Getz Bldg 8 2023.pdf
PDF 277 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Form for the fire alarm system at Building 8 of the Department of Military Affairs facility located in Springfield, Illinois. The inspection was conducted on May 16, 2023, by Getz Fire Equipment. The report details the results of visual and functional tests performed on the fire alarm control panel, notification appliances, and initiating devices such as manual pull stations, duct detectors, and smoke detectors. The report indicates that the majority of the system passed inspection, with one photo detector failing the test. The report also includes details on the control panel and battery readings.
The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineering Squadron (183 CES) facility. The solicitation, Solicitation# W50S7U-24-B-0001, is an Invitation for Bids (IFB) issued by the Department of the Army National Guard. The Performance Work Statement (PWS) and other documents are attached to the solicitation. A site visit is required, and the details are provided in the solicitation.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - BLDG 8 - Fail
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 14 14 0 14 0 14
Duct Detector 12 12 0 12 0 12
Smoke Detector 4 4 0 4 0 4
Photo Detector 18 17 1 18 0 18
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-8 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4100ES
Software Revision 1.03 Date Last Serviced 2020-12-17
Last Date and Software or Configuration was Revised
2020-08-08
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location PLC
Secondary Standby Sealed Lead-Acid Storage Battery: Amp Hour Rating 50
Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels N/A N/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
AHU 1 SUPPLY Duct Detector Yes Yes Pass
HALL BY
RESTROOM
Photo Detector Yes Yes Pass
FACP ROOM Photo Detector Yes Yes Pass
AHU 3 SUPPLY Duct Detector Yes Yes Pass
HALL BY 123 Photo Detector Yes Yes Pass
AHU 1 RETURN Duct Detector Yes Yes Pass
SPRINKLER RISER
ROOM
Manual Pull Station Yes Yes Pass
HALL BY 105B Photo Detector Yes Yes Pass
REAR ENTRY Manual Pull Station Yes Yes Pass
AHU 3 RETURN Duct Detector Yes Yes Pass
FACP ROOM Manual Pull Station Yes Yes Pass
Room 118 server room
Smoke Detector Yes Yes Pass
HALL BY 122 Photo Detector Yes Yes Pass
HALL BY 114 Photo Detector Yes Yes Fail
AHU 2 RETURN Duct Detector Yes Yes Pass
ROOM 118 EXIT Manual Pull Station Yes Yes Pass
AHU 2 SUPPLY Duct Detector Yes Yes Pass
ROOM 105B Photo Detector Yes Yes Pass
ROOM 104 EXIT Manual Pull Station Yes Yes Pass
ROOM 105A Photo Detector Yes Yes Pass
HALL BY REAR
EXIT
Photo Detector Yes Yes Pass
Room 119 server room
Smoke Detector Yes Yes Pass
EXIT BY 107 Manual Pull Station Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
ROOM 117A EXIT Manual Pull Station Yes Yes Pass
FACP ROOM Photo Detector Yes Yes Pass
HALL BY 105B Photo Detector Yes Yes Pass
AHU 2 RETURN Duct Detector Yes Yes Pass
HALL BY 114 Photo Detector Yes Yes Pass
AHU 3 RETURN Duct Detector Yes Yes Pass
ROOM 105B Photo Detector Yes Yes Pass
ROOM 118 EXIT Manual Pull Station Yes Yes Pass
Room 118 server room
Smoke Detector Yes Yes Pass
FACP ROOM Manual Pull Station Yes Yes Pass
HALL BY 123 Photo Detector Yes Yes Pass
HALL BY
RESTROOM
Photo Detector Yes Yes Pass
AHU 1 SUPPLY Duct Detector Yes Yes Pass
HALL BY 122 Photo Detector Yes Yes Pass
AHU 1 RETURN Duct Detector Yes Yes Pass
EXIT BY 107 Manual Pull Station Yes Yes Pass
AHU 2 SUPPLY Duct Detector Yes Yes Pass
ROOM 117A EXIT Manual Pull Station Yes Yes Pass
ROOM 104 EXIT Manual Pull Station Yes Yes Pass
Room 119 server room
Smoke Detector Yes Yes Pass
REAR ENTRY Manual Pull Station Yes Yes Pass
AHU 3 SUPPLY Duct Detector Yes Yes Pass
SPRINKLER RISER
ROOM
Manual Pull Station Yes Yes Pass
HALL BY REAR
EXIT
Photo Detector Yes Yes Pass
ROOM 105A Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4100ES
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
6-2021 Yes Yes 12/33 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/33
Comments
Location: Power room
Manufacturer: Simplex
Model: 4100ES
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - BLDG 8
Deficiency #1
System Name: ES FA - BLDG 8 Model: PSD Photo Detector - HALL BY 114 -
Status: Fail
Notes: Detector failed inspection
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com