HVAC- Centreville, Stevensville - Systems Information.xlsx
XLSX spreadsheet 44 KB Posted
- Solicitation number
- BPM059074
- Issued by
- Queen Anne's County, Maryland
About this file
This document is an HVAC Systems Information inventory prepared by the Maryland State Highway Administration (SHA) for its Centreville maintenance facility on the Eastern Shore, in support of a one-year HVAC repair and preventive maintenance contract solicitation (QAHVAC28SB). The inventory catalogues comprehensive equipment specifications across multiple SHA-owned facilities, including the Centreville Maintenance Facility, Bay Country Welcome Center, Kent Narrows Bridge House, and Stevensville Maintenance Facility. The equipment list includes rooftop packaged air conditioning units (AC-1 and AC-2), heating and ventilating units (HV-1 through HV-3), fifteen duct and unit-mounted hydronic heating coils (HC-1 through HC-15) with varying capacities, two boilers with combined input of 1,077 MBH, seven in-line and duplex centrifugal pumps, eight centrifugal and propeller exhaust fans, five hot water unit heaters, zone dampers, infrared heaters, gas-fired furnaces, mini-split heat pump systems, and associated diffusers, registers, grilles, and control systems. The document provides original design specifications and nameplate data for each component, identifying manufacturers such as York, Customair, Cleaver Brooks, B&G, ILG Industries, Modine, Carrier, and Daikin across all facility locations.
The document does not specify contract pricing terms, set-asides, incumbent contractors, funding amounts, or response deadlines within the equipment list itself. However, the inventory serves as the technical baseline for the SHA's one-year HVAC repair and preventive maintenance contract, enabling qualified contractors to assess the scope and complexity of required services across four geographically dispersed Eastern Shore facilities. The detailed equipment data, including nameplate specifications and current design parameters, allows prospective bidders to develop accurate labor and parts estimates for repair and maintenance services throughout the contract period.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Oil Transfer Pump.doc | DOC document | |
| Exhaust Fan.doc | DOC document | |
| Attachment-L.-Reference-Check.pdf | ||
| Unit Heaters Gas Oil Fired.doc | DOC document | |
| QAHVAC28SB IFB.pdf | ||
| Unit Heaters Electric.doc | DOC document | |
| Attachment-A.-Bid-Proposal-Affidavit (required).pdf | ||
| Heat pump.doc | DOC document | |
| How to Respond to eMMA Solicitations (for new vendors).pdf | ||
| Centrifugal Pump.doc | DOC document | |
| Cabinet Heaters Electric.doc | DOC document | |
| VAV Box with Hot Water Heat.doc | DOC document | |
| Rooftop Unit.doc | DOC document | |
| Furnace.doc | DOC document | |
| Infrared Heaters Gas Oil Fired.doc | DOC document | |
| Appexdix 2 - Price form instruction (for new vendors).pdf | ||
| Exhibit 2 - Sample Contract revision 2024 Small Procurement (no action needed).pdf | ||
| Cast Iron Boiler.doc | DOC document | |
| Unit Heaters Hot Water.doc | DOC document | |
| QAHVAC28SB - Price form.xlsx | XLSX spreadsheet | |
| Attachment-1.-No-Bid_Proposal-Notice_Vendor-Feedback-Form-1-1 (optional).pdf | ||
| Attachment-I.-Conflict-of-Interest-Affidavit.pdf |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Summary
| Centreville | Rooftop Unit | AC-1 | Packaged Rooftop cooling only | York | AV15C0BQ4E1AAA42A2 | Office | 460-3-60 | MAA | |||||
| Centreville | Rooftop Unit | AC-2 | Packaged Rooftop cooling only | York | DH090C00N4AAAA1A | Roof-Locker Area | 93.6 MBH Tot, 68.4 MBH Sens. | 2400 cfm | MAA | ||||
| Centreville | Heating & Ventilating Unit | HV-1 | Horizontal Cabinet Unit clg mtd | Customair | AQ-UN1 01 048 ATL 12-12R | Old Shop | 3000 cfm | MAA | |||||
| Centreville | Heating & Ventilating Unit | HV-2 | Horizontal Cabinet Unit clg mtd | Customair | AQ-UN1 01 048 ATL 12-9 | New Shop | 4500 cfm | MAA | |||||
| Centreville | Heating & Ventilating Unit | HV-3 | In-line Cabinet Ventilator | Breidert | FFC250S | Parts Rm. Clg. Mtd. | 200 cfm | MAA | |||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-1 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Assembly | 9.4 mbh | 310 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-2 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Assembly | 9.4 mbh | 310 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-3 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Kitchen | 4.4 mbh | 145 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-4 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Lunch Room | 7.8 mbh | 260 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-5 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Chief Mechanic | 1.7 mbh | 60 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-6 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Sec Overnight | 2.0 mbh | 70 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-7 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Reception | 3.9 mbh | 130 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-8 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | RME | 7.2 mbh | 240 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-9 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | ARME | 3.6 mbh | 120 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-10 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Team Leader | 804 mbh | 280 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-11 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | File Room | 1.6 mbh | 55 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-12 | Hydronic Heating Coil Unit Mtd | AAON Coil Prod. | Unknown | HV-3 Parts Rm. | 12.3 mbh | 200 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-13 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Inventory | 95 mbh | 2375 cfm | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-14 | Hydronic Heating Coil Unit Mtd | Heatcraft | Unknown | HV-1 Old Shop | 3000 cfm | 200 mbh | MAA | ||||
| Centreville | Duct/Unit Mounted Hydronic Heating Coil | HC-15 | Hydronic Heating Coil Unit Mtd | Heatcraft | Unknown | HV-2 New Shop | 4500 cfm | 300 mbh | MAA | ||||
| Centreville | Boiler | B-1 | Hot Water, Firetube, Oil Fired | Cleaver Brooks | P143-20 | Mechanical Room | 837 mbh input, 670 mbh output | MAA | |||||
| Centreville | Boiler | B-2 | Hot Water, Cast Iron, Oil Fired | Clean Burn | CB-240-BLR (5 section) | Mechanical Room | 240 mbh input | MAA | |||||
| Centreville | Pump | BP-1 | In-line Centrifugal | B&G | 60 2x5.25 w/ 4.625 BF imp. | Mechanical Room | MAA | ||||||
| Centreville | Pump | BP-2 | In-line Centrifugal | B&G | 60 1x5.25 w/ 4.62 BF imp. | Mechanical Room | MAA | ||||||
| Centreville | Pump | HWP-1 | In-line Centrifugal | B&G | 60 2x5.25 w/ 4.875 BF imp. | Mechanical Room | MAA | ||||||
| Centreville | Pump | HWP-2 | In-line Centrifugal | B&G | 60 2x5.25 w/ 4.875 BF imp. | Mechanical Room | MAA | ||||||
| Centreville | Pump | HWP-3 | In-line Centrifugal | B&G | NRF 22 | Mechanical Room | MAA | ||||||
| Centreville | Pump | HWP-4 | In-line Centrifugal | B&G | NRF 22 | Mechanical Room | MAA | ||||||
| Centreville | Pump | HWP-5 | In-line Centrifugal | B&G | NRF 22 | Mechanical Room | MAA | ||||||
| Centreville | Pump | FOP-1 | Duplex Fuel Oil Pumps | Webester | SPM-15-1 | Mechanical Room | MAA | ||||||
| Centreville | Pump | WOP-1 | Duplex Waste Oil Pumps | Webester | SPM-15-1 | Mechanical Room | MAA | ||||||
| Centreville | Fan | EF-1 | Rooftop Centrifugal | Old Shop Roof | 3000 cfm | MAA | |||||||
| Centreville | Fan | EF-2 | Rooftop Centrifugal | ILG Industries | GRBCA20LD8363 | New Shop Roof | 4500 cfm | MAA | |||||
| Centreville | Fan | EF-3 | Cabinet Exhaust | RME Restroom | 75 cfm | MAA | |||||||
| Centreville | Fan | EF-4 | Cabinet Exhaust | Office Restrooms | 500 cfm | MAA | |||||||
| Centreville | Fan | EF-5 | Cabinet Exhaust | Shop Restroom | 200 cfm | MAA | |||||||
| Centreville | Fan | EF-6 | Cabinet Exhaust | Coolair | CFL-90 | Inventory Restrooms | 725 cfm | MAA | |||||
| Centreville | Fan | EF-7 | Rooftop Centrifugal | ILG Industries | GRBCA08FD1151LD | Electric Room | 400 cfm | MAA | |||||
| Centreville | Fan | EF-8 | Wall Mounted Propeller Fan | Greenheck | Mechanical Room | MAA | |||||||
| Centreville | Fan | VEF-1 | Vehicle Exhaust Fan | CAR-MON | CMB-10F | Old Shop Roof | 1300 cfm | MAA | |||||
| Centreville | Fan | VEF-2 | Vehicle Exhaust Fan | CAR-MON | CMB-20F | New Shop Roof | 2000 cfm | MAA | |||||
| Centreville | Fan | VEF-3 | Vehicle Exhaust Fan | CAR-MON | CMB-20F | New Shop Roof | 2000 cfm | MAA | |||||
| Centreville | Unit Heater | UH-1 | Hot Water Unit Heater | Modine | HS 18501 | Electrical Room | 8 mbh | MAA | |||||
| Centreville | Unit Heater | UH-2 | Hot Water Unit Heater | Modine | HS 18501 | Mechanical Room | 8 mbh | MAA | |||||
| Centreville | Unit Heater | UH-3 | Hot Water Unit Heater | Modine | HS 18501 | Mechanical Room | 8 mbh | MAA | |||||
| Centreville | Unit Heater | UH-4 | Hot Water Unit Heater | Modine | HS 18501 | Parts Room | 8 mbh | MAA | |||||
| Centreville | Unit Heater | UH-5 | Hot Water Unit Heater | Modine | HS 18501 | Oil Room | 8 mbh | MAA | |||||
| Centreville | Unit Heater | UH-6to21 | Propane Fired Unit Heaters | Modine | PD-30AA0111 | Vehicle Storage Bldg | 30 mbh | TLA x16 | |||||
| Centreville | Fintube Radiation | BB-1 | Hot Water Baseboard | Modine | Model "T" | Vestibule | 6.2 mbh | MAA | |||||
| Centreville | Fintube Radiation | BB-2 | Hot Water Baseboard | Modine | Model "T" | Vestibule | 4.6 mbh | MAA | |||||
| Centreville | Zone Damper | ZD-1 | Zone Damper | Wattmaster | 20x20 | Assembly | 550 cfm cooling, 310 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-2 | Zone Damper | Wattmaster | 20x20 | Assembly | 550 cfm cooling, 310 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-3 | Zone Damper | Wattmaster | 20x10 | Kitchen | 500 cfm cooling, 145 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-4 | Zone Damper | Wattmaster | 20x10 | Lunch Room | 400 cfm cooling, 260 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-5 | Zone Damper | Wattmaster | 8x8 | Chief Mechanic | 175 cfm cooling, 60 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-6 | Zone Damper | Wattmaster | 8x8 | Waiting | 70 cfm cooling, 70 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-7 | Zone Damper | Wattmaster | 20x10 | Reception | 500 cfm cooling, 130 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-8 | Zone Damper | Wattmaster | 20x20 | RME | 450 cfm cooling, 240 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-9 | Zone Damper | Wattmaster | 8x8 | ARME | 200 cfm cooling, 120 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-10 | Zone Damper | Wattmaster | 14x8 | Team Leader | 375 cfm cooling, 280 cfm heating | MAA | |||||
| Centreville | Zone Damper | ZD-11 | Zone Damper | Wattmaster | 8x8 | File Room | 75 cfm cooling, 55 cfm heating | MAA | |||||
| Centreville | Infrared Heater | Gas Fired Infra-red heater | Space Ray | LTU-130-L5 | Washbay | 100 mbh input | MAA | ||||||
| Centreville | Misc. Equipment | 1 | Gas Fired Heaters | Jackson Church | OL-280-HB23 | Inventory Bays | Gas | MAA | |||||
| Centreville | Misc. Equipment | Elec. Heaters | Qmark | MUH0381 | Inventory Bays | Electric | 5 Units | MAA | |||||
| Centreville | Misc. Equipment | Elec. Heater | TPI | HF684T2M | Washbay Mec. | Electric | MAA | ||||||
| Centreville | Misc. Equipment | 2 | Control System | Control Sources | All Buildings | ||||||||
| Centreville | Misc. Equipment | 3 | Heat Pump (condensing unit) | RHEEM | RP14AZ36AJ2NA | Sign Team Bay | ESA | ||||||
| Centreville | Misc. Equipment | 4 | Heat Pump (AHU) | RHEEM | RH2VZ3617STANNJ | Sign Team Bay | Htg KFCH1101C10 | ESA | |||||
| Centreville | Misc. Equipment | 5 | Diffusers, Registers & Grilles | Varies | Vares | Conditioned Spaces | |||||||
| Centreville | Misc. Equipment | 6 | Intake Ventilator | Loren Cook | #PR-29 | Washbay | MAA | ||||||
| Centreville | Misc. Equipment | 7 | Exhaust Fan | Loren Cook | #120R4B | Washbay | MAA | ||||||
| Centreville | Misc. Equipment | 8 | Gas Fired Furnace | Williamson | #WLBO-140R / SU--4 N/P | Bay 9 | Gas | 140 mbh | MAA | ||||
| Bay country welcome center (Centreville) | Packaged A/C Unit | AHU-1 | Packaged A/C Unit (Cooling Only) | Koldwave | # AVT090X32 | Mechanical Rm. 108 | 67.6 mbh | 2975 cfm | 208-3-60 | WCA | |||
| Bay country welcome center (Centreville) | Cabinet Heater | Ceiling Mounted Cabinet Heater | Chromalox | CUC-RAF-131 | Rm. 106 | 250 cfm | 208-1-60 | WCA | |||||
| Bay country welcome center (Centreville) | Cabinet Heater | Ceiling Mounted Cabinet Heater | Chromalox | CUC-RFF-121 | Rm. 111 | 250 cfm | 208-1-60 | WCA | |||||
| Bay country welcome center (Centreville) | Cabinet Heater | Wall Mounted Cabinet Heater | Chromalox | CUW-SFF | Rm. 105 | 250 cfm | 208-1-60 | WCA | |||||
| Bay country welcome center (Centreville) | Cabinet Heater | Ceiling Mounted Cabinet Heater (Recessed) | Chromalox | Family Toilet Rm. | 250 cfm | 208-1-60 | WCA | ||||||
| Bay country welcome center (Centreville) | Unit Heater | Electric Unit Heater | Chromalox | MUH-03-2 | Various | 7.5 mbh | 350 cfm | 208-1-60 | 4 units | WCA | |||
| Bay country welcome center (Centreville) | Duct Heater | Electric Duct Heater | Brasch | Super-X | Mech. Rm. Attic | 2957 cfm | 208-3-60 | WCA | |||||
| Bay country welcome center (Centreville) | Duct Heater | Electric Duct Heater | Brasch | Super-X | Rm. 110 | 310 cfm | 208-3-60 | WCA | |||||
| Bay country welcome center (Centreville) | Misc. Equipment | Electric Baseboard | Chromalox | BBS-28 | 208-1-60 | WCA | |||||||
| Bay country welcome center (Centreville) | Misc. Equipment | Electric Baseboard | Chromalox | BBS-108 | 208-1-60 | WCA | |||||||
| Bay country welcome center (Centreville) | Misc. Equipment | Electric Baseboard | Chromalox | APH-070 | Welcome Center | 208-1-60 | WCA | ||||||
| Bay country welcome center (Centreville) | Exhaust Fan | Cabinet Fan | Penn Ventilator | WCA | |||||||||
| Bay country welcome center (Centreville) | Exhaust Fan | Cabinet Fan | Penn Ventilator | WCA | |||||||||
| Bay country welcome center (Centreville) | Exhaust Fan | Cabinet Fan | Penn Ventilator | WCA | |||||||||
| Bay country welcome center (Centreville) | Exhaust Fan | Cabinet Fan | Penn Ventilator | WCA | |||||||||
| Bay country welcome center (Centreville) | Exhaust Fan | Propeller Fan | Penn Ventilator | P12R | Skylight Tower | 955 cfm | 115-1-60 | WCA | |||||
| Bay country welcome center (Centreville) | Exhaust Fan | Propeller Fan | Penn Ventilator | P12R | Skylight Tower | 955 cfm | 115-1-60 | WCA | |||||
| Kent Narrows Bridge (Centreville) | Misc. Equipment | Mini split ( condensing unit) | DAIKIN | 3MXS24RMVJUA | Under bridge | 208-1-60 | |||||||
| Kent Narrows Bridge (Centreville) | Misc. Equipment | Mini split (fan coil unit) | DAIKIN | FFQ18Q2VJU | Upper and lower floor | 208-1-60 | 2 units | ||||||
| Kent Narrows Bridge (Centreville) | Misc. Equipment | Electric Unit Heater | Upper and lower floor | 3 units | |||||||||
| Stevensville Shop (Centreville) | Furnace | Oil Fired Furnace | Armstrong Air | Ultra 80 | LUF80C112/125D20 - 1 | Upstairs / Shop | Oil | SAA | |||||
| Stevensville Shop (Centreville) | Furnace | Oil Fired Furnace | Armstrong Air | Ultra 80 | Upstairs / Shop | Oil | SAA | ||||||
| Stevensville Shop (Centreville) | Condensing Unit | Condensing Unit | DURASTAR | DRAC14B30AJ1ANA | On Grade Behind Shop | 208-1-60 | SAA | ||||||
| Stevensville Shop (Centreville) | Condensing Unit | Fan coil unit | DURASTAR | DRBEF3617STANMC | Above Office | 208-1-60 | SAA |
Centreville EQUIPMENT LIST - CENTREVILLE MAINTENANCE FACILITY Prepared by H. Albert, OOM/FMD Date; 9/2/05
Drawing Tag Equipment Type Manufacturer Model Number Location Original Design Specifications Nameplate Data Naneplate Data Comments
| Rooftop Units | |||||||
| AC-1 | Packaged Rooftop cooling only | York | AV15C0BQ4E1AAA42A2 | Roof-Admin. Offices | 4000 cfm, 192 MBH Tot, 152.4 MBH Sens. | See Heating Coils | |
| AC-2 | Packaged Rooftop cooling only | York | DH090C00N4AAAA1A | Roof-Stock Area | 2400 cfm. 93.6 MBH Tot, 68.4 MBH Sens. | See Heating Coils | |
| Heating & Ventilating Units | |||||||
| HV-1 | Horizontal Cabinet Unit clg mtd | Customair | AQ-UN1 01 048 ATL 12-12R | Old Shop | 3000 cfm | See Heating Coils | |
| HV-2 | Horizontal Cabinet Unit clg mtd | Customair | AQ-UN1 01 048 ATL 12-9 | New Shop | 4500 cfm | See Heating Coils | |
| HV-3 | In-line Cabinet Ventilator | Breidert | FFC250S | Parts Rm. Clg. Mtd. | 200 cfm | See Heating Coils | |
| Duct and Unit Mounted Hydronic Heating Coils | |||||||
| HC-1 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Assembly | 310 cfm, 9.4 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-2 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Assembly | 310 cfm, 9.4 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-3 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Kitchen | 145 cfm, 4.4 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-4 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Lunch Room | 260 cfm, 7.8 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-5 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Chief Mechanic | 60 cfm, 1.7 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-6 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Sec Overnight | 70 cfm, 2.0 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-7 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Reception | 130 cfm, 3.9 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-8 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | RME | 240 cfm, 7.2 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-9 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | ARME | 120 cfm, 3.6 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-10 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Team Leader | 280 cfm, 804 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-11 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | File Room | 55 cfm, 1.6 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-12 | Hydronic Heating Coil Unit Mtd | AAON Coil Prod. | Unknown | HV-3 Parts Rm. | 200 cfm, 12.3 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-13 | Hydronic Heating Coil Duct Mtd | R.B.Lynch Co. | Unknown | Inventory | 2375 cfm, 95 mbh, 62 eat/90 lat, 200 ewt/180 lwt | ||
| HC-14 | Hydronic Heating Coil Unit Mtd | Heatcraft | Unknown | HV-1 Old Shop | 3000 cfm, 200 mbh, 62 eat/90 lat, 200 ewt/180 lwt | Floor Heat | |
| HC-15 | Hydronic Heating Coil Unit Mtd | Heatcraft | Unknown | HV-2 New Shop | 4500 cfm, 300 mbh, 62 eat/90 lat, 200 ewt/180 lwt | Floor Heat | |
| Boilers | |||||||
| B-1 | Hot Water, Firetube, Oil Fired | Cleaver Brooks | P143-20 | Mechanical Room | 837 mbh input, 670 mbh output, #2 oil, 6 gph | ||
| B-2 | Hot Water, Cast Iron, Oil Fired | Clean Burn | CB-240-BLR (5 section) | Mechanical Room | 240 mbh input, #2 oil, 1.7 gph max. | uses fuel oil | |
| Pumps | |||||||
| BP-1 | In-line Centrifugal | B&G | 60 2x5.25 w/ 4.625 BF imp. | Mechanical Room | 70 gpm @ 20' head | Cleaver Brooks | |
| BP-2 | In-line Centrifugal | B&G | 60 1x5.25 w/ 4.62 BF imp. | Mechanical Room | 20 gpm @ 20' head | Clean Burn | |
| HWP-1 | In-line Centrifugal | B&G | 60 2x5.25 w/ 4.875 BF imp. | Mechanical Room | 70 gpm @ 24' head | ||
| HWP-2 | In-line Centrifugal | B&G | 60 2x5.25 w/ 4.875 BF imp. | Mechanical Room | 70 gpm @ 24' head | ||
| HWP-3 | In-line Centrifugal | B&G | NRF 22 | Mechanical Room | 4 gpm @ 10' head | Stand-by | |
| HWP-4 | In-line Centrifugal | B&G | NRF 22 | Mechanical Room | 7 gpm @ 10' head | ||
| HWP-5 | In-line Centrifugal | B&G | NRF 22 | Mechanical Room | 7 gpm @ 10' head | ||
| FOP-1 | Duplex Fuel Oil Pumps | Webester | SPM-15-1 | Mechanical Room | 0.6 gpm @ 35' head | ||
| WOP-1 | Duplex Waste Oil Pumps | Webester | SPM-15-1 | Mechanical Room | 0.6 gpm @ 35' head | ||
| Fans | |||||||
| EF-1 | Rooftop Centrifugal | Old Shop Roof | 3000 cfm, 0.125" SP | ||||
| EF-2 | Rooftop Centrifugal | ILG Industries | GRBCA20LD8363 | New Shop Roof | 4500 cfm, 0.250" SP | ||
| EF-3 | Cabinet Exhaust | RME Restroom | 75 cfm, 0.125" SP | ||||
| EF-4 | Cabinet Exhaust | Office Restrooms | 500 cfm, 0.250" SP | ||||
| EF-5 | Cabinet Exhaust | Shop Restroom | 200 cfm, 0.125" SP | ||||
| EF-6 | Cabinet Exhaust | Coolair | CFL-90 | Inventory Restrooms | 725 cfm, 0.250" SP | ||
| EF-7 | Rooftop Centrifugal | ILG Industries | GRBCA08FD1151LD | Electric Room | 400 cfm, 0.125" SP | ||
| EF-8 | Wall Mounted Propeller Fan | Greenheck | Mechanical Room | ||||
| VEF-1 | Vehicle Exhaust Fan | CAR-MON | CMB-10F | Old Shop Roof | 1300 cfm, 3.5" SP | ||
| VEF-2 | Vehicle Exhaust Fan | CAR-MON | CMB-20F | New Shop Roof | 2000 cfm, 3.5" SP | ||
| EQUIPMENT LIST - CENTREVILLE MAINTENANCE FACILITY Prepared by H. Albert, OOM/FMD Date; 9/2/05 |
Drawing Tag Equipment Type Manufacturer Model Number Location Original Design Specifications Nameplate Data Naneplate Data Comments
| VEF-3 | Vehicle Exhaust Fan | CAR-MON | CMB-20F | New Shop Roof | 2000 cfm, 3.5" SP | ||
| Unit Heaters | |||||||
| UH-1 | Hot Water Unit Heater | Modine | HS 18501 | Electrical Room | 8 mbh, 0.8 gpm, 200° ewt, 180° lwt | ||
| UH-2 | Hot Water Unit Heater | Modine | HS 18501 | Mechanical Room | 8 mbh, 0.8 gpm, 200° ewt, 180° lwt | ||
| UH-3 | Hot Water Unit Heater | Modine | HS 18501 | Mechanical Room | 8 mbh, 0.8 gpm, 200° ewt, 180° lwt | ||
| UH-4 | Hot Water Unit Heater | Modine | HS 18501 | Parts Room | 8 mbh, 0.8 gpm, 200° ewt, 180° lwt | ||
| UH-5 | Hot Water Unit Heater | Modine | HS 18501 | Oil Room | 8 mbh, 0.8 gpm, 200° ewt, 180° lwt | ||
| UH-6to21 | Propane Fired Unit Heaters | Modine | PD-30AA0111 | Vehicle Storage Bldg | 30 mbh | ||
| Fintube Radiation | |||||||
| BB-1 | Hot Water Baseboard | Modine | Model "T" | Vestibule | 6.2 mbh, 180° ewt, 160° lwt | ||
| BB-2 | Hot Water Baseboard | Modine | Model "T" | Vestibule | 4.6 mbh, 180° ewt, 160° lwt | ||
| Zone Dampers | |||||||
| ZD-1 | Zone Damper | Wattmaster | 20x20 | Assembly | 550 cfm cooling, 310 cfm heating | ||
| ZD-2 | Zone Damper | Wattmaster | 20x20 | Assembly | 550 cfm cooling, 310 cfm heating | ||
| ZD-3 | Zone Damper | Wattmaster | 20x10 | Kitchen | 500 cfm cooling, 145 cfm heating | ||
| ZD-4 | Zone Damper | Wattmaster | 20x10 | Lunch Room | 400 cfm cooling, 260 cfm heating | ||
| ZD-5 | Zone Damper | Wattmaster | 8x8 | Chief Mechanic | 175 cfm cooling, 60 cfm heating | ||
| ZD-6 | Zone Damper | Wattmaster | 8x8 | Waiting | 70 cfm cooling, 70 cfm heating | ||
| ZD-7 | Zone Damper | Wattmaster | 20x10 | Reception | 500 cfm cooling, 130 cfm heating | ||
| ZD-8 | Zone Damper | Wattmaster | 20x20 | RME | 450 cfm cooling, 240 cfm heating | ||
| ZD-9 | Zone Damper | Wattmaster | 8x8 | ARME | 200 cfm cooling, 120 cfm heating | ||
| ZD-10 | Zone Damper | Wattmaster | 14x8 | Team Leader | 375 cfm cooling, 280 cfm heating | ||
| ZD-11 | Zone Damper | Wattmaster | 8x8 | File Room | 75 cfm cooling, 55 cfm heating | ||
| Infra-red Heater | |||||||
| Gas Fired Infra-red heater | Space Ray | LTU-130-L5 | Washbay | 100 mbh input | |||
| Other Equipment and Systems | |||||||
| 1 | Gas Fired Heaters | Jackson Church | OL-280-HB23 | Inventory Bays | Gas Fired | ||
| Elec. Heaters | Qmark | MUH0381 | Inventory Bays | 3 Uints | |||
| Elec. Heater | TPI | HF684T2M | Washbay Mec. | ||||
| 2 | Control System | Control Sources | All Buildings | ||||
| 3 | Heat Pump (condensing unit) | Carrier | #38BYC036310 | Sign Team Bay | OFS | ||
| 4 | Heat Pump (AHU) | Carrier | #40FKA003300 | Sign Team Bay | Htg KFCH1101C10 | ||
| 5 | Diffusers, Registers & Grilles | Varies | Vares | Conditioned Spaces | Varies | ||
| 6 | Intake Ventilator | Loren Cook | #PR-29 | Washbay | Info. from dwgs. | ||
| 7 | Exhaust Fan | Loren Cook | #120R4B | Washbay | Info. from dwgs. | ||
| 8 | Gas Fired Furnace | Williamson | #WLBO-140R / SU--4 N/P | Bay 9 | 140 mbh | ||
| 9 | Propane Fired Heater | York | #P4UGD16N14001A | Paint Bay | |||
| 10 |
Kent Narrows bridge House EQUIPMENT LIST- Kent Narrows Bridge House (Centreville Shop) Prepared by: LDobbs OOM/FMD Date:
Drawing Tag Equipment Type Manufacturer* Model Number* Location/Area served Original Design Specifications Nameplate Data Comments
| Mini split (fan coil unit) | DAIKIN | FFQ18Q2VJU | Bridge House/Upper Level | Upper and lower floor | |
| Mini split (fan coil unit) | DAIKIN | FFQ18Q2VJU | Bridge House/Middle Level | Upper and lower floor | |
| Mini split ( condensing unit) | DAIKIN | 3MXS24RMVJUA | Bridge House/Lower Level | ||
| Unit Heaters | |||||
| Electric Unit Heater | Various |
Stevensville EQUIPMENT LIST- Stevensville Maintenance Facility Prepared by: LDobbs OOM/FMD Date: 8/22/25
Drawing Tag Equipment Type Manufacturer* Model Number* Location/Area Served Original Design Specifications* Nameplate Data* Comments
| Oil Fired Furnace | Armstrong Air | LUF80C112/125D20 - 1 | Upstires / Office |
| Oil Fired Furnace | Armstrong Air | Upstires / Shop | |
| Condensing Units | |||
| Condensing Unit | DURASTAR | DRAC14B30AJ1ANA | Office / On Grade Behind Shop |
| Fan coil unit | DURASTAR | DRBEF3617STANMC | Office / Above Office |
Bay country EQUIPMENT LIST- Bay Contry Welcome Center Prepared by: H. Albert OOM/FMD Date:
Drawing Tag Equipment Type Manufacturer* Model Number* Location/Area served Original Design Specifications Nameplate Data Comments
| Packaged A/C Units | ||||||
| AHU-1 | Packaged A/C Unit (Cooling Only) | Koldwave | # AVT090X32 | Mechanical Rm. 108 | 2975 cfm, 92.7 tmbh, 67.6 mbh sens.,1 hp | 208-3-60 |
| Exhaust Fans | |||||
| EF-1 | Cabinet Fan | Penn Ventilator | # Z14L-TDA | Rm. 106 Abv. Clg. | 1420 cfm, 1/2 hp,0.31" esp, 115-1-60 |
| EF-2 | Cabinet Fan | Penn Ventilator | # Z6L-RA | Rm. 102 Abv. Clg. | 75 cfm, 1/25 hp,0.15" esp 115-1-60 |
| EF-3 | Cabinet Fan | Penn Ventilator | # Z10L-TDA | Rm. 109 & 110 Abv. Clg. | 265 cfm, 1/10 hp, 0.31" esp 115-1-60 |
| EF-4 | Cabinet Fan | Penn Ventilator | # Z10L-RA | Rm. 103 Abv. Clg. | 270 cfm, 0.20" esp, 1/10 hp, 115-1-60 |
| EF-5 | Propeller Fan | Penn Ventilator | P12R | Skylight Tower | 955 cfm, 1/7 hp 0.125" esp, 115-1-60 |
| EF-6 | Propeller Fan | Penn Ventilator | P12R | Skylight Tower | 955 cfm, 1/7 hp 0.125" esp, 115-1-60 |
| Cabinet Unit Heaters | |||||
| 7 | Ceiling Mounted Cabinet Heater | Chromalox | CUC-RAF-131 | Rm. 106 | 250 cfm, 3 kw, 15 amps, 208-1-60 |
| 8 | Ceiling Mounted Cabinet Heater | Chromalox | CUC-RFF-121 | Rm. 111 | 250 cfm, 2 kw, 10 amp, 208-1-60 |
| 9 | Wall Mounted Cabinet Heater | Chromalox | CUW-SFF | Rm. 105 | 250 cfm, 6 kw, 17 amp, 208-1-60 |
| CUH-1 | Ceiling Mounted Cabinet Heater (Recessed) | Chromalox | Family Toilet Rm. | 250 cfm, 6.8 mbh, 2 kw, 9.6 amps, 208-1-60 |
| Unit Heaters | ||||||
| 5 | Electric Unit Heater | Chromalox | MUH-03-2 | Various | 350 cfm, 7.5 mbh, 2.48 kw, 1/100 hp, 208-1-60 | Typ. For 4 units |
| Duct Heaters | |||||
| DH-1 | Electric Duct Heater | Brasch | Super-X | Mech. Rm. Attic | 2975 cfm, 25 kw, , 208-3-60 |
| DH-2 | Electric Duct Heater | Brasch | Super-X | Room 110 | 310 cfm, 2 kw, 208-3-60 |
| Baseboard Radiation | |||||
| 6 | Electric Baseboard | Chromalox | BBS-28 | Various | 0.5 kw, 208-1-60 |
| 3 | Electric Baseboard | Chromalox | BBS-108 | Various | 2.5 kw, 208-1-60 |
| 4 | Electric Baseboard | Chromalox | APH-070 | Welcome Center | 0.375/lf kw, 208-1-60 |