Getz Bldg 23 2023.pdf
PDF 275 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Report for the fire alarm system at a Department of Military Affairs facility located in Springfield, Illinois. The report provides details on the inspection and testing of various fire alarm system components such as manual pull stations, heat detectors, and photo detectors. It indicates that most components passed the inspection, with one photo detector in Office 2 failing the functional test. The report also includes information on the fire alarm control panel, power supply, and secondary standby battery.
The related federal contract opportunity is for the 183rd Civil Engineer Squadron to repair the base fire alarm system. The Invitation for Bids (IFB) solicitation number is W50S7U-24-B-0001. The Performance Work Statement and other relevant documents are attached. A site visit is required, with the date, time, and location specified in the solicitation. The solicitation is being issued by the Department of the Army National Guard.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - BLDG P-23 - Fail
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 12 12 0 12 0 12
Heat Detector 24 24 0 24 0 24
Photo Detector 10 9 1 10 0 10
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name P-25 Telephone 217-757-1369
Reference Number P-23 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4005
Software Revision 2.04 Date Last Serviced 2020-12-17
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location PLC
Disconnecting Means Location 14 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 18 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator N/A N/A N/A
Power Extender Panels N/A N/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
PT ROOM WEST Heat Detector Yes Yes Pass
MAIN ENTRY Manual Pull Station Yes Yes Pass
PDF ROOM NORTH Heat Detector Yes Yes Pass
HALL BY WOMENS
RESTROOM
Photo Detector Yes Yes Pass
WAIST MEASURE
ROOM WEST
Heat Detector Yes Yes Pass
LOCKED OFFICE Photo Detector Yes Yes Pass
PDF EXIT Manual Pull Station Yes Yes Pass
WAIST MEASURE
ROOM EAST
Heat Detector Yes Yes Pass
OFFICE 2 Photo Detector Yes Yes Fail
PDF ROOM SOUTH Heat Detector Yes Yes Pass
PT ROOM EAST Heat Detector Yes Yes Pass
JANITOR BY
WOMENS
RESTROOM
Heat Detector Yes Yes Pass
OFFICE BY
WOMENS
RESTROOM
Photo Detector Yes Yes Pass
WAIST MEASURE
EXIT
Manual Pull Station Yes Yes Pass
BOOT ROOM Heat Detector Yes Yes Pass
PDF ROOM ENTRY Manual Pull Station Yes Yes Pass
SUPPLY ROOM
WEST
Heat Detector Yes Yes Pass
FACP ROOM Heat Detector Yes Yes Pass
SUPPLY EXIT Manual Pull Station Yes Yes Pass
PT AREA EXIT Manual Pull Station Yes Yes Pass
PT KITCHEN Heat Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
OFFICE 3 Photo Detector Yes Yes Pass
SUPPLY ROOM
EAST
Heat Detector Yes Yes Pass
OFFICE 2 Photo Detector Yes Yes Pass
BOOT ROOM Heat Detector Yes Yes Pass
PDF ROOM NORTH Heat Detector Yes Yes Pass
PT ROOM WEST Heat Detector Yes Yes Pass
PT KITCHEN Heat Detector Yes Yes Pass
WAIST MEASURE
ROOM EAST
Heat Detector Yes Yes Pass
PDF EXIT Manual Pull Station Yes Yes Pass
PDF ROOM ENTRY Manual Pull Station Yes Yes Pass
PDF ROOM SOUTH Heat Detector Yes Yes Pass
JANITOR BY
WOMENS
RESTROOM
Heat Detector Yes Yes Pass
MAIN ENTRY Manual Pull Station Yes Yes Pass
SUPPLY EXIT Manual Pull Station Yes Yes Pass
FACP ROOM Heat Detector Yes Yes Pass
WAIST MEASURE
EXIT
Manual Pull Station Yes Yes Pass
OFFICE BY
WOMENS
RESTROOM
Photo Detector Yes Yes Pass
PT AREA EXIT Manual Pull Station Yes Yes Pass
SUPPLY ROOM
WEST
Heat Detector Yes Yes Pass
SUPPLY ROOM
EAST
Heat Detector Yes Yes Pass
HALL BY WOMENS
RESTROOM
Photo Detector Yes Yes Pass
LOCKED OFFICE Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
WAIST MEASURE
ROOM WEST
Heat Detector Yes Yes Pass
PT ROOM EAST Heat Detector Yes Yes Pass
OFFICE 3 Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4005
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Yes Yes 12/18 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/18
Comments
Location: Boiler room
Manufacturer: Simplex
Model: 4005
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - BLDG P-23
Deficiency #1
System Name: ES FA - BLDG P-23 Model: PSD Photo Detector - OFFICE 2 -
Status: Fail
Notes: Detector failed inspection
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com