This document is an Annual NFPA 72 Fire Alarm Inspection and Test Report for Building 48 on the Department of Military Affairs property located in Springfield, Illinois. The report details the inspection and functional testing performed on the fire alarm system components including control panels, notification appliances, and initiating devices. Several duct detectors were identified as failing the functional test and requiring service. The report includes battery readings and details on auxiliary functions such as fan shutdown, elevator recall, and HVAC shutdown.
The related federal contract opportunity is for the 183 CES Repair Base Fire Alarm System solicitation (W50S7U-24-B-0001) issued by the Department of the Army National Guard. This Invitation for Bids (IFB) requires repairs and upgrades to the fire alarm system at the facility. The Performance Work Statement and other solicitation documents are attached for reference.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P48 - Fail
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 13 13 0 13 0 13
Heat Detector 10 10 0 10 0 10
Duct Detector 4 1 3 4 0 4
Remote Relay 1 1 0 1 0 1
Photo Detector 37 37 0 37 0 37
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-48 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4010
Software Revision 3.03 Date Last Serviced 2020-12-17
Last Date and Software or Configuration was Revised
2020-04-27
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location ERP
Disconnecting Means Location 1 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 12 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels Yes Yes Pass
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall Yes Yes Pass
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
11 1ST FLOOR
ELECTRIC ROOM
Heat Detector Yes Yes Pass
12 1ST FLOOR
CORRIDOR 131
WEST
Photo Detector Yes Yes Pass
16 1ST FLOOR
CORRIDOR 131
WEST CENTER
Photo Detector Yes Yes Pass
17 1ST FLOOR
CORRIDOR 132 BY
ATSO 110
Photo Detector Yes Yes Pass
19 1ST FLOOR MAIN
CORRIDOR 131
EAST CENTER
Photo Detector Yes Yes Pass
20 1ST FLOOR
ELECTRIC ROOM
Heat Detector Yes Yes Pass
21 1FL MAIN
CORRIDOR 131
EAST
Photo Detector Yes Yes Pass
22 1FL ELEVATOR
LOBBY 130
Photo Detector Yes Yes Pass
23 1FL ELEVATOR
EQUIPMENT ROOM
Heat Detector Yes Yes Pass
24 1FL ELEVATOR
EQUIPMENT ROOM
Photo Detector Yes Yes Pass
30 1fl
COMMUNICATIONS
ROOM 115
Heat Detector Yes Yes Pass
31 1FL AHU 1 SUPPLY
ABOVE RM 116 N.E.
Duct Detector Yes Yes Pass
32 1FL AHU 1 RETURN
ABOVE RM 118
N.W.
Duct Detector Yes Yes Fail
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
34 1FL AHU 2 SUPPLY
ABOVE RM 118
WEST CE
Duct Detector Yes Yes Fail
35 1FL AHU 2 RETURN
ABOVE RM 116 E.
CENTER
Duct Detector Yes Yes Fail
39 1FL LOBBY 130
SOUTH
Photo Detector Yes Yes Pass
41 1FL LOBBY 130
NORTH
Photo Detector Yes Yes Pass
42 2ND FLOOR EAST
CORRIDOR 241 BY
Photo Detector Yes Yes Pass
43 2FL EAST NORTH
CORRIDOR 242 BY
Photo Detector Yes Yes Pass
44 2FL STORAGE
CLOSET 211
Heat Detector Yes Yes Pass
45 2FL ELEVATOR
CORRIDOR 243
NORTH
Photo Detector Yes Yes Pass
46 2FL NORTH
CORRIDOR 244
EAST BY 214
Photo Detector Yes Yes Pass
47 2FL NORTH
CORRIDOR 244
WEST BY 221
Photo Detector Yes Yes Pass
48 2FL
LOBBY/WAITING
222 WEST
Photo Detector Yes Yes Pass
50 2FL BY WEST
STAIRS
Photo Detector Yes Yes Pass
51 2FL SOUTH
CORRIDOR 245
WEST
Photo Detector Yes Yes Pass
52 2FL BY
RESTROOMS
Photo Detector Yes Yes Pass
53 2FL
COMMUNICATIONS
ROOM 234
Heat Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
54 2FL DENTAL EXAM
ROOM 230 WEST
Photo Detector Yes Yes Pass
55 2FL DENTAL EXAM
ROOM 230
Heat Detector Yes Yes Pass
56 2FL DENTAL EXAM
ROOM 230 EAST
Photo Detector Yes Yes Pass
57 2FL X-RAY ROOM
Heat Detector Yes Yes Pass
58 2FL X-RAY ROOM
Photo Detector Yes Yes Pass
59 2FL SOUTH
CORRIDOR 245
EAST
Photo Detector Yes Yes Pass
60 2FL ELEVATOR
CORRIDOR 243
CENTER BY 237
Photo Detector Yes Yes Pass
61 2FL ELEVATOR
LOBBY
Photo Detector Yes Yes Pass
63 2FL EAST SOUTH
CORRIDOE 240
Photo Detector Yes Yes Pass
64 3FL CORRIDOR 345
BY 308
Photo Detector Yes Yes Pass
65 3FL NORTH
CORRIDOR 346
EAST
Photo Detector Yes Yes Pass
66 3FL NORTH
CORRIDOR 346
WEST
Photo Detector Yes Yes Pass
67 3FL ELECTRIC
CLOSET 320
Heat Detector Yes Yes Pass
68 3FL WEST
CORRIDOR 348
EAST
Photo Detector Yes Yes Pass
69 3FL
COMMUNICATIONS
ROOM 325
Heat Detector Yes Yes Pass
70 3FL BY
RESTROOMS
Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
71 3FL WEST
CORRIDOR 348
WEST BY 336
Photo Detector Yes Yes Pass
73 3FL IN WEST
STAIRWELL
Photo Detector Yes Yes Pass
74 3FL TOP ELEVATOR
SHAFT
Photo Detector Yes Yes Pass
75 3FL ELEVATOR
LOBBY
Photo Detector Yes Yes Pass
76 3FL ELEVATOR
CORRIDOR 347
CENTER
Photo Detector Yes Yes Pass
78 3FL EAST
STAIRWELL
Photo Detector Yes Yes Pass
79 3FL EAST SOUTH
CORRIDOR 344 BY
Photo Detector Yes Yes Pass
3 1FL DINNING HALL
EAST RM 113
Manual Pull Station Yes Yes Pass
14 1FL VESTIBULE 134 Manual Pull Station Yes Yes Pass
15 1FL PHYSICAL
FITNESS ROOM
Manual Pull Station Yes Yes Pass
18 1FL ATSO ROOM
Manual Pull Station Yes Yes Pass
33 1FL CE READINESS
STORAGE ROOM
Manual Pull Station Yes Yes Pass
36 1FL CLIPPER
DISHWASHER
ROOM 117
Manual Pull Station Yes Yes Pass
37 1FL DINING HALL
WEST ROOM 113
Manual Pull Station Yes Yes Pass
38 1FL LOBBY 130 Manual Pull Station Yes Yes Pass
40 1FL AUDITORIUM
ROOM 100
Manual Pull Station Yes Yes Pass
49 2FL WEST STAIRS Manual Pull Station Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
62 2FL BY EAST
STAIRS
Manual Pull Station Yes Yes Pass
72 3FL BY WEST
STAIRS
Manual Pull Station Yes Yes Pass
77 3FL BY EAST
STAIRS
Manual Pull Station Yes Yes Pass
Boiler Room HVAC Shutdown
Remote Relay Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4010
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
6-2021 Yes Yes 12/12 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/12
Comments
Location: Boiler Room
Manufacturer: Simplex
Model: 4099 NAC (7AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
2-2023 Yes Yes 12/7 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/7
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Location: Room 320
Manufacturer: Simplex
Model: 4099 NAC (7AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
2-2023 Yes Yes 12/7 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/7
Comments
Location: Main Entry
Manufacturer: Simplex
Model: Remote Annunciator
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Location: Rear Entrance
Manufacturer: Simplex
Model: Remote Annunciator
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
Comments
Location: Room 122
Manufacturer: Simplex
Model: 4099 NAC (7AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
2-2023 Yes Yes 12/7 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/7
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P48
Deficiency #1
System Name: ES FA - FIRE ALARM P48 Loop: M1 Model: DSD Duct Detector - 1FL AHU 2 RETURN ABOVE RM 116 E. CENTER - 35
Status: Fail
Notes: Detector is showing trouble
Deficiency #2
System Name: ES FA - FIRE ALARM P48 Loop: M1 Model: DSD Duct Detector - 1FL AHU 2 SUPPLY ABOVE RM 118 WEST CE - 34
Status: Fail
Notes: Detector is showing trouble
Deficiency #3
System Name: ES FA - FIRE ALARM P48 Loop: M1 Model: DSD Duct Detector - 1FL AHU 1 RETURN ABOVE RM 118 N.W. - 32
Status: Fail
Notes: Detector is showing trouble
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com