This document is an Inspection and Testing Report for the fire alarm system at a Department of Military Affairs facility located in Springfield, Illinois. The report provides details on the inspection and testing of various fire alarm system components such as manual pull stations, heat detectors, and photo detectors. It indicates that most components passed the inspection, with one photo detector in Office 2 failing the functional test. The report also includes information on the fire alarm control panel, power supply, and secondary standby battery.

The related federal contract opportunity is for the 183rd Civil Engineer Squadron to repair the base fire alarm system. The Invitation for Bids (IFB) solicitation number is W50S7U-24-B-0001. The Performance Work Statement and other relevant documents are attached. A site visit is required, with the date, time, and location specified in the solicitation. The solicitation is being issued by the Department of the Army National Guard.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - BLDG P-23 - Fail

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 12 12 0 12 0 12

Heat Detector 24 24 0 24 0 24

Photo Detector 10 9 1 10 0 10

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name P-25 Telephone 217-757-1369

Reference Number P-23 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4005

Software Revision 2.04 Date Last Serviced 2020-12-17

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location PLC

Disconnecting Means Location 14 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 18 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator N/A N/A N/A

Power Extender Panels N/A N/A N/A

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

PT ROOM WEST Heat Detector Yes Yes Pass

MAIN ENTRY Manual Pull Station Yes Yes Pass

PDF ROOM NORTH Heat Detector Yes Yes Pass

HALL BY WOMENS

RESTROOM

Photo Detector Yes Yes Pass

WAIST MEASURE

ROOM WEST

Heat Detector Yes Yes Pass

LOCKED OFFICE Photo Detector Yes Yes Pass

PDF EXIT Manual Pull Station Yes Yes Pass

WAIST MEASURE

ROOM EAST

Heat Detector Yes Yes Pass

OFFICE 2 Photo Detector Yes Yes Fail

PDF ROOM SOUTH Heat Detector Yes Yes Pass

PT ROOM EAST Heat Detector Yes Yes Pass

JANITOR BY

WOMENS

RESTROOM

Heat Detector Yes Yes Pass

OFFICE BY

WOMENS

RESTROOM

Photo Detector Yes Yes Pass

WAIST MEASURE

EXIT

Manual Pull Station Yes Yes Pass

BOOT ROOM Heat Detector Yes Yes Pass

PDF ROOM ENTRY Manual Pull Station Yes Yes Pass

SUPPLY ROOM

WEST

Heat Detector Yes Yes Pass

FACP ROOM Heat Detector Yes Yes Pass

SUPPLY EXIT Manual Pull Station Yes Yes Pass

PT AREA EXIT Manual Pull Station Yes Yes Pass

PT KITCHEN Heat Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

OFFICE 3 Photo Detector Yes Yes Pass

SUPPLY ROOM

EAST

Heat Detector Yes Yes Pass

OFFICE 2 Photo Detector Yes Yes Pass

BOOT ROOM Heat Detector Yes Yes Pass

PDF ROOM NORTH Heat Detector Yes Yes Pass

PT ROOM WEST Heat Detector Yes Yes Pass

PT KITCHEN Heat Detector Yes Yes Pass

WAIST MEASURE

ROOM EAST

Heat Detector Yes Yes Pass

PDF EXIT Manual Pull Station Yes Yes Pass

PDF ROOM ENTRY Manual Pull Station Yes Yes Pass

PDF ROOM SOUTH Heat Detector Yes Yes Pass

JANITOR BY

WOMENS

RESTROOM

Heat Detector Yes Yes Pass

MAIN ENTRY Manual Pull Station Yes Yes Pass

SUPPLY EXIT Manual Pull Station Yes Yes Pass

FACP ROOM Heat Detector Yes Yes Pass

WAIST MEASURE

EXIT

Manual Pull Station Yes Yes Pass

OFFICE BY

WOMENS

RESTROOM

Photo Detector Yes Yes Pass

PT AREA EXIT Manual Pull Station Yes Yes Pass

SUPPLY ROOM

WEST

Heat Detector Yes Yes Pass

SUPPLY ROOM

EAST

Heat Detector Yes Yes Pass

HALL BY WOMENS

RESTROOM

Photo Detector Yes Yes Pass

LOCKED OFFICE Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

WAIST MEASURE

ROOM WEST

Heat Detector Yes Yes Pass

PT ROOM EAST Heat Detector Yes Yes Pass

OFFICE 3 Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4005

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Yes Yes 12/18 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/18

Comments

Location: Boiler room

Manufacturer: Simplex

Model: 4005

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - BLDG P-23

Deficiency #1

System Name: ES FA - BLDG P-23 Model: PSD Photo Detector - OFFICE 2 -

Status: Fail

Notes: Detector failed inspection

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com