183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Annual NFPA 72 Fire Alarm Inspection and Test Report for Building 48 on the Department of Military Affairs property located in Springfield, Illinois. The report details the inspection and functional testing performed on the fire alarm system components including control panels, notification appliances, and initiating devices. Several duct detectors were identified as failing the functional test and requiring service. The report includes battery readings and details on auxiliary functions such as fan shutdown, elevator recall, and HVAC shutdown.

The related federal contract opportunity is for the 183 CES Repair Base Fire Alarm System solicitation (W50S7U-24-B-0001) issued by the Department of the Army National Guard. This Invitation for Bids (IFB) requires repairs and upgrades to the fire alarm system at the facility. The Performance Work Statement and other solicitation documents are attached for reference.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P48 - Fail

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 13 13 0 13 0 13

Heat Detector 10 10 0 10 0 10

Duct Detector 4 1 3 4 0 4

Remote Relay 1 1 0 1 0 1

Photo Detector 37 37 0 37 0 37

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-48 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4010

Software Revision 3.03 Date Last Serviced 2020-12-17

Last Date and Software or Configuration was Revised

2020-04-27

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location ERP

Disconnecting Means Location 1 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 12 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels Yes Yes Pass

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall Yes Yes Pass

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

11 1ST FLOOR

ELECTRIC ROOM

Heat Detector Yes Yes Pass

12 1ST FLOOR

CORRIDOR 131

WEST

Photo Detector Yes Yes Pass

16 1ST FLOOR

CORRIDOR 131

WEST CENTER

Photo Detector Yes Yes Pass

17 1ST FLOOR

CORRIDOR 132 BY

ATSO 110

Photo Detector Yes Yes Pass

19 1ST FLOOR MAIN

CORRIDOR 131

EAST CENTER

Photo Detector Yes Yes Pass

20 1ST FLOOR

ELECTRIC ROOM

Heat Detector Yes Yes Pass

21 1FL MAIN

CORRIDOR 131

EAST

Photo Detector Yes Yes Pass

22 1FL ELEVATOR

LOBBY 130

Photo Detector Yes Yes Pass

23 1FL ELEVATOR

EQUIPMENT ROOM

Heat Detector Yes Yes Pass

24 1FL ELEVATOR

EQUIPMENT ROOM

Photo Detector Yes Yes Pass

30 1fl

COMMUNICATIONS

ROOM 115

Heat Detector Yes Yes Pass

31 1FL AHU 1 SUPPLY

ABOVE RM 116 N.E.

Duct Detector Yes Yes Pass

32 1FL AHU 1 RETURN

ABOVE RM 118

N.W.

Duct Detector Yes Yes Fail

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

34 1FL AHU 2 SUPPLY

ABOVE RM 118

WEST CE

Duct Detector Yes Yes Fail

35 1FL AHU 2 RETURN

ABOVE RM 116 E.

CENTER

Duct Detector Yes Yes Fail

39 1FL LOBBY 130

SOUTH

Photo Detector Yes Yes Pass

41 1FL LOBBY 130

NORTH

Photo Detector Yes Yes Pass

42 2ND FLOOR EAST

CORRIDOR 241 BY

Photo Detector Yes Yes Pass

43 2FL EAST NORTH

CORRIDOR 242 BY

Photo Detector Yes Yes Pass

44 2FL STORAGE

CLOSET 211

Heat Detector Yes Yes Pass

45 2FL ELEVATOR

CORRIDOR 243

NORTH

Photo Detector Yes Yes Pass

46 2FL NORTH

CORRIDOR 244

EAST BY 214

Photo Detector Yes Yes Pass

47 2FL NORTH

CORRIDOR 244

WEST BY 221

Photo Detector Yes Yes Pass

48 2FL

LOBBY/WAITING

222 WEST

Photo Detector Yes Yes Pass

50 2FL BY WEST

STAIRS

Photo Detector Yes Yes Pass

51 2FL SOUTH

CORRIDOR 245

WEST

Photo Detector Yes Yes Pass

52 2FL BY

RESTROOMS

Photo Detector Yes Yes Pass

53 2FL

COMMUNICATIONS

ROOM 234

Heat Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

54 2FL DENTAL EXAM

ROOM 230 WEST

Photo Detector Yes Yes Pass

55 2FL DENTAL EXAM

ROOM 230

Heat Detector Yes Yes Pass

56 2FL DENTAL EXAM

ROOM 230 EAST

Photo Detector Yes Yes Pass

57 2FL X-RAY ROOM

Heat Detector Yes Yes Pass

58 2FL X-RAY ROOM

Photo Detector Yes Yes Pass

59 2FL SOUTH

CORRIDOR 245

EAST

Photo Detector Yes Yes Pass

60 2FL ELEVATOR

CORRIDOR 243

CENTER BY 237

Photo Detector Yes Yes Pass

61 2FL ELEVATOR

LOBBY

Photo Detector Yes Yes Pass

63 2FL EAST SOUTH

CORRIDOE 240

Photo Detector Yes Yes Pass

64 3FL CORRIDOR 345

BY 308

Photo Detector Yes Yes Pass

65 3FL NORTH

CORRIDOR 346

EAST

Photo Detector Yes Yes Pass

66 3FL NORTH

CORRIDOR 346

WEST

Photo Detector Yes Yes Pass

67 3FL ELECTRIC

CLOSET 320

Heat Detector Yes Yes Pass

68 3FL WEST

CORRIDOR 348

EAST

Photo Detector Yes Yes Pass

69 3FL

COMMUNICATIONS

ROOM 325

Heat Detector Yes Yes Pass

70 3FL BY

RESTROOMS

Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

71 3FL WEST

CORRIDOR 348

WEST BY 336

Photo Detector Yes Yes Pass

73 3FL IN WEST

STAIRWELL

Photo Detector Yes Yes Pass

74 3FL TOP ELEVATOR

SHAFT

Photo Detector Yes Yes Pass

75 3FL ELEVATOR

LOBBY

Photo Detector Yes Yes Pass

76 3FL ELEVATOR

CORRIDOR 347

CENTER

Photo Detector Yes Yes Pass

78 3FL EAST

STAIRWELL

Photo Detector Yes Yes Pass

79 3FL EAST SOUTH

CORRIDOR 344 BY

Photo Detector Yes Yes Pass

3 1FL DINNING HALL

EAST RM 113

Manual Pull Station Yes Yes Pass

14 1FL VESTIBULE 134 Manual Pull Station Yes Yes Pass

15 1FL PHYSICAL

FITNESS ROOM

Manual Pull Station Yes Yes Pass

18 1FL ATSO ROOM

Manual Pull Station Yes Yes Pass

33 1FL CE READINESS

STORAGE ROOM

Manual Pull Station Yes Yes Pass

36 1FL CLIPPER

DISHWASHER

ROOM 117

Manual Pull Station Yes Yes Pass

37 1FL DINING HALL

WEST ROOM 113

Manual Pull Station Yes Yes Pass

38 1FL LOBBY 130 Manual Pull Station Yes Yes Pass

40 1FL AUDITORIUM

ROOM 100

Manual Pull Station Yes Yes Pass

49 2FL WEST STAIRS Manual Pull Station Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

62 2FL BY EAST

STAIRS

Manual Pull Station Yes Yes Pass

72 3FL BY WEST

STAIRS

Manual Pull Station Yes Yes Pass

77 3FL BY EAST

STAIRS

Manual Pull Station Yes Yes Pass

Boiler Room HVAC Shutdown

Remote Relay Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4010

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

6-2021 Yes Yes 12/12 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/12

Comments

Location: Boiler Room

Manufacturer: Simplex

Model: 4099 NAC (7AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

2-2023 Yes Yes 12/7 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/7

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Location: Room 320

Manufacturer: Simplex

Model: 4099 NAC (7AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

2-2023 Yes Yes 12/7 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/7

Comments

Location: Main Entry

Manufacturer: Simplex

Model: Remote Annunciator

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Location: Rear Entrance

Manufacturer: Simplex

Model: Remote Annunciator

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Location: Room 122

Manufacturer: Simplex

Model: 4099 NAC (7AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

2-2023 Yes Yes 12/7 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/7

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P48

Deficiency #1

System Name: ES FA - FIRE ALARM P48 Loop: M1 Model: DSD Duct Detector - 1FL AHU 2 RETURN ABOVE RM 116 E. CENTER - 35

Status: Fail

Notes: Detector is showing trouble

Deficiency #2

System Name: ES FA - FIRE ALARM P48 Loop: M1 Model: DSD Duct Detector - 1FL AHU 2 SUPPLY ABOVE RM 118 WEST CE - 34

Status: Fail

Notes: Detector is showing trouble

Deficiency #3

System Name: ES FA - FIRE ALARM P48 Loop: M1 Model: DSD Duct Detector - 1FL AHU 1 RETURN ABOVE RM 118 N.W. - 32

Status: Fail

Notes: Detector is showing trouble

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com