Getz Bldg 1 2023.pdf

PDF 298 KB Posted

Attached to
183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Inspection and Testing Report for the fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The report details the annual inspection and testing of the fire alarm system components, including detectors, pull stations, and notification appliances. All components were visually inspected and functionally tested, with the results indicating the system is operating properly. The report includes details on the control panel, power supply, and battery backup system. No deficiencies were noted.

The related federal contract opportunity is for the Repair of the Base Fire Alarm System at the 183rd Civil Engineer Squadron. The solicitation, identified as W50S7U-24-B-0001, is an Invitation for Bids (IFB) issued by the Department of the Army National Guard. The Performance Work Statement (PWS) and other associated documents are attached. A site visit is required, with the date, time, and location provided in the solicitation.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P1 - Pass

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Heat Detector 2 2 0 2 0 2

Duct Detector 3 3 0 3 0 3

Pull Station 12 12 0 12 0 12

Photo Detector 28 28 0 28 0 28

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-1 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4100U

Software Revision 14.01 Date Last Serviced 2020-12-18

Last Date and Software or Configuration was Revised

2020-01-11

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location PLC

Disconnecting Means Location 23 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 33 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels Yes Yes Pass

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation No No Pass

Elevator Recall Yes Yes Pass

Elevator Shunt-Trip No No Pass

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

North Wing RTU East

Duct Detector Yes Yes Pass

North Wing RTU West

Duct Detector Yes Yes Pass

RTU South Return Duct Detector Yes Yes Pass

Top of shaft Heat Detector Yes Yes Pass

HANGER

NORTHWEST EXIT

Pull Station Yes Yes Pass

HANGER

SOUTHWEST EXIT

Pull Station Yes Yes Pass

NORTH EXIT Pull Station Yes Yes Pass

NORTHEAST

STAIRS EXIT

Pull Station Yes Yes Pass

NORTHEAST

STAIRS

Pull Station Yes Yes Pass

NORTHWEST BY

STAIRS

Pull Station Yes Yes Pass

ROOM 111

NORTHEAST EXIT

Pull Station Yes Yes Pass

SOUTHEAST STAIR

EXIT

Pull Station Yes Yes Pass

STAIRWELL

LANDING BY 210

Pull Station Yes Yes Pass

SOUTHWEST HALL

BY STAIRS

Pull Station Yes Yes Pass

SOUTHWEST STAIR

EXIT

Pull Station Yes Yes Pass

NORTHWEST

STAIR EXIT

Pull Station Yes Yes Pass

1ST FLOOR

ELEVATOR LOBBY

Photo Detector Yes Yes Pass

1ST FLOOR

NORTHEAST EXIT

Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

1ST FLOOR

NORTHWEST EXIT

Photo Detector Yes Yes Pass

1ST FLOOR

SOUTHWEST EXIT

Photo Detector Yes Yes Pass

2ND FLOOR

ELEVATOR LOBBY

Photo Detector Yes Yes Pass

ABOVE FACP Photo Detector Yes Yes Pass

HALL BY ROOM 201 Photo Detector Yes Yes Pass

HALL BY ROOM 202 Photo Detector Yes Yes Pass

HALL BY ROOM 203 Photo Detector Yes Yes Pass

HALL BY ROOM 205 Photo Detector Yes Yes Pass

HALL BY ROOM 207 Photo Detector Yes Yes Pass

HALL BY ROOM 210 Photo Detector Yes Yes Pass

HALL BY ROOM 212

NORTH

Photo Detector Yes Yes Pass

HALL BY ROOM 212

SOUTH

Photo Detector Yes Yes Pass

HALL BY ROOM 215 Photo Detector Yes Yes Pass

HALL BY ROOM 216 Photo Detector Yes Yes Pass

HALL BY ROOM 222 Photo Detector Yes Yes Pass

HALL BY ROOM 227 Photo Detector Yes Yes Pass

HALL BY BREAK

ROOM

Photo Detector Yes Yes Pass

HALL BY MENS

ROOM

Photo Detector Yes Yes Pass

HALL BY ORDERLY

ROOM

Photo Detector Yes Yes Pass

HALL BY WOMENS

ROOM

Photo Detector Yes Yes Pass

TOP STAIRS

NORTH EAST

Photo Detector Yes Yes Pass

TOP STAIRS

NORTH WEST

Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

TOP STAIRS

SOUTH EAST

Photo Detector Yes Yes Pass

TOP STAIRS

SOUTH WEST

Photo Detector Yes Yes Pass

1st Floor ELEVATOR

EQUIPMENT ROOM

Photo Detector Yes Yes Pass

1st Floor Elevator Equipment room

Heat Detector Yes Yes Pass

TOP OF SHAFT Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Northeast entry

Manufacturer: Simplex

Model: PSSA

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Location: By FACP

Manufacturer: Simplex

Model: 4099 NAC (12AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.2 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2020 Yes Yes 12/12 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/12

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4100U

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.1 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2020 Yes Yes 12/33 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/33

Comments

Location: By FACP

Manufacturer: Simplex

Model: 4099 NAC (12AH)

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.2 27.2

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2020 Yes Yes 12/12 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/12

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P1

None

Report of Inspection / Test Annual NFPA 72

2023-05-15 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

File details come from the government source that posted it. Updated .