About this file

This document comprises mechanical design drawings and schedules for HVAC renovation of Building B3 at the U.S. Department of Veterans Affairs facility in Columbia, South Carolina, as part of the EHRM (Employee Housing and Renovations Management) Admin and Training project.

The scope includes installation of a new 6,000 CFM variable volume air handling unit (AHU-09) serving third-floor spaces, with associated ductwork, terminal units, and piping systems. Key mechanical components specified include: nine variable volume reheat boxes (9-3-1V through 9-3-9V) with CFM ranges from 300-1,000, two split-system ductless units (SSCU-1 condensing unit and SSEU-1 evaporating unit) for supplemental cooling in the OIT room, one hydronic unit heater (UH-1) in the mechanical room, and chilled water supply/return and hot water supply/return piping connections to existing building systems. The terminal unit schedule specifies 3/4-inch water connections, heating and cooling setpoints of 68°F and 72°F respectively during occupied modes, and DDC controls provided by the controls contractor. Construction requirements mandate lateral restraint of all duct and pipe systems per state building code, fire damper installation with U.L. listings, seismic support where required, and coordination drawings submitted prior to fabrication. All work must comply with SMACNA standards, and the mechanical contractor is responsible for trade coordination to eliminate conflicts, with any resulting changes made at no additional cost to the owner.

View the file

Other files

File Type Posted
S06 - Amendment 0006-Att 2-Tech Questions-Columbia.pdf PDF
S06-Amendment 0006-Att 1-SF30-Columbia.pdf PDF
S06 - Amendment 0005-Att 1-Tech Questions-Columbia.pdf PDF
S06-Amendment 0005-Att 2-SF30-Columbia.pdf PDF
S06-Amendment 0004-Att 1- BLDG 3 EHRM - DIV 23 Specs Combined.pdf PDF
S06-Amendment 0004-Att 3-HL100.pdf PDF
S06 -Amendment 0004-Att 4- Tech Questions-Columbia.pdf PDF
S06-Amendment 0004-Att 2 - Lim. AB LBP Report - Bld3 EHRM.pdf PDF
S06-Amendment 0004-Att 5- SF30-Columbia.pdf PDF
S06-36C77626R0032-Amendment 0003.pdf PDF
S06-36C77626R0032 Amendment 0002.pdf PDF
S04- Pre Bid Conference - Columbia.pptx PPTX presentation
S06-36C77626R0032 0001.pdf PDF
S06-Site Visit Sign-In Sheet 03062026-Columbia.pdf PDF
S06-RFP Attachment 17-Spce Update for 01321615-2025-12.pdf PDF
S02-RFP Attachment 15-Specifications-Columbia_Part5.pdf PDF
S02-RFP Attachment 8- Fire Sup Drawings-COL.pdf PDF
S02-RFP Attachment 5- ARCH Drawings-COL.pdf PDF
S02-RFP Attachment 4-Campus Map-Columbia.pdf PDF
S02-36C77626R0032-Columbia.pdf PDF
S02-RFP Attachment 12-Specifications-Columbia_Part2.pdf PDF
S02-RFP Attachment 10- Plumbing Drawings-COL.pdf PDF
S02-RFP Attachment 13-Specifications-Columbia_Part3.pdf PDF
S02-RFP Attachment 11-Specifications-Columbia_Part1.pdf PDF
S02-RFP Attachment 6- Electrical Drawings-COL.pdf PDF
S02 - RFP Attachment 3 - Limitations on Subcontracting - Columbia.docx DOCX document
S02-RFP Attachment 1-Wage Rates-Col.txt TXT text file
S02-RFP Attachment 16-Final SOW-Col.pdf PDF
S02-RFP Attachment 14-Specifications-Columbia_Part4.pdf PDF
S02-RFP Attachment 7- Fire Alarm Drawings-COL.pdf PDF
S02-RFP Attachment 2 Site Visit Information-Columbia.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

,8 ,9 ,1 h w r e h e a t

DIRECT EXPANSIONDX

TEMPERATURE SENSOR

UNDERWRITER'S LABORATORIES

UNLESS OTHERWISE NOTED

SYMBOL OR SYMMETRICAL

TEST, ADJUST, BALANCE

TRANSFER DUCT

SUPPLY REGISTER

STANDARD CUBIC FEET PER MINUTE

SHEET METAL AND AIR CONDITIONING

CONTRACTORS NATIONAL ASSOCIATION

STATIC PRESSURE SENSOR

VENT THRU ROOF

VARIABLE SPEED

YARD CLEAN OUT

WEATHER PROOF

VARIABLE FREQUENCY DRIVE

VARIABLE VOLUME

WET BULB TEMPERATUREWb

GP

INSUL

INV

LAT

LB/HR

KW

HTG

HVAC

HOA

HORZ

H'STAT

HR

HP

HD

GPH

GPM

HC

IB

IN

ID

HEATING, VENTILATING, AND AIR CONDITIONING

INVERTED BUCKET

INSIDE DIAMETER

LEAVING AIR TEMPERATURE

POUNDS PER HOUR

INSULATED

INVERT

KILOWATT

HEATING

INCH

HEAT DETECTOR

HAND-OFF-AUTOMATIC

HORSEPOWER

GALLONS PER HOUR

GALLONS PER MINUTE

HUMIDITY CONTROLLER

HORIZONTAL

HUMIDISTAT

HOUR

GUIDE POINT

YCO

WP

WG WATER GAGE

FCV

GALV

GC

GAL

FSD

FT

FV

FS

FPC

FPM

FPS

FOB

FP

FO

FLEX

FLG

FLR-FLR

FD

FACP

F&T

F.D.

FC

EQUIP

ESP

EWT

EXH

ER

EC

EFF

ELEC

EL

EQ

EAT

EA

F

EJ

FIRE PROTECTION CONTRACTOR

FEET PER SECOND

FLOW SWITCH/SENSOR

GENERAL CONTRACTOR

COMBINATION FIRE/SMOKE DAMPER

FEET PER MINUTE

FEET

GALVANIZED

GALLON(S)

FLOW VALVE

FLOW CONTROL VALVE

FLOOR TO FLOOR HEIGHT

FIRE PROTECTI0N

FLAT ON BOTTOM

FLANGE

FLAT OVAL

FIRE DAMPER

FLEX

VERT

W/

W/O

VFD

VTR

VOL

VS

VP

VLV

WITHOUT

WITH

VERTICAL

VOLUME

VENT POINT

VALVE

THRU

T'STAT

UL

V

UON

TYP

TOP

TS

TOS

TOD

THERMOSTAT

TYPICAL

THROUGH

TOP OF DUCT

TOP OF STEEL

TOP OF PIPE

EXHAUST REGISTER

EXTERNAL STATIC PRESSURE

ENTERING WATER TEMPERATURE

FIRE ALARM CONTROL PANEL

FLOAT AND THERMOSTATIC

FLOW CONTROLLER

FAHRENHEIT

FLOOR DRAIN

EXHAUST

ENTERING AIR TEMPERATURE

ELECTRICAL CONTRACTOR

EXPANSION JOINT

ELEVATION

ELECTRICAL

EQUAL

EQUIPMENT

EXHAUST AIR

EFFICIENCY

SPRINKLERSPR

STRUCT

TAB

T/D

SYM

SYS

STL

STM

SR

SQ

STRUCTURAL

SYSTEM

STEEL

STEAM

SQUARE

SMACNA

SPEC

SECT

SCFM

SP

SCH

SD

SA

SECTION

SPECIFICATION

SMOKE DAMPER

SCHEDULE

SUPPLY AIR

LOW SIDE WALL EXHAUST REGISTER

LEAVING WATER TEMPERATURE

RELATIVE HUMIDITY

REVOLUTIONS PER MINUTE

POUNDS PER SQUARE INCH ABSOLUTE

POUNDS PER SQUARE INCH GAGE

REFLECTED CEILING PLAN

POLYVINYL CHLORIDE

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH

PRESSURE REDUCING STATION

PLUMBING CONTRACTOR

OUTSIDE DIAMETER

MOTOR OPERATED DAMPER

NATIONAL ELECTRIC CODE

NATIONAL ELECTRICAL MANUFACTURER'S

NATIONAL FIRE PROTECTION ASSOCIATION

NET POSITIVE SUCTION HEAD

NOT IN CONTRACT

NORMALLY OPEN

NORMALLY CLOSED

MECHANICAL CONTRACTOR

MANUAL AIR VENT

MANUAL DAMPER

MANUFACTURERMFR

ARCH ARCHITECTURAL

DWG

DWV

Db

DEG(°)

DPR

DTF

DP

DN

CU.FT.

CTR

CU.YD.

DD

CU

CONN

CONT

CONTR

COP

CONST

COORD

CFH

CFM

CLG

CONC

CO

ASHRAE

BFP

BDD

ASME

BHP

AUTO

BOP

BOD

BTUH

BTU

BOS

BV

C

CUBIC YARD

DRAIN, WASTE, AND VENT

DOWN THRU FLOOR

DUCT MOUNTED SMOKE DETECTOR

DRAIN POINT

DRAWING

DAMPER

DRY BULB TEMPERATURE

DEGREE(S)

DOWN

COEFFICIENT OF PERFORMANCE

CONSTRUCTION

COPPER

CUBIC FEET

CENTER

CONNECTION

CONTINUATION

CONTRACTOR

COORDINATE

RECIRC

REINF

REQD

RH

RPM

RM

REV

RD

RA

RCP

REQUIRED

ROOM

REVISION

RETURN AIR

RECIRCULATING

REINFORCING

ROUND

PLBG

PSIG

QTY

PVC

PSI

PSIA

PRV

PRS

PL

QUANTITY

PILOT LIGHT

PLUMBING

AMERICAN SOCIETY OF MECHANICAL ENGINEERS

CONSTANT VOLUME

CUBIC FEET PER HOUR

CUBIC FEET PER MINUTE

BRITISH THERMAL UNIT PER HOUR

BRITISH THERMAL UNIT

BOTTOM OF STEEL

BUTTERFLY VALVE

CEILING

CLEAN OUT

CONCRETE

BACKFLOW PREVENTER

BOTTOM OF PIPE

BOTTOM OF DUCT

BACKDRAFT DAMPER

AND AIR CONDITIONING ENGINEERS

BOILER HORSEPOWER OR BRAKE HORSEPOWER

AUTOMATIC

NIC

OPNG

NPSH

OA

P.C.

OD

OC

NTS

NO.

NO

OUTSIDE AIR

ON CENTER

OPENING

NOT TO SCALE

NUMBER

NFPA

NEMA

NC

NEC

MOD

MTD

MIN

MH

ASSOCIATION

MOUNTED

MINIMUM

MANHOLE

AD

AFMS

ALUM

AFF

AC/HR

AP

ANSI

APPROX

AMCA

ABV.CLG.

AIR MOVEMENT AND CONTROL ASSOCIATION

AMERICAN NATIONAL STANTDARDS INSTITUTE

ANCHOR POINT

AIR FLOW MONITORING STATION

ACCESS DOOR

ABOVE FINISHED FLOOR

AIR CHANGES PER HOUR

ALUMINUM

APPROXIMATE

ABOVE CEILING

POUNDS OR NUMBER

ROUND, DIAMETER OR PHASE

LSWER

MEZZ

MECH

MFG

MD

MAX

MC

MBH

MAV

MEZZANINE

MANUFACTURING

MECHANICAL

MAXIMUM

BTUH x 1000

LF

LP

LWT

LINEAR FEET

LOW PRESSURE

FSS FUSED SAFETY SWITCH

S/S STAINLESS STEEL

RVNR REDUCED VOLTAGE, NON-REVERSING, MAGNETIC

FVNR FULL VOLTAGE, NON-REVERSING, MAGNETIC

MRS MOTOR RATED SWITCH

W WATTS

ACU-1 AIR CONDITIONING UNIT & TAG

AHU-1 AIR HANDLING UNIT & TAG

CC COOLING COIL

CP-1 CONDENSATE PUMP & TAG

DB DECIBELS

Dp DEWPOINT TEMPERATURE

EDH ELECTRIC COIL DUCT HEATER

CUH-1 CABINET UNIT HEATER & TAG

CU-1 CONDENSING UNIT & TAG

CW COLD WATER (DOMESTIC)

EER ENERGY EFFICIENCY RATIO

EF-1 EXHAUST FAN & TAG

E or EX. EXISTING

FCU-1 FAN COIL UNIT & TAG

H&V-1 HEATING AND VENTILATING UNIT & TAG

NOT ALL ABBREVIATIONS

SHOWN IN THIS LIST WERE

UTILIZED FOR THIS PROJECT.

AMERICAN SOCIETY OF HEATING, REFRIGERATING,

AFLD AUTOMATIC FLOW LIMITING DEVICE

NOT APPLICABLEN/A

GENERAL PROJECT NOTESMECHANICAL ABBREVIATIONS( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )MECHANICAL SYMBOLS

DUCTWORKVALVES

GAUGE CONNECTION ONLY

PLUG VALVE WITH PRESSURE

GLOBE VALVE

THREE WAY VALVE

AUTOMATIC CONTROL VALVE

ANGLE VALVE

BALL VALVE

ISOLATION VALVE

CHECK VALVE

BUTTERFLY VALVE

TRIPLE DUTY VALVE

CONTROL VALVE

PRESSURE INDEPENDANT

ACCESSORIES

THERMOMETER WELL AND CAP ONLY

THERMOMETER WITH WELL

UNION

LINE PRESSURE RELIEF VALVE

PRESSURE GAGE WITH COCK

MANUAL AIR VENT POINT ON PIPE

LOW PRESSURE TRAP ASSEMBLY

MEDIUM PRESSURE

AUTOMATIC FLOW LIMITING DEVICE

REDUCED PRESSURE

PIPE UP

PIPE DOWN

STRAINER

BACKFLOW PREVENTER

(SEE SPECS)

FLOW SWITCH

TRAP ASSEMBLY

DIRECTION OF FLOW

FLOW CONTROL DEVICE

ECCENTRIC REDUCER

DRAIN POINT OF PIPE

DIRECTION OF SLOPE

ANCHOR POINT

CONCENTRIC REDUCER

FLOW METER

PRESSURE AND TEMP. TEST PORT

FM

MISCELLANEOUS

DRAWING NUMBER WHERE SECTION

DUCT SYMBOL: FLAT OVAL

EMERGENCY STOP SWITCH

DIRECTION OF AIR FLOW

CONNECT TO EXISTING SYMBOL

12x10 DUCT SYMBOL: RECTANGULAR

THERMOSTAT

IS LOCATED

T

FLOOR DRAIN

SECTION NUMBER

HUMIDISTATH

ESS

CFM

ARROW AND CFM

DUCT SYMBOL: ROUND12∅

12/12

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

M4.1

M4

SIDEWALL RETURN REGISTER

CEILING RETURN GRILLE/

SIDEWALL EXHAUST REGISTER

CEILING EXHAUST GRILLE/

DUCTWORK W/O DUCTLINER

SIDEWALL SUPPLY REGISTER

CEILING SUPPLY DIFFUSER/

TRANSITION

OVAL TRANSITION

SQUARE TO ROUND/

CONICAL TAKEOFF

RECTANGULAR DUCT

MITERED TAKEOFF

(SEE SCH)

(SEE SCH)

REGISTER (SEE SCH)

(SEE SCH)

REGISTER (SEE SCH)

REGISTER (SEE SCH)

EXHAUST DUCT UP

SUPPLY AND RETURN SIMILAR

RETURN DUCT DOWN

SUPPLY AND EXHAUST SIMILAR

SUPPLY DUCT, UP THROUGH ROOF

RETURN AND EXHAUST SIMILAR

EQUIPMENT

MOTOR OPERATED DAMPER

DAMPER WITH ACCESS DOOR

COMBINATION FIRE/SMOKE

DOOR

ACCESS DOOR

DETECTOR WITH ACCESS

DUCT MOUNTED SMOKE

SMOKE DAMPER WITH

WITH ACCESS DOOR

MANUAL DAMPER

ACCESS DOOR

FIRE DAMPER WITH

HUMIDIFIER WITH ACCESS

DOOR

AIR FLOW

MONITORING STATION

DUCT MOUNTED COIL

DUCT MOUNTED COIL

(ELECTRIC)

(HOT WATER OR STEAM COIL)

AIR VALVE

FSD

SD

M

FD

DD

NO SCALE

500 CFM

1 - 4 - XC

VARIABLE OR CONSTANT VOLUME BOX WITH REHEAT

1 GPM

BOX NUMBER (C OR V INDICATES

HOT WATER GPM

CONSTANT OR VARIABLE FLOW)

VARIABLE OR CONSTANT REGULATOR

ACCESS DOOR

SUPPLY CFM

REHEAT COIL

FLOOR

AIR HANDLING UNIT NUMBER

PIPING

HWR

HWS HOT WATER SUPPLY

HOT WATER RETURN

D

CHWS

CHWR

DRAIN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

TO REMAIN

TO BE REMOVED

EXISTING DUCT

EXISTING EQUIPMENT

TO REMAIN

TO BE REMOVED

EXISTING PIPING

EXISTING PIPING

TO REMAIN

EXISTING CONDENSATE DRAIN

TO BE REMOVED

EXISTING EQUIPMENT

TO REMAIN

EXISTING DUCT

NEW EQUIPMENT

NEW PIPING

NEW

DUCTWORK

D

A. ALL DUCT, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED TO

COMPLY WITH STATE BUILDING CODE.

B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE LOCATION

AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS, LIGHT FIXTURES,

STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE NOT SHOP DRAWINGS.

SUBMIT DUCTWORK COORDINATION DRAWINGS, AS SPECIFIED.

C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES AVAILABLE FOR

MECHANICAL EQUIPMENT AND PROVISION ALL STARTERS AND DISCONNECT

SWITCHES WITH ELECTRICAL CONTRACTOR.

D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING A

CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE STATIC

PRESSURE OF THE UNIT SUPPLY FAN.

E. ALL EQUIPMENT SHALL BE U.L. LISTED.

F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT;

PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL STARTERS, AND MOUNT

AND WIRE VFD, UNLESS OTHERWISE NOTED.

G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE ACCORDANCE

WITH THE MFR'S. U.L. LISTING AND INSTALLATION INSTRUCTIONS. FIRE AND

SMOKE DAMPERS SHALL HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION

IN WHICH THEY ARE INSTALLED.

H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH

OTHER TRADES TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK

INSTALLED BY THIS CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK

OF COORDINATION BETWEEN TRADES, SHALL BE CHANGED AS DIRECTED BY

THE ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE

CONTRACTOR.

I. SMOKE DETECTORS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR AND

INSTALLED BY THE MECHANICAL CONTRACTOR. PROVIDE DUCT ACCESS DOOR

AT EACH DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH

THE MANUFACTURER'S INSTRUCTIONS.

J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH ROOFING

CONTRACTOR.

K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF DUCTWORK TO

ENSURE DUCTWORK DOES NOT PASS OVER ELECTRICAL PANELS.

L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE

SCALE, WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.

M. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE

OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF TWO

WEEKS.THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS

AND SHALL BE AT THE OWNERS DISCRETION.

N. PROVIDE ESCUTCHEON PLATES WHERE DUCTS PENETRATE CEILINGS OR WALLS

IN AREAS EXPOSED TO VIEW. ESCUTCHEONS FOR DUCTS SHALL BE

CONSTRUCTED OF SAME MATERIAL AS DUCT. PIPE ESCUTCHEONS SHALL BE

CHROME-PLATED BRASS.

O. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED DAMPERS,

FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE DETECTORS, AND

SIMILAR ITEMS REQUIRING MAINTENANCE OR ADJUSTMENT.

P. PROVIDE FIRE CAULKING OR OTHER APPROVED FIRESTOP SYSTEM AT ALL

MECHANICAL PIPING PENETRATIONS OF RATED ASSEMBLY WITHIN THE LIMITS OF

CONSTRUCTION (NEW AND EXISTING).

Q. SEISMICALLY SUPPORT DUCTWORK, AIR HANDLING UNIT, PIPING, ETC. AS

REQUIRED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:3

A

M

M001

MECHANICAL - SYMBOLS, NOTES

AND DRAWING INDEX

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

MECHANICAL - DRAWING INDEX

Sheet

Number Sheet Name

M001 MECHANICAL - SYMBOLS, NOTES AND DRAWING INDEX

M002 MECHANICAL - DETAILS

M003 MECHANICAL - SCHEDULES

M004 MECHANICAL - AHU CONTROL SCHEMATICS

MD100 MECHANICAL - LEVEL 03 - DEMOLITION - DUCTWORK

MH100 MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - OVERALL

MH100A MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - AREA A

MH100B MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - AREA B

MP100 MECHANICAL - LEVEL 03 - NEW WORK - PIPING

Rev. No. Revisions: Date:

NOTES:

1. ROLLERS, SHOES AND SUPPORTS SELECTED PER PIPE SIZE

2. SECURE W/APPROVED ANCHORS TO MATCH BASE MATERIALS AND

LOAD REQUIREMENTS

TYP FOR TRAPEZE

OR BASE MOUNTED

SEE NOTE 2

SIMILAR TO UNISTRUT P 2474 GALV CI ROLLERS

BOLTED TO P 1000 GALV CHANNEL

PIPE W

INSULATION

TYPE 44

ROLLER

BASE

MOUNTED

INSULATE AS REQD

ATTACH TO

STRUCTURE

WITH PROTECTIVE

SPRING CUSHION

W/OR W/OUT TYPE 48

VIBRATION ISOLATOR

TYPE 1 CLEVIS HANGER

SADDLE OR SHIELD

TYPE 40

PROTECTIVE

SHIELD

STACKED CHILLED WATER CONTROL

VALVE PIPING

NOTES:

1. INSTALL AIR VENT AT HIGH POINTS ON PIPING.

2. INSTALL DRAIN VALVES AT LOW POINTS OF PIPING.

3. EXTEND COIL VENTS AND DRAINS (IF PROVIDED BY COIL MANUFACTURER)

THROUGH AIR HANDLING UNIT HOUSING.

4. INSTALL FLOW CONTROL DEVICE MINIMUM OF 10 PIPE DIAMETERS STRAIGHT PIPE

(OR MORE IF REQUIRED BY MANUFACTURER) DOWNSTREAM OF NEAREST FITTING.

(LUG TYPE)

BUTTERFLY VALVE

PT TEST PLUG

SUPPLY

RETURN

UNION

THERMOMETER

MANUAL AIR VENT

BUTTERFLY VALVE

AIR FLOW

DRAIN VALVE

PRESSURE

INDEPENDENT

2-WAY CONTROL VALVE

WITH STRAINER

VICTAULIC COUPLING

OR UNION

TYPE 44 SINGLE ROLLER PIPE GUIDE AND

SUPPORT

TYPE 1 CLEVIS HANGER

DN

3 3

A

A

Section A-ANOTES:

1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR

PARTITION TYPE & RATING ENCOUNTERED.

2. THROUGH PENETRATION (INSULATED OR BARE DEPENDING ON SERVICE) -

PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE & MATERIAL OF THROUGH

PENETRATION UTILIZED.

3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL

ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR

CAVITY ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM

UTILIZED.

ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL

LISTED FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE

SEPARATION PENETRATED AND THE THROUGH PENETRATION MATERIAL.

DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE

AVAILABLE AT THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION

AND SHALL BE PROVIDED TO THE BUILDING OWNER AT THE PROJECT

COMPLETION.

PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER

AND UL LISTED ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE

STOPPING SYSTEM IS INSTALLED.

THROUGH PENETRATION FIRESTOP SYSTEM

(PROVIDE UL LISTED SYSTEM)

SIDE VIEW

ELEVATION CHANGE - OGEE TRANSITION

DETAIL

PLAN VIEW

R .5

D

D

NOTES:

1. CHANGES IN DUCTWORK ELEVATION SHALL BE ACCOMPLISHED BY UTILIZING

RADIUS ELBOW TRANSITIONS EQUAL TO NO LESS THAN R=1.5D. IN ORDER TO

MINIMIZE DUCT STATIC PRESSURE LOSSES.

2. ELEVATION TRANSITION ARROW INDICATING UP OR DOWN (DN) IS SHOWN WITH

RESPECT TO AIRFLOW DIRECTION.

R

RECTANGULAR SHEETMETAL ELBOWS

TYPE RE 2 SQUARE

THROAT

ELBOW WITH VANES

TYPE RE 1 RADIUS ELBOW

AIR

FLOW

BRANCH DUCT

BRANCH DUCTWORK TAKEOFFS

MAIN EXHAUST OR

RETURN AIR FLOW

NOTE:

ALL BRANCH TAKEOFFS SHALL BE 45°, CONICAL OR BELLMOUTH TYPE.

AIR

FLOW

BRANCH DUCT

MAIN SUPPLY

AIR FLOW

VOLUME DAMPER (REFER

TO

VOLUME DAMPER DETAIL).

VOLUME DAMPER (REFER

TO

VOLUME DAMPER DETAIL).

DUCT

MANUAL VOLUME DAMPER WITH

QUADRANT LOCKING DEVICE,

WITH STANDOFF RUSKIN MODEL

MDRS25 OR EQUAL.

EXTEND TAP AS REQ.D TO

ALLOW

MAX 5' LENGTH OF FLEX DUCT

BETWEEN CONNECTION AND

DIFFUSER

FLEX DUCT WITH

EXTERNAL BLANKET

INSULATION (TYP)

CONNECTIONS BETWEEN LOW PRESSURE DUCT

AND AIR DISTRIBUTION DEVICE

NOTES:

1. ONLY ONE 90° TURN ALLOWED IN FLEX DUCT. DUCT MUST BE PROPERLY

SUPPORTED TO PREVENT KINKING.

2. IF ADDITIONAL 90° TURNS ARE REQD TO CONNECT OUTLET TO DIFFUSER, EXTEND

TAP AND PROVIDE EXTERNALLY INSULATED SHEET METAL ELLS AS REQD.

SEAL WITH DRAW

BAND AT TAP

CONNECTION AND

DIFFUSER/FIXTURE

SEAL INSULATION TO

DUCT WITH CAULKING

AIR DISTRIBUTION DEVICE

SPIN IN COLLAR.

48"

2"

FINISH FLOOR

DEVICES BY ELECTRICAL

CONTRACTOR

THERMOSTAT

THERMOSTAT ALIGNMENT

NOTES:

1. PROPERLY COORDINATE DEVICE LOCATION TO ALIGN VERTICALLY.

VARIABLE OR CONSTANT VOLUME

TERMINAL UNIT WITH REHEAT

NOTES:

1. MAINTAIN CLEARANCE ON CONTROL SIDE OF BOX AND INSTALL

SO THAT ACCESS DOORS ARE NOT BLOCKED.

HWS

HWR

UNION

BALL VALVE

AFLD

AIR VENT

HOT WATER HEATING

COIL. (PROVIDE ACCESS

DOOR PRIOR TO COIL FOR

CLEANING COIL)

24" OF ROUND HARD

DUCTWORK

(VARIABLE VOLUME

BOX ONLY)

CENTER

AVERAGING

INLET

SENSOR

DDC CONTROLLER SHALL

BE FACTORY MOUNTED

HOSE END DRAIN

VALVE WITH CAP

2-WAY VALVE BY CONTROLS

CONTRACTOR, UNLESS NOTED

OTHERWISE ON PLANS

PRESSURE/

TEMPERATURE

TEST PLUG

J 120V TOGGLE DISCONNECT BY

TERMINAL MANUFACTURER.

120/24V TRANSFORMER BY

TERMINAL MANUFACTURER.

24V WIRING BY

CONTROLS

CONTRACTOR

120V BY ELECTRICAL

CONTRACTOR

120V WIRING

BY CONTROLS

CONTRACTOR

3NTS

2NTS

1NTS9NTS

10NTS 6NTS

7NTS

8NTS

11NTS

12NTS

EXTERIOR WALL SLEEVE DETAIL 13

NTS

EXTERIOR

WALL

INTERIOR

WALL

FILL W/

MASTIC

LINK SEAL

SCH. 10 ST. OR

C.I. WALL SLEEVE

1" MIN

PIPE O.D.

1" MIN

FIRE DAMPER 14

NTS

DUCT

SLEEVE

SLEEVE

DUCT

NOTES:

INSULATE

EXTERNALLY

AS REQD

FACTORY

STANDARD

SLEEVE

FIELD

FABRICATED

SLEEVE

MOUNTING ANGLE

FUSIBLE

LINK

1. FIRE DAMPER SHALL BE U.L. LABELED AND INSTALLED PER MANUFACTURER'S

REQUIREMENTS FOR U.L.

2. FIRE DAMPER RETAINING ANGLE SHALL BE SIZED PER MANUFACTURERS

REQUIREMENTS.

3. PROVIDE MINIMUM 12"X12" ACCESS DOOR IN DUCT FOR FUSIBLE LINK REPLACEMENT.

4. USE TYPE "C" FIRE.

5. FUSIBLE LINK SHALL BE RATED FOR 165°F

6. PROVIDE MINIMUM 12"X12" ACCESS DOOR FOR ALL FIRE DAMPERS.

NOTES:

1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE

SIMILAR FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION

1/8" [6mm] CLEARANCE

ALL AROUND

OUTSIDE END

BEARING

INSIDE END

BEARING

HANDLE

WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" [15mm]

ROUND ROD PIN

DUCTSTIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

VOLUME DAMPER DETAIL

DAMPER

BLADE

5NTS

FLARE CONNECTION

PIPE CAP

6" NIPPLE

SYSTEM PIPE

FULL SIZE TEE

1/4" LINE

1/4" BALL VALVE MANUAL AIR VENT,

EXTEND VENT LINE TO WITHIN 6" ABOVE

CEILING WHERE PIPING IS CONCEALED

ABOVE CEILING. PROVIDE HOSE END

ADAPTER AND END CAP.

NTS

15MANUAL AIR VENT

PRESSURE GAGE

ISOLATION VALVE

NIPPLE

MAIN

PIPE

NTS

16PRESSURE GAUGE DETAIL

BUTTERFLY

VALVE (LUG TYPE)

PT TEST PLUG

SUPPLY

FLOW CONTROL

DEVICE

RETURN

UNION

THERMOMETER

MANUAL AIR VENT

DRAIN

VALVE

TWO WAY VALVE

HW

S

HW

R

BUTTERFLY

VALVE

TYPICAL SINGLE HOT WATER COIL PIPING

NOTES:

1. INSTALL AIR VENT AT HIGH POINTS ON PIPING.

2. INSTALL DRAIN VALVES AT LOW POINTS OF PIPING.

3. EXTEND COIL VENTS AND DRAINS (IF PROVIDED BY COIL MANUFACTURER)

THROUGH AIR HANDLING UNIT HOUSING.

4. INSTALL FLOW CONTROL DEVICE MINIMUM OF 10 PIPE DIAMETERS STRAIGHT

PIPE (OR MORE IF REQUIRED BY MANUFACTURER

DOWNSTREAM OF NEAREST FITTING.

AIR

FLOW

NTS

FIRE DAMPER AT FLOOR PENETRATION

NOTES:

1. ALL DUCTWORK RISERS THAT RUN EXPOSED, SUCH AS THROUGH ATTIC

FLOORS AND MECHANICAL ROOM FLOORS SHALL BE PROVIDED WITH 3" (75mm)

HIGH CONCRETE CURB AROUND OPENING FOR DUCT.

2. ALL DETAILS SHALL COMPLY WITH FIRE DAMPER MANUFACTURER'S UL

MOUNTING AND INSTALLATION REQUIREMENTS.

3. WHERE HVAC AIR DUCT PENETRATES ONLY ONE FLOOR AND PROTECTED WITH

A FIRE DAMPER, AN AIR DUCT ENCLOSURE IS NOT REQUIRED.

4. HORIZONTAL DAMPER SHOWN, FOLLOW MANUFACTURER'S INSTRUCTIONS,

INCLUDING GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST

BE INSTALLED IN LINE WITH FLOOR AND NOT OUTSIDE THE PENETRATION.

5. GALVANIZED SLEEVE GAGE NOT LESS THAN CONNECTING DUCT, FASTEN

SLEEVE TO DAMPER AND FLOOR SLAB WITH PERIMETER ANGLES.

6. BREAKAWAY DUCT CONNECTION OF TYPES INDICATED IN SMACNA. ACCESS

PANELS: SIZE AND LOCATION TO PERMIT SERVICING FUSIBLE LINK OR LINKS.

18NTS

FIRE

BARRIER

SLAB

FIRE

BARRIER

SLAB

ACCESS

PANEL

TYPICAL DUCT INSULATION

TOP OF SLAB

DAMPER COLLAR EXTENSION IS

INTEGRAL PART OF SLEEVE

NTS

21AHU DRAIN TRAP DETAIL

DRAIN LINE SHALL BE AT LEAST THE SAME

SIZE AS THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR

TYPE M UNLESS NOTE BELOW IS MET

PITCH DOWN TOWARD DRAIN

CLEAN OUT

FLOOR SINK

DRAIN PAN

DIELECTRIC

FITTING

NOTES:

1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS INDOORS

AND DOES NOT PASS THROUGH RATED BARRIERS.

2. DIELECTRIC FITTINGS TO BE USED WHEN TWO DISSIMILAR METALS ARE TO

BE CONNECTED.

DRAW THRU

2" [50mm]

PLUS X

X

BLOW THRU

1" [25mm]

MINIMUM

2X

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

[2 m m

B A

STATIONARY LOUVER IN MASONRY WALL

NTS

35° DRAINABLE BLADE

STEEL ANGLE LINTELS

CONCRETE

BRICK

SEALANT

FOR OPENING AND LINTEL

REFER TO ARCH DRAWINGS

FACE

BLOCK

REMOVABLE BIRD EXCLUSION

SCREEN WITH 1/2" x 1/2" MIN GRID

METAL SILL TO DIRECT WATER OUTSIDE

& AWAY FROM BASE OF LOUVER

NOTES:

1. OVERALL SIZE OF OPENING SHOULD BE 1/4" AND 1/2" GREATER IN BOTH

DIRECTIONS THAN EXTERNAL DIMENSIONS OF LOUVER FOR SIZES < 48" AND > 48",

RESPECTIVELY.

2. MAX LOUVER WIDTH < 5FT, USE MULLION CONNECTED SECTIONS FOR GREATER

WIDTHS.

3. CAULK AND SEAL AROUND PERIMETER OF LOUVER SECTION AT WALL.

4. PROVIDE ALUMINUM OR GALV EXPANDED BIRD EXCLUSION SCREEN ON INSIDE (OR

OUTSIDE) OF LOUVER. (MIN FREE AREA 80% OF GROSS AREA) ATTACH TO OUTSIDE

IF BLADE SEPARATION IS > 2 1/2".

5. CONSTRUCT EXTRUDED LOUVER OF NON-FERROUS CORROSION RESISTANT

MATERIAL AND SECURE WITH SS OR ALUMINUM FASTENERS.

CONDENDING UNIT WALL-BRACKET/MOUNTING

NTS

NOTES:

1. ONCE BRACKET IS SECURED TO THE EXTERIOR WALL, PLACE THE CONDENSING

UNIT ON THE BRACKETS AND ADJUST AS NEEDED TO SECURE IT IN PLACE.

DUCTLESS SPLIT SYSTEM

NTS

OUTDOOR (CONDENSING) UNIT

WALL-MOUNTED

INDOOR (EVAPORATING)

UNIT)

REFRIGERANT PIPING - ROUTE

AND SIZE PER

MANUFACTURER'S

RECOMMENDATIONS.

CONDENSATE PIPING - SEE

MECHANICAL PLANS FOR

SIZE, ROUTING AND

TERMINATION.

DOOR FRAME

POWER PROVIDED BY EC. SEE

MECHANICAL SCHEDULE FOR

ELECTRICAL INFORMATION.

MOUNT TO EXTERIOR WALL

WITH MANUFACTURER'S

WALL-MOUNTING

HARDWARE. SEE DETAIL 20

ON THIS SHEET.

MANUFACTURER

PROVIDED WALL

PLATE. HANG THE

EVAPORATOR TO

THE WALL PLATE ON

THE WALL.

NOTE:

PROVIDE PIPE CLAMPS FOR VERTICAL

REFRIGERANT AND CONDENSATE DRAIN

PIPING ON EXTERIOR WALLS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:3

A

M

M002

MECHANICAL - DETAILS EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

TERMINAL

NO.

CFM

E.A.T.

(°F)

HEATING

L.A.T.

(°F)

MINIMUM

OPERATING

PD (in.wg)

GPM MBH

E.W.T.

(°F)

L.W.T.

(°F)

WATER

PRESSURE

DROP(FT)MAX. MIN.

AIR

RUNOUT

SIZE

UNIT SIZE

WATER

RUNOUT

SIZE

55 180 159

180 159

9-3-1V 700 350 10 14x12 114.4 0.16 2.2 22.6 0.32

540 270 08 12x10 0.20 1.7 16.9 0.40

ROWS

REHEAT

111.8

GENERAL NOTES

1. BOXES SHALL HAVE PIPE CONNECTIONS ON SAME SIDE AND BE FOR FLARED FITTINGS.

2. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.

3. BOXES SHALL BE SET FOR MAXIMUM CFM SHOWN ON PLANS.

4. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.

5. MAXIMUM WATER PRESSURE DROP SHALL BE 4 FEET.

6. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.

7. CONSTANT VOLUME BOXES SHALL BE THE SAME BOX USED FOR VARIABLE VOLUME BOX EXCEPT CFM SHALL BE LOCKED AT CAPACITY SHOWN. BOX SHALL NOT OPERATE AS

VARIABLE VOLUME.

8. CONTROLS SHALL BE DDC PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY BOX MANUFACTURER.

9. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.

3/4"

3/4"

TERMINAL UNIT SCHEDULE

SYMBOL REGISTER SIZE 24"x24"

136-210 CFM 8" ROUND NECK

0-135 CFM 6" ROUND NECK

211-325 CFM 10" ROUND NECK

326-475 CFM 12" ROUND NECK

651-840 CFM 16" ROUND NECK

841-2000 CFM 22"x22" NECK

476-650 CFM 14" ROUND NECK

CFM

CFM

CFM

CFM

CFM

CFM

CFM

NOTES:

1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

SYMBOL TYPICAL MODULE SIZE - 24"x24"

136-210 CFM 9"x9" FACE 8" ROUND NECK

0-135 CFM 6"x6" FACE 6" ROUND NECK

211-325 CFM 12"x12" FACE 10" ROUND NECK

326-475 CFM 12"x12" FACE 12" ROUND NECK

476-650 CFM 15"x15" FACE 14" ROUND NECK

CFM

CFM

CFM

CFM

CFM

CFM

CFM

650-840 CFM 18"x18" FACE 16" ROUND NECK

841-1125 CFM 18"X18" FACE & NECK

NOTES:

1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. PROVIDE ROUND NECK ADAPTER.

CFM RANGE, FACE SIZE, & NECK SIZE

CFM

0-120 CFM 6"X6" FACE 6" ROUND NECK

CFM

121-240 CFM 9"X9" FACE 8" ROUND NECK

12"x12" REGISTER

12"x12" REGISTER

CFM

CFM

CFM

0-120 CFM 6" ROUND NECK

12"x12" REGISTER

0-135 CFM 6" ROUND NECK

24"x12" REGISTER

0-130 CFM 6" ROUNDNECK

16"x16" REGISTER

PERFORATED RETURN REGISTERS

LOUVERED SUPPLY DIFFUSER

CFM

0-130 CFM 6"X6" FACE 6" ROUND NECK

24"x12" REGISTER

1000 500 12 16x14 0.17 3.2 32.6 0.77115.2 3/4"

410 210 08 12x10 0.13 1.4 13.9 0.28117.6 3/4"

800 400 10 14x12 0.20 2.4 24.6 0.38111.8 3/4"

10 14x12 0.20 2.4 24.6 0.38111.8 3/4"

06 12x08 0.12 1 10 0.14116.2 3/4"

450 225 08 12x10 0.15 1.5 14.8 0.31115.8 3/4"

SPLIT SYSTEM AIR HANDLING UNITS (DUCTLESS)

GENERAL NOTES:

1. INSTALL REFRIGERANT PIPING IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION

RECOMMENDATIONS. PROVIDE PIPING APPURTENANCES AS REQUIRED.

2. UNIT SHALL BE PROVIDED WITH THE FOLLOWING FACTORY INSTALLED ACCESSORIES: (MODEL

NUMBER WILL REFLECT SOME OF THESE ACCESSORIES BUT NOT NECESSARILY ALL)

· LOW VOLTAGE INDOOR UNIT

· INDOOR UNIT IS POWERED FROM OUTDOOR UNIT. MECHANICAL CONTRACTOR SHALL

CONNECT ELECTRICAL SERVICE FROM OUTDOOR CONDENSER TO INDOOR EVAPORATOR

UNIT.

· AUTO RESTART

· DEHUMIDIFICATION MODE

· CLEANABLE FILTERS

· WALL MOUNTED THERMOSTATS

3.

SYSTEM DESCRIPTION

OUTDOOR UNIT ELECT. CONN. MCA/MOCP

ELECTRICAL CHARACTERISTICS

COOLING EDB/EWB (°F)

GROSS COOLING CAP (MBH)

TOTAL CFM

UNIT TAG:

SEER

FAN MOTOR FLA

SPLIT SYSTEM

SSCU-1

SPLIT SYSTEM

SSEU-1

LOCATION 1ST FLOOR ROOF

CONDENSING UNIT EVAPORATOR UNIT

DUCTLESS SPLIT SYSTEM 1

OIT

1,940 775

15.5 15.5

0.75 0.36

208/1Ø 208/1Ø

25/40 SEE NOTE 2

95/75 80/67

30 30

PROVIDE UNIT WITH CONDENSATE PUMP.

9-3-2V

9-3-3V

9-3-4V

9-3-5V

9-3-6V

9-3-7V

9-3-8V

400800

300 150

SYMBOL REGISTER SIZE 24"x24"

136-210 CFM 8" ROUND NECK

0-135 CFM 6" ROUND NECK

211-325 CFM 10" ROUND NECK

326-475 CFM 12" ROUND NECK

651-840 CFM 16" ROUND NECK

841-2000 CFM 22"x22" NECK

476-650 CFM 14" ROUND NECK

CFM

A

CFM

B

CFM

C

CFM

D

CFM

E

CFM

F

CFM

G

NOTES:

1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

2. REGISTERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE

MOUNTED FRAMES.

12"x12" REGISTER

CFM

H

0-135 CFM 6" ROUND NECK

PERFORATED EXHAUST REGISTERS

159.1

159.1

159.1

159.1

159.1

4. PROVIDE LINESET OF EXTERIOR PIPING COVERING PIPES ROUTED ON EXTERIOR WALL.

400 200 08 12x10 0.12 1.3 13.7 0.27118.1 3/4"9-3-9V 200 55 2 180 159.1

5. MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT WITH INDOOR UNIT.

UH NO. LOCATION E.A.T. °F L.A.T. °F GPM CAPACITY

BTU/HR MIN.

UH-1 MECHANICAL 312C 94

NOTES:

1. PROVIDE DISCONNECT SWITCHES FOR EACH UNIT.

HYDRONIC UNIT HEATER SCHEDULE

60 1.9 18,400

SYMBOL SIZE TYPE

111-250 CFM 10"x6"

0-110 CFM 8"x4"

251-480 CFM 14"x8"

481-650 CFM 18"x10"

651-835 CFM 18"x12"

836-1400 CFM 24"x18"

PRICE 530/630

PRICE 530/630

PRICE 530/630

PRICE 530/630

PRICE 530/630

PRICE 530/630

ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 5145/6145, TITUS 350FL/350RL.

SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.

SIDEWALL EXHAUST REGISTER

CFM

A

CFM

B

CFM

C

CFM

D

CFM

E

CFM

F

CFM

VOLTS/

PHASE

120/1

RPM

MCA

1.0

MOCP

1.8

6. PROVIDE MANUFACTURER-SUPPLIED WALL-MOUNTING HARDWARE FOR EVAPORATOR AND

CONDENSING UNITS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:3

A

M

M003

MECHANICAL - SCHEDULES EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

NTS

AHU-09 CONTROLS SCHEMATIC 1

DP

HSTS

LL

RETURN

SUPPLY

AFMS

RELIEF

DAMPER

M

PRE-

FILTER

HEATING

COIL

COOLING

COIL AFMS

SUPPLY

FAN

LEGEND

AFMS - AIR FLOW MONITORING STATION

DD - DUCT DETECTOR

DP - DIFFERENTIAL PRESSURE

AHS - AVERAGING HUMIDITY SENSOR

AHSPS - AVERAGING HIGH STATIC PRESSURE SENSOR

LL - LOW LIMIT

SP - STATIC PRESSURE SENSOR

ATS - AVERAGING TEMPERATURE SENSOR

VFD - VARIABLE FREQUENCY DRIVE

M

OUTSIDE AIR

DAMPER

M

OUTSIDE

AIR

AFMS

RELIEF

V

D F

RETURN AIR

DAMPER

V

D F

RETURN

FANS

AIR HANDLING EQUIPMENT

VARIABLE AIR VOLUME AIR HANDLING UNIT (AHU-09)

1. OCCUPIED MODE

A. THE AHU WILL START ON COMMAND FROM THE BAS, WHEN THE HOA SWITCH IS IN THE "AUTO" MODE. THE AHU MAY ALSO BE STARTED LOCALLY WHEN THE HOA

SWITCH IS PLACED IN THE "HAND MODE".

B. WHEN THE AIR HANDLER IS COMMANDED TO START THE OUTDOOR AIR DAMPER SHALL BE OPENED 100% AND PROVE "OPEN" BASED ON INPUT FROM THE DAMPER END SWITCH, PRIOR TO STARTING THE SUPPLY AND RETURN FANS. IF THE OUTDOOR AIR DAMPERS DO NOT PROVE OPEN THE FAN SHALL REMAIN OFF AND AN ALARM SHALL BE ROUTED TO THE OPERATOR'S WORKSTATION. ONCE THE OUTDOOR AIR DAMPER IS VERIFIED OPEN, THE DAMPER SHALL MODULATE TO MINIMUM

POSITION.

C. WITH THE OUTDOOR DAMPER VERIFIED OPEN THE VFD SHALL START AND MODULATE THE SUPPLY AND RETURN FANS. CURRENT TRANSFORMER (CT) SWITCHES SHALL SIGNAL THE CONTROLLER TO VERIFY OPERATION OF THE SUPPLY AND RETURN FANS. IF SUPPLY FAN OPERATION IS NOT VERIFIED WITHIN 30 SECONDS (CUSTOMER ADJUSTABLE) THEN THE UNIT SHALL BE SHUT DOWN AND AN ALARM BE ROUTED TO THE OPERATORS WORKSTATION. IF THE RETURN FAN OPERATION IS NOT VERIFIED THE UNIT SHALL CONTINUE TO OPERATE AND AN ALARM SHALL BE ROUTED TO THE OPERATORS WORKSTATION.

D. THE AHU SHALL STOP WHEN COMMANDED BY THE BAS, OR WHEN THE HOA SWITCH IS PLACED IN "HAND". THE UNIT SHALL SHUT DOWN BY FIRST COMMANDING OFF THE FAN VFDS, WHEN THE FANS ARE PROVEN OFF (BY THE CT INPUT) THE OUTDOOR AIR DAMPER SHALL THEN BE CLOSED.

2. UNOCCUPIED MODE

A. WHEN IN UNOCCUPIED MODE, THE UNIT SHALL BE DE-ENERGIZED (FANS OFF, OUTSIDE AIR DAMPER CLOSED).

B. IN UNOCCUPIED MODE, WHEN A MINIMUM OF TWO (2) (ADJ.) VAV TERMINAL UNITS CALL FOR HEATING OR COOLING, THE AIR HANDLING UNIT SHALL BE ENERGIZED.

THE UNIT SHALL OPERATE NORMALLY IN EITHER HEATING OR COOLING MODE, BUT THE OUTSIDE AIR DAMPER SHALL BE CLOSED. ECONOMIZER SHALL BE DISABLED

DURING UNOCCUPIED MODE.

3. THE AHU WILL STOP (FANS OFF, ALL DAMPERS CLOSED) AND AN ALARM BE ROUTED TO THE OPERATORS WORKSTATION WHEN ANY OF THE FOLLOWING CONDITIONS

OCCUR:

A. IF EMERGENCY STOP SWITCH IS IN "PUSHED" POSITION, THEN THE SWITCH MUST BE MANUALLY "PULLED" IN ORDER TO RESTART THE AHU.

B. IF HIGH DISCHARGE PRESSURE SWITCH LOCATED IN THE UNIT AND AFTER THE SUPPLY FAN IS TRIGGER DUE TO HIGH PRESSURE, THE AHU SHALL SHUT DOWN AND

WILL NOT RESTART AUTOMATICALLY. (HIGH STATIC PRESSURE SWITCH SHALL BE SET ACCORDING TO TEST AND BALANCE'S INSTRUCTION.)

C. IF THE VAPOR TENSION LOW LIMIT THERMOSTAT ("FREEZESTAT") SENSE A TEMPERATURE BELOW 35 DEGREES (SHALL REQUIRE A MANUAL RESET.)

D. IF RETURN DUCT HIGH TEMPERATURE ("FIRESTAT") IS TRIGGERED, THE AHU SHALL SHUT DOWN AND WILL NOT RESTART. (SET AT 125 DEGREES, F.)

E. SMOKE MODE - IF ANY OF THE DUCT MOUNTED SMOKE DETECTORS (FURNISHED AND INSTALLED BY DIVISION 28) AND INSTALLED IN THE SUPPLY AIR STREAM

DETECT SMOKE OR A SPACE DETECTOR DETECTS SMOKE THE SUPPLY AIR FANS AND RETURN AIR FANS SHALL SHUT DOWN AND ALL DAMPERS SHALL CLOSE.

4. DISCHARGE CONTROL

A. THE PRE-HEAT COIL AIR TEMPERATURE SENSOR IS LOCATED DIRECTLY DOWNSTREAM OF THE PRE-HEAT COIL. CONTROL THE PRE-HEAT COIL DISCHARGE TEMPERATURE TO 50 DEGREES F (ADJUSTABLE) BY MODULATING THE PRE-HEAT COIL CONTROL VALVE.

B. THE COOLING COIL AIR TEMPERATURE SENSOR IS LOCATED DIRECTLY DOWNSTREAM OF THE COOLING COIL. CONTROL THE COOLING COIL DISCHARGE TEMPERATURE TO 60 DEGREES F (ADJUSTABLE) BY MODULATING THE COOLING COIL CONTROL VALVE.

C. THE PRE-HEAT VALVE WILL FAIL SAFE TO THE NORMAL OPEN POSITION. WHEN THE OA TEMPERATURE FALLS BELOW 45 DEGREES (SET POINT ADJUSTABLE), THE PRE-HEAT VALVE SHALL MODULATE TO MAINTAIN DOWNSTREAM AIR TEMPERATURE SET POINT. WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 50 DEGREES (SET

POINT ADJUSTABLE), THE PRE-HEAT CONTROL VALVE SHALL CLOSE.

D. AHU COILING COILS SHALL UTILIZE A STANDARD CONTROL VALVE ARRANGEMENT AND SHALL BE CONTROLLED AS FOLLOWS:

a. ON AN INCREASE IN COOLING LOAD, THE CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SET POINT. UPON A

DECREASE IN COOLING LOAD, THE CONTROL SHALL MODULATE CLOSED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SET POINT.

5. SUPPLY FAN CONTROL

A. MODULATE ALL VFD'S AT THE SAME SPEED TO MAINTAIN THE SUPPLY AIR DUCT STATIC PRESSURE SENSOR WITH THE LOWEST READING AT SET POINT. A STATIC

PRESSURE TRANSMITTER SHALL BE LOCATED 2/3 DOWN THE LONGEST DUCT.

B. IF THE STATIC PRESSURE SENSOR BECOMES UNRELIABLE, THE CONTROLLER WILL COMMAND THE SUPPLY FAN VFD TO ITS MINIMUM SPEED AND AN ALARM SHALL

BE ROUTED TO THE OPERATOR'S WORKSTATION.

C. RESET THE DUCT STATIC PRESSURE SENSOR TO KEEP AT LEAST ONE VAV BOX SUPPLY AIR DAMPER AT 95% OPEN.

6. RETURN FAN TRACKING

A. THE RETURN FAN AIRFLOW SHALL TRACK THE SUPPLY AIRFLOW UTILIZING AN OFFSET VALUE AS MEASURED WITH THE AIRFLOW MONITORS IN THE UNIT. THE OFFSET SHALL BE ESTABLISHED AT FINAL TEST AND BALANCE TO KEEP THE BUILDING AT SLIGHTLY POSITIVE PRESSURE.

7. ECONOMIZER MODE

A. OUTSIDE AIR TEMPERATURE SHALL BE COMPARED WITH A REFERENCE DRY BULB SETPOINT (OWNER ADJUSTABLE). ECONOMIZER MODE SHALL BE ENABLED WHEN

THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE REFERENCE DRY BULB SETPOINT. ECONOMIZER MODE SHALL BE DISABLED WHEN THE OUTSIDE AIR

TEMPERATURE IS GREATER THAN THE REFERENCE DRY BULB SETPOINT.

B. THE DISCHARGE AIR SENSOR SHALL MEASURE THE DRY BULB TEMPERATURE OF THE AIR LEAVING THE COOLING COIL WHEN ECONOMIZER MODE IS ENABLED. THE OUTSIDE AIR DAMPER SHALL MODULATE BETWEEN IT'S MINIMUM POSITION AND 100% TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT.

C. OUTSIDE AIR DAMPER SHALL MODULATE TO MINIMUM POSITION IN EVENT MIXED AIR TEMPERATURE FALLS BELOW LOW LIMIT TEMPERATURE SETTING AND

ECONOMIZER MODE SHALL BE DISABLED.

D. WHEN THE ECONOMIZER MODE IS DISABLED THE OUTDOOR AIR DAMPER SHALL BE SET TO MINIMUM POSITION REQUIRED BY VENTILATION.

VAV TERMINALS

1. ALL VAVS SHALL OPERATE ON A 7-DAY OCCUPIED/UNOCCUPIED SCHEDULE. INITIAL OCCUPIED SCHEDULE SHALL BE MONDAY – FRIDAY FROM 8:00AM TO 5:00PM AND SHALL

BE FULLY ADJUSTABLE VIA THE BAS.

2. SPACE TEMPERATURE SETPOINTS IN EACH MODE SHALL BE AS FOLLOWS AND SHALL BE FULLY ADJUSTABLE VIA THE BAS:

COOLING HEATING

OCCUPIED MODE 72 DEF F 68 DEG F

UNOCCUPIED MODE 78 DEF F 62 DEG F

3. PROVIDE PRESSURE INDEPENDENT CONTROL (I.E., THE SUPPLY AIR CFM SET POINT IS RESET TO MAINTAIN THE SPACE TEMPERATURE COOLING SET POINT.)

4. OCCUPIED / UNOCCUPIED MODE - INDEX BASED ON THE ASSOCIATED ZONE'S TIME SCHEDULE (OR THAT FOR THE AHU IF ALL BOXES SERVED THE BY THE AHU HAVE THE

SAME SCHEDULE) OR BY THE ASSOCIATED OCCUPANCY SENSOR. THE SUPPLY AIR DAMPER AND REHEAT COIL VALVE SHALL BE CLOSED IF THE ASSOCIATED AHU IS OFF.

5. HEATING - MODULATE THE HEATING COIL TO MAINTAIN THE OCCUPIED OR UNOCCUPIED SPACE HEATING SET POINT WHILE MAINTAINING THE BOX SUPPLY AIR CFM AT THE

MINIMUM SETTING FOR THE HEATING MODE (WHICH MAY BE A DIFFERENT VALUE THAN THAT FOR COOLING IF PROVIDED).

6. COOLING OPERATION - DO NOT RESET THE SUPPLY AIR CFM BELOW THE MINIMUM SUPPLY AIR SET POINT OR ABOVE THE MAXIMUM.

7. DEADBAND - PROVIDE A DEADBAND BETWEEN THE HEATING AND COOLING SPACE TEMPERATURE SET POINTS IN WHICH THE MINIMUM SUPPLY AIR CFM IS DELIVERED AND

NO HEATING IS PROVIDED.

8. MINIMUM SUPPLY AIR SET POINT (WHEN COOLING OR IN THE DEADBAND) - THE SET POINT SHALL BE THAT NEEDED FOR VENTILATION WHILE OPERATING IN THE OCCUPIED

MODE ONLY; OTHERWISE THE MINIMUM SHALL BE "ZERO" (I.E., DURING AHU UNOCCUPIED HEATING / COOLING, OR AHU WARM-UP OR COOL-DOWN DUE TO OPTIMUM START.)

HYDRONIC UNIT HEATER

1. ELECTRIC UNIT HEATERS EUH-1 SHALL BE CONTROLLED BY LINE-VOLTAGE THERMOSTATS INTEGRAL TO THE UNITS. THERMOSTATS SHALL BE PROVIDED BY THE UNIT MANUFACTURER. TEMPERATURE SETPOINT SHALL BE SET AT 60 DEG F AND SHALL BE ADJUSTABLE AT THE UNIT.

2. A SPACE TEMPERATURE SENSOR SHALL BE LOCATED IN THE MECHANICAL ROOM AT THE LOCATION SHOWN ON THE FLOOR PLAN. SENSOR SHALL REPORT BACK TO THE BUILDING AUTOMATION SYSTEM. A LOW SPACE TEMPERATURE ALARM SHALL BE DISPLAYED ON THE BAS WHEN THE SPACE TEMPERATURE DROPS BELOW 55 DEG F (ADJ.).

SEQUENCE OF OPERATION

REMARKS:

SERVES

TYPE UNIT

LOCATION

SYSTEM NO.

REMARKS:

REMARKS:

FILTER TYPE

VIBRATION ISOLATORS

MOTOR OPER. SMOKE DAMPERS

DISCHARGE AIR PLENUM W/AD

RETURN AIR PLENUM W/AD

MIXING SECTION W/AD

TOTAL CFM

SYSTEM TYPE

ECONOMIZER

OUTSIDE AIR (CFM)

DISCONNECT SWITCH BY E.C.

S U

P P

L Y

F A

N A

C C

E S

S

P R

E -F

IL

T

E R

H E

A T

IN

G

C O

IL

E

L E

C T

R

IC

A L

AIR HANDING UNIT SCHEDULE

C O

O L

IN

G C

O

IL

YES

YES

6,000

VARIABLE VOLUME

THIRD FLOOR EHRM

MECHANICAL - 312B

AHU-09

1,400

2" PLEATED

6,000

CHILLED WATER

6,000

HOT WATER

CUSTOM

VOLTAGE/PHASE/HZ 460/60/3

MOCP MCA

CIRCUIT #1 - SUPPLY FAN MOTOR 25 A 14.40 A

TOTAL CFM

MBH TOTAL LOAD

EAT DB (°F)

LAT DB (°F)

TYPE COIL & PRESSURE

REMARKS:

6,000

NONE

TOTAL CFM

TOTAL LOAD (MBH)

SENSIBLE LOAD (MBH)

EAT DB/WB (°F)

LAT DB/WB (°F)

TYPE COIL

ROWS MIN.

REMARKS

TOTAL CFM

EXTERNAL STATIC PRESSURE (IN WG)

TOTAL STATIC PRESSURE (IN WG)

WHEEL DIAMETER MIN. (IN)

RPM APPROX.

TYPE DRIVE

HP MIN/VOLT/PH/HZ

NONE

FILTER MINIMUM EFFICIENCY

FILTER AREA (SQFT)

NO

YES

YES

YES

ROWS MINIMUM

FINS/FT MINIMUM

FLOW RATE (GPM)

SQFT FACE AREA MIN.

FACE VELOCITY MAX. (FPM)

AIR PRESSURE DROP (INCHES H2O)

FINS PER FOOT MAX.

SQFT FACE AREA MIN.

FACE VELOCITY MAX.

EWT (°F)

LWT (°F)

GPM

AIR PRESSURE DROP (IN WG)

WATER PRESSURE DROP (FT WG)

TYPE FAN

CLASS FAN

ARRANGEMENT

VFD

FILTER PRESSURE DROP (INWG)

CIRCUIT #2 - RETURN FAN MOTOR 15 A 6.0 A

MERV 8

16.67

0.595

0.13

11.25

12.3

0.50

6.0

NONE

2.00

3.75

22.25

1,808

DIRECT

7.5/460/3/60

PLENUM

CLASS II

1X1

YES

REMARKS:

R E

T U

R N

F A

N

6,000TOTAL CFM

EXTERNAL STATIC PRESSURE (IN WG)

TOTAL STATIC PRESSURE (IN WG)

WHEEL DIAMETER MIN. (IN)

RPM APPROX.

TYPE DRIVE

HP MIN/VOLT/PH/HZ

NONE

TYPE FAN

CLASS FAN

ARRANGEMENT

VFD

1.00

1.20

1,592

DIRECT

3.0/460/3/60

PLENUM

CLASS II

1X1

YES

NONE

WATER PRESSURE DROP (INCHES H2O) 4.54

SUPPLY AIR

DAMPERM

M

RETURN AIR

SMOKE DAMPER

TO FIRE

ALARM

SYSTEM

DD SPHSHSTS

DP

FINAL

FILTER

TSTSTSHSTS

D A

WALL-MOUNTED

TEMPERATURE

SENSOR W/

SETPOINT

ADJUSTMENT

HOT WATER

REHEAT COIL

SUPPLY AIR

TO SPACE

120/1Ph

TO AHU

CONTROL

LER

AIRFLOW

MEASURING

DEVICE

VOLUME

REGULATOR

T

TERMINAL UNIT CONTROL DIAGRAM

CONTROLLER

H

C

SUPPLY AIR

FROM AHU

NOTE: PROVIDE 2-WAY CONTROL

VALVES UNLESS OTHERWISE NOTED

TO BUILDING

AUTOMATION SYSTEM

AI

T

CONDENSING UNIT

REFRIGERANT

COOLING COIL

D

X

RETURN AIR

FILTER

SUPPLY FAN

DUCTLESS SPLIT SYSTEM DIAGRAM

N.T.S.

SPLIT SYSTEM AIR HANDLING UNIT CONTROL (TYPICAL)

SPACE TEMPERATURE CONTROL: THE SPACE TEMPERATURE CONTROLLED LOCALLY. A DDC TEMPERATURE

SENSOR SHALL BE PROVIDED. THIS TEMPERATURE SENSOR SHALL REPORT THE SPACE TEMPERATURE TO THE BAS.

ALARMS: ALARM IF SPACE TEMPERATURE REPORTED BY THE DDC TEMPERATURE SENSOR REPORTS A TEMPERATURE

ABOVE 80 DEGREES FAHRENHEIT.

PROVIDE DDC TEMP SENSOR

LOCATED IN EACH DIT ROOM

TT

T-1

BI-1

HIGH TEMPERATURE

AI-1

SPACE TEMPERATURE

PROVIDE DDC HUMIDITY SENSOR

LOCATED IN EACH DIT ROOM

HH

H-1

BI-1

HIGH HUMIDITY

AI-1

SPACE HUMIDITY

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:3

A

M

M004

MECHANICAL - AHU CONTROL

SCHEMATICS

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

FD

FD FD

FD

FD

NOT IN SCOPE

NOT IN SCOPE

(E)

(E) (E)(E)

(E)

2 2 2 2

(E)VAV

3 3

3 3 6"ø

6"ø 24"x12"

8"ø

"x

6"øCFM

CFM

CFM

NOT IN SCOPE

20"X20" EA UP

TO EXISTING

EXHAUST FAN

IN ATTIC.

A2

A3

A4 A5

A6 A7 A8 A9 A10 A11

A12 A13 A14

A15

A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED

TO COMPLY WITH THE STATE BUILDING CODE.

B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE

LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,

LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE

NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION

DRAWINGS, AS SPECIFIED.

C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES

AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL

STARTERS AND DISCONNECT SWITCHES WITH ELECTRICAL

CONTRACTOR.

D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING

A CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE

STATIC PRESSURE OF THE UNIT SUPPLY FAN.

E. ALL EQUIPMENT SHALL BE U.L. LISTED.

F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL

EQUIPMENT; PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL

STARTERS, AND MOUNT AND WIRE VARIABLE SPEED DRIVES, UNLESS

OTHERWISE NOTED.

G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE

ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND

INSTALLATION INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL

HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY

ARE INSTALLED. PROVIDE DYNAMIC FIRE DAMPERS.

H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH

OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT

RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN

TRADES, SHALL BE CHANGED AS DIRECTED BY THE

ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE

CONTRACTOR.

I. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM

CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR

UNLESS OTHERWISE NOTED. PROVIDE DUCT ACCESS DOOR AT EACH

DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH

THE MANUFACTURER'S INSTRUCTIONS.

J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH

ROOFING

CONTRACTOR.

K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF

DUCTWORK TO ENSURE DUCTWORK DOES NOT PASS OVER

ELECTRICAL PANELS.

L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION

PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL

REFERENCE ONLY.

M. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH

THE OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE

OF ONE WEEK. THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR

SOME SHUTDOWNS AND SHALL BE AT THE OWNERS DISCRETION.

N. LEAVE A MINIMUM CLEARANCE OF 2 INCHES ABOVE DUCTS INSTALLED

IN RATED PARTITIONS TO ALLOW SPACE FOR THE GENERAL

CONTRACTOR TO SEAL THE WALL ABOVE THE DUCTS. DO NOT INSTALL

FLEXIBLE DUCT THROUGH RATED WALLS, BARRIERS OR PARTITIONS.

O. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED

DAMPERS, FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE

DETECTORS, AND SIMILAR ITEMS REQUIRING MAINTENANCE OR

ADJUSTMENT.

P. MECHANICAL CONTRACTOR SHALL INSTALL MANUAL VOLUME DAMPERS

ON ALL BRANCH DUCTWORK CONNECTIONS.

Q. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.

GENERAL NOTES

EXISTING VAV BOX TO REMAIN.

EXISTING KEYED NOTES

EXISTING DUCTWORK EXTEND OUTSIDE SCOPE OF WORK.2

EXISTING AIR TERMINAL TO BE REMOVED, CLEANED AND RELOCATED AS

REQUIRED TO ACCOMODATE ARCHITECTURAL RENOVATIONS.

DEMOLISH EXISTING FIRE DAMPER COMPLETE. PATCH AND REPAIR WALL

AS REQUIRED.

DEMOLITION KEYED NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:3

A

M

MD100

MECHANICAL - LEVEL 03 -

DEMOLITION - DUCTWORK

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

1/8" = 1'-0"

MECHANICAL - LEVEL 03 - DEMOLITION - DUCTWORK

GRAPHIC SCALE

( in Feet )

1 inch = 8 ft.

8 84 16 32

FD

FD

DD

D D

OIT

320A

BRIEFING CENTER

320B

PRIVATE OFFICE

320D

PRIVATE OFFICE

320E

MECHANICAL

312C

CONFERENCE ROOM/ADHOC

WORK AREA

PIPE CLOSET

330A

CERNER ARCHITECTS

9-3-3V

1000 CFM

9-3-7V

300 CFM

9-3-8V

450 CFM

9-3-2V

540 CFM

9-3-4V

410 CFM 9-3-5V

800 CFM

9-3-6V

800 CFM

STORAGE

320C

PRIVATE OFFICE

320F

PRIVATE OFFICE

320G

CERNER CONTROL

CENTER/WORK SPACES

SSEU-1

AHU-09

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

(E)VAV

9-3-1V

700 CFM

SSCU-1

(E) (E)

(E)

(E)

RECEPTION

312A

RECEPTION

312A

WOMENS

CONFERENCE ROOM/ADHOC

WORK AREA

312B

A2

A3

A4 A5

A6 A7 A8 A9 A10 A11

A12 A13 A14

A15

9-3-9V

1.3 GPM

FIRST FLOOR ROOF

UH-1

SP

A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED

TO COMPLY WITH THE STATE BUILDING CODE.

B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE

LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,

LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE

NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION

DRAWINGS, AS SPECIFIED.

C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES

AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL

STARTERS AND DISCONNECT SWITCHES WITH ELECTRICAL

CONTRACTOR.

D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING

A CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE

STATIC PRESSURE OF THE UNIT SUPPLY FAN.

E. ALL EQUIPMENT SHALL BE U.L. LISTED.

F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL

EQUIPMENT; PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL

STARTERS, AND MOUNT AND WIRE VARIABLE SPEED DRIVES, UNLESS

OTHERWISE NOTED.

G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE

ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND

INSTALLATION INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL

HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY

ARE INSTALLED. PROVIDE DYNAMIC FIRE DAMPERS.

H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH

OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT

RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN

TRADES, SHALL BE CHANGED AS DIRECTED BY THE

ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE

CONTRACTOR.

I. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM

CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR

UNLESS OTHERWISE NOTED. PROVIDE DUCT ACCESS DOOR AT EACH

DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH

THE MANUFACTURER'S INSTRUCTIONS.

J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH

ROOFING

CONTRACTOR.

K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF

DUCTWORK TO ENSURE DUCTWORK DOES NOT PASS OVER

ELECTRICAL PANELS.

L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION

PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL

REFERENCE ONLY.

M. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH

THE OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE

OF ONE WEEK. THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR

SOME SHUTDOWNS AND SHALL BE AT THE OWNERS DISCRETION.

N. LEAVE A MINIMUM CLEARANCE OF 2 INCHES ABOVE DUCTS INSTALLED

IN RATED PARTITIONS TO ALLOW SPACE FOR THE GENERAL

CONTRACTOR TO SEAL THE WALL ABOVE THE DUCTS. DO NOT INSTALL

FLEXIBLE DUCT THROUGH RATED WALLS, BARRIERS OR PARTITIONS.

O. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED

DAMPERS, FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE

DETECTORS, AND SIMILAR ITEMS REQUIRING MAINTENANCE OR

ADJUSTMENT.

P. MECHANICAL CONTRACTOR SHALL INSTALL MANUAL VOLUME DAMPERS

ON ALL BRANCH DUCTWORK CONNECTIONS.

Q. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.

GENERAL NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:4

A

M

MH100

MECHANICAL - LEVEL 03 - NEW

WORK - DUCTWORK - OVERALL

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

1/8" = 1'-0"

MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - OVERALL

GRAPHIC SCALE

( in Feet )

1 inch = 8 ft.

8 84 16 32

FOR REFERENCE ONLY. REFER TO

1/4" SCALED DRAWINGS FOR SIZES

AND AIRFLOWS.

DD

OIT

320A

BRIEFING CENTER

320B

PRIVATE OFFICE

320D

PRIVATE OFFICE

320E

9-3-3V

1000 CFM

9-3-2V

540 CFM

9-3-4V

410 CFM

STORAGE

320C

PRIVATE OFFICE

320F

PRIVATE OFFICE

320G

CERNER CONTROL

CENTER/WORK SPACES

SSEU-1

NOT IN SCOPE

16"x15"

18"x12"

"ø

"x

8"ø

"ø

8"ø

"x

"ø

6"ø

"ø

14"x12"

"ø

"ø

8"ø

"ø 8

"ø

"ø

"ø

"ø

14"x12"

8"ø

140 4

9-3-1V

700 CFM

14"x14" 28"x14"

10"ø

20"x14"

"ø

"ø

"ø

"ø 8 "ø 8 "ø

12"ø

A2

A3

A4 A5

A6

A15

MH100B

MH100B

"x

10"ø

FIRST FLOOR ROOF

"ø

A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED

TO COMPLY WITH THE STATE BUILDING CODE.

B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE

LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,

LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE

NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION

DRAWINGS, AS SPECIFIED.

C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES

AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL

STARTERS AND DISCONNECT SWITCHES WITH ELECTRICAL

CONTRACTOR.

D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING

A CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE

STATIC PRESSURE OF THE UNIT SUPPLY FAN.

E. ALL EQUIPMENT SHALL BE U.L. LISTED.

F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL

EQUIPMENT; PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL

STARTERS, AND MOUNT AND WIRE VARIABLE SPEED DRIVES, UNLESS

OTHERWISE NOTED.

G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE

ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND

INSTALLATION INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL

HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY

ARE INSTALLED. PROVIDE DYNAMIC FIRE DAMPERS.

H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH

OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT

RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN

TRADES, SHALL BE CHANGED AS DIRECTED BY THE

ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE

CONTRACTOR.

I. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM

CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR

UNLESS OTHERWISE NOTED. PROVIDE DUCT ACCESS DOOR AT EACH

DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH

THE MANUFACTURER'S INSTRUCTIONS.

J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH

ROOFING

CONTRACTOR.

K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF

DUCTWORK TO ENSURE DUCTWORK DOES NOT PASS OVER

ELECTRICAL PANELS.

L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION

PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL

REFERENCE…