This document is a set of fire alarm design and installation drawings and specifications for a federal construction project at a Veterans Affairs facility in Columbia, South Carolina. The project involves renovating Building B3 for the EHRM Admin and Training Center, requiring expansion and modification of the existing addressable fire alarm system to serve the renovated areas.
The scope of work includes furnishing and installing new fire alarm devices compatible with the existing system, including photoelectric smoke detectors, heat detectors, manual pull stations, horn-strobes, duct smoke detectors, and remote indicator stations. The fire alarm contractor is responsible for complete system design with sealed shop drawings prepared by a licensed professional engineer or NICET Level III/IV certified designer. Key requirements include: sealing all fire-rated wall and floor penetrations with UL-listed materials; installing conductors in 3/4-inch minimum conduit colored red; providing end-of-line resistors; coordinating device locations with other building systems; programming the existing fire alarm control panel to accommodate new points; providing a 100% system acceptance test; and delivering as-built drawings, zone maps, and maintenance schedules upon completion. The contractor must also manage interim fire protection during system impairment, including providing temporary heat detectors and fire watches where required. All work must comply with NFPA 72, NFPA 70, NFPA 1, NFPA 101, ADA standards, and the VA Fire Protection Design Manual (November 2023, Ninth Edition). The existing fire alarm monitoring service with the DACT communicator shall remain operational throughout construction.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C
RI
FIRE ALARM GENERAL NOTES
1. BEFORE SUBMITTING A PROPOSAL FOR THE WORK, EACH BIDDER WILL BE HELD RESPONSIBLE TO HAVE EXAMINED THE EXISTING SITE CONDITIONS FOR THE WORK INCLUDED UNDER THIS CONTRACT.
NO ALLOWANCE WILL BE MADE SUBSEQUENTLY IN THIS CONNECTION ON BEHALF OF THE
CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.
2. NO FIRE ALARM DOCUMENTS/PLANS SHALL BE USED FOR DEMOLITION OF THIS SYSTEM UNLESS THEY CONTAIN A REVIEW AND APPROVAL STAMP FROM THE VA FIRE OFFICIAL AND A COMPLETED REVIEW BY THE ARCHITECT/ENGINEER. THE VA FIRE OFFICIAL OR ARCHITECT/ENGINEER HAS THE
AUTHORITY TO STOP ANY WORK UNTIL SUCH PLANS ARE ON SITE AND IN USE.
3. THE NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM.
4. ALL ALARM DEVICE LOCATIONS SHALL BE COORDINATED WITH LIGHT FIXTURES, HVAC DIFFUSERS, SPRINKLERS, SIGNS, AND OTHER MEP TRADES PRIOR TO CONSTRUCTION.
5. UNLESS NOTED OTHERWISE ELSEWHERE, FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR
SEALING ALL FIRE RATED WALL PARTITIONS WITH A UL LISTED ASSEMBLY.
6. WALL PENETRATIONS THROUGH NON-RATED PARTITIONS SHALL BE PROVIDED WITH A NON-
SHRINKING GROUT OR CAULKING MATERIAL AND APPROVED ASSEMBLY.
7. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN OF THE FIRE
ALARM SYSTEMS AND SHALL PROVIDE SEALED SHOP DRAWINGS. FIRE ALARM DEVICE LAYOUTS,
DEVICES COUNTS, CONDUCTOR TYPES, WIRING DIAGRAMS, I/O MATRIX, RISER DIAGRAMS, AND BATTERY CALCULATIONS SHALL BE SEALED BY AN PROFESSIONAL ENGINEER OR A NICET LEVEL III OR LEVEL IV FIRE ALARM DESIGNER THAT IS REGISTERED IN THE STATE WHERE THE WORK IS TO
OCCUR.
8. FLOOR/WALL PENETRATIONS THROUGH RATED SEPARATIONS SHALL BE SEALED WITH AN APPROVED
FIRE RATED MATERIAL.
9. THE FIRE ALARM PLANS ARE FOR COORDINATION AND BIDDING PURPOSES ONLY. THE FIRE ALARM
CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN.
10. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF WALLS
AND CEILING REQUIRED FOR THE INSTALLATION OF THE NEW FIRE SUPPRESSION SYSTEM.
11. UNLESS NOTED OTHERWISE ELSEWHERE, FIRE ALARM SHOP DRAWINGS SHALL INCLUDE
REFLECTIVE CEILING PLANS THAT INDICATE THE FOLLOWING:
A. CEILING TYPES AND GRID
B. ALL CEILING MOUNTED DEVICES (LIGHTS, DIFFUSERS, SPRINKLERS, AND ALL SPECIAL
ELECTRICAL SYSTEMS).
12. THE FIRE ALARM CONTRACTOR SHALL LOCATE CEILING MOUNTED DEVICES AS FOLLOWS:
A. ALL DEVICES SHALL BE LOCATED IN THE CENTER OF ONE QUADRANT (2' x 4').
B. IN GYP. BOARD CEILINGS FIRE ALARM DEVICES SHALL BE LOCATED IN SYMMETRICAL PATTERNS
RELATIVE TO OTHER DEVICES LOCATED IN THE CEILING.
13. THE CIRCUIT WIRING SHALL BE SIZED AS FOLLOWS
A. NOTIFICATION APPLIANCE CIRCUITS SHALL BE A MINIMUM OF #14 AWG.
B. SIGNAL LINE CIRCUITS SHALL BE A MINIMUM OF #18 AWG AND MAXIMUM OF #14 AWG.
14. ALL SMOKE DUCT DETECTORS CONCEALED ABOVE CEILINGS SHALL BE PROVIDED WITH A REMOTE
LED INDICATING TEST STATION AT THE NEAREST CORRIDOR.
15. THE FIRE ALARM SYSTEM SHALL BE AN ADDRESSABLE SYSTEM INCLUDING INDIVIDUALLY
ADDRESSED DEVICES.
16. ALL FIRE ALARM HORN-STROBES SHALL BE TAPPED AT 1/2 WATT UNLESS NOTED OTHERWISE.
17. ALL FIRE ALARM DEVICES ARE TO BE WHITE WITH CONTRASTING LETTERING.
18. CONDUCTORS FOR DETECTORS, MANUAL STATIONS AND SUPERVISORY DEVICES CAN BE INSTALLED IN THE SAME CONDUIT BUT MUST BE INSTALLED IN A SEPARATE CONDUIT FROM ALL INDICATING
DEVICES (HORN/STROBE,STROBE) AND FROM 120 VAC CIRCUITS.
19. USE THE EXISTING LOCAL FIRE ALARM CONTROL PANEL AND ADD ZONE CARD AND POWER SUPPLY
AS NECESSARY.
20. FURNISH AND INSTALL END-OF-LINE RESISTORS AND CLEARLY MARK THE LOCATION OF THIS DEVICE.
21. CONNECT DUCT SMOKE DETECTORS IN THE HVAC SYSTEM (FURNISHED BY THE FIRE ALARM
CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR) TO ACTIVATE THE FIRE ALARM
SYSTEM AND SHUTDOWN THE HVAC SYSTEM IN THE EVENT OF SMOKE DETECTED IN THE HVAC
DUCTS.
22. ALL FIRE ALARM SYSTEM COMPONENTS SHALL BE UL LISTED.
23. FURNISH AND INSTALL DUCT SMOKE DETECTOR TEST STATION IN CEILING TO SHOW LOCATION OF
DETECTOR WHEN IN ALARM OR TROUBLE.
24. WHERE APPLICABLE, ELECTRICAL AND FIRE ALARM CONTRACTORS ARE TO PROVIDE CONNECTIONS
TO EACH FIRE DAMPER AND SMOKE DAMPER TO PERMIT OPERATION OF THE DAMPERS IN ALARM
AND TEST MODES. FIRE DAMPERS REQUIRE POWER FOR ELECTRICAL RESET. REFER TO FIRE/SMOKE
DAMPER DETAIL AND REFER TO ELECTRICAL CONTRACT DRAWINGS FOR PANEL SCHEDULES AND
CIRCUIT NUMBER.
25. IN THE EVENT OF A CODE CONFLICT, THE MOST RESTRICTIVE CODE OR STANDARD SHALL BE
OBSERVED AND COMPLIED FOR THIS PROJECT.
26. FOLLOWING THE FIRE ALARM SYSTEM INSTALLATION, A 100% FIRE ALARM SYSTEM ACCEPTANCE
TEST SHALL BE CONDUCTED BY THE FIRE ALARM CONTRACTOR FOR THE SCOPE OF WORK SHOWN
ON THESE DOCUMENTS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT, ENGINEER, OWNER AND
ALL AUTHORITIES HAVING JURISDICTION WITHIN FIVE (5) WORKING DAYS OF THE TEST FOR
SCHEDULING.
27. ALL FIRE ALARM NOTIFICATION APPLIANCE SIGNALS SHALL SOUND A TEMPORAL THREE PATTERN
UNLESS OTHERWISE SPECIFIED BY THE AUTHORITY HAVING JURISDICTION.
28. ALL VISUAL APPLIANCE CANDELA RATING SHALL CONFORM TO NFPA, ADA AND ALL AUTHORITIES
HAVING JURISDICTION REQUIREMENTS.
29. ALL NOTIFICATION DEVICES SHALL BE SYNCHRONIZED AND INSTALLED AS DEFINED BY NFPA 72 AND
INTERNATIONAL BUILDING CODE REQUIREMENTS.
30. ALL FIRE ALARM DEVICES AND NOTIFICATION APPLIANCES SHALL BE ACCESSIBLE FOR PERIODIC
INSPECTIONS, MAINTENANCE AND TESTING PURPOSES.
31. ALL FIRE ALARM DEVICES AND NOTIFICATION APPLIANCES SUBJECT TO MECHANICAL DAMAGE SHALL
BE PROTECTED BY A MANUFACTURER'S APPROVED PROTECTIVE COVER/GUARD.
32. THE FIRE ALARM CONTRACTOR SHALL NOT PROTECTIVE COVERS FROM DETECTORS UNTIL AFTER
THE CONSTRUCTION CLEAN UP OF ALL TRADES IS COMPLETE AND FINAL.
33. THE FIRE ALARM CONTRACTOR SHALL PREPARE AS-BUILT DRAWINGS DURING THE INSTALLATION
OF THE FIRE ALARM SYSTEM.
34. A FIRE ALARM SYSTEM RECORD OF COMPLETION SHALL BE PRESENTED TO THE ARCHITECT, ENGINEER, AND OWNER'S REPRESENTATIVE AT THE CONCLUSION OF THIS FIRE ALARM SYSTEM
INSTALLATION.
35. A VOLTAGE DROP CALCULATION SHALL BE PERFORMED AND SUBMITTED BY THE FIRE ALARM CONTRACTOR FOR POWER CONSUMING CIRCUITS; IN ORDER TO VALIDATE THAT THE SYSTEM HAS BEEN DESIGNED WITHIN NFPA TOLERABLE LIMITS. NOTIFICATION APPLIANCE DEVICES CIRCUIT VOLTAGE DROP CALCULATIONS SHALL HAVE A MAXIMUM VOLTAGE DROP OF 15% AND A PREFERRED
VOLTAGE DROP OF 10% MEETING NFPA 72, SECTION 10.3.5.
36. THE FIRE ALARM SYSTEM SHALL BE AN ADDRESSABLE SYSTEM INCLUDING INDIVIDUALLY
ADDRESSED DEVICES.
37. THE CONTRACTOR SHALL PROVIDE THE OWNER WITH OPERATING, TESTING, MAINTENANCE
INSTRUCTION, SITE SPECIFIC SOFTWARE CHANGES/ADDITIONS, AND AS-BUILT DRAWINGS AT THE CONCLUSION OF THIS FIRE ALARM INSTALLATION. IT IS THE OWNER'S RESPONSIBILITY TO MAINTAIN ALL RECORDS OF THIS FIRE ALARM INSTALLATION IN A LOCATION APPROVED BY THE AUTHORITY
HAVING JURISDICTION.
38. THE CONTRACTOR SHALL PROVIDE THE OWNER WITH A ZONE MAP IN ACCORDANCE WITH NFPA
STANDARDS AT THE CONCLUSION OF THIS FIRE ALARM INSTALLATION. IT IS THE OWNER'S
RESPONSIBILITY TO MAINTAIN ZONE MAPS IN CURRENT CONDITIONS THROUGHOUT THE LIFE OF THIS
FIRE ALARM SYSTEM.
39. THE CONTRACTOR SHALL PROVIDE THE OWNER WITH MAINTENANCE AND TESTING SCHEDULE FOR ALL EQUIPMENT FURNISH/INSTALLED UNDER THIS SCOPE OF WORK IN ACCORDANCE WITH NFPA 72
GUIDELINES.
40. ALL FIRE ALARM CABLE SHALL BE INSTALLED PER NFPA 70 REQUIREMENT.
41. ALL FIRE ALARM CABLE SHALL BE MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 70 AND NFPA 72
REQUIREMENTS.
42. ALL FIRE ALARM CABLE SHALL BE INSTALLED IN A NEAT, WORKMAN LIKE MANNER.
43. ALL FIRE ALARM CABLES SHALL BE INSTALLED IN A CONDUIT OR METALLIC RACEWAY AND BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE. FIRE ALARM CABLE SHALL NOT BE STRAPPED, TAPED OR ATTACHED BY ANY MEANS TO THE EXTERIOR OF ANY CONDUIT OR OTHER RACEWAY AS A MEANS OF SUPPORT.
44. ALL FIRE ALARM CABLE SHALL BE SUPPORTED BY STRAPS, HANGERS OR SIMILAR FITTING DESIGNED AND
INSTALLED SO AS NOT TO DAMAGE THE CABLE.
45. ALL FIRE ALARM CABLES SHALL BE ACCESSIBLE; WHERE, BUILDING FEATURES DO NOT PROVIDE ACCESSIBILITY, OR THE FIRE ALARM CABLE SHALL BE INSTALLED IN AN APPROVED METAL RACEWAY.
46. ALL WIRING SHALL BE SECURED TO THE STRUCTURE AS SPECIFIED IN NFPA 70.
47. ALL CONDUIT/RACEWAY SHALL BE SECURED TO THE STRUCTURE AS SPECIFIED IN NFPA 70.
48. THE FIRE ALARM SYSTEM ADDITION AND/OR MODIFICATIONS SHALL BE TEST FREE OF GROUNDS.
49. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR DETERMINING CABLE FILL/CONDUIT SIZING PER NFPA 70
REQUIREMENTS (ALL FIRE ALARM CONDUIT SHALL BE A MINIMUM SIZE OF 3/4 - INCH).
50. ALL FIRE ALARM CABLE, CONDUIT AND METALLIC RACEWAYS SHALL BE RED.
51. THE EXISTING ADDRESSABLE FIRE ALARM SYSTEM SHALL BE EXPANDED AS NEEDED TO SERVE THE RENOVATED AREA. NEW ADDRESSABLE DEVICES AND CONDUCTORS SHALL BE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM. PROVIDE NEW BATTERIES AND POWER SUPPLIES, AS REQUIRED. PROVIDE PROGRAMMING OF EXISTING FIRE ALARM SYSTEM IN ORDER TO ADD NEW POINTS AS REQUIRED DUCTS THE RENOVATION SHOWN ON THESE
CONTRACT DOCUMENTS.
52. WHERE, VISUAL, AUDIBLE AND NOTIFICATION DEVICES ARE ADDED TO THE EXISTING SYSTEM THE FIRE ALARM CONTRACTOR SHALL BE REQUIRED TO INCLUDE POWER AVAILABILITY ANALYSIS SHOWING THAT THE INTENDED SOURCE OF POWER, THE NOTIFICATION CIRCUIT CAPACITY AND STABILITY POWER AVAILABILITY; IN ORDER TO VALIDATE THAT THE EXISTING BATTERY SECONDARY POWER SOURCE SHALL HAVE A MINIMUM OF 20 PERCENT SAFETY MARGIN ABOVE THE CALCULATED AMP-HOUR CAPACITY REQUIRED. ANY CASES WHERE THE 20 PERCENT SAFETY MARGIN ABOVE THE CALCULATED AMP-HOUR CAPACITY IS NOT BEING MET THE SECONDARY SOURCE BATTERIES SHALL BE REPLACED AND UPGRADED AT THE BUILDING'S MAIN FIRE ALARM CONTROL PANEL TO MEET
NFPA 72 REQUIREMENTS BY THIS FIRE ALARM CONTRACTOR/INSTALLER.
53. DUCT DETECTORS SHALL BE MONITORED FOR INTEGRITY AND PROVIDE A SUPERVISOR SIGNAL AT THE SUPERVISORY FIRE ALARM CONTROL PANEL (FACP). AIR HANDLER SYSTEMS SHALL BE RAN AND BLOWN OUT
PRIOR TO THE INSTALLATION OF SMOKE DETECTORS.
54. MAINTAINABILITY
A. EXTERNAL AND INTERNAL PARTS SHALL BE ARRANGED SO THAT WHEN INSTALLED, ALL PARTS REQUIRING MANIPULATION, OBSERVATION, AND/OR MAINTENANCE ARE READILY ACCESSIBLE AND SAFE FOR OPERATION AND MAINTENANCE PERSONNEL. WHEREVER PRACTICAL, INSTRUMENTS AND EQUIPMENT SHALL BE LOCATED
SUCH THAT THEY CAN BE OPERATED AND EASILY ACCESSED FROM GRADE LEVEL.
B. MAINTAINABILITY SHALL BE INCORPORATED INTO THE DESIGN OF ALL CONTRACTOR SUPPLIED EQUIPMENT.
THE PRIMARY MAINTAINABILITY OBJECT SHALL BE TO MINIMIZE THE COMPLEXITY AND TIME REQUIRED FOR MAINTENANCE. THE FOLLOWING GENERAL CRITERIA SHALL BE FOLLOWED TO ACHIEVE THIS OBJECTIVE:
a. CONTRACTOR SUPPLIED EQUIPMENT SHALL BE LOW MAINTENANCE DESIGN AND SHALL BE EASILY
MAINTAINABLE.
b. CONTRACTOR SUPPLIED EQUIPMENT SHALL BE DESIGNED TO BE MAINTAINED IN PLACE, IF POSSIBLE, WITH MINIMUM DISASSEMBLY OF SURROUNDING EQUIPMENT AND MINIMUM USAGE OF TEMPORARY
SCAFFOLDING AND HANDLING EQUIPMENT.
55. DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EACH AND EVERY CONDUCTOR, FITTING DEVICE, RACEWAY OR COMPLETE DETAIL OF ALL THE WORK TO BE PERFORMED, BUT ARE FOR THE PURPOSES OF ILLUSTRATING THE TYPE OF SYSTEM AND CONDITIONS NECESSARY FOR AN EXPERIENCED TRADESMAN TO LAY OUT HIS WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING SUCH SITE EVALUATIONS AND
MEASUREMENTS AS NECESSARY TO PROPERLY COMPLETE THE WORK.
56. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL PRESENT THE ENGINEER, ARCHITECT AND OWNER WITH A REPORT CONFIRMING TESTING OF ALL NEW DEVICES IN THE PROJECT ZONE; ALONG WITH APPROPRIATE SELECTED TESTING OF THE MAIN FIRE ALARM SYSTEM TO CONFIRM CONTINUED PROPER OPERATION. A CERTIFICATE OF APPROVAL FROM THE APPROPRIATE AGENCY INSPECTION AGENT WILL BE REQUIRED PRIOR TO
FINAL ACCEPTANCE OF THE PROJECT.
57. ALL CONCEALED CONDUCTORS SHALL BE INSTALLED IN EMT RACEWAYS, JUNCTION AND OUTLET BOXES SHALL
BE STEEL; EXPOSED BOXES SHALL HAVE SOLID SIDES WITH ONLY ONE ENTRANCE KNOCKOUT.
58. A FIRE ALARM SYSTEM RECORD OF COMPLETION SHALL BE PRESENTED TO THE ARCHITECT, ENGINEER, AND
OWNER'S REPRESENTATIVE AT THE CONCLUSION OF THIS FIRE ALARM SYSTEM INSTALLATION.
59. DUCT DETECTORS SHALL BE MONITORED FOR INTEGRITY AND PROVIDE A SUPERVISOR SIGNAL AT THE SUPERVISORY FIRE ALARM CONTROL PANEL (FACP). AIR HANDLER SYSTEMS SHALL BE OPERATED AND PURGED
PRIOR TO THE INSTALLATION OF SMOKE DETECTORS.
60. WHERE A DUCT SMOKE DETECTOR IS LOCATED ABOVE A CEILING OR IN A DIFFICULT TO REACH LOCATION, PROVIDE A REMOTE INDICATING LAMP AND A TEST KEY SWITCH ON NEARBY WALL AT 7 FEET AFF TO FACILITATE
TESTING.
61. UNLESS OTHERWISE NOTED THE FOLLOWING MINIMUM SURVIVABILITY CRITERIA SHALL BE MET:
A. SIGNALING LINE CIRCUIT (SLC) CLASS “ B ”.
B. NOTIFICATION ALARM CIRCUIT (NAC) CLASS “ B ”.
62. SPRINKLER SYSTEM MONITORING: FIRE ALARM CONTRACTOR SHALL MAINTAIN SUPERVISION OF ANY EXISTING SPRINKLER SYSTEM BEING MODIFIED AS PART OF THIS PROJECT AT ALL TIMES. CONTRACTOR SHALL
COORDINATE TRANSFER WITH OWNER AND ENGINEER OF RECORD.
63. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH OTHER TRADES TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK INSTALLED BY THIS CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN TRADES, SHALL BE CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER
WITHOUT ADDITIONAL COMPENSATION TO THE CONTRACTOR.
64. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR PROVIDING DESIGN SHOP DRAWINGS, CALCULATIONS, ETC., INCLUDING BUT NOT LIMITED TO ALL ITEMS WHICH APPLY AS OUTLINED IN NFPA 72 SECTIONS 7.2, 7.4 AND 7.5, TITLED, "MINIMUM REQUIRED DOCUMENTATION", "SHOP DRAWINGS (INSTALLATION DOCUMENTATION)," AND
"COMPLETION DOCUMENTATION".
65. FIRE/SMOKE AND DUCT SMOKE DETECTORS SHALL BE PLACED ON THE NORMAL POWER PANEL CIRCUIT. REFER
TO ELECTRICAL DISCIPLINE DRAWINGS FOR WIRING CONFIGURATION.
66. THIS CONTRACTOR IS RESPONSIBLE FOR SUBMISSION OF SYSTEM RECORD OF COMPLETION MEETING NFPA 72, FIGURES 7.8.2(a) FOR REVIEW AND COMMENT BY THE VA AND ENGINEER OF RECORD. ALL SYSTEM RECORD OF COMPLETIONS MUST BE DATED, PRINTED NAME OF INDIVIDUALS WHO SIGNED THE SYSTEM RECORD OF COMPLETION AND SIGNATURES. ALL TEST MUST BE COORDINATED WITH THE VA COR, VA FIRE SAFETY OFFICIAL AND THE ENGINEER OF RECORD. SIGNATURES BY NON VA FIRE OFFICIALS WILL NOT BE ACCEPTED.
DESIGN CODES, STANDARDS & PARTIES OF REFERENCE
THE FOLLOWING PUBLICATIONS AND AUTHORITIES HAVING JURISDICTION SHALL BE
REFERENCED FOR THE DESIGN OF THE FIRE PROTECTION SYSTEM ON THIS PROJECT:
1. ANSI, A117.1 STANDARD, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES. 2017
EDITION
2. NFPA 1 - FIRE CODE, 2024 EDITION
3. NFPA 10 - STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2022 EDITION
4. NFPA 70 - NATIONAL ELECTRIC CODE, 2023 EDITION
5. NFPA 72 - NATIONAL FIRE ALARM & SIGNALING CODE, 2022 EDITION
6. NFPA 101 - LIFE SAFETY CODE. 2024 EDITION
7. NFPA 170 - LIFE SAFETY CODE, 2024 EDITION
8. NFPA 241 - STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERNATION AND
DEMOLITION OPERATIONS, 2022 EDITION
9. VA FIRE PROTECTION DESIGN MANUAL, NOVEMBER 1. 2023, NINETH EDITION
10. VA SEISMIC DESIGN REQUIREMENTS, REVISED JULY 1, 2023 EDITION
11. VA FIRE SAFETY
ADA
AHJ
AIM
AOM
A
AUTO
A/CO
NC
AFF
AFG
AWG
BATT
BSMT
BR
BOB
BMS
CD
CLG
CM
C
DN
DACT
EA
ELEC
EL
EOL
EXIST
XP
EX
FM
FA
FAA
FL
GALV
GPM
GA
GC
GR
GND
GFI
HP
HVAC
FIRE ALARM ABBREVIATIONS
AMERICANS WITH DISABILITIES ACT
AUTHORITY HAVING JURISDICTION
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
AMPERE
AUTOMATIC
ABOVE CONCRETE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMERICAN WIRE GAUGE
BATTERY
BASEMENT
BREAKER
BOTTOM OF BEAM
BUILDING MANAGEMENT SYSTEM
CANDELA
CEILING
CEILING MOUNTED
CONDUIT
DOWN
DIGITAL ALARM COMMUNICATOR
TRANSMITTER
EACH
ELECTRIC/ELECTRICAL
ELEVATION
END ON LINE RESISTOR
EXISTING
EXPLOSION PROOF
EXTERIOR
FACTORY MUTUAL GLOBAL
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FLOOR
GALVANIZED
GALLONS PER MINUTE
GENERAL ALARM (BUILDING WIDE)
GENERAL CONTRACTOR
GRADE
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
HORSEPOWER
HEATING VENTING AND AIR CONDITIONING
INPUT / OUTPUT
INTERIOR
ISOLATOR MODULE
JUNCTION BOX
LIGHTING
LIQUID CRYSTAL DISPLAY
LOCAL OPERATING CONSOLE
MAIN CIRCUIT BREAKER
MAIN FIRE ALARM PANEL
MASS NOTIFICATION SYSTEM
NATIONAL FIRE PROTECTION ASSOCIATION
NATIONAL ELECTRIC CODE
NORMALLY CLOSED
NORMALLY OPENED
NOT IN CONTRACT
NOTIFICATION APPLIANCE CIRCUIT
NOT APPLICABLE
NOT TO SCALE
PANEL
PHASE
PROTECTOWIRE
PRESSURE SWITCH
SIGNALING LINE CIRCUIT
SOLENOID
SPECIFICATION
STEEL
TAMPER SWITCH
TOP OF CONCRETE
TOP OF STEEL
TYPICAL
UNDERWRITERS LABORATORY
UNLESS NOTED OTHERWISE
UNITED STATES DEPARTMENT OF VETERANS AFFAIRS
VALVE
VOLT
VOLTS DIRECT CURRENT
WATERFLOW SWITCH
WATT
WALL MOUNTED
WEATHERPROOF
WIREGUARD
I/O
INT
ISO
JB
LTG
LCD
LOC
MCB
MFAP
MNS
NFPA
NEC
NC
NO
NIC
NAC
NA
NTS
PNL
PH
PW
PS
SLC
SOL
SPEC
STL
TS
TOC
TOS
TYP
UL
UNO
VA
VAL
V
VDC
FS
W
WM
WP
WG
FIRE ALARM AND DETECTION NOTE
FIRE ALARM AND DETECTION PLANS ARE SHOWN FOR BIDDING
PURPOSES. FIRE ALARM AND DETECTION CONTRACTOR IS TO
SUBMIT SHOP DRAWING. FIRE ALARM CALCULATIONS MEETING
NFPA 72 AND VA FIRE PROTECTION DESIGN MANUAL, ALL SHOP
DRAWINGS AND CALCULATION ARE TO BE SIGNED, STAMPED AND
SEALED BY EITHER A LICENSED FIRE PROTECTION ENGINEER IN
THE STATE WHERE WORK WILL BE PERFORMED OR A NICET
LEVEL III OR IV CERTIFICATION IN FIRE ALARM SYSTEM LAYOUT.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH THE VA
REQUIREMENTS AND APPLICABLE CODES.
FIRE ALARM INSPECTION NOTE
A CONTRACTOR SHALL PROVIDE THE ENGINEER FIVE(5) WORKING DAYS
NOTICE FOR ALL REQUESTED REVIEWS OF THE WORK. AS A MINIMUM THE
FOLLOWING REVIEWS SHALL BE CONDUCTED PRIOR TO COVERING UP ANY
CONCEALED WORK:
1.
2.
IN-WALL ROUGH-IN WORK SHALL BE VISIBLE. FIRE ALARM AND FIRE
DETECTION INSPECTIONS SHALL BE COMPLETE AND PASSED.
ABOVE CEILING WORK AN ABOVE CEILING WORK SHALL BE
COMPLETE INCLUDING WIRING TO ALL INITIATING DEVICES AND
NOTIFICATION APPLIANCES; E.G. MANUAL PULL STATIONS, AUDIO
VISUAL DEVICES, SMOKE DETECTORS, ETC. FIRE ALARM AND FIRE
DETECTION INSPECTIONS SHALL BE COMPLETED AND PASSED. ALL
CEILING GRIDS SHALL BE INSTALLED. NO CEILING TILES SHALL BE
INSTALLED.
RE-REVIEW SHALL BE REQUIRED IF THE WORK IS COMPLETE OR NOT
INSTALLED PER THE CONTRACT DOCUMENTS.
FIRE ALARM GENERAL NOTES - DEMOLITION
1. THE INTENTS OF THE DEMOLITION ON THIS PROJECT IS FOR REMOVAL/REWORK OF THE EXISTING FIRE ALARM SYSTEM REQUIRED FOR THE INSTALLATION OF NEW DEVICES. REMOVAL SHALL INCLUDE WIRE, EXPOSED RACEWAYS, FIRE ALARM EQUIPMENT & ASSOCIATED DEVICES, SUPPORTING DEVICES AND ANY OTHER
MISCELLANEOUS EQUIPMENT ASSOCIATED WITH THE FIRE ALARM SYSTEM.
2. THE DEMOLITION OF THE FIRE ALARM SYSTEM MUST BE PHASED. NEW AND EXISTING FIRE ALARM DEVICES AND SYSTEMS MUST BE INTERCONNECTED TO PROVIDE SIMULTANEOUS ACTIVATION AND NOTIFICATION.
EXISTING FIRE ALARM SYSTEMS SHALL BE TREATED AS SEPARATE ADDRESSES ON THE NEW SYSTEM UNTIL
THEY ARE REMOVED OR REPLACED.
3. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR, BUT NOT LIMITED TO: ALL TEMPORARY AND PERMANENT CROSSOVER CONNECTIONS, RELOCATION OF SYSTEM EQUIPMENT AND REPROGRAMMING OF
THE SYSTEM AND EQUIPMENT TO THE NEW AND EXISTING FIRE ALARM SYSTEM.
RENOVATION/CONSTRUCTION FOR THIS SCOPE OF WORK SHALL INCLUDE BUT NOT LIMITED TO THE
FOLLOWING SYSTEMS:
A. NORMAL POWER/LIGHTING CIRCUITS
B. EMERGENCY POWER/LIGHTING CIRCUITS
C. FIRE ALARM SYSTEMS
D. TELEPHONE SYSTEMS
E. DATA SYSTEMS.
4. THE VA RETAINS RIGHTS OF SALVAGE FOR EQUIPMENT AND FIXTURES TO BE REMOVED. COORDINATE WITH THE OWNER THE EQUIPMENT AND FIXTURES TO BE SALVAGED AND THE LOCATION FOR STORAGE. AVOID DAMAGE TO EQUIPMENT, FIXTURES AND DEVICES DURING DEMOLITION WORK AND DURING TRANSPORT TO
OWNER’S DESIGNATED STORAGE LOCATION.
5. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES, FITTINGS, CONDUITS, ETC., IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF EXISTING CONDITIONS WITHIN
THE PROJECT AREA.
6. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE TO SUPPORT ALL EXISTING FIRE ALARM EQUIPMENT, SYSTEM WIRING AND CABLES THAT ARE TO REMAIN WHEN EXISTING CEILINGS ARE REMOVED AND REPLACED.
PROVIDE THE APPROPRIATE LISTED INDUSTRY RECOGNIZED SUPPORTS FOR ALL APPLICATIONS.
7. ALL WORK SHALL BE PERFORMED SO AS TO NOT INTERRUPT SERVICE TO THE ENTIRE AFFECTED BUILDING.
THE CONTRACTOR SHALL PROPERLY NOTIFY THE BUILDING OWNER AS APPLICABLE WITH A MINIMUM NOTICE
OF 48 HOURS IN ADVANCE BEFORE PROCEEDING WITH THIS WORK.
8. REMOVE ALL UNUSED AND DEMOLISHED EQUIPMENT AND ASSOCIATED MATERIAL FROM THE SITE.
ABANDONING UNUSED PORTIONS WILL NOT BE ACCEPTABLE.
9. AVOID DAMAGING EXISTING SURFACES AND EQUIPMENT AND ASSOCIATED MATERIALS FROM THE SITE.
REPAIR ANY DAMAGE CAUSED DURING WORK AT NO EXTRA COST TO THE OWNER.
10. REPAIR FIRE AND SMOKE RATED PARTITIONS SURROUNDING FIRE ALARM WORK AS SPECIFIED. REFER TO
ARCHITECTURE PLANS FOR LOCATIONS OF SMOKE AND FIRE PARTITIONS.
11. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR ALL CONDUIT PENETRATIONS THROUGH CHASES, WALLS, FLOORS OR CEILING WHICH ARE FIRE-RATED. THE FIRE ALARM CONTRACTOR SHALL UNDER THE DIRECTION OF THE ARCHITECT, PROPERLY SEAL ALL PENETRATIONS TO MAINTAIN FIRE PROTECTION RATING.
ALL PIPING PENETRATIONS MUST BE SEALED IN ACCORDANCE WITH “UL” LISTING SEALING METHOD AND/OR AS DETAILED IN THESE CONTRACT DOCUMENTS AND SPECIFICATIONS. REPAIR SURFACES TO MATCH ADJACENT AREAS. REFER TO ARCHITECTURE PLANS FOR LOCATIONS OF SMOKE AND FIRE PARTITIONS.
12. ALL CUTTING AND PATCHING, RELOCATING OF ANY EQUIPMENT, LIGHT FIXTURES, CONDUITS, PIPING, ETC., NECESSARY TO PERFORM THE WORK WILL BE THE CONTRACTOR’S RESPONSIBILITY UNLESS NOTED
OTHERWISE. ALL AFFECTED SURFACES WILL BE RESTORED TO THEIR ORIGINAL CONDITION.
13. REMOVE ANY CEILING TILES, GRID, AND LIGHT FIXTURES REQUIRED TO ACCOMPLISH THE WORK. REPLACE SAME AFTER THE INSTALLATION IS COMPLETE. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REPLACE ANY
ITEMS DAMAGED DURING CONSTRUCTION.
14. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING ELECTRICAL & FIRE ALARM LINES, PLUMBING LINES, DUCTWORK OR MECHANICAL PIPING LOCATED IN THE CEILING SPACE, WALLS OR FLOOR PRIOR TO SAW CUTTING OR ANY CORE DRILLING. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REPAIR SUCH ITEMS
DAMAGED.
15. CONTRACTOR SHALL PATCH, PAINT AND MATCH FINISH WITH EXISTING SURFACES TO REMAIN WHERE FIRE
ALARM DEVICES ARE BEING REMOVED.
16. THE BUILDING WILL BE IN OPERATION DURING THE DEMOLITION AND CONSTRUCTION. CONTRACTOR SHALL REFER TO PHASING PLAN AND NOTIFY OWNER A MINIMUM OF 48 HOURS PRIOR TO DISCONNECTION OF
EXISTING FIRE ALARM SIGNALING AND MONITORING SYSTEM.
17. BEFORE DEMOLITION OF ANY FIRE ALARM CONDUIT, WIRING OR CIRCUIT THE FIRE ALARM CONTRACTOR SHALL VERIFY ALL CIRCUITS BEING SERVED OUTSIDE THE CONSTRUCTION AREA ARE OPERATIONAL. VERIFY WITH OWNER BEFORE DISRUPTING THE EXISTING FIRE ALARM SERVICES WHICH MAY HAVE AN AFFECT ON FIRE ALARM DEVICES OUTSIDE THE CONSTRUCTION AREA. ANY EXISTING FIRE ALARM DEVICES DISRUPTED BY THE DEMOLITION ARE TO BE RESTORED TO OPERATION IMMEDIATELY OR WITH THE TIME AGREED UPON
WITH THE OWNER.
18. VERIFY THAT EXISTING EQUIPMENT, I.E., TAMPER SWITCHES, WATER FLOW SWITCHES, ETC., TO REMAIN IS OPERATING PROPERLY. NOTIFY THE ARCHITECT, ENGINEER AND OWNER OF ANY DAMAGED AND/OR
MALFUNCTIONING COMPONENTS.
19. COORDINATE FIRE ALARM SYSTEM MODIFICATIONS TO MINIMIZE SYSTEM IMPAIRMENT. PROVIDE FIRE WATCH AND INTERIM FIRE PROTECTION MEASURES WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION OR
THE OWNER.
20. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE AND LEGALLY DISPOSE OF DEMOLISHED
MATERIALS.
21. THE OWNER RESERVES THE RIGHT TO INSPECT THE MATERIAL SCHEDULED FOR REMOVAL AND SALVAGE
ANY ITEMS DEEMED USEABLE AS SPARE PARTS.
22. REFER TO DEMOLITION DRAWINGS FOR FURTHER DEMOLITION INFORMATION. CONTRACTOR SHALL REMOVE ASSOCIATED FIRE ALARM DEVICES, EQUIPMENT OR ACCESSORIES OF EXISTING SYSTEM TO BE REMOVED.
23. WHERE INDICATED ON PLANS, THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR REMOVING ALL
PORTIONS OF ABANDONED FIRE ALARM CABLE AND CONDUIT IN ACCORDANCE WITH NFPA 70.
FIRE EXTINGUISHER SCHEDULE
FE1
FIRE EXTINGUISHER, 20 LB (4A:80B:C) DRY CHEMICAL FOR
OFFICE AREAS AND HEALTH CARE FINISHED SPACES
FE2
FIRE EXTINGUISHER, CLEAN-AGENT 14 LB (2-A:10-B:C)
FOR TELECOMMUNICATION FINISHED SPACES
SCOPE OF WORK
NOT IN CONTRACT
AREA OF WORK
DD FIRE ALARM DUCT MOUNTED SMOKE DETECTOR.
FIRE ALARM SYMBOLS
ROR
HEAT DETECTOR - RATE OF RISE
FIRE EXTINGUISHER, DRY CHEMICAL FOR ALL TYPES OF FIRES
ALARM, FIRE, MANUAL PULL STATION.
SMOKE DETECTOR, PHOTOELECTRIC TYPE ONLY
WALL MOUNTED STROBE
CEILING OR WALL MOUNTED HORN-STROBE
CEILING OR WALL MOUNTED REMOTE INDICATOR
F
HORN-STROBE DEVICES WIRING REQUIREMENT
FOR THIS PROJECT
ALL NEW HORN-STROBES SHALL BE FITTED TO ALLOW REMOVAL OF THE
HORN-STROBES IN THE FUTURE TO ALLOW INSTALLATION OF A NOTIFIER
"SPEAKER-STROBE FIRE ALARM SYSTEM." THE REMOVAL OF NOTIFICATION
DEVICES INSTALLED AS PART OF THIS PROJECT AND TIE-IN TO A NOTIFIER FIRE
ALARM SYSTEM SHALL BE PART OF A FUTURE PROJECT. THIS CONTRACTOR
SHALL CONFIRM AND VALIDATE THAT THE NOTIFICATION DEVICES INSTALLED
CAN BE REMOVED AND SEAMLESSLY REPLACED WITH A "SPEAKER-STROBE"
DEVICE. CONTRACTOR SHALL VALIDATE THAT THE CORRECT NUMBER OF
WIRES ARE PULLED TO EACH NOTIFICATION DEVICES FOR FUTURE CHANGE.
WORK AREAS OUTSIDE OF A RATED
CONSTRUCTION BARRIER
CONTRACTOR SHALL BE REQUIRED TO PROVIDE/INSTALL THE
REPLACEMENT OF CEILING TILES AT THE END OF EACH SHIFT
FOR WORK AREAS OUTSIDE A RATED CONSTRUCTION BARRIER.
IF THE TILES CAN NOT BE REPLACED THE SPRINKLER SYSTEM
MAY BE CONSIDERED OUT OF SERVICE IN THESE AREAS AND A
1-HOUR FIRE RATED SEPARATION WILL BE REQUIRED BETWEEN
THE CONSTRUCTION AREA AND THE OCCUPIED PORTION OF
THE BUILDING.
REFERENCE NFPA 1, PARAGRAPH 13.3.3.3
MISCELLLANEOUS
RL = EXISTING DEVICES TO BE RELOCATED
RDL = RELOCATED DEVICES, SHOWN IN FINAL LOCATION
RM = EXISTING DEVICES TO REMAIN
RV = EXISTING DEVICES TO BE REMOVED
RP = EXISTING DEVICES TO BE REPLACED WITH A NEW DEVICE
N = NEW DEVICE
RHA = RATE OF RISE / FIXED TEMPERATURE HEAT DETECTOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
FA001
FIRE ALARM - SYMBOLS, NOTES
AND DRAWING INDEX
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT JRC
FIRE ALARM - DRAWING INDEX
Sheet Number Sheet Name
FA001 FIRE ALARM - SYMBOLS, NOTES AND DRAWING INDEX
FA002 FIRE ALARM - DETAILS
FA003 FIRE ALARM - INPUT/OUTPUT MATRIX
FA004 FIRE ALARM - INTERIM FIRE & MISCELLANEOUS REQUIREMENTS
FA100 FIRE ALARM - LEVEL 03 - DEMOLITION
FA101 FIRE ALARM - LEVEL 03 - NEW WORK
Rev. No. Revisions: Date:
NTS
TO
NEXT
DEVICE
FROM
FCP
OR
PREVIOUS
DEVICE
DATA
OUT(+)
DATA
OUT(-)
DAT
A
IN(+)
DAT
A
IN(-)
34 2 1
ALARM/
ACTIVE
NORMAL
RED
LED
GRN
LED
SIGA-CT1
TB2
TB1
TYP.N.O.
INITIATING
DEVICE
EOL
47K
OHM
NTS
TO
NEXT
DEVICE
FROM
FCP
OR
PREVIOUS
DEVICE
DATA
OUT(-)
DATA
OUT(+)
DAT
A
IN(-)
DAT
A
IN(+)
NTS
MOUNTING
BASE
ASSY.
ADAPTER
STRAP
(PART OF BASE ASSY.)
4"X 4"X 2-1/8"
JUNCTION
BOX
ALARM
HORN
JUNCTION
BOX
MOUNTING
PLATE
XENON
STROBE
ALARM LAMP
SINGLE INPUT MODULE 3
INTELLIGENT PHOTOELECTRIC SMOKE
DETECTOR 2TYPICAL SMOKE DETECTOR MOUNTING DETAIL 4
FIRE ALARM HORN/STROBE LIGHT 5NTS
HVAC EQUIPMENT
TERMINAL UNITS, CONTROL
PANELS, CONTROL VALVES,
FIRE/SMOKE DAMPERS, SMOKE
DAMPERS ETC.
DUCT MOUNTED SMOKE
DETECTOR PROVIDED BY
FIRE ALARM CONTRACTOR,
TESTED BY FIRE ALARM
CONTRACTOR, INSTALLED
BY MECHANICAL
CONTRACTOR.
SMOKE DAMPER OR
COMBINATION FIRE
SMOKE DAMPER
REMOTE INDICATOR
LIGHT AND KEYED
SWITCH, PLACE IS
VISIBLE LOCATION,
COORDINATE WITH
ELECTRICAL PLANS.
NOTES:
PROVIDE DUCT DETECTOR AT ALL
LOCATIONS A COMBINATION FIRE SMOKE
DAMPER OR SMOKE DAMPER IS INSTALLED.
EQUIPMENT BRANCH PANEL
DD
DUCT DETECTOR AND POWER DETAIL 6NTS
MAX 5 FT
NTS
6" MIN
80" MIN &
96" MAX
FINISHED FLOOR
CEILING
MANUAL FIRE
ALARM
STATION
5'-0" MAX
TYPICAL EXIT DOORWAY
48" MAX
42" MAX
4" MIN
12" MAX
20" MAX
WALL MOUNTED
HEAT
DETECTOR
WALL MOUNTED
SMOKE DETECTOR
1MOUNTING HEIGHTS OF DEVICES
GENERAL DETAIL NOTES:
A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF
DEVICES. WHEREVER DEVICES, ON THIS SHEET OR OTHER SHEETS,
ARE SHOWN AT GIVEN LOCATION WITH DIFFERENT MOUNTING HEIGHTS
THEY SHALL BE ALIGNED VERTICALLY (TO THE CENTER LINE). IF THEY
ARE SHOWN AT THE SAME MOUNTING HEIGHT THEY SHALL BE ALIGNED
HORIZONTALLY (TO THE TOP OF COVER PLATE). REFER TO THE
ARCHITECTURAL PLANS, ELEVATIONS AND DETAILS. COORDINATE
WITH ARCHITECT PRIOR TO ROUGH-IN.
B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS
INDICATED OTHERWISE.
C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN,
COORDINATE WITH ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS.
IF A CONFLICT OCCURS, REQUEST CLARIFICATION FROM ARCHITECT/
ENGINEER PRIOR TO ROUGH-IN.
STANDARD C-CLAMP PIPE HANGER 8
NTS
DESIGN DATA FOR C-CLAMP HANGER
A
C R
1-1/8" or Bar Joist
6. Steel Beam
Ring
5. Adjustable Hanger
4. Hanger Rod
3. Lock Nut
2. Set Screw
1. C-Clamp
Components:
1/2-69 1/48
1/2-4 1/27 3/46
1/2-3 3/46 3/45
3/8-364
3/8-2 1/25 1/23
3/8-2 1/452 1/2
3/8-1 3/44 1/42
3/8-1 1/241 1/2
3/8-1 1/23 3/41 1/4
3/8-1 1/43 1/21
3/8-1 1/43 1/23/4
3/8-1 1/43 1/21/2
Diameter
Rod
Takeout
Hanger
A Dimension
Minimum
Size
Pipe
Nominal inchesinchesinches
A
A
Section A-A
1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR
PARTITION TYPE & RATING ENCOUNTERED.
2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE &
MATERIAL OF THROUGH PENETRATION UTILIZED.
3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL
ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR
CAVITY ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM
UTILIZED.
ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED
FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION
PENETRATED AND THE THROUGH PENETRATION MATERIAL.
DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT
THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED
TO THE AUTHORITY HAVING JURISDICTION AND TO THE BUILDING OWNER AT THE
PROJECT COMPLETION.
PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER AND UL
LISTED ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM
IS INSTALLED.
THROUGH PENETRATION FIRESTOP SYS.
(PROVIDE UL LISTED SYSTEM)
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
FA002
FIRE ALARM - DETAILS EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT JRC
FSDDD
FIRE ALARM RISER DIAGRAM AND INPUT/OUTPUT MATRIX 1
ADDRESSABLE
TSFS
CONDUCTORS PER MANUFACTURER'S
PUBLISHED RECOMMENDATIONS
IN 3/4"C MINIMUM (TYPICAL)
FATC
NOTES:
1. DEVICES SHOWN ARE TYPICAL. REFER TO FIRE ALARM SHEETS FOR DEVICE
LOCATIONS AND QUANTITIES.
2. PROVIDE END OF LINE RESISTORS AS REQUIRED.
3. ANNUNCIATION SHALL BE THREE TEMPORAL BEEPS.
4. DUCT SMOKE DETECTORS AND DAMPERS SHALL BE PROVIDED AND WIRED TO
FATC AND POWER BY ELECTRICAL CONTRACTOR. MECHANICAL CONTRACTOR
SHALL INSTALL DUCT SMOKE DETECTORS AND DAMPERS.
5. FOR LARGER DUCTS, PROVIDE ADDITIONAL DUCT DETECTORS AS REQUIRED BY NFPA 72.
6. EQUIPMENT MUST BE COMPATIBLE WITH THE FIRE ALARM CONTROL PANEL SOFTWARE.
NTS
FIRE ALARM SEQUENCE OF OPERATION
THE FIRE ALARM NOTIFICATION SYSTEM SHALL GO INTO ALARM UPON ACTIVATION OF A MANUAL PULL, AREA SMOKE DETECTOR, DUCT SMOKE DETECTOR, OR FLOW SWITCH. THE ALARM SHALL BE DISPLAYED BY AUDIBLE AND VISUAL NOTIFICATION APPLIANCES. THE AIR HANDLING UNITS WILL SHUTDOWN THROUGH INTERFACE BETWEEN THE FIRE ALARM SYSTEM AND THE AIR HANDLER CONTROL PANEL. THE FIRE ALARM SYSTEM SHALL DISPLAY A TROUBLE CONDITION UNDER LOSS OF POWER, OR IF A SMOKE DETECTOR IS REMOVED FROM THE BASE. THE FIRE ALARM SYSTEM SHALL DISPLAY A SUPERVISORY CONDITION UPON ACTIVATION OF A TAMPER SWITCH OR DUCT SMOKE DETECTOR.
NEW
7. EXTEND EXISTING ADDRESSABLE FIRE ALARM SYSTEM INTO RENOVATED AREA,
PROVIDE LATEST DESIGN AND MODEL DEVICES COMPATIBLE WITH
MANUFACTURER, MAKE AND MODEL OF EXISTING FIRE ALARM SYSTEM.
PROVIDED ALL REQUIRED CONDUIT, CONDUCTORS, TERMINATORS, SOFTWARE,
RE-PROGRAMMING, TESTING, ADDITIONAL POWER SUPPLIES, EXTENDERS,
MODULES, ETC., AS REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.
EXISTING DACT COMMUNICATOR TO REMAIN CONNECTED TO UL APPROVED
MONITORING SERVICE.
P
C C
P
EXISTING
DUCT SMOKE DETECTOR *
AREA SMOKE DETECTOR *
DOOR RELEASE SMOKE DETECTOR *
INPUTS
OUTPUTS
.S
O U
N D
G E
N E
R A
L B
U
IL
D
IN
G A
L A
R M
F O
R
T
H E
R A
N D
N O
N -H
IG
H
R
IS
E
N O
N -H
E A
L
H
A
R E
S
E E
S E
C T
IO
N
.2
.1
N
O T
IF
Y
N E
C E
S S
A R
Y S
T A
F F
F
E
S P
O N
S E
F O
R H
E A
L T
H C
A R
E
A M
B U
L A
T O
R Y
H E
A L T
H C
A R
E
A N
D H
IG
H
R
IS
E B
U
IL
D
IN
G S
O N
L Y
A
L A
M
S
IG
N
A L M
A Y
B E
D
IF
F E
R E
N T
O N
D
IF
F E
R E
F
L O
O R
S
N
O T
IF
Y
F
IR
E D
E P
A R
T M
E N
IN
IT
IA
T E
S U
P E
R V
IS
O
R Y
S
IG
N A
L T
O A
H O
U R
M A
N N
E D
P O
IN
T
F O
R I M
M E
D
IA
S
P O
N S
E
C
L O
S E
A S
S O
C
IA
T E
D S
M O
K E
B A
R R
IE
D
O
R S
O N
T H
E F
L O
O R
C
L O
S E
D A
M P
E R
S O
N F
A N
P R
O X
IM
A
D
E T
E C
T O
R
S
H U
T D
O W
N A
IR
H
A N
D L E
R S
E R
V E
D B
Y
H
E D
E T
E C
T O
R
R
E C
A L L E
L E
V A
T O
R
IN
IT
IA
T E
E L E
V A
T O
R S
H U
T D
O W
N A
IS
C
O N
N E
C T
E L E
V A
T O
R P
O W
E R
ELEVATOR SMOKE DETECTOR *
MANUAL PULL STATION
ELEVATOR MACHINE ROOM HEAT DETECTOR
GENERATOR ROOM HEAT DETECTOR
SPRINKLER WATERFLOW / PRESSURE SWITCH
WATER CONTROL VALVE TAMPER
FIRE PUMP (ANY ALARM CONDITION REQUIRED
BY NFPA 20
HIGH / LOW PRESSURE DRY - PIPE SPRINKLER
SYSTEM
O
P E
N
*L O
C K
E D
E G
R E
S S
D O
O R
S
L O
O R
O F
F
IR
E O
R
IG
IN
D
IS
C
O N
N E
C T
F U
E L S
O U
R C
E F
R
M
O K
IN
G
E Q
U
IP
M E
N T
KITCHEN HOOD SUPPRESSION SYSTEM
GAS EXTINGUISHING SYSTEM
DRY-PIPE VALVE ROOM TEMPERATURE ALARM
DEDICATED FIRE WATER STORAGE TANK LOW
LEVEL
DEDICATED FIRE WATER STORAGE TANK LOW
TEMPERATURE
* WHILE NFPA 101 DOES NOT REQUIRE SOME DETECTORS TO NOTIFY BUILDING OCCUPANTS, VA REQUIRES ALL SMOKE DETECTORS, OTHER THAN DUCT SMOKE DETECTORS, TO NOTIFY BUILDING OCCUPANTS. ONLY INSTALL SMOKE DETECTORS WHEN REQUIRED BY NFPA 101 OR ITS REFERENCES.
** THOSE DOORS THAT ARE REQUIRED TO BE TIED TO THE FIRE ALARM SYSTEM SUCH AS DELAYED EGRESS ELECTRICAL LOCKING SYSTEMS AND SENSOR
RELEASE ELECTRICAL LOCKING SYSTEMS.
*** THIS APPLIES TO AMBULATORY HEALTH CARE OCCUPANCIES THAT REQUIRE SMOKE BARRIERS PER NFPA 101 OR ARE DESIGNED WITH MULTIPLE SMOKE
ZONES.
A – DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
B – THE FACILITY IS PERMITTED TO SOUND THE GENERAL ALARM/NOTIFY NECESSARY STAFF OR INITIATE A SUPERVISORY SIGNAL TO BE CONSISTENT WITH THE
OPERATION OF EXISTING SYSTEMS/FIRE PLAN.
X(B) X(B) X(B) X(B) X(A)X
X X X X
X X X X X X
X X X X
X X X X X
X X X X
X X X X
X X X X X
X
X
X
X X X X X X
X X X X X
X
X
X
NO PROGRAMMING CHANGES REQUIRED FOR THIS SCOPE OF WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
FA003
FIRE ALARM - INPUT/OUTPUT
MATRIX
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
A. FIRE ALARM REQUIREMENTS:
1. THE CONTRACTOR SHALL COORDINATE WITH THE VA FIRE OFFICIAL AS TO THE CLOSEST
READILY ACCESSIBLE PUBLIC FIRE ALARM BOX NEAR THE CONSTRUCTION PREMISE TO REPORT
A FIRE INCIDENT OR OCCURRENCE.
a. INSTRUCTIONS SHALL BE CREATED AND ISSUED FOR ALL CONTRACTOR AND SUB-TIER
CONTRACTORS FOR PROCEDURES FOR IMMEDIATE NOTIFICATION TO THE VA FIRE SAFETY
REPRESENTATIVE AND/OR LOCAL FIRE DEPARTMENT IN THE CASE OF A FIRE. WHERE
TELEPHONE SERVICE IS EMPLOYED, E.G., CELLULAR OF LAND LINE SERVICE TO THE
RESPONDING FIRE DEPARTMENT OR EQUIVALENT FACILITIES.
2. THE FIRE ALARM CONTRACTOR SHALL PROVIDE, FURNISH AND INSTALL, NEW FIXED
TEMPERATURE HEAT DETECTORS IN THE WORK AREA DURING CONSTRUCTION AND THE HEAT
DETECTORS ARE PROVIDED AS AN INTERIM EQUIVALENT SAFETY MEASURE TO BE PROVIDED
DURING A FIRE ALARM OR FIRE SUPPRESSION SYSTEM IMPAIRMENT OF RENOVATION TO THE
EXISTING SPACE IN BUILDING 3, EHRM ADMIN & TRAINING CENTER.
3. THE HEAT DETECTORS SPACING WITHIN THE CONSTRUCTION AREAS SHALL FOLLOW NFPA 72
AND NFPA 241 REQUIREMENTS. THE HEAT DETECTORS SHALL BE CONFIGURED/INTERFACED
WITH THE NEW LOCAL FIRE ALARM PANEL AND THE SITE'S EXISTING MAIN FIRE ALARM AND
DETECTION SYSTEM FOR MONITORING DURING A SYSTEM IMPAIRMENT AND DURING THE
RENOVATION TO THE EXISTING SPACE IN BUILDING 3, EHRM ADMIN & TRAINING CENTER.
4. THE INTERIM FIRE DETECTION SYSTEM FOR BUILDING 3, EHRM ADMIN & TRAINING SHALL BE
FULLY OPERATIONAL PRIOR TO ANY SIGNIFICANT COMBUSTIBLE MATERIALS ARE PRESENT
WITHIN THE PERIMETER OF THE BUILDING.
5. THE INTERIM FIRE DETECTION SYSTEM FOR RENOVATED AREAS AND NEW CONSTRUCTION
BUILDING SHALL INCLUDE THE HEAT DETECTORS INCLUDING ALL WIRING, PROGRAMMING, ETC., TO/FROM THE INDIVIDUAL DEVICES TO THE LOCAL FIRE ALARM PANEL AND INTERFACE WITH
THE MAIN FIRE ALARM CONTROL PANEL FOR 24/7 MONITORING IS A PROJECT REQUIREMENT.
THE INTERIM FIRE ALARM DEVICES SHALL BE REMOVED OR LEFT IN PLACE DEPENDENT ON THE
COR'S REQUIREMENT.
6. ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE COR'S
REPRESENTATIVE AND SHALL REQUIRE A MINIMUM OF 15 DAYS ADVANCED NOTICE, THIS TIME
LENGTH MAY BE LONGER OF SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE COR'S
DISCRETION. DRAINING AND REFILLING OF THE EXISTING SYSTEM IS A RESPONSIBILITY OF THE
COR'S REPRESENTATIVE.
7. ALL DISRUPTIONS IN THE FIRE SUPPRESSION SYSTEM SHALL BE COMPENSATED WITH AN
APPROVED FIRE WATCH AND STANDBY PERSONAL.
INTERIM FIRE ALARM, FIRE EXTINGUISHERS AND FIRE SUPPRESSION REQUIREMENTS
B. FIRE EXTINGUISHERS REQUIREMENTS:
1. THE RENOVATION OF THE EXISTING SPACE WITHIN BUILDING 3, EHRM, ADMIN & TRAINING SHALL
REQUIRE THE PLACEMENT OF FIRE EXTINGUISHERS AS FOLLOWS:
a. PROVIDE AT EACH LOCATION A PORTABLE FIRE EXTINGUISHER SHALL BE PROVIDED WHERE
HAZARDS EXIST, SUCH AS THE STORAGE AND USED OF FLAMMABLE AND COMBUSTIBLE
LIQUIDS OR COMBUSTIBLE MATERIAL ARE PRESENT WITHIN THE PERIMETER OF THE
BUILDING CONSTRUCTION.
b. FIRE EXTINGUISHERS SHALL BE LOCATED SO THAT THE TRAVEL DISTANCE TO A FIRE
EXTINGUISHER DOES NOT EXCEED FIFTY FEET.
c. FIRE EXTINGUISHERS TO BE PROVIDED DURING CONSTRUCTION SHALL BE EQUAL TO AN ABC 10 LB., FIRE EXTINGUISHER DRY CHEMICAL (4A:80B:C) FOR BUSINESS OCCUPANCIES TO
INCLUDE THE ENTIRE BUILDING FLOOR AREA.
C. HYDRANTS:
1. FREE ACCESS FROM THE CONSTRUCTION SITE TO THE CLOSEST FIRE HYDRANT OR OTHER
FIRE EXTINGUISHING EQUIPMENT SHALL BE PROVIDED AND MAINTAINED BY THE VA FIRE
SAFETY REPRESENTATIVE OR EQUIVALENT.
D. TEMPORARY HEATING:
1. TEMPORARY HEATING SHALL BE PROVIDED MEETING THE REQUIREMENTS OF NFPA 241,
SECTION 5.2.
2. TEMPORARY HEATING SHALL BE OPERATIONAL PRIOR TO ACTIVATION OF THE WET/DRY-PIPE
SPRINKLER SYSTEM AND THE INDOOR TEMPERATURE SHALL BE NO LOWER THAN 40 DEGREE F,
TO AVOID FIRE SUPPRESSION PIPING FREEZING.
E. FLAMMABLE AND COMBUSTIBLE LIQUIDS:
1. STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL BE IN ACCORDANCE WITH NFPA 30
AND NFPA 241, SECTION 5.5
F. FIRE SUPPRESSION REQUIREMENTS DURING CONSTRUCTION:
1. FIRE WATER SUPPLY:
a. THE WATER SUPPLY FOR FIRE PROTECTION SHALL BE MADE AVAILABLE PRIOR TO ANY
SIGNIFICANT COMBUSTIBLE MATERIAL SHALL BE MADE WITHIN THE PERIMETER OF THE
AREA OF RENOVATION TO THE EHRM ADMIN & TRAINING CENTER.
b. THERE SHALL BE NO DELAY IN THE INSTALLATION OF THE FIRE SUPPRESSION EQUIPMENT.
2. OPERATION OF VALVES: OPERATION OF SPRINKLER CONTROL VALVES SHALL BE PERMITTED
ONLY BY AUTHORIZED PERSONNEL AND SHALL BE ACCOMPANIED BY NOTIFICATION OF DULY
DESIGNATED PARTIES. WHEN THE SPRINKLER SYSTEM IS BEING REGULARLY TURNED OFF TO
FACILITATE CONNECTION OF NEWLY COMPLETED SEGMENTS, THE SPRINKLER CONTROL VALVE
SHALL BE CHECKED AT THE END OF EACH WORK DAY TO ASCERTAIN THAT THE PROTECTION IS
IN SERVICE.
FIRE WATCH PROCEDURES AND REQUIREMENTS
A. THE FIRE WATCH PERSONNEL SHALL BE TRAINED TO UNDERSTAND THE INHERENT HAZARDS OF THE
WORK SITE AND OF THE HOT WORK TO OCCUR.
B. THE FIRE WATCH SHALL ENSURE THAT SAFE CONDITIONS ARE MAINTAINED DURING OUTAGE OF THE
FIRE ALARM/FIRE SUPPRESSION SYSTEM AND/OR DURING THE OCCURRENCE OF HOT WORK
OPERATION.
C. THE FIRE WATCH SHALL HAVE THE AUTHORITY TO STOP HOT WORK OPERATIONS IF UNSAFE
OPERATIVE DEVELOPS.
D. THE FIRE WATCH SHALL HAVE FIRE EXTINGUISHING EQUIPMENT READILY AVAILABLE AND TRAINED IN
ITS USE, E.G., FIRE EXTINGUISHERS.
E. THE FIRE WATCH SHALL BE FAMILIAR WITH OWNER'S FACILITIES AND PROCEDURES FOR SOUNDING
AN ALARM IN THE EVENT OF A FIRE.
F. THE FIRE WATCH SHALL WATCH FOR FIRES IN ALL EXPOSED AREAS AND TRY TO EXTINGUISH A FIRE ONLY WHEN THE FIRES ARE OBVIOUSLY WITHIN THE CAPACITY OF THE AVAILABLE EXTINGUISHING EQUIPMENT. IF THE FIRE WATCH DETERMINES THAT THE FIRE IS NOT WITHIN THE CAPACITY OF THE EQUIPMENT THE FIRE WATCH SHALL SOUND AN ALARM IMMEDIATELY (E.G.,INITIATE A MANUALLY ACTUATED ALARM INDICATING DEVICE THAT IS OUTSIDE OF THE CONSTRUCTION AREA DURING THE DISRUPTION OF THE FIRE ALARM/DETECTION WITHIN THE CONSTRUCTION WORK SCOPE OR WITHIN THE CONSTRUCTION WORK SCOPE IF THE FIRE ALARM/DETECTION SYSTEM HAS BEEN ACTIVATED).
G. BEFORE STARTING ANY HOT WORK, CONTRACTORS AND THEIR OWNERS SHALL DISCUSS THE
PLANNED PROJECT COMPLETELY INCLUDING THE TYPE OF HOT WORK TO BE CONDUCTED AND THE HAZARDS IN THE AREA WITH THE ASSOCIATED PLAN OF ACTION, IN ORDER, TO PROVIDE EQUIVALENT
SAFETY MEASURES TAKEN DURING THE FIRE DETECTION OR FIRE SUPPRESSION IMPAIRMENT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
FA004
FIRE ALARM - INTERIM FIRE &
MISCELLANEOUS REQUIREMENTS
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
C
NOT IN SCOPE
NOT IN SCOPE
RM
RL RM RV
RM
RV
RM
RM
RV
RM
NOT IN SCOPE
RV
RV
A2
A3
A4 A5
A6 A7 A8 A9 A10 A11
A12 A13 A14
A15
MISCELLLANEOUS
RL = EXISTING DEVICES TO BE RELOCATED
RDL = RELOCATED DEVICES, SHOWN IN FINAL LOCATION
RM = EXISTING DEVICES TO REMAIN
RV = EXISTING DEVICES TO BE REMOVED
RP = EXISTING DEVICES TO BE REPLACED WITH A NEW DEVICE
N = NEW DEVICE
A. REFER TO FA001 FOR FIRE ALARM GENERAL NOTES, FIRE ALARM DEMOLITION
NOTES, ABBREVIATIONS AND SYMBOLS.
B. REFER TO DRAWING FA-004 FOR TEMPORARY FIRE REQUIREMENTS.
C. BEFORE DEMOLITION OF ANY FIRE ALARM CONDUIT, WIRING OR CIRCUIT THE FIRE
ALARM CONTRACTOR SHALL VERIFY ALL CIRCUITS BEING SERVED OUTSIDE THE
CONSTRUCTION AREA ARE OPERATIONAL. VERIFY WITH COR BEFORE DISRUPTING
THE EXISTING FIRE ALARM SERVICES WHICH MAY HAVE AN AFFECT ON FIRE ALARM
DEVICES OUTSIDE THE CONSTRUCTION AREA. ANY EXISTING FIRE ALARM DEVICES
DISRUPTED BY THE DEMOLITION ARE TO BE RESTORED TO OPERATION IMMEDIATELY
OR WITH THE TIME AGREED UPON WITH THE COR.
D. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING ELECTRICAL AND FIRE ALARM
LINES, PLUMBING LINES DUCTWORK OR MECHANICAL PIPING LOCATED IN THE
CEILING SPACE, WALLS OR FLOOR PRIOR TO SAW CUTTING OR ANY CORE DRILLING.
IT IS THE CONTRACTOR’S RESPONSIBILITY TO REPAIR SUCH ITEMS DAMAGED.
E. EXISTING CONDITIONS WERE TAKEN FROM SITE VISITS, AND MAY NOT REFLECT "AS-
BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS.
COORDINATE NEW WORK AND DEMOLITION WITH OTHER DISCIPLINES AND EXISTING
CONDITIONS.
F. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR ALL CONDUIT PENETRATIONS
THOUGH CHASES, WALLS, FLOORS OR CEILINGS WHICH ARE FIRE-RATED. THE FIRE
ALARM CONTRACTOR SHALL UNDER THE DIRECTION OF THE ARCHITECT, PROPERLY
SEAL ALL PENETRATIONS TO MAINTAIN FIRE PROTECTION RATING. ALL PIPING /
CONDUIT PENETRATIONS MUST BE SEALED IN ACCORDANCE WITH THE "UL" LISTING
SEALING METHOD AND/OR AS DETAILED IN THE CONTRACT DOCUMENTS AND
SPECIFICATIONS. REPAIR SURFACES TO MATCH ADJACENT AREAS. REFER TO
ARCHITECTURE PLANS FOR LOCATION OF SMOKE AND FIRE PARTITIONS.
G. ALL CUTTING AND PATCHING, RELOCATING OF ANY EQUIPMENT, LIGHT FIXTURES,
CONDUITS, PIPING, ETC NECESSARY TO PERFORM THE WORK WILL BE THE
CONTRACTOR’S RESPONSIBILITY UNLESS NOTED OTHERWISE. ALL AFFECTED
SURFACES WILL BE RESTORED TO THEIR ORIGINAL CONDITION.
H. REMOVE ANY CEILING TILES, GRID, AND LIGHT FIXTURES REQUIRED TO ACCOMPLISH
THE WORK. REPLACE SAME AFTER THE INSTALLATION IS COMPLETE. IT IS THE
CONTRACTOR’S RESPONSIBILITY TO REPLACE ANY ITEMS DAMAGED DURING
CONSTRUCTION.
I. THE EXISTING BUILDING'S LOCAL FIRE ALARM CONTROL PANEL SHALL REMAIN IN
SERVICE AT ALL TIMES THROUGHOUT THE RENOVATION AREAS SHOWN ON THESE
CONTRACT DOCUMENTS; SPECIAL PROVISIONS SHALL BE MADE BETWEEN THE FIRE
ALARM CONTRACTOR AND THE ARCHITECT, THE ENGINEER AND THE COR'S
REPRESENTATIVE TO DISCONNECT POWER TO THE AREAS OF THE RENOVATION TO
MINIMIZE THE INTERRUPTIONS IN THE FIRE ALARM SERVICE.
J. A FIRE WATCH SHALL BE PROVIDED FOR AREAS WITH INTERRUPTIONS IN FIRE ALARM
SERVICE.
FIRE ALARM DEMOLITION GENERAL NOTES:
SCOPE OF WORK
NOT IN CONTRACT
AREA OF WORK
FIRE ALARM SYMBOLS
FIRE EXTINGUISHER, DRY CHEMICAL FOR ALL TYPES OF FIRES
F ALARM, FIRE, MANUAL PULL STATION.
SMOKE DETECTOR, PHOTOELECTRIC TYPE ONLY
WALL MOUNTED STROBE
CEILING OR WALL MOUNTED SPEAKER-STROBE
WORK AREAS OUTSIDE OF A RATED
CONSTRUCTION BARRIER
CONTRACTOR SHALL BE REQUIRED TO PROVIDE/INSTALL THE
REPLACEMENT OF CEILING TILES AT THE END OF EACH SHIFT
FOR WORK AREAS OUTSIDE A RATED CONSTRUCTION BARRIER.
IF THE TILES CAN NOT BE REPLACED THE SPRINKLER SYSTEM
MAY BE CONSIDERED OUT OF SERVICE IN THESE AREAS AND A
1-HOUR FIRE RATED SEPARATION WILL BE REQUIRED BETWEEN
THE CONSTRUCTION AREA AND THE OCCUPIED PORTION OF
THE BUILDING.
REFERENCE NFPA 1, PARAGRAPH 13.3.3.3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
100% BID DOCUMENTS
FOR CONSTRUCTION
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT
GMK Associates, Inc.
1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA
STAMPPROGRAM MANAGER
321 4 5 6 7 8 9 10
Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA
CONSULTANT
Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED
Approved:
U A
C a lla h a n \L o c a l R e v it \R
\4
C
E C e n tr a l M o d e l.
rv t
/9 /2
:3
:3
A
M
FA100
FIRE ALARM - LEVEL 03 -
DEMOLITION
EHRM - RENOVATE B3 FOR EHRM
ADMIN AND TRAINING
COLUMBIA, SC
544-22-703
B3
07/15/2025 GAT JRC
1/8" = 1'-0"
FIRE ALARM - LEVEL 03 - DEMOLITION
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
8 84 16 32
F F
DD
FIRE ALARM GENERAL NOTES - NEW WORK
A. REFER TO DRAWING FA001 FOR FIRE ALARM GENERAL NOTES, ABBREVIATIONS AND SYMBOLS.
B. REFER TO FA003 FOR FIRE ALARM INPUT / OUTPUT MATRIX. ALL FIRE ALARM DEVICES SHALL BE INTERFACED WITH THE EXISTING FIRE ALARM SYSTEM AND PROGRAMMING OF THE NEW POINTS AT THE
LOCAL AND MAIN FIRE ALARM CONTROL PANELS..
C. REFER TO DRAWING FA004 AND FX004 FOR IMPAIRMENT REQUIREMENTS AND PROCEDURES THAT SHALL BE MET BY THE CONTRACTOR PRIOR TO THE REMOVAL AND/OR DEACTIVATION OF ANY FIRE DETECTION
DEVICE.
D. ALL THROUGH WALL OR THROUGH FLOOR PENETRATIONS SHALL BE SLEEVED AND FIRE ALARM CONTRACTOR SHALL SEAL ALL FIRE RATED FLOOR AND WALL PENETRATIONS WITH A UL LISTED
MATERIAL AND METHODS.
E. ALL OUTLET LOCATIONS ARE APPROXIMATE POSITIONS. THE EXACT LOCATIONS SHALL BE DETERMINED BY PROVIDED BOX LOCATIONS AND FIELD CONDITIONS. ALL LOCATIONS SHALL BE FIELD VERIFIED.
F. THE INFORMATION GIVEN HEREIN IS AS EXACT AS COULD BE SECURED FOR BIDDING PURPOSES AND ITS ACCURACY IS NOT GUARANTEED. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR EXAMINING NEW JOB CONDITIONS AND VERIFYING ALL MEASUREMENTS, DISTANCES, ELEVATIONS, CLEARANCES, PIPE
SIZES, ETC., BEFORE STARTING THE DEMOLITION OR NEW WORK.
G. THE DRAWING SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE WHEN INDICATED
FOR GENERAL REFERENCE ONLY.
H. COORDINATE FIRE ALARM SYSTEM MODIFICATIONS TO MINIMIZE SYSTEM IMPAIRMENT. PROVIDE FIRE WATCH AND INTERIM FIRE PROTECTION MEASURES WHERE REQUIRED BY THE AUTHORITY HAVING
JURISDICTION OR THE COR.
I. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING EXISTING CONDITIONS PRIOR TO CONSTRUCTION. THE EXISTING FIRE ALARM EQUIPMENT ABOVE CEILING AND WITHIN WALLS
WILL NEED TO BE FIELD VERIFIED.
J. THE EXISTING BUILDING'S LOCAL FIRE ALARM CONTROL PANEL SHALL REMAIN IN SERVICE AT ALL TIMES
THROUGHOUT THE RENOVATION AREAS SHOWN ON THESE CONTRACT DOCUMENTS; SPECIAL
PROVISIONS SHALL BE MADE BETWEEN THE FIRE ALARM CONTRACTOR AND THE ARCHITECT, THE
ENGINEER AND THE COR'S REPRESENTATIVE TO DISCONNECT POWER TO THE AREAS OF THE
RENOVATION TO MINIMIZE THE INTERRUPTIONS IN THE FIRE ALARM SERVICE.
K. THE FIRE ALARM SYSTEM SHALL BE AN ADDRESSABLE SYSTEM INCLUDING INDIVIDUALLY ADDRESSED
DEVICES.
L. THE EXISTING BUILDING'S LOCAL FIRE ALARM CONTROL PANEL SHALL REMAIN IN SERVICE AT ALL TIMES THROUGHOUT THE NEW ADDITION AS SHOWN ON THESE CONTRACT DOCUMENTS; SPECIAL PROVISIONS SHALL BE MADE BETWEEN THE FIRE ALARM CONTRACTOR AND THE ENGINEER OF RECORD AND THE COR'S REPRESENTATIVE TO DISCONNECT POWER TO THE AREAS OF THE NEW WORK TO MINIMIZE THE
INTERRU…