Getz Bldg 25 2023.pdf

PDF 328 KB Posted

Attached to
183 CES Repair Base Fire Alarm System
Solicitation number
W50S7U-24-B-0001
Issued by

About this file

This document is an Annual NFPA 72 Inspection and Test Report for a fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The report details the results of the inspection, testing, and maintenance activities performed on the Simplex Model 4100ES fire alarm control panel and associated devices, including manual pull stations, smoke detectors, duct detectors, control modules, and notification appliances. The report indicates that the majority of the system components passed the visual and functional tests, with the exception of the need to replace the batteries for the main fire alarm control panel. The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineering Squadron (183 CES) location, as detailed in Solicitation# WS0S7U-24-B-0001 issued by the Department of the Army National Guard.

View the file

Other files

File Type Posted
Bid Abstract W50S7U-24-B-0001.pdf PDF
W50S7U-24-B-0001-0003 Amenndment 3- CES Repair Base Fire Alarm System- Wage Dec.pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
W50S7U-24-B-0001-0002 Amendment 2- CES Repair Base Fire Alarm System - Time Ext..pdf PDF
Old Fire Alarm PDF Plans.zip ZIP file
Getz Bldg 119 2023.pdf PDF
Getz Bldg 15 2023.pdf PDF
RFI 1 CES Repair Base Fire Alarm.pdf PDF
Getz Bldg 18 2023.pdf PDF
Getz Bldg 17 2023.pdf PDF
Getz Bldg 16 2022.pdf PDF
Getz Bldg 50 2023.pdf PDF
W50S7U-24-B-0001-0001 Amenndment 1- CES Repair Base Fire Alarm System.pdf PDF
FIRE PANEL Bldgs 17.19.237.docx DOCX document
Getz Bldg 37 2023.pdf PDF
Getz Bldg 26 2023.pdf PDF
Getz Bldg 152 2023.pdf PDF
Getz Bldg 20 2023.pdf PDF
Getz Bldg 36 2023.pdf PDF
Getz Bldg 8 2023.pdf PDF
Getz Bldg 48 2023.pdf PDF
Getz Bldg 40 2023.pdf PDF
Getz Bldg 143 2023.pdf PDF
Getz Bldg 1 2023.pdf PDF
Gtez Bldg 46 2023.pdf PDF
Getz Bldg 154 2023.pdf PDF
Getz Bldg 23 2023.pdf PDF
SBSA Pre-Bid Slides - CES Repair Base Fire Alarm.pdf PDF
Site Visit Sign In - Repair Base Fire Alarm System 09 Apr 24.pdf PDF
Site Visit Minutes Repair Base Fire Alarm - 09 Apr 24.pdf PDF
SF 1705 Consent for Background Check.pdf PDF
FIRE PANEL Images.pdf PDF
W50S7U-24-B-0001 CES Repair Base Fire Alarm System.pdf PDF
PWS Services - DCFT 1720085.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Form - ES FA - FIRE ALARM P25 - Pass

Devices Tested this Inspection Pass Fail Tested

YTD

Not Tested

YTD

Total

Manual Pull Station 20 20 0 20 0 20

Duct Detector 4 4 0 4 0 4

Control Module 2 2 0 2 0 2

Remote Relay 2 2 0 2 0 2

Photo Detector 36 36 0 36 0 36

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Copyright 2023 Inspect Point

Monitoring Entity

Contact Name Building P-25 Telephone 217-757-1369

Reference Number P-25 Type Transmission IP / Radio

System Type

Control Unit Manufacturer Simplex Model Number 4100ES

Software Revision 2.01 Date Last Serviced 2020-12-18

Last Date and Software or Configuration was Revised

2020-11-20

Power Supply

Main Nominal Voltage 120VAC Main Nominal Amps 20

Overcurrent Protection Breaker Panel Board Location RIPA

Disconnecting Means Location 5 Secondary Standby Sealed Lead-Acid

Storage Battery: Amp Hour Rating 50 Calculated Capacity to operate system (Hours)

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time

Building Occupants

SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments

Control Unit Yes Yes Pass

Lamps/LEDS Yes Yes Pass

Primary Power Supply Yes Yes Pass

Disconnect Switches Yes Yes Pass

Remote Annunciator Yes Yes Pass

Power Extender Panels N/A N/A N/A

NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments

Audible Yes Yes Pass

Visual Yes Yes Pass

AUXILIARY FUNCTIONS/INTERFACE

EQUIPMENT/SPECIAL HAZARDS

Visual Functional Pass/Fail Comments

Fan Shutdown Yes Yes Pass

Smoke Damper Operation N/A N/A N/A

Elevator Recall Yes Yes Pass

Elevator Shunt-Trip N/A N/A N/A

SUPERVISING STATION MONITORING Yes No N/A Who Time

Alarm Signal

Trouble Signals

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time

Building Occupants

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

HALL BY ROOM

116B

Photo Detector Yes Yes Pass

TOP OF SHAFT Photo Detector Yes Yes Pass

2ND FLOOR

NORTH STIRWELL

Manual Pull Station Yes Yes Pass

HALL BY ROOM

120A

Photo Detector Yes Yes Pass

2ND FLOOR HALL

BY WOMENS

ROOM

Photo Detector Yes Yes Pass

2ND FLOOR WEST

OF ELERVATOR

Photo Detector Yes Yes Pass

HALL BY ROOM

116A

Photo Detector Yes Yes Pass

2ND FLOOR HIGH

AREA EAST

Photo Detector Yes Yes Pass

EXIT BY 108 Manual Pull Station Yes Yes Pass

AHU Remote Relay Yes Yes Pass

2ND FLOOR

STAIRWELL BY

MENS RM

Manual Pull Station Yes Yes Pass

2ND FLOOR HALL

BY ROOM 204

Photo Detector Yes Yes Pass

SOUTH WEST

STAIRWELL

Photo Detector Yes Yes Pass

ERU-1 SUPPLY Duct Detector Yes Yes Pass

NORTH STAIRWELL Photo Detector Yes Yes Pass

2ND FLOOR HALL

BY MENS ROOM

Photo Detector Yes Yes Pass

MAIN ENTRY Manual Pull Station Yes Yes Pass

2ND FLOOR HALL

WEST OF HIGH

AREA

Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Setting

Measured Setting

Visual Functional Pass/Fail

ELEVATOR Control Module Yes Yes Pass

HALL BY ROOM 112 Manual Pull Station Yes Yes Pass

EXIT BY ROOM 108 Photo Detector Yes Yes Pass

EXIT BY ROOM

120B

Manual Pull Station Yes Yes Pass

SUPPLY BAY EXIT Manual Pull Station Yes Yes Pass

2ND FLOOR

SOUTH STAIRWELL

FRONT

Manual Pull Station Yes Yes Pass

SOUTHEAST

STAIRWELL

Photo Detector Yes Yes Pass

EXIT BY 120A Manual Pull Station Yes Yes Pass

1ST FLOOR

ELEVATOR EQUIP.

RM

Photo Detector Yes Yes Pass

2ND FLOOR HIGH

AREA WEST

Photo Detector Yes Yes Pass

BOILER ROOM Manual Pull Station Yes Yes Pass

1ST FLOOR

ELEVATOR LOBBY

Photo Detector Yes Yes Pass

2ND FLOOR

ELEVATOR LOBBY

Photo Detector Yes Yes Pass

ERU-1 RETURN Duct Detector Yes Yes Pass

1ST FLOOR

ELEVATOR EQUIP.

RM

Photo Detector Yes Yes Pass

HALL BY ROOM 112 Manual Pull Station Yes Yes Pass

2ND FLOOR HALL

BY ROOM 204

Photo Detector Yes Yes Pass

NORTH STAIRWELL Photo Detector Yes Yes Pass

MAIN ENTRY Manual Pull Station Yes Yes Pass

EXIT BY ROOM 108 Photo Detector Yes Yes Pass

AHU Remote Relay Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

HALL BY ROOM

120A

Photo Detector Yes Yes Pass

1ST FLOOR

ELEVATOR LOBBY

Photo Detector Yes Yes Pass

2ND FLOOR

ELEVATOR LOBBY

Photo Detector Yes Yes Pass

HALL BY ROOM

116B

Photo Detector Yes Yes Pass

EXIT BY 120A Manual Pull Station Yes Yes Pass

EXIT BY 108 Manual Pull Station Yes Yes Pass

ERU-1 RETURN Duct Detector Yes Yes Pass

2ND FLOOR HIGH

AREA WEST

Photo Detector Yes Yes Pass

SOUTHEAST

STAIRWELL

Photo Detector Yes Yes Pass

TOP OF SHAFT Photo Detector Yes Yes Pass

2ND FLOOR HALL

BY WOMENS

ROOM

Photo Detector Yes Yes Pass

ERU-1 SUPPLY Duct Detector Yes Yes Pass

BOILER ROOM Manual Pull Station Yes Yes Pass

SOUTH WEST

STAIRWELL

Photo Detector Yes Yes Pass

HALL BY ROOM

116A

Photo Detector Yes Yes Pass

2ND FLOOR WEST

OF ELERVATOR

Photo Detector Yes Yes Pass

2ND FLOOR HALL

BY MENS ROOM

Photo Detector Yes Yes Pass

2ND FLOOR

SOUTH STAIRWELL

FRONT

Manual Pull Station Yes Yes Pass

2ND FLOOR HIGH

AREA EAST

Photo Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Measured Setting

Visual Functional Pass/Fail

2ND FLOOR

STAIRWELL BY

MENS RM

Manual Pull Station Yes Yes Pass

2ND FLOOR HALL

WEST OF HIGH

AREA

Photo Detector Yes Yes Pass

ELEVATOR Control Module Yes Yes Pass

SUPPLY BAY EXIT Manual Pull Station Yes Yes Pass

2ND FLOOR

NORTH STIRWELL

Manual Pull Station Yes Yes Pass

EXIT BY ROOM

120B

Manual Pull Station Yes Yes Pass

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Control Panel and Battery Readings

Location: Main FACP

Manufacturer: Simplex

Model: 4100ES

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 24 100 26.3 26.4

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

5-2019 Yes Yes 12/33 Yes

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12/33

Comments

Location: Boiler room

Manufacturer: Simplex

Model: 4100ES

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

Comments

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

Deficiencies - ES FA - FIRE ALARM P25

Deficiency #1

System Name: ES FA - FIRE ALARM P25 4100ES - Main FACP Battery Pass/Fail: Fail Secondary Battery Pass/Fail:

Notes: Batteries need replaced

Report of Inspection / Test Annual NFPA 72

2023-05-16 Property

DEPT OF MILITARY AFFAIRS

54100-01

3101 DAVID JONES PARKWAY

SPRINGFIELD IL 62702

TREVOR HOWARD (217) 891-1501

Conducted by: Scott Calhoon

Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com

File details come from the government source that posted it. Updated .