Unit Heaters Gas Oil Fired.doc
DOC document 33 KB Posted
- Solicitation number
- BPM059074
- Issued by
- Queen Anne's County, Maryland
About this file
This is a preventive maintenance checklist for unit heaters (gas/oil fired) related to a one-year HVAC repair contract opportunity with the Maryland State Housing Authority (SHA) at the Centreville facility on the Eastern Shore.
The checklist outlines two categories of maintenance service requirements: quarterly tasks and seasonal tasks. Quarterly maintenance includes checking fan belts for tension, alignment, and wear; inspecting access panels; verifying thermostat and sensor accuracy; inspecting for vibration and unusual noises; checking bird screens and outside air hoods; inspecting for fuel leaks; and changing oil filters. Seasonal maintenance encompasses verifying the sequence of operation, tuning burners and replacing electrodes/nozzles/seals/gaskets, replacing oil/fuel filters and nozzles, verifying safety and auxiliary controls, cleaning strainers, adjusting regulators and pressure-reducing valves, testing interlock controls, verifying actuator operation, checking flue temperatures and inspecting for leaks/cracks, inspecting and tightening electrical connections, lubricating bearings/fans/motors, cleaning intake screens, inspecting fan wheels and blades, and inspecting structural equipment supports for corrosion and damage.
The document serves as a performance standard and service specification for contractors bidding on the SHA Centreville HVAC repair and preventive maintenance contract. No specific pricing information, set-asides, award dates, or response deadlines are included in this checklist document. Contractors should reference the primary solicitation for complete contract terms, pricing requirements, and submission details.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNIT HEATERS-GAS/OIL FIRED CHECKLIST
Type of Service:
Date Of Service:
Unit Being Serviced:
Facility:
Service Technician:
QUARTERLY
FORMCHECKBOX
Check Fan Belts for tension, alignment and wear. Adjust/Replace as needed.
FORMCHECKBOX
Check access panels for tight fit. Replace screws, handles etc. as needed. Oil hinges if applicable.
FORMCHECKBOX
Verify Thermostat/sensors indication of room temperature is actual room temperature.
FORMCHECKBOX
Inspect for vibration and unusual noises.
FORMCHECKBOX
Check bird screens and outside air hoods for damage, blockage and cleanliness. Repair/Clean as needed.
FORMCHECKBOX
Inspect for fuel leaks.
FORMCHECKBOX
Change oil filter(s).
SEASONAL
FORMCHECKBOX
Verify Sequence of Operation.
FORMCHECKBOX
Tune burners. Replace Electrodes, Nozzles, seals, gaskets etc.
FORMCHECKBOX
Replace Oil/Fuel Filters and nozzles.
FORMCHECKBOX
Verify functioning of all safety and auxiliary controls.
FORMCHECKBOX
Clean strainers. Adjust regulators and pressure reducing valves. Operate shutoff valves.
FORMCHECKBOX
Test and verify interlock controls.
FORMCHECKBOX
Verify proper operation of all actuators.
FORMCHECKBOX
Check flue temperatures. Inspect flues for leaks and cracks. Drain flues of condensation and dirt.
FORMCHECKBOX
Inspect and Tighten electric connections. Clean contacts and verify proper operation.
FORMCHECKBOX
Lubricate Bearings, fans and motors.
FORMCHECKBOX
Clean intake screen on motors.
FORMCHECKBOX
Inspect Fan Wheel/Blades for free rotation, cracks and alignment.
FORMCHECKBOX
Inspect all structural equipment supports for corrosion and damage. Repair/Replace as required.