Getz Bldg 37 2023.pdf
PDF 173 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Form for an annual NFPA 72 fire alarm inspection at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The inspection was conducted on May 17, 2023 by Scott Calhoon of Getz Fire Equipment. The form provides details on the fire alarm system components tested, including manual pull stations, heat detectors, and horn strobes, all of which passed the inspection. It also includes information on the fire alarm control panel, power supply, and backup battery. No deficiencies were noted in the report.
The related federal contract opportunity is for the 183 CES Repair Base Fire Alarm System, Solicitation# W50S7U-24-B-0001, issued by the Department of the Army National Guard. The Invitation for Bids (IFB) seeks contractors to repair the fire alarm system at the facility. The solicitation includes a Performance Work Statement (PWS) and other supporting documents. A site visit is required, with details provided in the solicitation.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P37 - Pass
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 5 5 0 5 0 5
Heat Detector 3 3 0 3 0 3
Horn Strobe 4 4 0 4 0 4
Report of Inspection / Test Annual NFPA 72
2023-05-17 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-37 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Silent Knight Model Number SK-5208
Software Revision 2.1 Date Last Serviced 2020-12-18
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 30
Overcurrent Protection Breaker Panel Board Location RIPA
Disconnecting Means Location 12 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 7 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-17 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator N/A N/A N/A
Power Extender Panels N/A N/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual N/A N/A N/A
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown N/A N/A N/A
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-17 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
MAIN BAY EAST Heat Detector Yes Yes Pass
MAIN BAY WEST Heat Detector Yes Yes Pass
EAST STORAGE Heat Detector Yes Yes Pass
AREA 113 EAST Manual Pull Station Yes Yes Pass
AREA 113 WEST Manual Pull Station Yes Yes Pass
BY SOUTH EXIT Manual Pull Station Yes Yes Pass
E STORAGE
SOUTH EXIT
Manual Pull Station Yes Yes Pass
NORTHWEST EXIT Manual Pull Station Yes Yes Pass
Outside Horn Strobe Yes Yes Pass
Outside Horn Strobe Yes Yes Pass
Outside Horn Strobe Yes Yes Pass
Outside Horn Strobe Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-17 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Silent Knight
Model: 5208
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
6-2021 Yes Yes 12/7 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/7
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-17 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P37
None
Report of Inspection / Test Annual NFPA 72
2023-05-17 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com