Furnace.doc

DOC document 41 KB Posted

Attached to
QAHVAC28SB 1-year HVAC repair contract for SHA Centreville (Eastern Shore)
Solicitation number
BPM059074
Issued by
Queen Anne's County, Maryland

About this file

This is a Gas/Oil Fired Furnace Checklist document related to a one-year HVAC repair and preventive maintenance contract for SHA Centreville on the Eastern Shore in Maryland. The document outlines comprehensive service requirements for gas and oil-fired furnace systems, divided into quarterly and seasonal maintenance tasks. Quarterly services include replacing air filters, checking fan belts for tension and alignment, inspecting damper linkage, verifying access panel integrity, identifying vibration and unusual noises, checking for fuel leaks, inspecting bird screens and outside air dampers, and examining flexible duct connections and coils. Seasonal services encompass changing oil filters and nozzles, verifying variable frequency drive operation, tuning burners with electrode and nozzle adjustments, checking pump pressure, measuring draft and combustion parameters including CO2, O2, stack temperature, smoke density, and carbon monoxide levels, verifying safety controls, testing interlock controls, inspecting flues for leaks, cleaning coils and heat exchangers, and lubricating bearings, fans, motors, and dampers.

The checklist serves as the operational framework for the HVAC service contract, establishing specific inspection, maintenance, and repair protocols that service technicians must complete and document during each service visit. The document indicates that maintenance activities should be tracked by facility, unit serviced, service date, and technician name, with notation of all vacuum and pressure readings and supply air temperature measurements required in service logs. This checklist format ensures standardized service delivery and compliance with manufacturer specifications across the contracted HVAC systems at the SHA Centreville facility.

View the file

Other files

File Type Posted
Oil Transfer Pump.doc DOC document
Exhaust Fan.doc DOC document
Attachment-L.-Reference-Check.pdf PDF
Unit Heaters Gas Oil Fired.doc DOC document
QAHVAC28SB IFB.pdf PDF
Unit Heaters Electric.doc DOC document
Attachment-A.-Bid-Proposal-Affidavit (required).pdf PDF
Heat pump.doc DOC document
How to Respond to eMMA Solicitations (for new vendors).pdf PDF
Centrifugal Pump.doc DOC document
Cabinet Heaters Electric.doc DOC document
VAV Box with Hot Water Heat.doc DOC document
Rooftop Unit.doc DOC document
Infrared Heaters Gas Oil Fired.doc DOC document
Appexdix 2 - Price form instruction (for new vendors).pdf PDF
Exhibit 2 - Sample Contract revision 2024 Small Procurement (no action needed).pdf PDF
HVAC- Centreville, Stevensville - Systems Information.xlsx XLSX spreadsheet
Cast Iron Boiler.doc DOC document
Unit Heaters Hot Water.doc DOC document
QAHVAC28SB - Price form.xlsx XLSX spreadsheet
Attachment-1.-No-Bid_Proposal-Notice_Vendor-Feedback-Form-1-1 (optional).pdf PDF
Attachment-I.-Conflict-of-Interest-Affidavit.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GAS/OIL FIRED FURNACE CHECKLIST

Type of Service:

Date Of Service:

Unit Being Serviced:

Facility:

Service Technician:

QUARTERLY

FORMCHECKBOX

Replace air filters

FORMCHECKBOX

Check Fan Belts for tension, alignment and wear. Adjust/Replace as needed.

FORMCHECKBOX

Check Damper Linkage/Movement. Adjust and Lubricate as needed.

FORMCHECKBOX

Check access panels for tight fit. Replace screws, handles etc. as needed. Oil hinges if applicable.

FORMCHECKBOX

Inspect for vibration and unusual noises.

FORMCHECKBOX

Inspect for fuel leaks.

FORMCHECKBOX

Check bird screens and outside air dampers for damage, blockage and cleanliness.

FORMCHECKBOX

Repair/clean as needed. Inspect flexible duct connections for damage and leakage.

FORMCHECKBOX

Repair/Replace as needed. Inspect coils for damage, blockage, dirt etc. Clean as needed.

SEASONAL

FORMCHECKBOX

Change oil filter(s) and nozzles.

FORMCHECKBOX

Verify Variable Frequency Drive operation.

FORMCHECKBOX

Tune burners. Check/Adjust/Replace electrodes, nozzles, seals, gaskets etc.

FORMCHECKBOX

Check pump pressure and adjust to manufacturer’s specs, Clean burner air tube, fan housing and blower wheel. Seal any air leaks into combustion chamber.

FORMCHECKBOX

Check fuel train. Repair/Replace as required.

FORMCHECKBOX

Measure draft, CO2 or O2, net stack temperature, smoke density and carbon monoxide.

FORMCHECKBOX

Verify functioning of all safety and auxiliary controls.

FORMCHECKBOX

Check gages. Replace as needed. Note all vacuum and pressure readings in logs.

FORMCHECKBOX

Measure and note supply air temperatures during normal operation.

FORMCHECKBOX

Test and verify interlock controls.

FORMCHECKBOX

Verify proper operation of all actuators.

FORMCHECKBOX

Inspect flues for leaks and cracks. Drain/Clean flues of condensation and dirt. Check the barometric damper.

FORMCHECKBOX

wash coils with a coil cleaner and flush.

FORMCHECKBOX

Clean secondary heat exchanger and combustion area. Clean transformer bushings, springs and cad cell surface.

GAS/OIL FIRED FURNACE CHECKLIST

SEASONAL (cont.)

FORMCHECKBOX

Check safety and auxiliary controls.

FORMCHECKBOX

Verify Sequence of operation

FORMCHECKBOX

Inspect and tighten electric connections. Clean contacts and verify proper operation.

FORMCHECKBOX

Lubricate bearings, fans and motors.

FORMCHECKBOX

Lubricate dampers. Adjust damper linkage.

FORMCHECKBOX

Clean intake screen on motors.

FORMCHECKBOX

Inspect fan wheel/blades for free rotation, cracks and alignment.

FORMCHECKBOX

Inspect all structural equipment supports for corrosion and damage.