Getz Bldg 16 2022.pdf
PDF 209 KB Posted
- Attached to
- 183 CES Repair Base Fire Alarm System
- Solicitation number
- W50S7U-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document is an Inspection and Testing Form for the fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The inspection was conducted on May 25, 2022 by Scott Calhoon of Getz Fire Equipment. The form details the testing and inspection of various fire alarm components, including manual pull stations, photo detectors, duct detectors, and smoke detectors, all of which passed the inspection. The report also includes information on the fire alarm control panel, power supply, and battery backup system, indicating they were functioning properly. No deficiencies were noted.
The related federal contract opportunity is Solicitation #W50S7U-24-B-0001 issued by the Department of the Army National Guard for the 183 CES Repair Base Fire Alarm System. This is an Invitation for Bids (IFB) to repair the base fire alarm system. The solicitation package includes the PWS, fire panel images, and an SF1705 form for a required site visit. Interested parties are instructed to read the solicitation and related documents thoroughly and comply with all requirements.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P16 - Pass
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 6 6 0 6 0 6
Photo Detector 15 15 0 15 0 15
Duct Detector 2 2 0 2 0 2
Smoke Detector 2 2 0 2 0 2
Report of Inspection / Test Annual NFPA 72
2022-05-25 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Print Date: 2022-05-26
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2022 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-16 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4100ES
Software Revision 2.1 Date Last Serviced 2020-12-19
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location PLC
Disconnecting Means Location 2 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 50 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2022-05-25 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Print Date: 2022-05-26
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Lamps/LEDS Yes Yes Pass
Control Unit Yes Yes Pass
Power Extender Panels N/A N/A N/A
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Primary Power Supply Yes Yes Pass
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Visual Yes Yes Pass
Audible Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Elevator Recall N/A N/A N/A
Smoke Damper Operation N/A N/A N/A
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2022-05-25 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Print Date: 2022-05-26
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Addre ss
Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/ Fail
FACP ROOM Manual Pull Station Yes Yes Pass
EAST AHU ROOM Manual Pull Station Yes Yes Pass
MAIN ENTRY Manual Pull Station Yes Yes Pass
EXIT BY ROOM 132 Manual Pull Station Yes Yes Pass
EXIT HALL BY ROOM 123 Manual Pull Station Yes Yes Pass
EXIT BY ROOM 115 Manual Pull Station Yes Yes Pass
FRONT DESK Photo Detector Yes Yes Pass
HALL BY ROOM 123 EAST Photo Detector Yes Yes Pass
ROOM 123 Photo Detector Yes Yes Pass
ROOM 123 WEST Photo Detector Yes Yes Pass
BY ROOM 132 Photo Detector Yes Yes Pass
HALL BY ROOM 123 WEST Photo Detector Yes Yes Pass
HALL BY ROOM 106 Photo Detector Yes Yes Pass
ROOM 106 SOUTH Photo Detector Yes Yes Pass
ROOM 106 NORTH Photo Detector Yes Yes Pass
HALL BY ROOM 117 Photo Detector Yes Yes Pass
ROOM 117 Photo Detector Yes Yes Pass
ROOM 115 SOUTH Photo Detector Yes Yes Pass
ROOM 115 NORTH Photo Detector Yes Yes Pass
HALL BY ROOM 115 Photo Detector Yes Yes Pass
ROOM 105 Photo Detector Yes Yes Pass
AHU 1 RETURN Duct Detector Yes Yes Pass
AHU 1 SUPPLY Duct Detector Yes Yes Pass
ROOM 108 Smoke Detector Yes Yes Pass
ROOM 126 Smoke Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2022-05-25 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Print Date: 2022-05-26
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4100ES
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 27.2 27.3
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
11-2020 Yes Yes 12/55 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/55
Comments
Report of Inspection / Test Annual NFPA 72
2022-05-25 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Print Date: 2022-05-26
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473
Deficiencies - ES FA - FIRE ALARM P16
None
Report of Inspection / Test Annual NFPA 72
2022-05-25 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Print Date: 2022-05-26
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473