Specs_Project Manual_Appendix.pdf
PDF 407 KB Posted
- Solicitation number
- S-DASOBO-00009472
- Issued by
- Lake County, Albany City, Oregon
About this file
This document provides standardized LAN wiring specifications for contractors working on projects for the Oregon Youth Authority (OYA). It outlines the process for determining data jack needs and locations, ordering, maintenance, and installation. The specifications cover requirements for wall jacks, cabling, labeling, testing, and final walkthrough and sign-off. The document also includes a Security Technology Program Construction and Renovation Matrix that details the responsibilities of the Primary Systems Contractor, Owner Furnished/Contractor Installed, and Owner Furnished/Owner Installed components for security access control, security IP surveillance systems, and related infrastructure.
The related state and local contract opportunity is for the construction of a new parole and probation building at the Oak Creek Youth Correctional Facility (OCYCF) in Albany, Oregon. The work includes all labor, materials, transportation, equipment, and services as described in the attachments and ITB documents. The contract will be awarded to a single contractor to perform the construction work.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OREGON YOUTH
AUTHORITY
Information Systems – Technical Services
Procedure Statement
Standardized LAN Wiring Specifications for Contractors
IS-12
Approved
Signature on File Technical Services Manager
Effective: 01/21/2011
Supersedes: None
Interpretation:
Information Systems
REFERENCE
▪ OYA form: YA 1603 (TSO Attachment)
DEFINITIONS
Word: None.
PROCEDURE STATEMENT
Information technology (IT) asset management provides for policies, procedures, and guidelines for lifecycle management of the OYA IT assets from standards and acquisition to installations, management, and surplus.
PROCEDURE ACTION PLAN
The purpose of this procedure is to outline the process for standardized LAN wiring specification for contractors. This procedure outlines determining data jack needs and locations, maintenance, ordering, and installation.
I. Standardized LAN Wiring Specifications for Contractors
Step Responsible Party
Action
1. Facilities Maintenance
Determine data jack needs and locations
Maintenance will field requests for new computer data & phone jacks that are needed at OYA Facilities.
Maintenance will work collaboratively with facility personal
Specifications, Project Manual for Oak Creek Youth Correctional Facility, APPENDIX http://oyanet.oya.state.or.us/ResourceCenter/Forms/TSO%20Attachment.docx to determine locations for new computer data jacks and phone jacks.
2. Facilities Maintenance
Ordering
▪ Maintenance will either submit a TSO to DAS
(YA 1603)
or place an order with appropriate contractor of their choice or have internal personal install the wiring.
▪ Facilities Maintenance
Lead on new installation
Maintenance is the primary contact for all work to be done.
Information Systems will provide guidance to maintenance staff as requested.
Procedure Specifics
4. Facilities Maintenance
Maintenance is responsible that the following specifications are adhered to by all contractors for LAN wiring.
5. Information Systems
Information Systems will determine the specifications and standards for network infrastructure.
A. All facility wall jacks require the use of security face plates with security screws.
B. Agency standard is AMP 110 connect, rj11 for voice and rj45 for wall jacks.
C. Data closet hardware would be AMP high density 24 or 48 port patch panels
D. CAT 6e blue cabling for data, CAT 6e white cabling for voice CAT6e yellow for video.
E. Existing pathways must be followed for the data and voice runs. Any exposed wiring must be concealed within an agency approved conduit or raceway.
F. All Jacks must be sequentially labeled both at the wall and at the patch panel with professional label.
G. All wiring must be tested and meet Category 6e specifications.
H. Certified results of test need to be provided by the vendor to maintenance.
F. Facilities Maintenance and Information Systems
Maintenance and IS will conduct a final walk through and sign off on all completed work.
http://oyanet.oya.state.or.us/ResourceCenter/Forms/TSO%20Attachment.docx
7. Information System
Information Systems will perform final connection from wall jack to client computer and from patch panel to network switch.
From <https://oya.sharepoint.com/sites/ts/TeamSite/TS%20Documents/IS%20Standards/TS- 12%20Standardized%20LAN%20Wiring%20Specifications%20for%20Contractors%20Dev%2001-2011.docx> https://oya.sharepoint.com/sites/ts/TeamSite/TS%20Documents/IS%20Standards/TS-12%20Standardized%20LAN%20Wiring%20Specifications%20for%20Contractors%20Dev%2001-2011.docx https://oya.sharepoint.com/sites/ts/TeamSite/TS%20Documents/IS%20Standards/TS-12%20Standardized%20LAN%20Wiring%20Specifications%20for%20Contractors%20Dev%2001-2011.docx
Security Technology Program Construction and Renovation Matrix
Updated: 6/1/24
Security Technology Program - Project Matrix Primary Systems
Contractor Furnished / Contractor Installed
Owner Furnished / Contractor Installed
Owner Furnished /
Owner Installed
Delegated Design
Comments
Security Access Control - Administration {Motorola Avigilon} Horizontal Raceway's X Devices, Conduit and Rough-in
X Includes electric strikes, door contacts, card readers, combo key pad, panic and lockdown push buttons. Must follow current system standards
Fiber Optic Distribution Units X Infrastructure Back Bone Fiber Cabling X 6 pair OM3 50um Multimode. Single mode where needed.
Infrastructure Back Bone Fiber Terminations X Connection type: LC/LC Testing: >0.50 dB loss. OYA to relabel.
Horizontal Category 6 X Color Required {PURPLE}. Cat 5 not prohibited
120v Electrical Connections X Low Voltage cabling X Color Required {White} Recommend shielded. Labeling and as-builds required
Low Voltage terminations X Tested and Labeled.
Low voltage Security and Door Control Devices X
Includes electric strikes, door contacts, card readers, combo key pad, panic and lockdown push buttons. Motorola Avigilon resource guide section 2.4 for compatibility list for only Avigilon.
Network Switch Equipment / SFP's X Shared infrastructure with IP camera systems
Uninterrupted Power Supply X IDF Rack X Enterprise Servers / Workstations / Monitors X ACMS Virtual Appliance / Appliance / and Support X ACMS Software X Motorola Partner Required
ACMS Programming X Owner supported after install tier 1-3. Motorola tier 4
ACMS Licensing X Motorola Partner Required. Owner supported after install.
ACMS Support X X Owner tier 1-3. Motorola tier 4
Security Access Control - Corrections {GE/Emerson PLC} Horizontal Raceway's X Device Conduit and Rough-in
X Includes electric strikes, door contacts, card readers, combo key pad, panic and lockdown push buttons. Must follow current system standards
Fiber Optic Distribution Units X Infrastructure Back Bone Fiber Cabling X 6 pair OM3 50um Multimode. Single mode where needed.
Infrastructure Back Bone Fiber Terminations X Connection type: LC/LC Testing: >0.50 dB loss. OYA to relabel.
Horizontal Category 6 X Color Required {PURPLE}. Cat 5 not prohibited
120v Electrical Connections X Low Voltage cabling X Color Required {White} Recommend shielded. Labeling and as-builds required
Low Voltage terminations X Tested and Labeled.
Low voltage Security and Door Control Devices X
Includes electric strikes, door contacts, card readers, combo key pad, panic and lockdown push buttons.
Programmable Logic Controller (PLC) Network drops. X Terminated and tested
TOA Intercom installed and patched to network. X TOA Speaker wiring X Direct connect to i/o cards (daisy chaining prohibited)
Lighting completed and security lights completed X Uninterrupted Power Supply X IDF Rack X Enterprise Servers / Workstations / Monitors X Network Switch Equipment / SFP's X Isolated network.
ACMS Programming X Owner tier 1-2. Contractor tier 3. GE/Emerson tier 4
ACMS Software / Licensing X Owner
ACMS Support X X Owner tier 1-2. Contractor tier 3. GE/Emerson tier 4
Security IP Surveillance System - {Motorola Unity/Pelco} Horizontal Raceway's X Single Gang Box at all Camera Location/s. X OMIT with corner mounted cameras where special mounting hardware may be required.
Device Conduit X
3/4" EMT to open accessible space at all camera locations from single gang box. Stubs are recommended for corner mounted cameras.
Fiber Optic Distribution Units X LC type
Infrastructure Back Bone Fiber Cabling X 6 pair OM3 50um Multimode. Single mode where needed.
Infrastructure Back Bone Fiber Terminations X Connection type: LC/LC Testing: >0.50 dB loss. OYA to relabel.
Horizontal Category 6 X Color Required {Yellow}. Cat 5 not prohibited
Horizontal Copper Terminations X 2' Service loop recommended. Includes testing. OYA to relabel.
Head-End Cooper Terminations X 10' Service loop required at MDF/ IDF rack location/s. Includes testing. OYA to relabel.
Patch Panels / Cables NA NA NA Not Prohibited
Rack's and Equipment Mounts X Unless otherwise specified for MDF areas
Control Consoles X
Winstead Console Vue Series {sit stand} strongly preferred with monitor mount assembly.
Amounts based on per need basis
Powder Distribution Unit X Wire Ladder X Cable Management / LOOM X Uninterrupted Power Supply's X Network Switch Equipment / SFP's X Requires DCS coordination. 1440watts required POE++
Enterprise Servers / Workstations / Monitors X KVM Console X Cameras & Assessories X Camera Placement (PREA approval required) X VMS Software / Programming / Licensing X VMS Support X Owner tier 1-3. Motorola tier 4
OYA Information Services Patch Cable Color Standard
Creation date: 3-16-2012 Revised:
Ethernet Cable Color Descriptions
Description Cable Color
Workstations Blue
Printers Grey
Servers Green
ILO/Management TBD
External Pink
WAP Orange
Video Yellow
Voice White
Crossover Red
Routers/Switches Purple
Workstation to wall jack Black
Section 1: Patch Panel Cable Site Codes (3 characters – spaces 1-3) Description: Space 1-3 contains the three-letter Site Code of an OYA office location; use the available options listed in Table 1
Table 1 - Site Codes
Site Code
Description Site
Code Description
Site Code
Description
BEN Benton P&P HIL Hillcrest YCF OAK Oak Creek YCF
CEN Central Office JAC Jackson P&P POL Polk P&P
CLA Clackamas P&P JEF Jefferson P&P RIV Riverbend
CLT Clatsop P&P JOS Josephine P&P ROG Rogue Valley YCF
COO Coos P&P KLA Klamath P&P TIL Tillamook YCF
CPF Camp Florence LAN Lane P&P TPP Tillamook P&P
CPT Camp Tillamook LIN Linn P&P TRA Training Academy
CRO Crook P&P LNC Lincoln P&P UMA Umatilla P&P
CUR Curry P&P MAC MacLaren YCF UNI Union P&P
DAL Wasco P&P (The Dalles) MAL Malheur P&P WAS Washington P&P
DES Deschutes P&P MAR Marion P&P YAM Yamhill P&P
DOU Douglas P&P MUL Multnomah P&P
EAS Eastern YCF NOR North Coast YCF
Section 2: Patch cable label standard example: BEN-001
Section 3: All wiring closets will have a primary and secondary site contact. Anyone not a site contact for a specific closet will coordinate through either the primary or secondary site contact before adding/removing and ordering cables for that site.
REVISED SPECIFICATIONS 11-13-2024_corrected.pdf