Rooftop Unit.doc

DOC document 42 KB Posted

Attached to
QAHVAC28SB 1-year HVAC repair contract for SHA Centreville (Eastern Shore)
Solicitation number
BPM059074
Issued by
Queen Anne's County, Maryland

About this file

This is a Rooftop Unit Checklist document supporting an HVAC repair and preventive maintenance contract for the State of Maryland's SHA Centreville facility on the Eastern Shore. The checklist establishes comprehensive maintenance standards for rooftop HVAC units, divided into quarterly and seasonal changeover service requirements. Quarterly maintenance tasks include air filter replacement, fan belt inspection, refrigerant checks, access panel verification, static pressure control sensor operation, ductwork inspection, drain pan evaluation, condensate line inspection, vibration and noise assessment, moisture eliminator and bird screen inspection, flexible duct connection review, and coil inspection and cleaning. Seasonal changeover procedures encompass verification of operation sequences, variable frequency drive functionality, burner tuning with electrode and nozzle inspection, fuel train evaluation, combustion measurements including draft, carbon dioxide, oxygen levels, stack temperature, smoke density, and carbon monoxide readings, safety control verification, gauge replacement, supply air temperature measurement, strainer cleaning, regulator and valve adjustment, compressor motor ground resistance measurement, interlock control testing, actuator operation verification, flue inspection and cleaning, coil washing, secondary heat exchanger cleaning, electric connection inspection and tightening, bearing and motor lubrication, motor amp draw recording, damper lubrication and adjustment, motor intake screen cleaning, fan wheel inspection, and structural equipment support assessment for corrosion and damage.

The document does not specify pricing terms, contract duration, renewal options, set-asides, incumbent contractor information, funding sources, or other financial details. The checklist serves as a technical specification document outlining the scope of work and performance standards required for HVAC maintenance services under the one-year repair contract for SHA Centreville, with no information provided regarding bid response dates, award dates, or site visit requirements.

View the file

Other files

File Type Posted
Oil Transfer Pump.doc DOC document
Exhaust Fan.doc DOC document
Attachment-L.-Reference-Check.pdf PDF
Unit Heaters Gas Oil Fired.doc DOC document
QAHVAC28SB IFB.pdf PDF
Unit Heaters Electric.doc DOC document
Attachment-A.-Bid-Proposal-Affidavit (required).pdf PDF
Heat pump.doc DOC document
How to Respond to eMMA Solicitations (for new vendors).pdf PDF
Centrifugal Pump.doc DOC document
Cabinet Heaters Electric.doc DOC document
VAV Box with Hot Water Heat.doc DOC document
Furnace.doc DOC document
Infrared Heaters Gas Oil Fired.doc DOC document
Appexdix 2 - Price form instruction (for new vendors).pdf PDF
Exhibit 2 - Sample Contract revision 2024 Small Procurement (no action needed).pdf PDF
HVAC- Centreville, Stevensville - Systems Information.xlsx XLSX spreadsheet
Cast Iron Boiler.doc DOC document
Unit Heaters Hot Water.doc DOC document
QAHVAC28SB - Price form.xlsx XLSX spreadsheet
Attachment-1.-No-Bid_Proposal-Notice_Vendor-Feedback-Form-1-1 (optional).pdf PDF
Attachment-I.-Conflict-of-Interest-Affidavit.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOFTOP UNIT CHECKLIST

Type of Service:

Date Of Service:

Unit Being Serviced:

Facility:

Service Technician:

QUARTERLY

FORMCHECKBOX

Replace Air Filters.

FORMCHECKBOX

Check Fan Belts for tension, alignment and wear. Adjust/Replace as needed.

FORMCHECKBOX

Check Damper Linkage/Movement. Adjust and Lubricate as needed.

FORMCHECKBOX

Check Refrigerant, both site glass and refrigerant charge. Adjust as needed. Check for leaks and repair if undercharged.

FORMCHECKBOX

Check access panels for tight fit. Replace screws, handles etc. as needed. Oil hinges if applicable.

FORMCHECKBOX

Verify operation of rooftop unit static pressure control sensor.

FORMCHECKBOX

Inspect Ductwork, insulation and covering on roof for air and water leakage. Repair as needed.

FORMCHECKBOX

Check Drain Pans for proper drainage, leakage, dirt and mold. Clean/Repair as needed.

FORMCHECKBOX

Check condensate lines for clog or physical damage. Repair or replace as needed.

FORMCHECKBOX

Inspect for vibration and unusual noises.

FORMCHECKBOX

Check moisture eliminators, bird screens and outside air hoods for damage, blockage and cleanliness. Repair/clean as needed.

FORMCHECKBOX

Inspect flexible duct connections for damage and leakage. Repair/Replace as needed.

FORMCHECKBOX

Inspect coils for damage, blockage, dirt etc. Clean as needed. Comb/Straighten fins.

SEASONAL CHANGEOVER

FORMCHECKBOX

Verify Sequence of operation.

FORMCHECKBOX

Verify Variable Frequency Drive operation.

FORMCHECKBOX

Tune burners. Check/Adjust/Replace electrodes, nozzles, seals, gaskets etc. Check pump pressure and adjust to manufacturer’s specs, Clean burner air tube, fan housing and blower wheel. Seal any air leaks into combustion chamber.

FORMCHECKBOX

Check fuel train. Repair/Replace as required.

FORMCHECKBOX

Measure draft, CO2 or O2, net stack temperature, smoke density and carbon monoxide. Note final readings, after adjustments, in logs. Check for restrictions in flues/chimneys. Adjust barometric dampers, flue/chimney caps and fans/damper for combustion air sources. Check for pulsations and rumbles. Clean bird and insect screens.

FORMCHECKBOX

Verify functioning of all safety and auxiliary controls.

FORMCHECKBOX

Check gages. Replace as needed. Note all vacuum and pressure readings in logs. Measure and note supply air temperatures during normal operation.

ROOFTOP UNIT CHECKLIST

FORMCHECKBOX

Clean strainers. Adjust regulators and pressure reducing valves. Operate shutoff valves.

FORMCHECKBOX

Measure ground resistance of compressor motor windings.

FORMCHECKBOX

Test and verify interlock controls.

FORMCHECKBOX

Verify proper operation of all actuators.

FORMCHECKBOX

Inspect flues for leaks and cracks. Drain/Clean flues of condensation and dirt. Check the barometric damper.

FORMCHECKBOX

wash coils with a coil cleaner and flush.

FORMCHECKBOX

Clean secondary heat exchanger and combustion area. Clean transformer bushings, springs and cad cell surface.

FORMCHECKBOX

Check safety and auxiliary controls.

FORMCHECKBOX

Inspect and tighten electric connections. Clean contacts and verify proper operation.

FORMCHECKBOX

Lubricate bearings, fans and motors.

FORMCHECKBOX

Take amp draw of motors and record amp readings in the log.

FORMCHECKBOX

Lubricate dampers. Adjust damper linkage.

FORMCHECKBOX

Clean intake screen on motors.

FORMCHECKBOX

Inspect fan wheel/blades for free rotation, cracks and alignment.

FORMCHECKBOX

Inspect all structural equipment supports for corrosion and damage.