S02-RFP Attachment 9- Mechanical Drawings-COL.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77626R0032_2
About this file
This document comprises mechanical design drawings and schedules for HVAC renovation of Building B3 at the U.S. Department of Veterans Affairs facility in Columbia, South Carolina, as part of the EHRM (Employee Housing and Renovations Management) Admin and Training project.
The scope includes installation of a new 6,000 CFM variable volume air handling unit (AHU-09) serving third-floor spaces, with associated ductwork, terminal units, and piping systems. Key mechanical components specified include: nine variable volume reheat boxes (9-3-1V through 9-3-9V) with CFM ranges from 300-1,000, two split-system ductless units (SSCU-1 condensing unit and SSEU-1 evaporating unit) for supplemental cooling in the OIT room, one hydronic unit heater (UH-1) in the mechanical room, and chilled water supply/return and hot water supply/return piping connections to existing building systems. The terminal unit schedule specifies 3/4-inch water connections, heating and cooling setpoints of 68°F and 72°F respectively during occupied modes, and DDC controls provided by the controls contractor. Construction requirements mandate lateral restraint of all duct and pipe systems per state building code, fire damper installation with U.L. listings, seismic support where required, and coordination drawings submitted prior to fabrication. All work must comply with SMACNA standards, and the mechanical contractor is responsible for trade coordination to eliminate conflicts, with any resulting changes made at no additional cost to the owner.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
,8 ,9 ,1 h w r e h e a t
DIRECT EXPANSIONDX
TEMPERATURE SENSOR
UNDERWRITER'S LABORATORIES
UNLESS OTHERWISE NOTED
SYMBOL OR SYMMETRICAL
TEST, ADJUST, BALANCE
TRANSFER DUCT
SUPPLY REGISTER
STANDARD CUBIC FEET PER MINUTE
SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
STATIC PRESSURE SENSOR
VENT THRU ROOF
VARIABLE SPEED
YARD CLEAN OUT
WEATHER PROOF
VARIABLE FREQUENCY DRIVE
VARIABLE VOLUME
WET BULB TEMPERATUREWb
GP
INSUL
INV
LAT
LB/HR
KW
HTG
HVAC
HOA
HORZ
H'STAT
HR
HP
HD
GPH
GPM
HC
IB
IN
ID
HEATING, VENTILATING, AND AIR CONDITIONING
INVERTED BUCKET
INSIDE DIAMETER
LEAVING AIR TEMPERATURE
POUNDS PER HOUR
INSULATED
INVERT
KILOWATT
HEATING
INCH
HEAT DETECTOR
HAND-OFF-AUTOMATIC
HORSEPOWER
GALLONS PER HOUR
GALLONS PER MINUTE
HUMIDITY CONTROLLER
HORIZONTAL
HUMIDISTAT
HOUR
GUIDE POINT
YCO
WP
WG WATER GAGE
FCV
GALV
GC
GAL
FSD
FT
FV
FS
FPC
FPM
FPS
FOB
FP
FO
FLEX
FLG
FLR-FLR
FD
FACP
F&T
F.D.
FC
EQUIP
ESP
EWT
EXH
ER
EC
EFF
ELEC
EL
EQ
EAT
EA
F
EJ
FIRE PROTECTION CONTRACTOR
FEET PER SECOND
FLOW SWITCH/SENSOR
GENERAL CONTRACTOR
COMBINATION FIRE/SMOKE DAMPER
FEET PER MINUTE
FEET
GALVANIZED
GALLON(S)
FLOW VALVE
FLOW CONTROL VALVE
FLOOR TO FLOOR HEIGHT
FIRE PROTECTI0N
FLAT ON BOTTOM
FLANGE
FLAT OVAL
FIRE DAMPER
FLEX
VERT
W/
W/O
VFD
VTR
VOL
VS
VP
VLV
WITHOUT
WITH
VERTICAL
VOLUME
VENT POINT
VALVE
THRU
T'STAT
UL
V
UON
TYP
TOP
TS
TOS
TOD
THERMOSTAT
TYPICAL
THROUGH
TOP OF DUCT
TOP OF STEEL
TOP OF PIPE
EXHAUST REGISTER
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
FIRE ALARM CONTROL PANEL
FLOAT AND THERMOSTATIC
FLOW CONTROLLER
FAHRENHEIT
FLOOR DRAIN
EXHAUST
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
EXPANSION JOINT
ELEVATION
ELECTRICAL
EQUAL
EQUIPMENT
EXHAUST AIR
EFFICIENCY
SPRINKLERSPR
STRUCT
TAB
T/D
SYM
SYS
STL
STM
SR
SQ
STRUCTURAL
SYSTEM
STEEL
STEAM
SQUARE
SMACNA
SPEC
SECT
SCFM
SP
SCH
SD
SA
SECTION
SPECIFICATION
SMOKE DAMPER
SCHEDULE
SUPPLY AIR
LOW SIDE WALL EXHAUST REGISTER
LEAVING WATER TEMPERATURE
RELATIVE HUMIDITY
REVOLUTIONS PER MINUTE
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCH GAGE
REFLECTED CEILING PLAN
POLYVINYL CHLORIDE
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PRESSURE REDUCING STATION
PLUMBING CONTRACTOR
OUTSIDE DIAMETER
MOTOR OPERATED DAMPER
NATIONAL ELECTRIC CODE
NATIONAL ELECTRICAL MANUFACTURER'S
NATIONAL FIRE PROTECTION ASSOCIATION
NET POSITIVE SUCTION HEAD
NOT IN CONTRACT
NORMALLY OPEN
NORMALLY CLOSED
MECHANICAL CONTRACTOR
MANUAL AIR VENT
MANUAL DAMPER
MANUFACTURERMFR
ARCH ARCHITECTURAL
DWG
DWV
Db
DEG(°)
DPR
DTF
DP
DN
CU.FT.
CTR
CU.YD.
DD
CU
CONN
CONT
CONTR
COP
CONST
COORD
CFH
CFM
CLG
CONC
CO
ASHRAE
BFP
BDD
ASME
BHP
AUTO
BOP
BOD
BTUH
BTU
BOS
BV
C
CUBIC YARD
DRAIN, WASTE, AND VENT
DOWN THRU FLOOR
DUCT MOUNTED SMOKE DETECTOR
DRAIN POINT
DRAWING
DAMPER
DRY BULB TEMPERATURE
DEGREE(S)
DOWN
COEFFICIENT OF PERFORMANCE
CONSTRUCTION
COPPER
CUBIC FEET
CENTER
CONNECTION
CONTINUATION
CONTRACTOR
COORDINATE
RECIRC
REINF
REQD
RH
RPM
RM
REV
RD
RA
RCP
REQUIRED
ROOM
REVISION
RETURN AIR
RECIRCULATING
REINFORCING
ROUND
PLBG
PSIG
QTY
PVC
PSI
PSIA
PRV
PRS
PL
QUANTITY
PILOT LIGHT
PLUMBING
AMERICAN SOCIETY OF MECHANICAL ENGINEERS
CONSTANT VOLUME
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BOTTOM OF STEEL
BUTTERFLY VALVE
CEILING
CLEAN OUT
CONCRETE
BACKFLOW PREVENTER
BOTTOM OF PIPE
BOTTOM OF DUCT
BACKDRAFT DAMPER
AND AIR CONDITIONING ENGINEERS
BOILER HORSEPOWER OR BRAKE HORSEPOWER
AUTOMATIC
NIC
OPNG
NPSH
OA
P.C.
OD
OC
NTS
NO.
NO
OUTSIDE AIR
ON CENTER
OPENING
NOT TO SCALE
NUMBER
NFPA
NEMA
NC
NEC
MOD
MTD
MIN
MH
ASSOCIATION
MOUNTED
MINIMUM
MANHOLE
AD
AFMS
ALUM
AFF
AC/HR
AP
ANSI
APPROX
AMCA
ABV.CLG.
AIR MOVEMENT AND CONTROL ASSOCIATION
AMERICAN NATIONAL STANTDARDS INSTITUTE
ANCHOR POINT
AIR FLOW MONITORING STATION
ACCESS DOOR
ABOVE FINISHED FLOOR
AIR CHANGES PER HOUR
ALUMINUM
APPROXIMATE
ABOVE CEILING
POUNDS OR NUMBER
ROUND, DIAMETER OR PHASE
LSWER
MEZZ
MECH
MFG
MD
MAX
MC
MBH
MAV
MEZZANINE
MANUFACTURING
MECHANICAL
MAXIMUM
BTUH x 1000
LF
LP
LWT
LINEAR FEET
LOW PRESSURE
FSS FUSED SAFETY SWITCH
S/S STAINLESS STEEL
RVNR REDUCED VOLTAGE, NON-REVERSING, MAGNETIC
FVNR FULL VOLTAGE, NON-REVERSING, MAGNETIC
MRS MOTOR RATED SWITCH
W WATTS
ACU-1 AIR CONDITIONING UNIT & TAG
AHU-1 AIR HANDLING UNIT & TAG
CC COOLING COIL
CP-1 CONDENSATE PUMP & TAG
DB DECIBELS
Dp DEWPOINT TEMPERATURE
EDH ELECTRIC COIL DUCT HEATER
CUH-1 CABINET UNIT HEATER & TAG
CU-1 CONDENSING UNIT & TAG
CW COLD WATER (DOMESTIC)
EER ENERGY EFFICIENCY RATIO
EF-1 EXHAUST FAN & TAG
E or EX. EXISTING
FCU-1 FAN COIL UNIT & TAG
H&V-1 HEATING AND VENTILATING UNIT & TAG
NOT ALL ABBREVIATIONS
SHOWN IN THIS LIST WERE
UTILIZED FOR THIS PROJECT.
AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AFLD AUTOMATIC FLOW LIMITING DEVICE
NOT APPLICABLEN/A
GENERAL PROJECT NOTESMECHANICAL ABBREVIATIONS( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )MECHANICAL SYMBOLS
DUCTWORKVALVES
GAUGE CONNECTION ONLY
PLUG VALVE WITH PRESSURE
GLOBE VALVE
THREE WAY VALVE
AUTOMATIC CONTROL VALVE
ANGLE VALVE
BALL VALVE
ISOLATION VALVE
CHECK VALVE
BUTTERFLY VALVE
TRIPLE DUTY VALVE
CONTROL VALVE
PRESSURE INDEPENDANT
ACCESSORIES
THERMOMETER WELL AND CAP ONLY
THERMOMETER WITH WELL
UNION
LINE PRESSURE RELIEF VALVE
PRESSURE GAGE WITH COCK
MANUAL AIR VENT POINT ON PIPE
LOW PRESSURE TRAP ASSEMBLY
MEDIUM PRESSURE
AUTOMATIC FLOW LIMITING DEVICE
REDUCED PRESSURE
PIPE UP
PIPE DOWN
STRAINER
BACKFLOW PREVENTER
(SEE SPECS)
FLOW SWITCH
TRAP ASSEMBLY
DIRECTION OF FLOW
FLOW CONTROL DEVICE
ECCENTRIC REDUCER
DRAIN POINT OF PIPE
DIRECTION OF SLOPE
ANCHOR POINT
CONCENTRIC REDUCER
FLOW METER
PRESSURE AND TEMP. TEST PORT
FM
MISCELLANEOUS
DRAWING NUMBER WHERE SECTION
DUCT SYMBOL: FLAT OVAL
EMERGENCY STOP SWITCH
DIRECTION OF AIR FLOW
CONNECT TO EXISTING SYMBOL
12x10 DUCT SYMBOL: RECTANGULAR
THERMOSTAT
IS LOCATED
T
FLOOR DRAIN
SECTION NUMBER
HUMIDISTATH
ESS
CFM
ARROW AND CFM
DUCT SYMBOL: ROUND12∅
12/12
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
M4.1
M4
SIDEWALL RETURN REGISTER
CEILING RETURN GRILLE/
SIDEWALL EXHAUST REGISTER
CEILING EXHAUST GRILLE/
DUCTWORK W/O DUCTLINER
SIDEWALL SUPPLY REGISTER
CEILING SUPPLY DIFFUSER/
TRANSITION
OVAL TRANSITION
SQUARE TO ROUND/
CONICAL TAKEOFF
RECTANGULAR DUCT
MITERED TAKEOFF
(SEE SCH)
(SEE SCH)
REGISTER (SEE SCH)
(SEE SCH)
REGISTER (SEE SCH)
REGISTER (SEE SCH)
EXHAUST DUCT UP
SUPPLY AND RETURN SIMILAR
RETURN DUCT DOWN
SUPPLY AND EXHAUST SIMILAR
SUPPLY DUCT, UP THROUGH ROOF
RETURN AND EXHAUST SIMILAR
EQUIPMENT
MOTOR OPERATED DAMPER
DAMPER WITH ACCESS DOOR
COMBINATION FIRE/SMOKE
DOOR
ACCESS DOOR
DETECTOR WITH ACCESS
DUCT MOUNTED SMOKE
SMOKE DAMPER WITH
WITH ACCESS DOOR
MANUAL DAMPER
ACCESS DOOR
FIRE DAMPER WITH
HUMIDIFIER WITH ACCESS
DOOR
AIR FLOW
MONITORING STATION
DUCT MOUNTED COIL
DUCT MOUNTED COIL
(ELECTRIC)
(HOT WATER OR STEAM COIL)
AIR VALVE
FSD
SD
M
FD
DD
NO SCALE
500 CFM
1 - 4 - XC
VARIABLE OR CONSTANT VOLUME BOX WITH REHEAT
1 GPM
BOX NUMBER (C OR V INDICATES
HOT WATER GPM
CONSTANT OR VARIABLE FLOW)
VARIABLE OR CONSTANT REGULATOR
ACCESS DOOR
SUPPLY CFM
REHEAT COIL
FLOOR
AIR HANDLING UNIT NUMBER
PIPING
HWR
HWS HOT WATER SUPPLY
HOT WATER RETURN
D
CHWS
CHWR
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
TO REMAIN
TO BE REMOVED
EXISTING DUCT
EXISTING EQUIPMENT
TO REMAIN
TO BE REMOVED
EXISTING PIPING
EXISTING PIPING
TO REMAIN
EXISTING CONDENSATE DRAIN
TO BE REMOVED
EXISTING EQUIPMENT
TO REMAIN
EXISTING DUCT
NEW EQUIPMENT
NEW PIPING
NEW
DUCTWORK
D
A. ALL DUCT, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED TO
COMPLY WITH STATE BUILDING CODE.
B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE LOCATION
AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS, LIGHT FIXTURES,
STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE NOT SHOP DRAWINGS.
SUBMIT DUCTWORK COORDINATION DRAWINGS, AS SPECIFIED.
C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES AVAILABLE FOR
MECHANICAL EQUIPMENT AND PROVISION ALL STARTERS AND DISCONNECT
SWITCHES WITH ELECTRICAL CONTRACTOR.
D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING A
CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE STATIC
PRESSURE OF THE UNIT SUPPLY FAN.
E. ALL EQUIPMENT SHALL BE U.L. LISTED.
F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT;
PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL STARTERS, AND MOUNT
AND WIRE VFD, UNLESS OTHERWISE NOTED.
G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE ACCORDANCE
WITH THE MFR'S. U.L. LISTING AND INSTALLATION INSTRUCTIONS. FIRE AND
SMOKE DAMPERS SHALL HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION
IN WHICH THEY ARE INSTALLED.
H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH
OTHER TRADES TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK
INSTALLED BY THIS CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK
OF COORDINATION BETWEEN TRADES, SHALL BE CHANGED AS DIRECTED BY
THE ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE
CONTRACTOR.
I. SMOKE DETECTORS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR AND
INSTALLED BY THE MECHANICAL CONTRACTOR. PROVIDE DUCT ACCESS DOOR
AT EACH DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS.
J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH ROOFING
CONTRACTOR.
K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF DUCTWORK TO
ENSURE DUCTWORK DOES NOT PASS OVER ELECTRICAL PANELS.
L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE
SCALE, WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
M. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE
OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF TWO
WEEKS.THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS
AND SHALL BE AT THE OWNERS DISCRETION.
N. PROVIDE ESCUTCHEON PLATES WHERE DUCTS PENETRATE CEILINGS OR WALLS
IN AREAS EXPOSED TO VIEW. ESCUTCHEONS FOR DUCTS SHALL BE
CONSTRUCTED OF SAME MATERIAL AS DUCT. PIPE ESCUTCHEONS SHALL BE
CHROME-PLATED BRASS.
O. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED DAMPERS,
FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE DETECTORS, AND
SIMILAR ITEMS REQUIRING MAINTENANCE OR ADJUSTMENT.
P. PROVIDE FIRE CAULKING OR OTHER APPROVED FIRESTOP SYSTEM AT ALL
MECHANICAL PIPING PENETRATIONS OF RATED ASSEMBLY WITHIN THE LIMITS OF
CONSTRUCTION (NEW AND EXISTING).
Q. SEISMICALLY SUPPORT DUCTWORK, AIR HANDLING UNIT, PIPING, ETC. AS
REQUIRED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
M001
MECHANICAL - SYMBOLS, NOTES
AND DRAWING INDEX
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT CAS
MECHANICAL - DRAWING INDEX
Sheet
Number Sheet Name
M001 MECHANICAL - SYMBOLS, NOTES AND DRAWING INDEX
M002 MECHANICAL - DETAILS
M003 MECHANICAL - SCHEDULES
M004 MECHANICAL - AHU CONTROL SCHEMATICS
MD100 MECHANICAL - LEVEL 03 - DEMOLITION - DUCTWORK
MH100 MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - OVERALL
MH100A MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - AREA A
MH100B MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - AREA B
MP100 MECHANICAL - LEVEL 03 - NEW WORK - PIPING
Rev. No. Revisions: Date:
NOTES:
1. ROLLERS, SHOES AND SUPPORTS SELECTED PER PIPE SIZE
2. SECURE W/APPROVED ANCHORS TO MATCH BASE MATERIALS AND
LOAD REQUIREMENTS
TYP FOR TRAPEZE
OR BASE MOUNTED
SEE NOTE 2
SIMILAR TO UNISTRUT P 2474 GALV CI ROLLERS
BOLTED TO P 1000 GALV CHANNEL
PIPE W
INSULATION
TYPE 44
ROLLER
BASE
MOUNTED
INSULATE AS REQD
ATTACH TO
STRUCTURE
WITH PROTECTIVE
SPRING CUSHION
W/OR W/OUT TYPE 48
VIBRATION ISOLATOR
TYPE 1 CLEVIS HANGER
SADDLE OR SHIELD
TYPE 40
PROTECTIVE
SHIELD
STACKED CHILLED WATER CONTROL
VALVE PIPING
NOTES:
1. INSTALL AIR VENT AT HIGH POINTS ON PIPING.
2. INSTALL DRAIN VALVES AT LOW POINTS OF PIPING.
3. EXTEND COIL VENTS AND DRAINS (IF PROVIDED BY COIL MANUFACTURER)
THROUGH AIR HANDLING UNIT HOUSING.
4. INSTALL FLOW CONTROL DEVICE MINIMUM OF 10 PIPE DIAMETERS STRAIGHT PIPE
(OR MORE IF REQUIRED BY MANUFACTURER) DOWNSTREAM OF NEAREST FITTING.
(LUG TYPE)
BUTTERFLY VALVE
PT TEST PLUG
SUPPLY
RETURN
UNION
THERMOMETER
MANUAL AIR VENT
BUTTERFLY VALVE
AIR FLOW
DRAIN VALVE
PRESSURE
INDEPENDENT
2-WAY CONTROL VALVE
WITH STRAINER
VICTAULIC COUPLING
OR UNION
TYPE 44 SINGLE ROLLER PIPE GUIDE AND
SUPPORT
TYPE 1 CLEVIS HANGER
DN
3 3
A
A
Section A-ANOTES:
1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR
PARTITION TYPE & RATING ENCOUNTERED.
2. THROUGH PENETRATION (INSULATED OR BARE DEPENDING ON SERVICE) -
PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE & MATERIAL OF THROUGH
PENETRATION UTILIZED.
3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL
ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR
CAVITY ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM
UTILIZED.
ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL
LISTED FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE
SEPARATION PENETRATED AND THE THROUGH PENETRATION MATERIAL.
DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE
AVAILABLE AT THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION
AND SHALL BE PROVIDED TO THE BUILDING OWNER AT THE PROJECT
COMPLETION.
PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER
AND UL LISTED ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE
STOPPING SYSTEM IS INSTALLED.
THROUGH PENETRATION FIRESTOP SYSTEM
(PROVIDE UL LISTED SYSTEM)
SIDE VIEW
ELEVATION CHANGE - OGEE TRANSITION
DETAIL
PLAN VIEW
R .5
D
D
NOTES:
1. CHANGES IN DUCTWORK ELEVATION SHALL BE ACCOMPLISHED BY UTILIZING
RADIUS ELBOW TRANSITIONS EQUAL TO NO LESS THAN R=1.5D. IN ORDER TO
MINIMIZE DUCT STATIC PRESSURE LOSSES.
2. ELEVATION TRANSITION ARROW INDICATING UP OR DOWN (DN) IS SHOWN WITH
RESPECT TO AIRFLOW DIRECTION.
R
RECTANGULAR SHEETMETAL ELBOWS
TYPE RE 2 SQUARE
THROAT
ELBOW WITH VANES
TYPE RE 1 RADIUS ELBOW
AIR
FLOW
BRANCH DUCT
BRANCH DUCTWORK TAKEOFFS
MAIN EXHAUST OR
RETURN AIR FLOW
NOTE:
ALL BRANCH TAKEOFFS SHALL BE 45°, CONICAL OR BELLMOUTH TYPE.
AIR
FLOW
BRANCH DUCT
MAIN SUPPLY
AIR FLOW
VOLUME DAMPER (REFER
TO
VOLUME DAMPER DETAIL).
VOLUME DAMPER (REFER
TO
VOLUME DAMPER DETAIL).
DUCT
MANUAL VOLUME DAMPER WITH
QUADRANT LOCKING DEVICE,
WITH STANDOFF RUSKIN MODEL
MDRS25 OR EQUAL.
EXTEND TAP AS REQ.D TO
ALLOW
MAX 5' LENGTH OF FLEX DUCT
BETWEEN CONNECTION AND
DIFFUSER
FLEX DUCT WITH
EXTERNAL BLANKET
INSULATION (TYP)
CONNECTIONS BETWEEN LOW PRESSURE DUCT
AND AIR DISTRIBUTION DEVICE
NOTES:
1. ONLY ONE 90° TURN ALLOWED IN FLEX DUCT. DUCT MUST BE PROPERLY
SUPPORTED TO PREVENT KINKING.
2. IF ADDITIONAL 90° TURNS ARE REQD TO CONNECT OUTLET TO DIFFUSER, EXTEND
TAP AND PROVIDE EXTERNALLY INSULATED SHEET METAL ELLS AS REQD.
SEAL WITH DRAW
BAND AT TAP
CONNECTION AND
DIFFUSER/FIXTURE
SEAL INSULATION TO
DUCT WITH CAULKING
AIR DISTRIBUTION DEVICE
SPIN IN COLLAR.
48"
2"
FINISH FLOOR
DEVICES BY ELECTRICAL
CONTRACTOR
THERMOSTAT
THERMOSTAT ALIGNMENT
NOTES:
1. PROPERLY COORDINATE DEVICE LOCATION TO ALIGN VERTICALLY.
VARIABLE OR CONSTANT VOLUME
TERMINAL UNIT WITH REHEAT
NOTES:
1. MAINTAIN CLEARANCE ON CONTROL SIDE OF BOX AND INSTALL
SO THAT ACCESS DOORS ARE NOT BLOCKED.
HWS
HWR
UNION
BALL VALVE
AFLD
AIR VENT
HOT WATER HEATING
COIL. (PROVIDE ACCESS
DOOR PRIOR TO COIL FOR
CLEANING COIL)
24" OF ROUND HARD
DUCTWORK
(VARIABLE VOLUME
BOX ONLY)
CENTER
AVERAGING
INLET
SENSOR
DDC CONTROLLER SHALL
BE FACTORY MOUNTED
HOSE END DRAIN
VALVE WITH CAP
2-WAY VALVE BY CONTROLS
CONTRACTOR, UNLESS NOTED
OTHERWISE ON PLANS
PRESSURE/
TEMPERATURE
TEST PLUG
J 120V TOGGLE DISCONNECT BY
TERMINAL MANUFACTURER.
120/24V TRANSFORMER BY
TERMINAL MANUFACTURER.
24V WIRING BY
CONTROLS
CONTRACTOR
120V BY ELECTRICAL
CONTRACTOR
120V WIRING
BY CONTROLS
CONTRACTOR
3NTS
2NTS
1NTS9NTS
10NTS 6NTS
7NTS
8NTS
11NTS
12NTS
EXTERIOR WALL SLEEVE DETAIL 13
NTS
EXTERIOR
WALL
INTERIOR
WALL
FILL W/
MASTIC
LINK SEAL
SCH. 10 ST. OR
C.I. WALL SLEEVE
1" MIN
PIPE O.D.
1" MIN
FIRE DAMPER 14
NTS
DUCT
SLEEVE
SLEEVE
DUCT
NOTES:
INSULATE
EXTERNALLY
AS REQD
FACTORY
STANDARD
SLEEVE
FIELD
FABRICATED
SLEEVE
MOUNTING ANGLE
FUSIBLE
LINK
1. FIRE DAMPER SHALL BE U.L. LABELED AND INSTALLED PER MANUFACTURER'S
REQUIREMENTS FOR U.L.
2. FIRE DAMPER RETAINING ANGLE SHALL BE SIZED PER MANUFACTURERS
REQUIREMENTS.
3. PROVIDE MINIMUM 12"X12" ACCESS DOOR IN DUCT FOR FUSIBLE LINK REPLACEMENT.
4. USE TYPE "C" FIRE.
5. FUSIBLE LINK SHALL BE RATED FOR 165°F
6. PROVIDE MINIMUM 12"X12" ACCESS DOOR FOR ALL FIRE DAMPERS.
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE
SIMILAR FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION
1/8" [6mm] CLEARANCE
ALL AROUND
OUTSIDE END
BEARING
INSIDE END
BEARING
HANDLE
WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm]
ROUND ROD PIN
DUCTSTIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
VOLUME DAMPER DETAIL
DAMPER
BLADE
5NTS
FLARE CONNECTION
PIPE CAP
6" NIPPLE
SYSTEM PIPE
FULL SIZE TEE
1/4" LINE
1/4" BALL VALVE MANUAL AIR VENT,
EXTEND VENT LINE TO WITHIN 6" ABOVE
CEILING WHERE PIPING IS CONCEALED
ABOVE CEILING. PROVIDE HOSE END
ADAPTER AND END CAP.
NTS
15MANUAL AIR VENT
PRESSURE GAGE
ISOLATION VALVE
NIPPLE
MAIN
PIPE
NTS
16PRESSURE GAUGE DETAIL
BUTTERFLY
VALVE (LUG TYPE)
PT TEST PLUG
SUPPLY
FLOW CONTROL
DEVICE
RETURN
UNION
THERMOMETER
MANUAL AIR VENT
DRAIN
VALVE
TWO WAY VALVE
HW
S
HW
R
BUTTERFLY
VALVE
TYPICAL SINGLE HOT WATER COIL PIPING
NOTES:
1. INSTALL AIR VENT AT HIGH POINTS ON PIPING.
2. INSTALL DRAIN VALVES AT LOW POINTS OF PIPING.
3. EXTEND COIL VENTS AND DRAINS (IF PROVIDED BY COIL MANUFACTURER)
THROUGH AIR HANDLING UNIT HOUSING.
4. INSTALL FLOW CONTROL DEVICE MINIMUM OF 10 PIPE DIAMETERS STRAIGHT
PIPE (OR MORE IF REQUIRED BY MANUFACTURER
DOWNSTREAM OF NEAREST FITTING.
AIR
FLOW
NTS
FIRE DAMPER AT FLOOR PENETRATION
NOTES:
1. ALL DUCTWORK RISERS THAT RUN EXPOSED, SUCH AS THROUGH ATTIC
FLOORS AND MECHANICAL ROOM FLOORS SHALL BE PROVIDED WITH 3" (75mm)
HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
2. ALL DETAILS SHALL COMPLY WITH FIRE DAMPER MANUFACTURER'S UL
MOUNTING AND INSTALLATION REQUIREMENTS.
3. WHERE HVAC AIR DUCT PENETRATES ONLY ONE FLOOR AND PROTECTED WITH
A FIRE DAMPER, AN AIR DUCT ENCLOSURE IS NOT REQUIRED.
4. HORIZONTAL DAMPER SHOWN, FOLLOW MANUFACTURER'S INSTRUCTIONS,
INCLUDING GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST
BE INSTALLED IN LINE WITH FLOOR AND NOT OUTSIDE THE PENETRATION.
5. GALVANIZED SLEEVE GAGE NOT LESS THAN CONNECTING DUCT, FASTEN
SLEEVE TO DAMPER AND FLOOR SLAB WITH PERIMETER ANGLES.
6. BREAKAWAY DUCT CONNECTION OF TYPES INDICATED IN SMACNA. ACCESS
PANELS: SIZE AND LOCATION TO PERMIT SERVICING FUSIBLE LINK OR LINKS.
18NTS
FIRE
BARRIER
SLAB
FIRE
BARRIER
SLAB
ACCESS
PANEL
TYPICAL DUCT INSULATION
TOP OF SLAB
DAMPER COLLAR EXTENSION IS
INTEGRAL PART OF SLEEVE
NTS
21AHU DRAIN TRAP DETAIL
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR
TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN PAN
DIELECTRIC
FITTING
NOTES:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS INDOORS
AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTINGS TO BE USED WHEN TWO DISSIMILAR METALS ARE TO
BE CONNECTED.
DRAW THRU
2" [50mm]
PLUS X
X
BLOW THRU
1" [25mm]
MINIMUM
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
[2 m m
B A
STATIONARY LOUVER IN MASONRY WALL
NTS
35° DRAINABLE BLADE
STEEL ANGLE LINTELS
CONCRETE
BRICK
SEALANT
FOR OPENING AND LINTEL
REFER TO ARCH DRAWINGS
FACE
BLOCK
REMOVABLE BIRD EXCLUSION
SCREEN WITH 1/2" x 1/2" MIN GRID
METAL SILL TO DIRECT WATER OUTSIDE
& AWAY FROM BASE OF LOUVER
NOTES:
1. OVERALL SIZE OF OPENING SHOULD BE 1/4" AND 1/2" GREATER IN BOTH
DIRECTIONS THAN EXTERNAL DIMENSIONS OF LOUVER FOR SIZES < 48" AND > 48",
RESPECTIVELY.
2. MAX LOUVER WIDTH < 5FT, USE MULLION CONNECTED SECTIONS FOR GREATER
WIDTHS.
3. CAULK AND SEAL AROUND PERIMETER OF LOUVER SECTION AT WALL.
4. PROVIDE ALUMINUM OR GALV EXPANDED BIRD EXCLUSION SCREEN ON INSIDE (OR
OUTSIDE) OF LOUVER. (MIN FREE AREA 80% OF GROSS AREA) ATTACH TO OUTSIDE
IF BLADE SEPARATION IS > 2 1/2".
5. CONSTRUCT EXTRUDED LOUVER OF NON-FERROUS CORROSION RESISTANT
MATERIAL AND SECURE WITH SS OR ALUMINUM FASTENERS.
CONDENDING UNIT WALL-BRACKET/MOUNTING
NTS
NOTES:
1. ONCE BRACKET IS SECURED TO THE EXTERIOR WALL, PLACE THE CONDENSING
UNIT ON THE BRACKETS AND ADJUST AS NEEDED TO SECURE IT IN PLACE.
DUCTLESS SPLIT SYSTEM
NTS
OUTDOOR (CONDENSING) UNIT
WALL-MOUNTED
INDOOR (EVAPORATING)
UNIT)
REFRIGERANT PIPING - ROUTE
AND SIZE PER
MANUFACTURER'S
RECOMMENDATIONS.
CONDENSATE PIPING - SEE
MECHANICAL PLANS FOR
SIZE, ROUTING AND
TERMINATION.
DOOR FRAME
POWER PROVIDED BY EC. SEE
MECHANICAL SCHEDULE FOR
ELECTRICAL INFORMATION.
MOUNT TO EXTERIOR WALL
WITH MANUFACTURER'S
WALL-MOUNTING
HARDWARE. SEE DETAIL 20
ON THIS SHEET.
MANUFACTURER
PROVIDED WALL
PLATE. HANG THE
EVAPORATOR TO
THE WALL PLATE ON
THE WALL.
NOTE:
PROVIDE PIPE CLAMPS FOR VERTICAL
REFRIGERANT AND CONDENSATE DRAIN
PIPING ON EXTERIOR WALLS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
M002
MECHANICAL - DETAILS EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT CAS
TERMINAL
NO.
CFM
E.A.T.
(°F)
HEATING
L.A.T.
(°F)
MINIMUM
OPERATING
PD (in.wg)
GPM MBH
E.W.T.
(°F)
L.W.T.
(°F)
WATER
PRESSURE
DROP(FT)MAX. MIN.
AIR
RUNOUT
SIZE
UNIT SIZE
WATER
RUNOUT
SIZE
55 180 159
180 159
9-3-1V 700 350 10 14x12 114.4 0.16 2.2 22.6 0.32
540 270 08 12x10 0.20 1.7 16.9 0.40
ROWS
REHEAT
111.8
GENERAL NOTES
1. BOXES SHALL HAVE PIPE CONNECTIONS ON SAME SIDE AND BE FOR FLARED FITTINGS.
2. COIL AND BOX SIZE MAY BE INCREASED TO MEET REQUIRED CONDITIONS; BUT SHALL NOT BE DECREASED FROM SIZE SHOWN.
3. BOXES SHALL BE SET FOR MAXIMUM CFM SHOWN ON PLANS.
4. DUCT CONNECTIONS TO BOXES SHALL BE SAME SIZE AS BOX INLET UNLESS SHOWN OTHERWISE.
5. MAXIMUM WATER PRESSURE DROP SHALL BE 4 FEET.
6. VARIABLE VOLUME BOXES SHALL OPERATE DOWN TO 50% OF MAXIMUM FLOW.
7. CONSTANT VOLUME BOXES SHALL BE THE SAME BOX USED FOR VARIABLE VOLUME BOX EXCEPT CFM SHALL BE LOCKED AT CAPACITY SHOWN. BOX SHALL NOT OPERATE AS
VARIABLE VOLUME.
8. CONTROLS SHALL BE DDC PROVIDED BY CONTROLS CONTRACTOR AND INSTALLED BY BOX MANUFACTURER.
9. PROVIDE DIFFERENTIAL AIRFLOW SWITCH.
3/4"
3/4"
TERMINAL UNIT SCHEDULE
SYMBOL REGISTER SIZE 24"x24"
136-210 CFM 8" ROUND NECK
0-135 CFM 6" ROUND NECK
211-325 CFM 10" ROUND NECK
326-475 CFM 12" ROUND NECK
651-840 CFM 16" ROUND NECK
841-2000 CFM 22"x22" NECK
476-650 CFM 14" ROUND NECK
CFM
CFM
CFM
CFM
CFM
CFM
CFM
NOTES:
1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
SYMBOL TYPICAL MODULE SIZE - 24"x24"
136-210 CFM 9"x9" FACE 8" ROUND NECK
0-135 CFM 6"x6" FACE 6" ROUND NECK
211-325 CFM 12"x12" FACE 10" ROUND NECK
326-475 CFM 12"x12" FACE 12" ROUND NECK
476-650 CFM 15"x15" FACE 14" ROUND NECK
CFM
CFM
CFM
CFM
CFM
CFM
CFM
650-840 CFM 18"x18" FACE 16" ROUND NECK
841-1125 CFM 18"X18" FACE & NECK
NOTES:
1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. PROVIDE ROUND NECK ADAPTER.
CFM RANGE, FACE SIZE, & NECK SIZE
CFM
0-120 CFM 6"X6" FACE 6" ROUND NECK
CFM
121-240 CFM 9"X9" FACE 8" ROUND NECK
12"x12" REGISTER
12"x12" REGISTER
CFM
CFM
CFM
0-120 CFM 6" ROUND NECK
12"x12" REGISTER
0-135 CFM 6" ROUND NECK
24"x12" REGISTER
0-130 CFM 6" ROUNDNECK
16"x16" REGISTER
PERFORATED RETURN REGISTERS
LOUVERED SUPPLY DIFFUSER
CFM
0-130 CFM 6"X6" FACE 6" ROUND NECK
24"x12" REGISTER
1000 500 12 16x14 0.17 3.2 32.6 0.77115.2 3/4"
410 210 08 12x10 0.13 1.4 13.9 0.28117.6 3/4"
800 400 10 14x12 0.20 2.4 24.6 0.38111.8 3/4"
10 14x12 0.20 2.4 24.6 0.38111.8 3/4"
06 12x08 0.12 1 10 0.14116.2 3/4"
450 225 08 12x10 0.15 1.5 14.8 0.31115.8 3/4"
SPLIT SYSTEM AIR HANDLING UNITS (DUCTLESS)
GENERAL NOTES:
1. INSTALL REFRIGERANT PIPING IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION
RECOMMENDATIONS. PROVIDE PIPING APPURTENANCES AS REQUIRED.
2. UNIT SHALL BE PROVIDED WITH THE FOLLOWING FACTORY INSTALLED ACCESSORIES: (MODEL
NUMBER WILL REFLECT SOME OF THESE ACCESSORIES BUT NOT NECESSARILY ALL)
· LOW VOLTAGE INDOOR UNIT
· INDOOR UNIT IS POWERED FROM OUTDOOR UNIT. MECHANICAL CONTRACTOR SHALL
CONNECT ELECTRICAL SERVICE FROM OUTDOOR CONDENSER TO INDOOR EVAPORATOR
UNIT.
· AUTO RESTART
· DEHUMIDIFICATION MODE
· CLEANABLE FILTERS
· WALL MOUNTED THERMOSTATS
3.
SYSTEM DESCRIPTION
OUTDOOR UNIT ELECT. CONN. MCA/MOCP
ELECTRICAL CHARACTERISTICS
COOLING EDB/EWB (°F)
GROSS COOLING CAP (MBH)
TOTAL CFM
UNIT TAG:
SEER
FAN MOTOR FLA
SPLIT SYSTEM
SSCU-1
SPLIT SYSTEM
SSEU-1
LOCATION 1ST FLOOR ROOF
CONDENSING UNIT EVAPORATOR UNIT
DUCTLESS SPLIT SYSTEM 1
OIT
1,940 775
15.5 15.5
0.75 0.36
208/1Ø 208/1Ø
25/40 SEE NOTE 2
95/75 80/67
30 30
PROVIDE UNIT WITH CONDENSATE PUMP.
9-3-2V
9-3-3V
9-3-4V
9-3-5V
9-3-6V
9-3-7V
9-3-8V
400800
300 150
SYMBOL REGISTER SIZE 24"x24"
136-210 CFM 8" ROUND NECK
0-135 CFM 6" ROUND NECK
211-325 CFM 10" ROUND NECK
326-475 CFM 12" ROUND NECK
651-840 CFM 16" ROUND NECK
841-2000 CFM 22"x22" NECK
476-650 CFM 14" ROUND NECK
CFM
A
CFM
B
CFM
C
CFM
D
CFM
E
CFM
F
CFM
G
NOTES:
1. SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
2. REGISTERS LOCATED IN HARD CEILING AREAS SHALL BE PROVIDED WITH SURFACE
MOUNTED FRAMES.
12"x12" REGISTER
CFM
H
0-135 CFM 6" ROUND NECK
PERFORATED EXHAUST REGISTERS
159.1
159.1
159.1
159.1
159.1
4. PROVIDE LINESET OF EXTERIOR PIPING COVERING PIPES ROUTED ON EXTERIOR WALL.
400 200 08 12x10 0.12 1.3 13.7 0.27118.1 3/4"9-3-9V 200 55 2 180 159.1
5. MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECT WITH INDOOR UNIT.
UH NO. LOCATION E.A.T. °F L.A.T. °F GPM CAPACITY
BTU/HR MIN.
UH-1 MECHANICAL 312C 94
NOTES:
1. PROVIDE DISCONNECT SWITCHES FOR EACH UNIT.
HYDRONIC UNIT HEATER SCHEDULE
60 1.9 18,400
SYMBOL SIZE TYPE
111-250 CFM 10"x6"
0-110 CFM 8"x4"
251-480 CFM 14"x8"
481-650 CFM 18"x10"
651-835 CFM 18"x12"
836-1400 CFM 24"x18"
PRICE 530/630
PRICE 530/630
PRICE 530/630
PRICE 530/630
PRICE 530/630
PRICE 530/630
ACCEPTABLE MANUFACTURERS: PRICE, NAILOR 5145/6145, TITUS 350FL/350RL.
SEE ARCHITECTURAL CEILING PLAN FOR PROPER FRAME STYLE.
SIDEWALL EXHAUST REGISTER
CFM
A
CFM
B
CFM
C
CFM
D
CFM
E
CFM
F
CFM
VOLTS/
PHASE
120/1
RPM
MCA
1.0
MOCP
1.8
6. PROVIDE MANUFACTURER-SUPPLIED WALL-MOUNTING HARDWARE FOR EVAPORATOR AND
CONDENSING UNITS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
M003
MECHANICAL - SCHEDULES EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
NTS
AHU-09 CONTROLS SCHEMATIC 1
DP
HSTS
LL
RETURN
SUPPLY
AFMS
RELIEF
DAMPER
M
PRE-
FILTER
HEATING
COIL
COOLING
COIL AFMS
SUPPLY
FAN
LEGEND
AFMS - AIR FLOW MONITORING STATION
DD - DUCT DETECTOR
DP - DIFFERENTIAL PRESSURE
AHS - AVERAGING HUMIDITY SENSOR
AHSPS - AVERAGING HIGH STATIC PRESSURE SENSOR
LL - LOW LIMIT
SP - STATIC PRESSURE SENSOR
ATS - AVERAGING TEMPERATURE SENSOR
VFD - VARIABLE FREQUENCY DRIVE
M
OUTSIDE AIR
DAMPER
M
OUTSIDE
AIR
AFMS
RELIEF
V
D F
RETURN AIR
DAMPER
V
D F
RETURN
FANS
AIR HANDLING EQUIPMENT
VARIABLE AIR VOLUME AIR HANDLING UNIT (AHU-09)
1. OCCUPIED MODE
A. THE AHU WILL START ON COMMAND FROM THE BAS, WHEN THE HOA SWITCH IS IN THE "AUTO" MODE. THE AHU MAY ALSO BE STARTED LOCALLY WHEN THE HOA
SWITCH IS PLACED IN THE "HAND MODE".
B. WHEN THE AIR HANDLER IS COMMANDED TO START THE OUTDOOR AIR DAMPER SHALL BE OPENED 100% AND PROVE "OPEN" BASED ON INPUT FROM THE DAMPER END SWITCH, PRIOR TO STARTING THE SUPPLY AND RETURN FANS. IF THE OUTDOOR AIR DAMPERS DO NOT PROVE OPEN THE FAN SHALL REMAIN OFF AND AN ALARM SHALL BE ROUTED TO THE OPERATOR'S WORKSTATION. ONCE THE OUTDOOR AIR DAMPER IS VERIFIED OPEN, THE DAMPER SHALL MODULATE TO MINIMUM
POSITION.
C. WITH THE OUTDOOR DAMPER VERIFIED OPEN THE VFD SHALL START AND MODULATE THE SUPPLY AND RETURN FANS. CURRENT TRANSFORMER (CT) SWITCHES SHALL SIGNAL THE CONTROLLER TO VERIFY OPERATION OF THE SUPPLY AND RETURN FANS. IF SUPPLY FAN OPERATION IS NOT VERIFIED WITHIN 30 SECONDS (CUSTOMER ADJUSTABLE) THEN THE UNIT SHALL BE SHUT DOWN AND AN ALARM BE ROUTED TO THE OPERATORS WORKSTATION. IF THE RETURN FAN OPERATION IS NOT VERIFIED THE UNIT SHALL CONTINUE TO OPERATE AND AN ALARM SHALL BE ROUTED TO THE OPERATORS WORKSTATION.
D. THE AHU SHALL STOP WHEN COMMANDED BY THE BAS, OR WHEN THE HOA SWITCH IS PLACED IN "HAND". THE UNIT SHALL SHUT DOWN BY FIRST COMMANDING OFF THE FAN VFDS, WHEN THE FANS ARE PROVEN OFF (BY THE CT INPUT) THE OUTDOOR AIR DAMPER SHALL THEN BE CLOSED.
2. UNOCCUPIED MODE
A. WHEN IN UNOCCUPIED MODE, THE UNIT SHALL BE DE-ENERGIZED (FANS OFF, OUTSIDE AIR DAMPER CLOSED).
B. IN UNOCCUPIED MODE, WHEN A MINIMUM OF TWO (2) (ADJ.) VAV TERMINAL UNITS CALL FOR HEATING OR COOLING, THE AIR HANDLING UNIT SHALL BE ENERGIZED.
THE UNIT SHALL OPERATE NORMALLY IN EITHER HEATING OR COOLING MODE, BUT THE OUTSIDE AIR DAMPER SHALL BE CLOSED. ECONOMIZER SHALL BE DISABLED
DURING UNOCCUPIED MODE.
3. THE AHU WILL STOP (FANS OFF, ALL DAMPERS CLOSED) AND AN ALARM BE ROUTED TO THE OPERATORS WORKSTATION WHEN ANY OF THE FOLLOWING CONDITIONS
OCCUR:
A. IF EMERGENCY STOP SWITCH IS IN "PUSHED" POSITION, THEN THE SWITCH MUST BE MANUALLY "PULLED" IN ORDER TO RESTART THE AHU.
B. IF HIGH DISCHARGE PRESSURE SWITCH LOCATED IN THE UNIT AND AFTER THE SUPPLY FAN IS TRIGGER DUE TO HIGH PRESSURE, THE AHU SHALL SHUT DOWN AND
WILL NOT RESTART AUTOMATICALLY. (HIGH STATIC PRESSURE SWITCH SHALL BE SET ACCORDING TO TEST AND BALANCE'S INSTRUCTION.)
C. IF THE VAPOR TENSION LOW LIMIT THERMOSTAT ("FREEZESTAT") SENSE A TEMPERATURE BELOW 35 DEGREES (SHALL REQUIRE A MANUAL RESET.)
D. IF RETURN DUCT HIGH TEMPERATURE ("FIRESTAT") IS TRIGGERED, THE AHU SHALL SHUT DOWN AND WILL NOT RESTART. (SET AT 125 DEGREES, F.)
E. SMOKE MODE - IF ANY OF THE DUCT MOUNTED SMOKE DETECTORS (FURNISHED AND INSTALLED BY DIVISION 28) AND INSTALLED IN THE SUPPLY AIR STREAM
DETECT SMOKE OR A SPACE DETECTOR DETECTS SMOKE THE SUPPLY AIR FANS AND RETURN AIR FANS SHALL SHUT DOWN AND ALL DAMPERS SHALL CLOSE.
4. DISCHARGE CONTROL
A. THE PRE-HEAT COIL AIR TEMPERATURE SENSOR IS LOCATED DIRECTLY DOWNSTREAM OF THE PRE-HEAT COIL. CONTROL THE PRE-HEAT COIL DISCHARGE TEMPERATURE TO 50 DEGREES F (ADJUSTABLE) BY MODULATING THE PRE-HEAT COIL CONTROL VALVE.
B. THE COOLING COIL AIR TEMPERATURE SENSOR IS LOCATED DIRECTLY DOWNSTREAM OF THE COOLING COIL. CONTROL THE COOLING COIL DISCHARGE TEMPERATURE TO 60 DEGREES F (ADJUSTABLE) BY MODULATING THE COOLING COIL CONTROL VALVE.
C. THE PRE-HEAT VALVE WILL FAIL SAFE TO THE NORMAL OPEN POSITION. WHEN THE OA TEMPERATURE FALLS BELOW 45 DEGREES (SET POINT ADJUSTABLE), THE PRE-HEAT VALVE SHALL MODULATE TO MAINTAIN DOWNSTREAM AIR TEMPERATURE SET POINT. WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 50 DEGREES (SET
POINT ADJUSTABLE), THE PRE-HEAT CONTROL VALVE SHALL CLOSE.
D. AHU COILING COILS SHALL UTILIZE A STANDARD CONTROL VALVE ARRANGEMENT AND SHALL BE CONTROLLED AS FOLLOWS:
a. ON AN INCREASE IN COOLING LOAD, THE CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SET POINT. UPON A
DECREASE IN COOLING LOAD, THE CONTROL SHALL MODULATE CLOSED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SET POINT.
5. SUPPLY FAN CONTROL
A. MODULATE ALL VFD'S AT THE SAME SPEED TO MAINTAIN THE SUPPLY AIR DUCT STATIC PRESSURE SENSOR WITH THE LOWEST READING AT SET POINT. A STATIC
PRESSURE TRANSMITTER SHALL BE LOCATED 2/3 DOWN THE LONGEST DUCT.
B. IF THE STATIC PRESSURE SENSOR BECOMES UNRELIABLE, THE CONTROLLER WILL COMMAND THE SUPPLY FAN VFD TO ITS MINIMUM SPEED AND AN ALARM SHALL
BE ROUTED TO THE OPERATOR'S WORKSTATION.
C. RESET THE DUCT STATIC PRESSURE SENSOR TO KEEP AT LEAST ONE VAV BOX SUPPLY AIR DAMPER AT 95% OPEN.
6. RETURN FAN TRACKING
A. THE RETURN FAN AIRFLOW SHALL TRACK THE SUPPLY AIRFLOW UTILIZING AN OFFSET VALUE AS MEASURED WITH THE AIRFLOW MONITORS IN THE UNIT. THE OFFSET SHALL BE ESTABLISHED AT FINAL TEST AND BALANCE TO KEEP THE BUILDING AT SLIGHTLY POSITIVE PRESSURE.
7. ECONOMIZER MODE
A. OUTSIDE AIR TEMPERATURE SHALL BE COMPARED WITH A REFERENCE DRY BULB SETPOINT (OWNER ADJUSTABLE). ECONOMIZER MODE SHALL BE ENABLED WHEN
THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE REFERENCE DRY BULB SETPOINT. ECONOMIZER MODE SHALL BE DISABLED WHEN THE OUTSIDE AIR
TEMPERATURE IS GREATER THAN THE REFERENCE DRY BULB SETPOINT.
B. THE DISCHARGE AIR SENSOR SHALL MEASURE THE DRY BULB TEMPERATURE OF THE AIR LEAVING THE COOLING COIL WHEN ECONOMIZER MODE IS ENABLED. THE OUTSIDE AIR DAMPER SHALL MODULATE BETWEEN IT'S MINIMUM POSITION AND 100% TO MAINTAIN DISCHARGE AIR TEMPERATURE AT SETPOINT.
C. OUTSIDE AIR DAMPER SHALL MODULATE TO MINIMUM POSITION IN EVENT MIXED AIR TEMPERATURE FALLS BELOW LOW LIMIT TEMPERATURE SETTING AND
ECONOMIZER MODE SHALL BE DISABLED.
D. WHEN THE ECONOMIZER MODE IS DISABLED THE OUTDOOR AIR DAMPER SHALL BE SET TO MINIMUM POSITION REQUIRED BY VENTILATION.
VAV TERMINALS
1. ALL VAVS SHALL OPERATE ON A 7-DAY OCCUPIED/UNOCCUPIED SCHEDULE. INITIAL OCCUPIED SCHEDULE SHALL BE MONDAY – FRIDAY FROM 8:00AM TO 5:00PM AND SHALL
BE FULLY ADJUSTABLE VIA THE BAS.
2. SPACE TEMPERATURE SETPOINTS IN EACH MODE SHALL BE AS FOLLOWS AND SHALL BE FULLY ADJUSTABLE VIA THE BAS:
COOLING HEATING
OCCUPIED MODE 72 DEF F 68 DEG F
UNOCCUPIED MODE 78 DEF F 62 DEG F
3. PROVIDE PRESSURE INDEPENDENT CONTROL (I.E., THE SUPPLY AIR CFM SET POINT IS RESET TO MAINTAIN THE SPACE TEMPERATURE COOLING SET POINT.)
4. OCCUPIED / UNOCCUPIED MODE - INDEX BASED ON THE ASSOCIATED ZONE'S TIME SCHEDULE (OR THAT FOR THE AHU IF ALL BOXES SERVED THE BY THE AHU HAVE THE
SAME SCHEDULE) OR BY THE ASSOCIATED OCCUPANCY SENSOR. THE SUPPLY AIR DAMPER AND REHEAT COIL VALVE SHALL BE CLOSED IF THE ASSOCIATED AHU IS OFF.
5. HEATING - MODULATE THE HEATING COIL TO MAINTAIN THE OCCUPIED OR UNOCCUPIED SPACE HEATING SET POINT WHILE MAINTAINING THE BOX SUPPLY AIR CFM AT THE
MINIMUM SETTING FOR THE HEATING MODE (WHICH MAY BE A DIFFERENT VALUE THAN THAT FOR COOLING IF PROVIDED).
6. COOLING OPERATION - DO NOT RESET THE SUPPLY AIR CFM BELOW THE MINIMUM SUPPLY AIR SET POINT OR ABOVE THE MAXIMUM.
7. DEADBAND - PROVIDE A DEADBAND BETWEEN THE HEATING AND COOLING SPACE TEMPERATURE SET POINTS IN WHICH THE MINIMUM SUPPLY AIR CFM IS DELIVERED AND
NO HEATING IS PROVIDED.
8. MINIMUM SUPPLY AIR SET POINT (WHEN COOLING OR IN THE DEADBAND) - THE SET POINT SHALL BE THAT NEEDED FOR VENTILATION WHILE OPERATING IN THE OCCUPIED
MODE ONLY; OTHERWISE THE MINIMUM SHALL BE "ZERO" (I.E., DURING AHU UNOCCUPIED HEATING / COOLING, OR AHU WARM-UP OR COOL-DOWN DUE TO OPTIMUM START.)
HYDRONIC UNIT HEATER
1. ELECTRIC UNIT HEATERS EUH-1 SHALL BE CONTROLLED BY LINE-VOLTAGE THERMOSTATS INTEGRAL TO THE UNITS. THERMOSTATS SHALL BE PROVIDED BY THE UNIT MANUFACTURER. TEMPERATURE SETPOINT SHALL BE SET AT 60 DEG F AND SHALL BE ADJUSTABLE AT THE UNIT.
2. A SPACE TEMPERATURE SENSOR SHALL BE LOCATED IN THE MECHANICAL ROOM AT THE LOCATION SHOWN ON THE FLOOR PLAN. SENSOR SHALL REPORT BACK TO THE BUILDING AUTOMATION SYSTEM. A LOW SPACE TEMPERATURE ALARM SHALL BE DISPLAYED ON THE BAS WHEN THE SPACE TEMPERATURE DROPS BELOW 55 DEG F (ADJ.).
SEQUENCE OF OPERATION
REMARKS:
SERVES
TYPE UNIT
LOCATION
SYSTEM NO.
REMARKS:
REMARKS:
FILTER TYPE
VIBRATION ISOLATORS
MOTOR OPER. SMOKE DAMPERS
DISCHARGE AIR PLENUM W/AD
RETURN AIR PLENUM W/AD
MIXING SECTION W/AD
TOTAL CFM
SYSTEM TYPE
ECONOMIZER
OUTSIDE AIR (CFM)
DISCONNECT SWITCH BY E.C.
S U
P P
L Y
F A
N A
C C
E S
S
P R
E -F
IL
T
E R
H E
A T
IN
G
C O
IL
E
L E
C T
R
IC
A L
AIR HANDING UNIT SCHEDULE
C O
O L
IN
G C
O
IL
YES
YES
6,000
VARIABLE VOLUME
THIRD FLOOR EHRM
MECHANICAL - 312B
AHU-09
1,400
2" PLEATED
6,000
CHILLED WATER
6,000
HOT WATER
CUSTOM
VOLTAGE/PHASE/HZ 460/60/3
MOCP MCA
CIRCUIT #1 - SUPPLY FAN MOTOR 25 A 14.40 A
TOTAL CFM
MBH TOTAL LOAD
EAT DB (°F)
LAT DB (°F)
TYPE COIL & PRESSURE
REMARKS:
6,000
NONE
TOTAL CFM
TOTAL LOAD (MBH)
SENSIBLE LOAD (MBH)
EAT DB/WB (°F)
LAT DB/WB (°F)
TYPE COIL
ROWS MIN.
REMARKS
TOTAL CFM
EXTERNAL STATIC PRESSURE (IN WG)
TOTAL STATIC PRESSURE (IN WG)
WHEEL DIAMETER MIN. (IN)
RPM APPROX.
TYPE DRIVE
HP MIN/VOLT/PH/HZ
NONE
FILTER MINIMUM EFFICIENCY
FILTER AREA (SQFT)
NO
YES
YES
YES
ROWS MINIMUM
FINS/FT MINIMUM
FLOW RATE (GPM)
SQFT FACE AREA MIN.
FACE VELOCITY MAX. (FPM)
AIR PRESSURE DROP (INCHES H2O)
FINS PER FOOT MAX.
SQFT FACE AREA MIN.
FACE VELOCITY MAX.
EWT (°F)
LWT (°F)
GPM
AIR PRESSURE DROP (IN WG)
WATER PRESSURE DROP (FT WG)
TYPE FAN
CLASS FAN
ARRANGEMENT
VFD
FILTER PRESSURE DROP (INWG)
CIRCUIT #2 - RETURN FAN MOTOR 15 A 6.0 A
MERV 8
16.67
0.595
0.13
11.25
12.3
0.50
6.0
NONE
2.00
3.75
22.25
1,808
DIRECT
7.5/460/3/60
PLENUM
CLASS II
1X1
YES
REMARKS:
R E
T U
R N
F A
N
6,000TOTAL CFM
EXTERNAL STATIC PRESSURE (IN WG)
TOTAL STATIC PRESSURE (IN WG)
WHEEL DIAMETER MIN. (IN)
RPM APPROX.
TYPE DRIVE
HP MIN/VOLT/PH/HZ
NONE
TYPE FAN
CLASS FAN
ARRANGEMENT
VFD
1.00
1.20
1,592
DIRECT
3.0/460/3/60
PLENUM
CLASS II
1X1
YES
NONE
WATER PRESSURE DROP (INCHES H2O) 4.54
SUPPLY AIR
DAMPERM
M
RETURN AIR
SMOKE DAMPER
TO FIRE
ALARM
SYSTEM
DD SPHSHSTS
DP
FINAL
FILTER
TSTSTSHSTS
D A
WALL-MOUNTED
TEMPERATURE
SENSOR W/
SETPOINT
ADJUSTMENT
HOT WATER
REHEAT COIL
SUPPLY AIR
TO SPACE
120/1Ph
TO AHU
CONTROL
LER
AIRFLOW
MEASURING
DEVICE
VOLUME
REGULATOR
T
TERMINAL UNIT CONTROL DIAGRAM
CONTROLLER
H
C
SUPPLY AIR
FROM AHU
NOTE: PROVIDE 2-WAY CONTROL
VALVES UNLESS OTHERWISE NOTED
TO BUILDING
AUTOMATION SYSTEM
AI
T
CONDENSING UNIT
REFRIGERANT
COOLING COIL
D
X
RETURN AIR
FILTER
SUPPLY FAN
DUCTLESS SPLIT SYSTEM DIAGRAM
N.T.S.
SPLIT SYSTEM AIR HANDLING UNIT CONTROL (TYPICAL)
SPACE TEMPERATURE CONTROL: THE SPACE TEMPERATURE CONTROLLED LOCALLY. A DDC TEMPERATURE
SENSOR SHALL BE PROVIDED. THIS TEMPERATURE SENSOR SHALL REPORT THE SPACE TEMPERATURE TO THE BAS.
ALARMS: ALARM IF SPACE TEMPERATURE REPORTED BY THE DDC TEMPERATURE SENSOR REPORTS A TEMPERATURE
ABOVE 80 DEGREES FAHRENHEIT.
PROVIDE DDC TEMP SENSOR
LOCATED IN EACH DIT ROOM
TT
T-1
BI-1
HIGH TEMPERATURE
AI-1
SPACE TEMPERATURE
PROVIDE DDC HUMIDITY SENSOR
LOCATED IN EACH DIT ROOM
HH
H-1
BI-1
HIGH HUMIDITY
AI-1
SPACE HUMIDITY
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
M004
MECHANICAL - AHU CONTROL
SCHEMATICS
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
FD
FD FD
FD
FD
NOT IN SCOPE
NOT IN SCOPE
(E)
(E) (E)(E)
(E)
2 2 2 2
(E)VAV
3 3
3 3 6"ø
6"ø 24"x12"
8"ø
"x
6"øCFM
CFM
CFM
NOT IN SCOPE
20"X20" EA UP
TO EXISTING
EXHAUST FAN
IN ATTIC.
A2
A3
A4 A5
A6 A7 A8 A9 A10 A11
A12 A13 A14
A15
A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED
TO COMPLY WITH THE STATE BUILDING CODE.
B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE
LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,
LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE
NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION
DRAWINGS, AS SPECIFIED.
C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES
AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL
STARTERS AND DISCONNECT SWITCHES WITH ELECTRICAL
CONTRACTOR.
D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING
A CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE
STATIC PRESSURE OF THE UNIT SUPPLY FAN.
E. ALL EQUIPMENT SHALL BE U.L. LISTED.
F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL
EQUIPMENT; PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL
STARTERS, AND MOUNT AND WIRE VARIABLE SPEED DRIVES, UNLESS
OTHERWISE NOTED.
G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE
ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND
INSTALLATION INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL
HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY
ARE INSTALLED. PROVIDE DYNAMIC FIRE DAMPERS.
H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH
OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT
RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE
ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE
CONTRACTOR.
I. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM
CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR
UNLESS OTHERWISE NOTED. PROVIDE DUCT ACCESS DOOR AT EACH
DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS.
J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH
ROOFING
CONTRACTOR.
K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF
DUCTWORK TO ENSURE DUCTWORK DOES NOT PASS OVER
ELECTRICAL PANELS.
L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL
REFERENCE ONLY.
M. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH
THE OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE
OF ONE WEEK. THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR
SOME SHUTDOWNS AND SHALL BE AT THE OWNERS DISCRETION.
N. LEAVE A MINIMUM CLEARANCE OF 2 INCHES ABOVE DUCTS INSTALLED
IN RATED PARTITIONS TO ALLOW SPACE FOR THE GENERAL
CONTRACTOR TO SEAL THE WALL ABOVE THE DUCTS. DO NOT INSTALL
FLEXIBLE DUCT THROUGH RATED WALLS, BARRIERS OR PARTITIONS.
O. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED
DAMPERS, FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE
DETECTORS, AND SIMILAR ITEMS REQUIRING MAINTENANCE OR
ADJUSTMENT.
P. MECHANICAL CONTRACTOR SHALL INSTALL MANUAL VOLUME DAMPERS
ON ALL BRANCH DUCTWORK CONNECTIONS.
Q. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
GENERAL NOTES
EXISTING VAV BOX TO REMAIN.
EXISTING KEYED NOTES
EXISTING DUCTWORK EXTEND OUTSIDE SCOPE OF WORK.2
EXISTING AIR TERMINAL TO BE REMOVED, CLEANED AND RELOCATED AS
REQUIRED TO ACCOMODATE ARCHITECTURAL RENOVATIONS.
DEMOLISH EXISTING FIRE DAMPER COMPLETE. PATCH AND REPAIR WALL
AS REQUIRED.
DEMOLITION KEYED NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
MD100
MECHANICAL - LEVEL 03 -
DEMOLITION - DUCTWORK
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT CAS
1/8" = 1'-0"
MECHANICAL - LEVEL 03 - DEMOLITION - DUCTWORK
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
8 84 16 32
FD
FD
DD
D D
OIT
320A
BRIEFING CENTER
320B
PRIVATE OFFICE
320D
PRIVATE OFFICE
320E
MECHANICAL
312C
CONFERENCE ROOM/ADHOC
WORK AREA
PIPE CLOSET
330A
CERNER ARCHITECTS
9-3-3V
1000 CFM
9-3-7V
300 CFM
9-3-8V
450 CFM
9-3-2V
540 CFM
9-3-4V
410 CFM 9-3-5V
800 CFM
9-3-6V
800 CFM
STORAGE
320C
PRIVATE OFFICE
320F
PRIVATE OFFICE
320G
CERNER CONTROL
CENTER/WORK SPACES
SSEU-1
AHU-09
NOT IN SCOPE
NOT IN SCOPE
NOT IN SCOPE
(E)VAV
9-3-1V
700 CFM
SSCU-1
(E) (E)
(E)
(E)
RECEPTION
312A
RECEPTION
312A
WOMENS
CONFERENCE ROOM/ADHOC
WORK AREA
312B
A2
A3
A4 A5
A6 A7 A8 A9 A10 A11
A12 A13 A14
A15
9-3-9V
1.3 GPM
FIRST FLOOR ROOF
UH-1
SP
A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED
TO COMPLY WITH THE STATE BUILDING CODE.
B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE
LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,
LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE
NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION
DRAWINGS, AS SPECIFIED.
C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES
AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL
STARTERS AND DISCONNECT SWITCHES WITH ELECTRICAL
CONTRACTOR.
D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING
A CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE
STATIC PRESSURE OF THE UNIT SUPPLY FAN.
E. ALL EQUIPMENT SHALL BE U.L. LISTED.
F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL
EQUIPMENT; PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL
STARTERS, AND MOUNT AND WIRE VARIABLE SPEED DRIVES, UNLESS
OTHERWISE NOTED.
G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE
ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND
INSTALLATION INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL
HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY
ARE INSTALLED. PROVIDE DYNAMIC FIRE DAMPERS.
H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH
OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT
RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE
ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE
CONTRACTOR.
I. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM
CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR
UNLESS OTHERWISE NOTED. PROVIDE DUCT ACCESS DOOR AT EACH
DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS.
J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH
ROOFING
CONTRACTOR.
K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF
DUCTWORK TO ENSURE DUCTWORK DOES NOT PASS OVER
ELECTRICAL PANELS.
L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL
REFERENCE ONLY.
M. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH
THE OWNERS REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE
OF ONE WEEK. THIS TIME LENGTH MAY BE LONGER OR SHORTER FOR
SOME SHUTDOWNS AND SHALL BE AT THE OWNERS DISCRETION.
N. LEAVE A MINIMUM CLEARANCE OF 2 INCHES ABOVE DUCTS INSTALLED
IN RATED PARTITIONS TO ALLOW SPACE FOR THE GENERAL
CONTRACTOR TO SEAL THE WALL ABOVE THE DUCTS. DO NOT INSTALL
FLEXIBLE DUCT THROUGH RATED WALLS, BARRIERS OR PARTITIONS.
O. PROVIDE REMOVABLE ACCESS DOORS AT ALL MOTOR OPERATED
DAMPERS, FIRE DAMPERS, SMOKE DAMPERS, DUCT COILS, SMOKE
DETECTORS, AND SIMILAR ITEMS REQUIRING MAINTENANCE OR
ADJUSTMENT.
P. MECHANICAL CONTRACTOR SHALL INSTALL MANUAL VOLUME DAMPERS
ON ALL BRANCH DUCTWORK CONNECTIONS.
Q. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.
GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:4
A
M
MH100
MECHANICAL - LEVEL 03 - NEW
WORK - DUCTWORK - OVERALL
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT CAS
1/8" = 1'-0"
MECHANICAL - LEVEL 03 - NEW WORK - DUCTWORK - OVERALL
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
8 84 16 32
FOR REFERENCE ONLY. REFER TO
1/4" SCALED DRAWINGS FOR SIZES
AND AIRFLOWS.
DD
OIT
320A
BRIEFING CENTER
320B
PRIVATE OFFICE
320D
PRIVATE OFFICE
320E
9-3-3V
1000 CFM
9-3-2V
540 CFM
9-3-4V
410 CFM
STORAGE
320C
PRIVATE OFFICE
320F
PRIVATE OFFICE
320G
CERNER CONTROL
CENTER/WORK SPACES
SSEU-1
NOT IN SCOPE
16"x15"
18"x12"
"ø
"x
8"ø
"ø
8"ø
"x
"ø
6"ø
"ø
14"x12"
"ø
"ø
8"ø
"ø 8
"ø
"ø
"ø
"ø
14"x12"
8"ø
140 4
9-3-1V
700 CFM
14"x14" 28"x14"
10"ø
20"x14"
"ø
"ø
"ø
"ø 8 "ø 8 "ø
12"ø
A2
A3
A4 A5
A6
A15
MH100B
MH100B
"x
10"ø
FIRST FLOOR ROOF
"ø
A. ALL DUCTS, PIPE, AND EQUIPMENT SHALL BE LATERALLY RESTRAINED
TO COMPLY WITH THE STATE BUILDING CODE.
B. BEFORE FABRICATING ANY SHEET METAL DUCTWORK, COORDINATE
LOCATION AND SIZE WITH SPRINKLER & PLUMBING PIPING, CONDUITS,
LIGHT FIXTURES, STRUCTURAL, ETC. PLANS ARE SCHEMATIC AND ARE
NOT SHOP DRAWINGS. SUBMIT DUCTWORK COORDINATION
DRAWINGS, AS SPECIFIED.
C. BEFORE SUBMITTING SHOP DRAWINGS, COORDINATE VOLTAGES
AVAILABLE FOR MECHANICAL EQUIPMENT AND PROVISION OF ALL
STARTERS AND DISCONNECT SWITCHES WITH ELECTRICAL
CONTRACTOR.
D. MECHANICAL CONTRACTOR SHALL MAKE PROVISIONS FOR PROVIDING
A CONDENSATE DRAIN TRAP A MINIMUM OF 4" DEEP OR 1/2" PLUS THE
STATIC PRESSURE OF THE UNIT SUPPLY FAN.
E. ALL EQUIPMENT SHALL BE U.L. LISTED.
F. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL MECHANICAL
EQUIPMENT; PROVIDE DISCONNECTS, WIRING AND CONDUIT, INSTALL
STARTERS, AND MOUNT AND WIRE VARIABLE SPEED DRIVES, UNLESS
OTHERWISE NOTED.
G. FIRE AND SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE
ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND
INSTALLATION INSTRUCTIONS. FIRE AND SMOKE DAMPERS SHALL
HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY
ARE INSTALLED. PROVIDE DYNAMIC FIRE DAMPERS.
H. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH
OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT
RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE
ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION TO THE
CONTRACTOR.
I. SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM
CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR
UNLESS OTHERWISE NOTED. PROVIDE DUCT ACCESS DOOR AT EACH
DETECTOR. INSTALL DETECTORS IN COMPLETE ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS.
J. COORDINATE HEIGHT OF ROOF CURBS AND ROOF SUPPORTS WITH
ROOFING
CONTRACTOR.
K. MECHANICAL CONTRACTOR SHALL COORDINATE ROUTING OF
DUCTWORK TO ENSURE DUCTWORK DOES NOT PASS OVER
ELECTRICAL PANELS.
L. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION
PURPOSES. THE SCALE, WHEN INDICATED IS INTENDED FOR GENERAL
REFERENCE…