Getz Bldg 8 2023.pdf

PDF 277 KB Posted

Attached to
183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Inspection and Testing Form for the fire alarm system at Building 8 of the Department of Military Affairs facility located in Springfield, Illinois. The inspection was conducted on May 16, 2023, by Getz Fire Equipment. The report details the results of visual and functional tests performed on the fire alarm control panel, notification appliances, and initiating devices such as manual pull stations, duct detectors, and smoke detectors. The report indicates that the majority of the system passed inspection, with one photo detector failing the test. The report also includes details on the control panel and battery readings.

The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineering Squadron (183 CES) facility. The solicitation, Solicitation# W50S7U-24-B-0001, is an Invitation for Bids (IFB) issued by the Department of the Army National Guard. The Performance Work Statement (PWS) and other documents are attached to the solicitation. A site visit is required, and the details are provided in the solicitation.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - BLDG 8 - Fail

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 14 14 0 14 0 14

Duct Detector 12 12 0 12 0 12

Smoke Detector 4 4 0 4 0 4

Photo Detector 18 17 1 18 0 18

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-8 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4100ES

Software Revision 1.03 Date Last Serviced 2020-12-17

Last Date and Software or Configuration was Revised

2020-08-08

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location PLC

Secondary Standby Sealed Lead-Acid Storage Battery: Amp Hour Rating 50

Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels N/A N/A N/A

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

AHU 1 SUPPLY Duct Detector Yes Yes Pass

HALL BY

RESTROOM

Photo Detector Yes Yes Pass

FACP ROOM Photo Detector Yes Yes Pass

AHU 3 SUPPLY Duct Detector Yes Yes Pass

HALL BY 123 Photo Detector Yes Yes Pass

AHU 1 RETURN Duct Detector Yes Yes Pass

SPRINKLER RISER

ROOM

Manual Pull Station Yes Yes Pass

HALL BY 105B Photo Detector Yes Yes Pass

REAR ENTRY Manual Pull Station Yes Yes Pass

AHU 3 RETURN Duct Detector Yes Yes Pass

FACP ROOM Manual Pull Station Yes Yes Pass

Room 118 server room

Smoke Detector Yes Yes Pass

HALL BY 122 Photo Detector Yes Yes Pass

HALL BY 114 Photo Detector Yes Yes Fail

AHU 2 RETURN Duct Detector Yes Yes Pass

ROOM 118 EXIT Manual Pull Station Yes Yes Pass

AHU 2 SUPPLY Duct Detector Yes Yes Pass

ROOM 105B Photo Detector Yes Yes Pass

ROOM 104 EXIT Manual Pull Station Yes Yes Pass

ROOM 105A Photo Detector Yes Yes Pass

HALL BY REAR

EXIT

Photo Detector Yes Yes Pass

Room 119 server room

Smoke Detector Yes Yes Pass

EXIT BY 107 Manual Pull Station Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

ROOM 117A EXIT Manual Pull Station Yes Yes Pass

FACP ROOM Photo Detector Yes Yes Pass

HALL BY 105B Photo Detector Yes Yes Pass

AHU 2 RETURN Duct Detector Yes Yes Pass

HALL BY 114 Photo Detector Yes Yes Pass

AHU 3 RETURN Duct Detector Yes Yes Pass

ROOM 105B Photo Detector Yes Yes Pass

ROOM 118 EXIT Manual Pull Station Yes Yes Pass

Room 118 server room

Smoke Detector Yes Yes Pass

FACP ROOM Manual Pull Station Yes Yes Pass

HALL BY 123 Photo Detector Yes Yes Pass

HALL BY

RESTROOM

Photo Detector Yes Yes Pass

AHU 1 SUPPLY Duct Detector Yes Yes Pass

HALL BY 122 Photo Detector Yes Yes Pass

AHU 1 RETURN Duct Detector Yes Yes Pass

EXIT BY 107 Manual Pull Station Yes Yes Pass

AHU 2 SUPPLY Duct Detector Yes Yes Pass

ROOM 117A EXIT Manual Pull Station Yes Yes Pass

ROOM 104 EXIT Manual Pull Station Yes Yes Pass

Room 119 server room

Smoke Detector Yes Yes Pass

REAR ENTRY Manual Pull Station Yes Yes Pass

AHU 3 SUPPLY Duct Detector Yes Yes Pass

SPRINKLER RISER

ROOM

Manual Pull Station Yes Yes Pass

HALL BY REAR

EXIT

Photo Detector Yes Yes Pass

ROOM 105A Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4100ES

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

6-2021 Yes Yes 12/33 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/33

Comments

Location: Power room

Manufacturer: Simplex

Model: 4100ES

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - BLDG 8

Deficiency #1

System Name: ES FA - BLDG 8 Model: PSD Photo Detector - HALL BY 114 -

Status: Fail

Notes: Detector failed inspection

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com