PWS), fire panel images, and an SF1705 form for a site visit. Interested bidders are advised to thoroughly review the solicitation and other provided documents and comply with the solicitation requirements.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P36 - Fail

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 20 20 0 20 0 20

Duct Detector 3 3 0 3 0 3

HSSD 4 4 0 4 0 4

Photo Detector 32 32 0 32 0 32

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-36 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4100ES

Software Revision 2.1 Date Last Serviced 2020-12-19

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location PLC

Secondary Standby Sealed Lead-Acid Storage Battery: Amp Hour Rating 33

Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels Yes Yes Failed M1-1 NAC panel is showing a battery fault

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

MAIN ENTRY Manual Pull Station Yes Yes Pass

FACP ROOM Manual Pull Station Yes Yes Pass

AHU ROOM Manual Pull Station Yes Yes Pass

EXIT BY 187C Manual Pull Station Yes Yes Pass

187C WORKSHOP Manual Pull Station Yes Yes Pass

187C WORKSHOP

EXIT

Manual Pull Station Yes Yes Pass

ROOM 172 EXIT

EAST

Manual Pull Station Yes Yes Pass

ROOM 172 ENTRY

WEST

Manual Pull Station Yes Yes Pass

ROOM 172 SOUTH

EXIT

Manual Pull Station Yes Yes Pass

ROOM 172 NORTH

EXIT

Manual Pull Station Yes Yes Pass

171 EXIT BY

RESTROOM

Manual Pull Station Yes Yes Pass

EXIT BY 170 Manual Pull Station Yes Yes Pass

EXIT BY 156 Manual Pull Station Yes Yes Pass

EXIT BY 152 Manual Pull Station Yes Yes Pass

ROOM 148 EAST Manual Pull Station Yes Yes Pass

ROOM 148 WEST Manual Pull Station Yes Yes Pass

ROOM 146 Manual Pull Station Yes Yes Pass

EXIT BY ROOM 117 Manual Pull Station Yes Yes Pass

ROOM 125 Manual Pull Station Yes Yes Pass

EXIT BY ROOM 103 Manual Pull Station Yes Yes Pass

ENTRY 187C Photo Detector Yes Yes Pass

ENTRY 179 Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

ENTRY TO 171 Photo Detector Yes Yes Pass

ROOM 171 Photo Detector Yes Yes Pass

ROOM 172 EAST Photo Detector Yes Yes Pass

ROOM 172 WEST Photo Detector Yes Yes Pass

171 BY RESTROOM Photo Detector Yes Yes Pass

HALL BY ROOM 170 Photo Detector Yes Yes Pass

ROOM 180 WEST Photo Detector Yes Yes Pass

ROOM 180 EAST Photo Detector Yes Yes Pass

ROOM 167 Photo Detector Yes Yes Pass

BY ROOM 168A Photo Detector Yes Yes Pass

HALL BY 180 Photo Detector Yes Yes Pass

HALL BY 108 Photo Detector Yes Yes Pass

HALL BY 112 Photo Detector Yes Yes Pass

HALL BY 156 Photo Detector Yes Yes Pass

HALL BY 152 Photo Detector Yes Yes Pass

ROOM 149 Photo Detector Yes Yes Pass

ROOM 148 EAST Photo Detector Yes Yes Pass

BY ROOM 147 Photo Detector Yes Yes Pass

ROOM 146 Photo Detector Yes Yes Pass

HALL BY 142 Photo Detector Yes Yes Pass

HALL BY 128 Photo Detector Yes Yes Pass

HALL BY 149 Photo Detector Yes Yes Pass

HALL BY 132 Photo Detector Yes Yes Pass

HALL BY 122 Photo Detector Yes Yes Pass

HALL BY 121 Photo Detector Yes Yes Pass

HALL BY 117 Photo Detector Yes Yes Pass

ROOM 125 Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

ROOM 159 Photo Detector Yes Yes Pass

HALL BY 103 Photo Detector Yes Yes Pass

ROOM 103 Photo Detector Yes Yes Pass

ROOM 134 HSSD Yes Yes Pass

ROOM 127 HSSD Yes Yes Pass

CSS ROOM 106 HSSD Yes Yes Pass

ROOM 144 HSSD Yes Yes Pass

ROOM 144 Duct Detector Yes Yes Pass

ROOM 162 Duct Detector Yes Yes Pass

ROOM 162 Duct Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4100ES

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 26.2 26.4

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Yes Yes 12/55 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/55

Comments

Location: Boiler Room

Manufacturer: Simplex

Model: 4099 NAC (7AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Yes Yes 12/7 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/7

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Boiler Room

Manufacturer: Simplex

Model: 4099 NAC (7AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Yes Yes 12/7 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/7

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P36

Deficiency #1

Power Extender Panels: Failed Model: 4100ES

Notes: M1-1 NAC panel is showing a battery fault

Deficiency #2

System Name: ES FA - FIRE ALARM P36 4099 NAC (7AH) - Boiler Room Battery Pass/Fail: Fail Secondary Battery Pass/Fail:

Notes: Control is showing a battery fault for this NAC

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com