Getz Bldg 16 2022.pdf

PDF 209 KB Posted

Attached to
183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Inspection and Testing Form for the fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The inspection was conducted on May 25, 2022 by Scott Calhoon of Getz Fire Equipment. The form details the testing and inspection of various fire alarm components, including manual pull stations, photo detectors, duct detectors, and smoke detectors, all of which passed the inspection. The report also includes information on the fire alarm control panel, power supply, and battery backup system, indicating they were functioning properly. No deficiencies were noted.

The related federal contract opportunity is Solicitation #W50S7U-24-B-0001 issued by the Department of the Army National Guard for the 183 CES Repair Base Fire Alarm System. This is an Invitation for Bids (IFB) to repair the base fire alarm system. The solicitation package includes the PWS, fire panel images, and an SF1705 form for a required site visit. Interested parties are instructed to read the solicitation and related documents thoroughly and comply with all requirements.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
Getz Bldg 25 2023.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P16 - Pass

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 6 6 0 6 0 6

Photo Detector 15 15 0 15 0 15

Duct Detector 2 2 0 2 0 2

Smoke Detector 2 2 0 2 0 2

Report of Inspection / Test Annual NFPA 72

2022-05-25 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Print Date: 2022-05-26

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2022 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-16 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4100ES

Software Revision 2.1 Date Last Serviced 2020-12-19

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location PLC

Disconnecting Means Location 2 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 50 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2022-05-25 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Print Date: 2022-05-26

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Lamps/LEDS Yes Yes Pass

Control Unit Yes Yes Pass

Power Extender Panels N/A N/A N/A

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Primary Power Supply Yes Yes Pass

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Visual Yes Yes Pass

Audible Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Elevator Recall N/A N/A N/A

Smoke Damper Operation N/A N/A N/A

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2022-05-25 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Print Date: 2022-05-26

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Addre ss

Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/ Fail

FACP ROOM Manual Pull Station Yes Yes Pass

EAST AHU ROOM Manual Pull Station Yes Yes Pass

MAIN ENTRY Manual Pull Station Yes Yes Pass

EXIT BY ROOM 132 Manual Pull Station Yes Yes Pass

EXIT HALL BY ROOM 123 Manual Pull Station Yes Yes Pass

EXIT BY ROOM 115 Manual Pull Station Yes Yes Pass

FRONT DESK Photo Detector Yes Yes Pass

HALL BY ROOM 123 EAST Photo Detector Yes Yes Pass

ROOM 123 Photo Detector Yes Yes Pass

ROOM 123 WEST Photo Detector Yes Yes Pass

BY ROOM 132 Photo Detector Yes Yes Pass

HALL BY ROOM 123 WEST Photo Detector Yes Yes Pass

HALL BY ROOM 106 Photo Detector Yes Yes Pass

ROOM 106 SOUTH Photo Detector Yes Yes Pass

ROOM 106 NORTH Photo Detector Yes Yes Pass

HALL BY ROOM 117 Photo Detector Yes Yes Pass

ROOM 117 Photo Detector Yes Yes Pass

ROOM 115 SOUTH Photo Detector Yes Yes Pass

ROOM 115 NORTH Photo Detector Yes Yes Pass

HALL BY ROOM 115 Photo Detector Yes Yes Pass

ROOM 105 Photo Detector Yes Yes Pass

AHU 1 RETURN Duct Detector Yes Yes Pass

AHU 1 SUPPLY Duct Detector Yes Yes Pass

ROOM 108 Smoke Detector Yes Yes Pass

ROOM 126 Smoke Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2022-05-25 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Print Date: 2022-05-26

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4100ES

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 27.2 27.3

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

11-2020 Yes Yes 12/55 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/55

Comments

Report of Inspection / Test Annual NFPA 72

2022-05-25 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Print Date: 2022-05-26

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473

Deficiencies - ES FA - FIRE ALARM P16

None

Report of Inspection / Test Annual NFPA 72

2022-05-25 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Print Date: 2022-05-26

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473

File details come from the government source that posted it. Updated .