This document is an Annual NFPA 72 Inspection and Test Report for a fire alarm system at the Department of Military Affairs facility located at 3101 David Jones Parkway in Springfield, Illinois. The report details the results of the inspection, testing, and maintenance activities performed on the Simplex Model 4100ES fire alarm control panel and associated devices, including manual pull stations, smoke detectors, duct detectors, control modules, and notification appliances. The report indicates that the majority of the system components passed the visual and functional tests, with the exception of the need to replace the batteries for the main fire alarm control panel. The related federal contract opportunity is for the repair of the base fire alarm system at the 183rd Civil Engineering Squadron (183 CES) location, as detailed in Solicitation# WS0S7U-24-B-0001 issued by the Department of the Army National Guard.
View the file
Other files
Show all 34
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Form - ES FA - FIRE ALARM P25 - Pass
Devices Tested this Inspection Pass Fail Tested
YTD
Not Tested
YTD
Total
Manual Pull Station 20 20 0 20 0 20
Duct Detector 4 4 0 4 0 4
Control Module 2 2 0 2 0 2
Remote Relay 2 2 0 2 0 2
Photo Detector 36 36 0 36 0 36
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Copyright 2023 Inspect Point
Monitoring Entity
Contact Name Building P-25 Telephone 217-757-1369
Reference Number P-25 Type Transmission IP / Radio
System Type
Control Unit Manufacturer Simplex Model Number 4100ES
Software Revision 2.01 Date Last Serviced 2020-12-18
Last Date and Software or Configuration was Revised
2020-11-20
Power Supply
Main Nominal Voltage 120VAC Main Nominal Amps 20
Overcurrent Protection Breaker Panel Board Location RIPA
Disconnecting Means Location 5 Secondary Standby Sealed Lead-Acid
Storage Battery: Amp Hour Rating 50 Calculated Capacity to operate system (Hours)
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Building Occupants
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fail Comments
Control Unit Yes Yes Pass
Lamps/LEDS Yes Yes Pass
Primary Power Supply Yes Yes Pass
Disconnect Switches Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels N/A N/A N/A
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
AUXILIARY FUNCTIONS/INTERFACE
EQUIPMENT/SPECIAL HAZARDS
Visual Functional Pass/Fail Comments
Fan Shutdown Yes Yes Pass
Smoke Damper Operation N/A N/A N/A
Elevator Recall Yes Yes Pass
Elevator Shunt-Trip N/A N/A N/A
SUPERVISING STATION MONITORING Yes No N/A Who Time
Alarm Signal
Trouble Signals
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Building Occupants
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
HALL BY ROOM
116B
Photo Detector Yes Yes Pass
TOP OF SHAFT Photo Detector Yes Yes Pass
2ND FLOOR
NORTH STIRWELL
Manual Pull Station Yes Yes Pass
HALL BY ROOM
120A
Photo Detector Yes Yes Pass
2ND FLOOR HALL
BY WOMENS
ROOM
Photo Detector Yes Yes Pass
2ND FLOOR WEST
OF ELERVATOR
Photo Detector Yes Yes Pass
HALL BY ROOM
116A
Photo Detector Yes Yes Pass
2ND FLOOR HIGH
AREA EAST
Photo Detector Yes Yes Pass
EXIT BY 108 Manual Pull Station Yes Yes Pass
AHU Remote Relay Yes Yes Pass
2ND FLOOR
STAIRWELL BY
MENS RM
Manual Pull Station Yes Yes Pass
2ND FLOOR HALL
BY ROOM 204
Photo Detector Yes Yes Pass
SOUTH WEST
STAIRWELL
Photo Detector Yes Yes Pass
ERU-1 SUPPLY Duct Detector Yes Yes Pass
NORTH STAIRWELL Photo Detector Yes Yes Pass
2ND FLOOR HALL
BY MENS ROOM
Photo Detector Yes Yes Pass
MAIN ENTRY Manual Pull Station Yes Yes Pass
2ND FLOOR HALL
WEST OF HIGH
AREA
Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Setting
Measured Setting
Visual Functional Pass/Fail
ELEVATOR Control Module Yes Yes Pass
HALL BY ROOM 112 Manual Pull Station Yes Yes Pass
EXIT BY ROOM 108 Photo Detector Yes Yes Pass
EXIT BY ROOM
120B
Manual Pull Station Yes Yes Pass
SUPPLY BAY EXIT Manual Pull Station Yes Yes Pass
2ND FLOOR
SOUTH STAIRWELL
FRONT
Manual Pull Station Yes Yes Pass
SOUTHEAST
STAIRWELL
Photo Detector Yes Yes Pass
EXIT BY 120A Manual Pull Station Yes Yes Pass
1ST FLOOR
ELEVATOR EQUIP.
RM
Photo Detector Yes Yes Pass
2ND FLOOR HIGH
AREA WEST
Photo Detector Yes Yes Pass
BOILER ROOM Manual Pull Station Yes Yes Pass
1ST FLOOR
ELEVATOR LOBBY
Photo Detector Yes Yes Pass
2ND FLOOR
ELEVATOR LOBBY
Photo Detector Yes Yes Pass
ERU-1 RETURN Duct Detector Yes Yes Pass
1ST FLOOR
ELEVATOR EQUIP.
RM
Photo Detector Yes Yes Pass
HALL BY ROOM 112 Manual Pull Station Yes Yes Pass
2ND FLOOR HALL
BY ROOM 204
Photo Detector Yes Yes Pass
NORTH STAIRWELL Photo Detector Yes Yes Pass
MAIN ENTRY Manual Pull Station Yes Yes Pass
EXIT BY ROOM 108 Photo Detector Yes Yes Pass
AHU Remote Relay Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
HALL BY ROOM
120A
Photo Detector Yes Yes Pass
1ST FLOOR
ELEVATOR LOBBY
Photo Detector Yes Yes Pass
2ND FLOOR
ELEVATOR LOBBY
Photo Detector Yes Yes Pass
HALL BY ROOM
116B
Photo Detector Yes Yes Pass
EXIT BY 120A Manual Pull Station Yes Yes Pass
EXIT BY 108 Manual Pull Station Yes Yes Pass
ERU-1 RETURN Duct Detector Yes Yes Pass
2ND FLOOR HIGH
AREA WEST
Photo Detector Yes Yes Pass
SOUTHEAST
STAIRWELL
Photo Detector Yes Yes Pass
TOP OF SHAFT Photo Detector Yes Yes Pass
2ND FLOOR HALL
BY WOMENS
ROOM
Photo Detector Yes Yes Pass
ERU-1 SUPPLY Duct Detector Yes Yes Pass
BOILER ROOM Manual Pull Station Yes Yes Pass
SOUTH WEST
STAIRWELL
Photo Detector Yes Yes Pass
HALL BY ROOM
116A
Photo Detector Yes Yes Pass
2ND FLOOR WEST
OF ELERVATOR
Photo Detector Yes Yes Pass
2ND FLOOR HALL
BY MENS ROOM
Photo Detector Yes Yes Pass
2ND FLOOR
SOUTH STAIRWELL
FRONT
Manual Pull Station Yes Yes Pass
2ND FLOOR HIGH
AREA EAST
Photo Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Measured Setting
Visual Functional Pass/Fail
2ND FLOOR
STAIRWELL BY
MENS RM
Manual Pull Station Yes Yes Pass
2ND FLOOR HALL
WEST OF HIGH
AREA
Photo Detector Yes Yes Pass
ELEVATOR Control Module Yes Yes Pass
SUPPLY BAY EXIT Manual Pull Station Yes Yes Pass
2ND FLOOR
NORTH STIRWELL
Manual Pull Station Yes Yes Pass
EXIT BY ROOM
120B
Manual Pull Station Yes Yes Pass
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Control Panel and Battery Readings
Location: Main FACP
Manufacturer: Simplex
Model: 4100ES
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 24 100 26.3 26.4
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
5-2019 Yes Yes 12/33 Yes
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12/33
Comments
Location: Boiler room
Manufacturer: Simplex
Model: 4100ES
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
Comments
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
Deficiencies - ES FA - FIRE ALARM P25
Deficiency #1
System Name: ES FA - FIRE ALARM P25 4100ES - Main FACP Battery Pass/Fail: Fail Secondary Battery Pass/Fail:
Notes: Batteries need replaced
Report of Inspection / Test Annual NFPA 72
2023-05-16 Property
DEPT OF MILITARY AFFAIRS
54100-01
3101 DAVID JONES PARKWAY
SPRINGFIELD IL 62702
TREVOR HOWARD (217) 891-1501
Conducted by: Scott Calhoon
Getz Fire Equipment 1615 S.W Adams Peoria IL 61602 800-747-3473 Getz@GetzFire.com
File details come from the government source that posted it. Updated .