Getz Bldg 50 2023.pdf
PDF 175 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Annual NFPA 72 Inspection Report for the fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway, Springfield, IL 62702. The report details the inspection and testing conducted on May 16, 2023, including the results for various fire alarm system components such as manual pull stations, heat detectors, horn strobes, and photo detectors. All tested devices passed the inspection. The report also includes information on the fire alarm control panel, power supply, and battery backup. No deficiencies were noted.
The related federal contract opportunity is a solicitation (Solicitation# W50S7U-24-B-0001) issued by the Department of the Army National Guard for the 183 CES Repair Base Fire Alarm System. The solicitation includes a Performance Work Statement (PWS) and requires a site visit. Interested contractors are advised to thoroughly review the solicitation and other provided documents to ensure compliance with the requirements.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P50 - Pass
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 3 3 0 3 0 3
Heat Detector 3 3 0 3 0 3
Horn Strobe 5 5 0 5 0 5
Photo Detector 1 1 0 1 0 1
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name P-25 Telephone 217-757-1369
Reference Number P-50 Type Transmission IP
System Type
Control Unit Manufacturer Monaco Model Number M Series
Software Revision 1.3 Date Last Serviced 2020-12-19
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 30
Overcurrent Protection Breaker Panel Board Location A-2
Disconnecting Means Location 19 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 18 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels N/A N/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown N/A N/A N/A
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
MAIN ROOM Heat Detector Yes Yes Pass
PIT Heat Detector Yes Yes Pass
RESTROOM Heat Detector Yes Yes Pass
MAIN ROOM EAST Manual Pull Station Yes Yes Pass
MAIN ROOM WEST Manual Pull Station Yes Yes Pass
PIT Manual Pull Station Yes Yes Pass
MAIN ROOM Photo Detector Yes Yes Pass main room Horn Strobe Yes Yes Pass mantrap Horn Strobe Yes Yes Pass
Outside east Horn Strobe Yes Yes Pass
Outside west Horn Strobe Yes Yes Pass
Restroom Horn Strobe Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Monaco
Model: M Series
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Yes Yes 12/18 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/18
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P50
None
Report of Inspection / Test Annual NFPA 72