Getz Bldg 1 2023.pdf
PDF 298 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Report for the fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The report details the annual inspection and testing of the fire alarm system components, including detectors, pull stations, and notification appliances. All components were visually inspected and functionally tested, with the results indicating the system is operating properly. The report includes details on the control panel, power supply, and battery backup system. No deficiencies were noted.
The related federal contract opportunity is for the Repair of the Base Fire Alarm System at the 183rd Civil Engineer Squadron. The solicitation, identified as W50S7U-24-B-0001, is an Invitation for Bids (IFB) issued by the Department of the Army National Guard. The Performance Work Statement (PWS) and other associated documents are attached. A site visit is required, with the date, time, and location provided in the solicitation.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P1 - Pass
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Heat Detector 2 2 0 2 0 2
Duct Detector 3 3 0 3 0 3
Pull Station 12 12 0 12 0 12
Photo Detector 28 28 0 28 0 28
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-1 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4100U
Software Revision 14.01 Date Last Serviced 2020-12-18
Last Date and Software or Configuration was Revised
2020-01-11
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location PLC
Disconnecting Means Location 23 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 33 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels Yes Yes Pass
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation No No Pass
Elevator Recall Yes Yes Pass
Elevator Shunt-Trip No No Pass
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
North Wing RTU East
Duct Detector Yes Yes Pass
North Wing RTU West
Duct Detector Yes Yes Pass
RTU South Return Duct Detector Yes Yes Pass
Top of shaft Heat Detector Yes Yes Pass
HANGER
NORTHWEST EXIT
Pull Station Yes Yes Pass
HANGER
SOUTHWEST EXIT
Pull Station Yes Yes Pass
NORTH EXIT Pull Station Yes Yes Pass
NORTHEAST
STAIRS EXIT
Pull Station Yes Yes Pass
NORTHEAST
STAIRS
Pull Station Yes Yes Pass
NORTHWEST BY
STAIRS
Pull Station Yes Yes Pass
ROOM 111
NORTHEAST EXIT
Pull Station Yes Yes Pass
SOUTHEAST STAIR
EXIT
Pull Station Yes Yes Pass
STAIRWELL
LANDING BY 210
Pull Station Yes Yes Pass
SOUTHWEST HALL
BY STAIRS
Pull Station Yes Yes Pass
SOUTHWEST STAIR
EXIT
Pull Station Yes Yes Pass
NORTHWEST
STAIR EXIT
Pull Station Yes Yes Pass
1ST FLOOR
ELEVATOR LOBBY
Photo Detector Yes Yes Pass
1ST FLOOR
NORTHEAST EXIT
Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
1ST FLOOR
NORTHWEST EXIT
Photo Detector Yes Yes Pass
1ST FLOOR
SOUTHWEST EXIT
Photo Detector Yes Yes Pass
2ND FLOOR
ELEVATOR LOBBY
Photo Detector Yes Yes Pass
ABOVE FACP Photo Detector Yes Yes Pass
HALL BY ROOM 201 Photo Detector Yes Yes Pass
HALL BY ROOM 202 Photo Detector Yes Yes Pass
HALL BY ROOM 203 Photo Detector Yes Yes Pass
HALL BY ROOM 205 Photo Detector Yes Yes Pass
HALL BY ROOM 207 Photo Detector Yes Yes Pass
HALL BY ROOM 210 Photo Detector Yes Yes Pass
HALL BY ROOM 212
NORTH
Photo Detector Yes Yes Pass
HALL BY ROOM 212
SOUTH
Photo Detector Yes Yes Pass
HALL BY ROOM 215 Photo Detector Yes Yes Pass
HALL BY ROOM 216 Photo Detector Yes Yes Pass
HALL BY ROOM 222 Photo Detector Yes Yes Pass
HALL BY ROOM 227 Photo Detector Yes Yes Pass
HALL BY BREAK
ROOM
Photo Detector Yes Yes Pass
HALL BY MENS
ROOM
Photo Detector Yes Yes Pass
HALL BY ORDERLY
ROOM
Photo Detector Yes Yes Pass
HALL BY WOMENS
ROOM
Photo Detector Yes Yes Pass
TOP STAIRS
NORTH EAST
Photo Detector Yes Yes Pass
TOP STAIRS
NORTH WEST
Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
TOP STAIRS
SOUTH EAST
Photo Detector Yes Yes Pass
TOP STAIRS
SOUTH WEST
Photo Detector Yes Yes Pass
1st Floor ELEVATOR
EQUIPMENT ROOM
Photo Detector Yes Yes Pass
1st Floor Elevator Equipment room
Heat Detector Yes Yes Pass
TOP OF SHAFT Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Northeast entry
Manufacturer: Simplex
Model: PSSA
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
Comments
Location: By FACP
Manufacturer: Simplex
Model: 4099 NAC (12AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.2 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
5-2020 Yes Yes 12/12 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/12
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4100U
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.1 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
5-2020 Yes Yes 12/33 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/33
Comments
Location: By FACP
Manufacturer: Simplex
Model: 4099 NAC (12AH)
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.2 27.2
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
5-2020 Yes Yes 12/12 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/12
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P1
None
Report of Inspection / Test Annual NFPA 72
2023-05-15 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com