About this file

This is a set of electrical construction drawings for a federal contract opportunity involving the renovation of Building 3 (B3) for the Electronic Health Records Management (EHRM) Administration and Training facility at the Columbia, South Carolina Veterans Affairs Medical Center (VAMC).

The project scope includes comprehensive electrical work across Level 03 of the facility, encompassing lighting, power distribution, and telecommunications systems. Key deliverables include new LED luminaires (types A421, IL1, S16, and E6 exit signs) with 0-10V dimming capabilities, installation of three new panelboards (3BLA-3 and 3BLA-4 at 208/120V and 100A capacity), and reconfiguration of existing electrical infrastructure. The work involves demolition of existing luminaires and receptacles, installation of approximately 40+ new duplex receptacles at various mounting heights (18", 42", 48", and 84" AFF), junction boxes, and emergency lighting controls integrated with automatic load control relays. Telecommunications infrastructure includes a new structured cabling system with CAT 6A U/UTP cabling terminated on RJ45 connectors, installation of wireless access points (WAP), a new telecommunications rack with patch panels and fiber enclosures in the OIT room (320A), and voice/data outlets throughout the occupied spaces. Power requirements include connections to HVAC equipment (AHU-09 with VFDs rated 460V, 3-phase), motorized dampers, and VAV controls. All work must comply with NEC Article 517 for critical and life-safety branch circuits, utilize 75-degree Celsius rated terminations, and include comprehensive fire stopping and bonding per ANSI/TIA-607-B standards. The contractor must coordinate with facility infection control protocols, develop an outage plan minimizing disruptions to operational areas, and provide temporary power at no additional cost to maintain building functionality during phased construction.

View the file

Other files

File Type Posted
S06-Amendment 0006-Att 1-SF30-Columbia.pdf PDF
S06 - Amendment 0006-Att 2-Tech Questions-Columbia.pdf PDF
S06 - Amendment 0005-Att 1-Tech Questions-Columbia.pdf PDF
S06-Amendment 0005-Att 2-SF30-Columbia.pdf PDF
S06-Amendment 0004-Att 1- BLDG 3 EHRM - DIV 23 Specs Combined.pdf PDF
S06-Amendment 0004-Att 3-HL100.pdf PDF
S06-Amendment 0004-Att 2 - Lim. AB LBP Report - Bld3 EHRM.pdf PDF
S06-Amendment 0004-Att 5- SF30-Columbia.pdf PDF
S06 -Amendment 0004-Att 4- Tech Questions-Columbia.pdf PDF
S06-36C77626R0032-Amendment 0003.pdf PDF
S06-36C77626R0032 Amendment 0002.pdf PDF
S04- Pre Bid Conference - Columbia.pptx PPTX presentation
S06-36C77626R0032 0001.pdf PDF
S06-Site Visit Sign-In Sheet 03062026-Columbia.pdf PDF
S06-RFP Attachment 17-Spce Update for 01321615-2025-12.pdf PDF
S02-RFP Attachment 15-Specifications-Columbia_Part5.pdf PDF
S02-RFP Attachment 8- Fire Sup Drawings-COL.pdf PDF
S02-RFP Attachment 5- ARCH Drawings-COL.pdf PDF
S02-RFP Attachment 4-Campus Map-Columbia.pdf PDF
S02-36C77626R0032-Columbia.pdf PDF
S02-RFP Attachment 12-Specifications-Columbia_Part2.pdf PDF
S02-RFP Attachment 10- Plumbing Drawings-COL.pdf PDF
S02-RFP Attachment 16-Final SOW-Col.pdf PDF
S02-RFP Attachment 14-Specifications-Columbia_Part4.pdf PDF
S02-RFP Attachment 7- Fire Alarm Drawings-COL.pdf PDF
S02-RFP Attachment 2 Site Visit Information-Columbia.pdf PDF
S02-RFP Attachment 13-Specifications-Columbia_Part3.pdf PDF
S02-RFP Attachment 11-Specifications-Columbia_Part1.pdf PDF
S02-RFP Attachment 9- Mechanical Drawings-COL.pdf PDF
S02 - RFP Attachment 3 - Limitations on Subcontracting - Columbia.docx DOCX document
S02-RFP Attachment 1-Wage Rates-Col.txt TXT text file
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PB

K

( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )ELECTRICAL SYMBOLS

DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.

ON CENTER.

ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.

TELEPHONE TERMINAL BOARD.

EMPTY CONDUIT.

ABBREVIATIONS

AFF

EC

OC

TTB

+60"

NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.NL

TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.

TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.

SECURITY SYSTEM CLOSED CIRCUIT T.V. CAMERA. SUBSCRIPT INDICATES PAN/TILT/ZOOM CONTROL.

SECURITY SYSTEM PUSHBUTTON STATION. SURFACE MOUNTED 42" AFF.

PUBLIC ADDRESS SYSTEM MICROPHONE OUTLET, WALL MOUNTED 18" AFF. COORDINATE TYPE OF

PUBLIC ADDRESS SYSTEM HORN, WALL MOUNTED 7'-6" AFF. UNLESS OTHERWISE INDICATED.

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

OUTLET WITH OWNER'S EQUIPMENT.

W = WALL MOUNTED STATION

INTERCOM OUTLET WALL MOUNTED 42" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION UNLESS

INTERCOM WALL MOUNTED 18" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION.

VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE. PROVIDE 3/4"C. FROM

MODIFIERS FOR INTERCOM:

S = SUB STATION

M = MASTER STATION

TELEPHONE OUTLET, WALL MOUNTED 48" AFF.

VOICE/DATA OUTLET, WALL MOUNTED 42" AFF

PROVIDE 3/4"C. FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.

TELEPHONE OUTLET WALL MOUNTED 42" AFF

PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR VOICE/DATA WIRING TO

PRE WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT

MODIFIERS FOR VOICE/DATA & TELEPHONE OUTLETS: (DEVICE AND CONDUCTORS BY TELECOM VENDOR) a = VOICE ONLY b = STANDARD (2 DATA / 1 VOICE SPLIT) c = 1 DATA ONLY d = 4 DATA / 1 VOICE SPLIT

COMMUNICATIONS

VOICE/DATA OUTLET, FLOOR POKETHRU.

GROUND BAR - 1/8"x1"x12" COPPER BUS IN NEMA 1 ENCLOSURE. LOCATE ABOVE SUSPENDED CEILING.

PUBLIC ADDRESS SYSTEM VOLUME CONTROL SWITCH, WALL MOUNTED 42" AFF.

CONDUIT SLEEVES. SEE PLANS FOR SIZE AND QUANTITY.

W

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.

LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,

DRAWINGS. SEE SCHEDULE FOR TYPE (*).

CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON

EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED

OTHERWISE. CONNECT UNSWITCHED.

LIGHTING

LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.

EQUIPMENT IDENTIFICATION

HORSEPOWER RATING

MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.

ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.

FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.

NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.

SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER

MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.

AMPACITY. SEE FEEDER SCHEDULE.

ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER

WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.

DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND OVERCURRENT BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC.

WIRING SYSTEM TURNED UP.

WIRING SYSTEM TURNED DOWN.

WIRING SYSTEM EXPOSED.

PROTECTION DEVICE NUMBER.

DRY TYPE TRANSFORMER.

NEC REQUIRED GROUND.

EF-1, 10 HP.460V, 3∅

208V, 3∅

120V, 1∅

MOTOR RATED SWITCH.

JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.

CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

PANELBOARD SURFACE MOUNTED.

N = NORMAL BRANCH

U = UNGROUNDED (ISOLATION) PANEL

Q = EQUIPMENT BRANCH

C = CRITICAL BRANCH

L = LIFE SAFETY BRANCH

M = MOTOR CONTROL CENTER

L = 120/208 VOLT

H = 277/480 VOLT

1,2,3 = FLOOR

A,B,C = LOCATION

PANELBOARD NAMING CONVENTION

JUNCTION OR PULL BOX. W = WEATHERPROOF.

CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.

POWER

TV = TELEVISION, SEE DETAIL.

G = GROUND FAULT CIRCUIT INTERRUPTER.

EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER

P = POKE-THR. SEE DETAIL 15 ON SHEET E003.

WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.

DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

DUPLEX RECEPTACLE FLOOR POKE-THRU.

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF OUTLET

OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES

OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY

DUPLEX RECEPTACLE, MOUNTED 48" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH

DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED.

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.

MODIFIERS FOR RECEPTACLES:

SPECIAL RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED. NEMA CONFIGURATION AS INDICATED.

LH2A-1

CH2A

EQUIPMENT CONNECTION DESIGNATION, SEE SCHEDULE FOR DETAILS.

M

RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE

LIGHTNING PROTECTION SYSTEM GROUND ROD.

75KVA

T

LIGHTNING PROTECTION SYSTEM AIR TERMINAL.

TR = TAMPER RESISTANT

MODIFIERS FOR SWITCHES:

3 = THREE WAY

D = DIMMER, 0-10 VOLT TO 1% UNLESS OTHERWISE NOTED

OS = OCCUPANCY SENSOR

a,b,c = MULTIPLE SWITCH LEGS

OD = OCCUPANCY SENSOR & DIMMER, 0-10 VOLT TO 1% UNLESS OTHERWISE NOTED

VD = VACANCY SENSOR & DIMMER, 0-10 VOLT TO 1% UNLESS OTHERWISE NOTED

SINGLE POLE SWITCH, MOUNTED 48" AFF TO CENTER OF DEVICE.

SWITCHES

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE, TO COMPLY WITH ENERGY CODE. EITHER SWITCH INBOARD AND OUTBOARD LAMPS SEPARATELY OR STEP-DIM BOTH

INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT

LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).

SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.

LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

SEE SCHEDULE FOR TYPE (*).*

REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.

HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.

LAMPS TO 50%.

NOTED OTHERWISE.

SUPPLIER/INSTALLER.

PTZ

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).

HEADWALL. SEE PLAN FOR NUMBER.HW#

POWER COLUMN. SEE PLAN FOR NUMBER.PC#

OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

POWER SYSTEM.

CONNECTED TO THE EMERGENCY POWER SYSTEM.

LED STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY

GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

WALL MOUNTED LOCAL ALARM BUZZER, 85dBA.

PUSH BUTTON DOOR RELEASE WITH SOUNDER COVER.

MAGNETIC LOCK FOR DOOR.

D

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.

PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

VARIABLE SPEED DRIVEVSD

EXPEDITOR SYSTEM

EXPEDITER BUTTON PANEL

EMERGENCY EGRESS PUSH BUTTON

KEY PAD CARD READER

EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.

PNEUMATIC TUBE STATIONPTS

BUTTON RELEASE.

BADGE ACCESS.

NURSE LOCATOR.

DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.

SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.

SYMBOL LOCATION LEADER

4/350

XXXX

ERS

GENERAL PROJECT NOTES

J

M

S

J

EXIT

KPCR

PP

ES

CR

ES

AL

PB

ML

BR

BA

SS

V

M

H

GB

P S

P S

C

SS

S

DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACHOS

SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

WIRELESS ACCESS POINTWAP

RL = EXISTING DEVICE TO BE RELOCATED.

DASHED SYMBOLS INDICATE EXISTING DEVICES.

RLD = RELOCATED DEVICE SHOWN IN FINAL LOCATION.

RM = EXISTING DEVICE TO REMAIN.

RM

RM

RV = EXISTING DEVICE TO BE REMOVED.

RP = EXISTING DEVICE TO BE REPLACED WITH NEW DEVICE.

EX = EXISTING DEVICE

ELECTRICAL ENERGY CODE SUMMARY

ELECTRICAL SUMMARY

ELECTRICAL SYSTEM AND EQUIPMENT

Method of Compliance:

Prescriptive Performance

Lighting schedule lamp type required in fixture - SEE LUMINAIRE SCHEDULE number of lamps in fixture - SEE LUMINAIRE SCHEDULE ballast type used in the fixture - SEE LUMINAIRE SCHEDULE number of ballasts in fixture - SEE LUMINAIRE SCHEDULE total wattage per fixture - SEE LUMINAIRE SCHEDULE total interior wattage specified vs. allowed - 2,889 vs 4,002 total exterior wattage specified vs. allowed - N/A

Additional Efficiency Package Options

C406.2 More Efficient HVAC Equipment Performance

C406.3 Reduced Lighting Power Density

C406.4 Enhanced Digital Lighting Controls

C406.5 On-Site Renewable Energy

C406.6 Dedicated Outdoor Air System

Energy Code:

ASHRAE 90.1: Prescriptive Performance

C406.7 Reduced Energy Use in Service Water Heating

(When using the 2018 NCECC; not required for ASHRAE 90.1)

TS AUTOMATIC TRANSFER SWITCH/ BYPASS DEVICE - FOR GENERATOR SUPPLIED LIGHTING. MOUNTED ABOVE ACCESSIBLE CEILING. INSTALL PER MANUFACTURE'S RECOMENDATIONS AND DIAGRAM ON DETAILS SHEET.

3-PHASE CIRCUITS (NO NEUTRAL) + GROUNDING

SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS

3 #12, 1#12 G, 3/4" C.

3 #10, 1#10 G, 3/4" C.

3#4, 1#10 G, 1" C.

3 #6, 1#10 G, 3/4" C.

3#1, 1#8 G, 1 1/2" C.

3#3, 1#8 G, 1 1/4" C.

3#1/0, 1#6 G, 1 1/2" C.

3#1/0, 1#6 G, 1 1/2" C.

3#2/0, 1#6 G, 1 1/2" C.

3#3/0, 1#6 G, 2" C.

3#4/0, 1#4 G, 2" C.

3-250 MCM, 1#4 G, 2" C.

3-350 MCM, 1#4 G, 2 1/2" C.

2 (3 #3/0, 1#3 G, 2" C) OR 3-500 MCM, 1#3 G, 3"C.

2 (3-250 MCM, 1#2 G, 2 1/2" C).

2 (3-350 MCM, 1#1 G, 2 1/2" C).

2 (3-500 MCM, 1#1/0 G, 3" C).

3 (3-400 MCM, 1#2/0 G, 3" C).

4 (3-350 MCM, 1#3/0 G, 2 1/2" C).

4 (3-600 MCM, 1#4/0 N, 3 1/2" C) OR 5 (3-400 MCM, 1#4/0 G, 3"C).

BRANCH CIRCUIT AND FEEDER SCHEDULE

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

4 #12, 1#12 G, 1/2" C.

4 #10, 1#10 G, 3/4" C.

4#6, 1#10 G, 1" C.

4#3, 1#8 G, 1 1/4" C.

4#4, 1#8 G, 1 1/4" C.

4 #8, 1#10 G, 1" C.

4#1, 1#6 G, 1 1/2" C.

4#1/0, 1#6 G, 2" C.

4#2/0, 1#4 G, 2" C.

4#3/0, 1#6 G, 2" C.

4#4/0, 1#4 G, 2 1/2" C.

4-250 MCM, 1#2 G, 2 1/2" C.

4-350 MCM, 1#2 G, 3" C.

2 (4 #3/0, 1#3 G, 2" C) OR 4-500 MCM, 1#3 G, 3 1/2"C.

2 (4-250 MCM, 1#2 G, 2 1/2" C).

2 (4-350 MCM, 1#1 G, 3" C).

2 (4-500 MCM, 1#1/0 G, 3 1/2" C).

3 (4-400 MCM, 1#2/0 G, 3 1/2" C).

4 (4-350 MCM, 1#3/0 G, 3 1/2" C).

4 (4-600 MCM, 1350 MCM N, 1#4/0 G, 3 1/2" C) OR 5 (3-400 MCM,

BRANCH CIRCUIT AND FEEDER SCHEDULE

3-PHASE CIRCUITS + NEUTRAL + GROUND

SYMBOL MINIMUM SIZE CONDUCTORS AND CONDUITS

NOTE: ALL CONDUCTORS ARE COPPER, THWN / THHN.

1-250 MCM N, 1#4/0 G, 3"C).

A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION

PURPOSES. THE SCALE, WHEN INDICATED, IS INTENDED FOR

REFERENCE PURPOSES ONLY.

B. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY, OR AT THE

OWNER'S REPRESENTATIVE’S DISCRETION.

C. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND FIXED

EQUIPMENT PROVIDED SHALL BE LISTED AND LABELED BY A

NATIONALLY RECOGNIZED AND STATE APPROVED THIRD PARTY

TESTING AGENCY. FACTORY LISTED COMPONENTS ASSEMBLED

TOGETHER SHALL BE REVIEWED AND LABELED AS AN ASSEMBLY BY

THE STATE APPROVED TESTING AGENCY.

D. ELECTRICAL WORK SHALL BE COMPLETED ACCORDING TO THE

PHASES SHOWN ON THE ARCHITECTURAL PLANS OR AS

ESTABLISHED IN THE "GENERAL CONDITIONS". THE ELECTRICAL

CONTRACTOR SHALL DEVELOP A PHASING PLAN THAT WILL WORK

WITH THE ARCHITECT’S PHASING PLAN, THE WORK TO BE

PERFORMED BY OTHER TRADES, AND WILL MAINTAIN THE OWNER’S

OPERATIONS.

E. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER

TO MAINTAIN THE OWNER’S OPERATIONS, AT NO EXTRA COST OR

TIME TO THE OWNER, AND KEEP THE BUILDING FUNCTIONAL

DURING EACH PHASE OF THE PROJECT.

F. ELECTRICAL CONTRACTOR SHALL PREPARE AN OUTAGE PLAN,

INCLUDING PROVISIONS FOR TEMPORARY POWER, AND SUBMIT IT

WITH THEIR BID. THE OUTAGE PLAN SHALL INCLUDE ALL OUTAGES

REQUIRED TO PERFORM THE WORK SHOWN IN THE CONTRACT

DOCUMENTS. NO EXTRA COST OR TIME TO THE OWNER SHALL BE

CONSIDERED FOR NOT INCLUDING REQUIRED OUTAGES. ALL

OUTAGES SHALL BE COORDINATED WITH, AND APPROVED BY, THE

OWNER’S REPRESENTATIVE AT LEAST TWO (2) WEEKS IN ADVANCE.

AT THE OWNER’S REPRESENTATIVE’S DISCRETION AND THE

SYSTEMS IMPACTED, THIS TIME MAY BE INCREASED OR

DECREASED FOR SOME SHUTDOWNS.

G. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE

FACILITY'S INFECTION CONTROL OFFICER TO VERIFY THAT

APPROPRIATE SAFEGUARDS ARE BEING TAKEN TO PROTECT

WORKERS INVOLVED IN CONSTRUCTION ACTIVITIES.

H. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE

FACILITY'S INFECTION CONTROL OFFICER TO VERIFY THAT

APPROPRIATE PRECAUTIONS ARE BEING TAKEN TO PROTECT

FACILITY STAFF AND PATIENTS DURING THE CONSTRUCTION

ACTIVITIES.

I. CONNECTIONS OF FEEDERS AND BRANCH CIRCUITS TO

SWITCHBOARDS AND/OR PANELBOARDS SHALL BE DONE IN A

MANNER AS TO LIMIT THE OUTAGES TO AN ABSOLUTE MINIMUM.

J. ALL TERMINATIONS, CONDUCTORS, AND DEVICES SHALL BE 75

DEGREE CELSIUS RATED, TO THE EXTENT FEASIBLE; OTHERWISE

COMPLY WITH NEC ARTICLE 110.14(C)(1).

K. ELECTRICAL CONTRACTOR SHALL NOT ROUTE WIRING CONNECTED

TO THE LIFE SAFETY BRANCH OR THE CRITICAL BRANCH IN

FLEXIBLE METAL RACEWAYS OR METAL SHEATHED CABLE

ASSEMBLIES, EXCEPT AS ALLOWED BY NEC ARTICLE 517.31(C)(3)(3).

L. ELECTRICAL CONTRACTOR SHALL PROVIDE RACEWAYS, JUNCTION

BOXES, CABINETS, ETC., IN ORDER TO SEPARATE THE LIFE SAFETY

BRANCH AND/OR THE CRITICAL BRANCH CIRCUIT WIRING FROM THE

WIRING AND EQUIPMENT SERVED BY ANY OTHER BRANCHES OF

POWER.

M. UNLESS OTHERWISE NOTED FOR MEDICAL EQUIPMENT,

ELECTRICAL CONTRACTOR SHALL INSTALL ALL RACEWAY, BOXES,

AND CABLES. THE CABLES, UNLESS OTHERWISE NOTED, SHALL BE

PROVIDED BY THE MEDICAL EQUIPMENT VENDOR.

N. THE EQUIPMENT GROUNDING TERMINAL BUSES OF THE NORMAL

AND THE ESSENTIAL ELECTRICAL SYSTEM BRANCH-CIRCUIT

PANELBOARDS, SERVING THE SAME INDIVIDUAL PATIENT CARE

VICINITY, SHALL BE BONDED TOGETHER WITH A CONTINUOUS,

INSULATED COPPER GROUNDING CONDUCTOR NOT SMALLER THAN

#10 AWG.

O. A MAXIMUM OF THREE (3) 20 AMPERE, 1 POLE BRANCH CIRCUITS

MAY BE COMBINED IN A COMMON HOMERUN SHARING A COMMON

GROUNDED (NEUTRAL) CONDUCTOR OR WITH DEDICATED

SEPARATE NEUTRALS (GROUNDED CONDUCTORS), FOR A TOTAL

OF SIX CURRENT CARRYING CONDUCTORS. ALL BRANCH CIRCUITS

LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO THE

PANELBOARD.

P. ALL CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN

600 VOLTS. MINIMUM SIZE SHALL BE #12 AWG, UNLESS OTHERWISE

NOTED ON THE DRAWINGS. ALL CONDUCTORS #8 AWG AND

LARGER SHALL BE STRANDED. #10 THRU #12 AWG CONDUCTORS

SHALL BE SOLID. ALL INSULATION TYPES SHALL BE THWN OR THHN,

UNLESS OTHERWISE NOTED.

S. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE CIRCUIT

BREAKERS FOR ALL BRANCH CIRCUITS WITH SHARED NEUTRALS

(GROUNDED CONDUCTORS) PER NEC ARTICLE 210.4(B) OR PROVIDE

SEPARATE NEUTRALS (GROUNDED CONDUCTORS) FOR EACH

BRANCH CIRCUIT. PANELBOARD SCHEDULES SHALL INDICATE IF

MULTI-POLE OR SINGLE-POLE CIRCUIT BREAKERS ARE BEING USED.

T. ALL BRANCH CIRCUIT WIRING SHALL BE SIZED TO PREVENT A

VOLTAGE DROP EXCEEDING 3%. THE FOLLOWING TABLE IS BASED

ON AN 80% LOADED 20 AMPERE SINGLE PHASE BRANCH CIRCUIT.

WIRING SHOWN IN PANELBOARD SCHEDULES IS THE HOMERUN

FROM THE DEVICE TO THE PANELBOARD:

VOLTS DISTANCE TO HOMERUN REMAINDER

FIRST OULET OF CIRCUIT

120 0' - 50' #12 #12 50' - 95' #10 #12 95' - 145' #8 #12 145' - 230' #6 #12

208 0' - 95' #12 #12 95' - 160' #10 #12 160' - 250' #8 #12

277 0' - 125' #12 #12 125' - 220' #10 #12 220' - 335' #8 #12

480 0' - 225' #12 #12 225' - 380' #10 #12 380' - 585' #8 #12

U. A SHORT-CIRCUIT/ARC FLASH AND SELECTIVE COORDINATION

STUDY SHALL BE PREPARED FOR THE ELECTRICAL OVERCURRENT

DEVICES BEING INSTALLED FOR THIS PROJECT. FINAL FIELD

SETTINGS AND MODIFICATIONS OF THE OVERCURRENT

PROTECTIVE DEVICES SHALL BE MADE TO CONFORM WITH THE

STUDY, WITHOUT ADDITIONAL COST OR TIME TO THE OWNER.

V. ALL BREAKERS 600 AMPERES AND ABOVE SHALL BE SOLID-STATE

TYPE. SELECT ELECTRONIC TRIP FUNCTIONS FOR LOW-VOLTAGE

CIRCUIT BREAKERS SO AS TO ACHIEVE SELECTIVE COORDINATION

AS REQUIRED BY NFPA 70 (NEC).

W. LIGHTING LAYOUTS ARE BASED ON LIGHTING LEVELS

RECOMMENDED BY THE IESNA (ILLUMINATING ENGINEERING

SOCIETY OF NORTH AMERICA). LIGHT LEVELS ARE AFFECTED BY

ENVIRONMENTAL CONDITIONS SUCH AS THE COLOR OF FINISHES

(CEILINGS, WALLS, FLOORS, ETC.), WINDOW TREATMENTS,

FURNISHINGS, AND FINAL LUMINAIRE SELECTIONS. IF ALL

ENVIRONMENTAL CONDITIONS WERE NOT ESTABLISHED DURING

DESIGN, LIGHTING LEVELS OBSERVED AFTER COMPLETION OF

CONSTRUCTION MAY DIFFER FROM CALCULATED LIGHTING LEVELS.

BASIS OF DESIGN LIGHTING CALCULATIONS FOR SPECIFIC AREAS

ARE AVAILABLE UPON REQUEST.

X. ALL DEMOLITION WORK SHALL BE COORDINATED WITH THE

OWNER’S REPRESENTATIVE PRIOR TO BEGINNING THE WORK.

Y. REMOVE ALL EXISTING ELECTRICAL DEVICES, LUMINAIRES, WIRING,

AND RACEWAYS IN WALLS AND IN CEILINGS BEING DEMOLISHED,

UNLESS OTHERWISE NOTED. RECONNECT EXISTING DEVICES AND

LUMINAIRES DOWNSTREAM OF THOSE BEING REMOVED. WIRING

AND RACEWAYS SHALL BE REMOVED BACK TO THEIR SOURCE OF

POWER, UNLESS OTHERWISE NOTED.

Z. EXISTING ELECTRICAL WORK SHOWN TO REMAIN, BUT THAT

INTERFERES WITH THE NEW WORK, SHALL BE REWORKED AND

RELOCATED TO AVOID ANY INTERFERENCE.

AA. REMOVE EXISTING ELECTRICAL GEAR AS SHOWN. DEMOLITION OF

FEEDERS AND BRANCH CIRCUITS OR TRANSFERRING FEEDERS AND

BRANCH CIRCUITS TO NEW PANELBOARDS, SHALL BE PERFORMED

IN A MANNER AS TO KEEP DOWNTIME AND OUTAGES TO AN

ABSOLUTE MINIMUM.

BB. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL ITEMS

ASSOCIATED WITH DEMOLITION WORK SHOWN ON THE

ARCHITECTURAL, CIVIL, STRUCTURAL, INTERIOR, PLUMBING,

MECHANICAL, AND FIRE PROTECTION DRAWINGS.

CC. EXISTING ELECTRICAL CONDITIONS ARE BASED UPON SITE SURVEY

INFORMATION AND EXISTING RECORD/AS-BUILT DRAWINGS MADE

AVAILABLE FROM THE OWNER. ELECTRICAL WORK SHOWN

CONVEYS THE GENERAL SCOPE OF THE DEMOLITION WORK TO BE

PERFORMED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE

AND OBSERVE THE EXISTING CONDITIONS PRIOR TO BIDDING. NO

CHANGE ORDERS WILL BE CONSIDERED FOR CONDITIONS VISIBLE

DURING A SITE VISIT.

DD. FIRE ALARM APPLIANCES AND DEVICES SHOWN IN AN AREA

INDICATE THAT THE CONTRACTOR SHALL PROVIDE COVERAGE IN

THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE

APPLIANCES AND DEVICES AS REQUIRED BY THE LATEST EDITION

OF NFPA 72 AND THE STATE BUILDING CODE. NO CHANGE ORDERS

WILL BE ALLOWED FOR APPLIANCES AND DEVICES REQUIRED BY

NFPA 72 AND THE STATE BUILDING CODE.

END OF PROJECT GENERAL NOTES

MON = MONITOR. SEE DETAIL 16 ON SHEET E003.

ELECTRICAL - DRAWING INDEX

Sheet Number Sheet Name

E001 ELECTRICAL - SYMBOLS, NOTES, & DRAWING INDEX (1 OF 2)

E002 ELECTRICAL - SYMBOLS, NOTES, & DRAWING INDEX (2 OF 2)

E003 ELECTRICAL - DETAILS

E004 ELECTRICAL - PANEL SCHEDULES

E005 ELECTRICAL - POWER RISER AND LUMINAIRE SCHEDULE

ED100 ELECTRICAL - LEVEL 03 - DEMOLITION

EL100 ELECTRICAL - LEVEL 03 - NEW WORK - LIGHTING - OVERALL

EL100A ELECTRICAL - LEVEL 03 - NEW WORK - LIGHTING - AREA A

EL100B ELECTRICAL - LEVEL 03 - NEW WORK - LIGHTING - AREA B

EP100 ELECTRICAL - LEVEL 03 - NEW WORK - POWER - OVERALL

EP100A ELECTRICAL - LEVEL 03 - NEW WORK - POWER - AREA A

EP100B ELECTRICAL - LEVEL 03 - NEW WORK - POWER - AREA B

EY100 ELECTRICAL - LEVEL 03 - NEW WORK - TELECOMMUNICATIONS OVERALL

EY100A ELECTRICAL - LEVEL 03 - NEW WORK - TELECOMMUNICATIONS - AREA A

EY100B ELECTRICAL - LEVEL 03 - NEW WORK - TELECOMMUNICATIONS - AREA B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

c h a re n g s rv

\s e rv e rf o ld e r\ p ro je c ts

\4

V

A M

C C o lu m b ia R e n o v a te B f o r E

H R

M A d m in

T ra in in g \1

R e f\

C E

C e n tr a l M o d e l.

rv t

/1

/2

:3

:1

A

M

E001

ELECTRICAL - SYMBOLS, NOTES, &

DRAWING INDEX (1 OF 2)

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 NGE ERF

Rev. No. Revisions: Date:

C

110 110 PUNCHDOWN BLOCKS, RACK OR WALL MOUNTED AS INDICATED

8P8C 8-PIN, 8-CONDUCTOR

ACS ACCESS CONTROL SYSTEM

AFF ABOVE FINISHED FLOOR

AWG AMERICAN WIRE GAUGE

BCT BONDING CONDUCTOR FOR TELECOMMUNICATIONS

C CONDUIT(S)

CAA CONTROLLED ACCESS AREA

CAT 6 CABLING ETL VERIFIED TO ANSI/TIA-568-C.2 CATEGORY 6

CATV CABLE TELEVISION

CCTV CLOSED-CIRCUIT TELEVISION

CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CP CONSOLIDATION POINT

DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER

DB DIRECT BURIED

DIA DIAMETER

DWG DRAWING

ER EXISTING RELOCATED

ETR EXISTING TO REMAIN

EXIST EXISTING

FACP FIRE ALARM CONTROL PANEL

FB FLOOR BOX

FT FEET

GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED

GND GROUND

GRS GALVANIZED RIGID STEEL

IAW IN ACCORDANCE WITH

IDS INTRUSION DETECTION SYSTEM

IN INCHES

LCA LIMITED CONTROL ACCESS

MC MECHANICAL CONTRACTOR

MIN MINIMUM

MTD MOUNTED

NEC NETWORK ENTERPRISE CENTER

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NESC NATIONAL ELECTRICAL SAFETY CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OEM ORIGINAL EQUIPMENT MANUFACTURER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

PA PUBLIC ADDRESS

PE POLYETHYLENE

PET PROTECTED ENTRANCE TERMINALS

POTS PLAIN OLD TELEPHONE SERVICE

(SWITCHED TELEPHONE LINE)

PSI POUNDS PER SQUARE INCH

PTZ PAN / TILT / ZOOM

QTY QUANTITY

RBB RACK BONDING BUSBAR

RR REMOVE AND RELOCATE

RS RIGID STEEL

STP SHIELDED TWISTED PAIR

TBB TELECOMMUNICATIONS BONDING BACKBONE

TE TELECOMMUNICATIONS ENCLOSURE

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TYP TYPICAL

U/G UNDERGROUND

UON UNLESS OTHERWISE NOTED

U/UTP UNSCREENED/UNSHIELDED TWISTED PAIR CABLE

VoIP VOICE OVER INTERNET PROTOCOL

WP WEATHERPROOF

XP EXPLOSION PROOF

TELECOMMUNICATIONS BACKBONE CABLING

SYSTEM DESIGNATION

VOICE MULTI-PAIR VOICE GRADE

DATA OPTICAL FIBER SINGLE-MODE

CATV RG-11 COAX

GRAY

YELLOW

WHITE

TELECOMMUNICATIONS HORIZONTAL CABLING

VOICE CAT 6A U/UTP WHITE

DATA CAT 6A U/UTP BLUE

CATV RG-6 COAX WHITE

COORDINATE ALL CABLE COLORS WITH AHJ BEFORE PURCHASE.

TELECOMMUNICATIONS ABBREVIATIONS

TELECOMMUNICATIONS GENERAL NOTES

TELECOMMUNICATIONS CABLING NOTES

CABLE TYPE CABLE COLOR

SYSTEM DESIGNATION CABLE TYPE CABLE COLOR

( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS

MAY NOT APPEAR ON THIS SET OF DRAWINGS. )

TELECOMMUNICATION SYMBOLS

PS

W

D

PS

PTZ

PP

ES

PB

ML

KPCR

EXIT

SS

SS

ELC

K

AL

CR

PB

GB

PS

V

M

H

BR

BA

NL

EMO

ERS

TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.

TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.

SECURITY SYSTEM CLOSED CIRCUIT T.V. CAMERA. SUBSCRIPT INDICATES PAN/TILT/ZOOM CONTROL.

SECURITY SYSTEM PUSHBUTTON STATION. SURFACE MOUNTED 42" AFF.

PUBLIC ADDRESS SYSTEM MICROPHONE OUTLET, WALL MOUNTED 18" AFF. COORDINATE TYPE OF

PUBLIC ADDRESS SYSTEM HORN, WALL MOUNTED 7'-6" AFF. UNLESS OTHERWISE INDICATED.

PUBLIC ADDRESS SYSTEM OR MUSIC SPEAKER, CEILING MOUNTED.

OUTLET WITH OWNER'S EQUIPMENT.

INTERCOM OUTLET WALL MOUNTED 42" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION

INTERCOM WALL MOUNTED 18" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION.

VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE. PROVIDE 1"C. FROM

MODIFIERS FOR INTERCOM:

M = MASTER STATION

S = SUB STATION

W = WALL MOUNTED STATION

TELEPHONE OUTLET, WALL MOUNTED 48" AFF.

VOICE/DATA OUTLET, WALL MOUNTED 42" AFF

PROVIDE 1"C. FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.

TELEPHONE OUTLET WALL MOUNTED 68" AFF

PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY

CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR

VOICE/DATA WIRING TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION

VOICE/DATA OUTLET, FLUSH FLOOR MOUNTED.

GROUND BAR - 1/8"x1"x12" COPPER BUS IN NEMA 1 ENCLOSURE. LOCATE ABOVE SUSPENDED CEILING.

PUBLIC ADDRESS SYSTEM VOLUME CONTROL SWITCH, WALL MOUNTED 42" AFF.

CONDUIT SLEEVES. SEE PLANS FOR SIZE AND QUANTITY.

UNLESS NOTED OTHERWISE.

WITH EQUIPMENT SUPPLIER/INSTALLER.

OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

WALL MOUNTED LOCAL ALARM BUZZER, 85dBA.

PUSH BUTTON DOOR RELEASE WITH SOUNDER COVER.

MAGNETIC LOCK FOR DOOR.

PUBLIC ADDRESS SYSTEM OR MUSIC SPEAKER, CEILING MOUNTED.

CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.

PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

WIRELESS TELEMETRY ANTENNA

WIRELESS TELEMETRY DEVICE

EXPEDITER BUTTON PANEL

EXAM LIGHT CONTROLLER

EMERGENCY EGRESS PUSH BUTTON

KEY PAD CARD READER

PUSH BUTTON

EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.

BUTTON RELEASE.

BADGE ACCESS.

NURSE LOCATOR.

EMERGENCY MANUAL OVERRIDE.

TERMINATIONS SHALL BE PERFORMED USING PIN/PAIR ASSIGNMENTS IN

ACCORDANCE WITH THE T568A PIN-OUT SEQUENCE USING 8-PIN 8

CONDUCTOR (8P8C) RJ45 TYPE CONNECTORS RATED FOR THE CATEGORY OF

THE INSTALLED CABLE; COLOR SHALL MATCH THE U/UTP OUTER JACKET.

TELECOMMUNICATIONS OUTLETS, 8P8C RJ45 TYPE CONNECTOR

· U/UTP CABLES FOR DATA SHALL HAVE A BLUE OUTER JACKET

· U/UTP CABLES FOR VOICE SHALL HAVE A WHITE OUTER JACKET

APPLICABLE TO ALL OUTLETS LISTED BELOW:

WAP WIRELESS ACCESS POINT WITH ONE OUTLET CONNECTOR LABELED FOR DATA

INSTALLED ABOVE CEILING

DPS 2P 2T BALANCED POSITION SWITCH INSTALLED LU FRAME AND CONNECTED TO ACCESS CONTROL

AND ALARM PANEL. SWITCH TO CONFORM WITH UL 634 2. WHERE DOOR IS NOT CONNECTED TO

ACCESS CONTROL SYSTEM, A SINGLE POLE SWITCH IS SUFFICIENT.

TELECOMMUNICATIONS STANDARDS

TELECOMMUNICATIONS INSTALLATION SHALL COMPLY WITH THE MOST CURRENT

VERSION OF THE FOLLOWING STANDARDS:

I3A - TECHNICAL CRITERIA FOR THE INSTALLATION INFORMATION INFRASTRUCTURE

ARCHITECTURE

OSPDPR: WORLDWIDE OUTSIDE PLANT DESIGN AND PERFORMANCE

REQUIREMENTS

ANSI/TIA-568-D.0, 2015 : GENERIC TELECOMMUNICATIONS CABLING FOR CUSTOMER

PREMISES

ANSI/TIA-568-D.1, 2015: COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING

STANDARD

ANSI/TIA-568-C.2, 2009 : BALANCED TWISTED PAIR TELECOMMUNICATIONS CABLING

AND COMPONENT STANDARD

ANSI/TIA-568-C.3, 2008 : OPTICAL FIBER CABLING COMPONENTS STANDARD

ANSI/TIA-568-C.4, 2011 - BROADBAND COAXIAL CABLING AND COMPONENTS

STANDARD

ANSI/TIA-569-D, 2015 : TELECOMMUNICATIONS PATHWAYS AND SPACES

ANSI/TIA-606-B, 2012 : ADMINISTRATION STANDARD FOR COMMERCIAL

TELECOMMUNICATIONS INFRASTRUCTURE

TIA-526-7 (OFSTP-7)-2002+A1:2008 : MEASUREMENT OF OPTICAL POWER LOSS OF

INSTALLED SINGLE-MODE FIBER CABLE PLANT

ANSI/TIA-607-B, 2011 : COMMERCIAL BUILDING GROUNDING (EARTHING) AND

BONDING REQUIREMENTS FOR TELECOMMUNICATIONS

ANSI/TIA-1152, 2009: REQUIREMENTS FOR FIELD TEST INSTRUMENTS AND

MEASUREMENTS FOR BALANCED TWISTED-PAIR CABLING

TIA TSB-162-A, 2013 : TELECOMMUNICATIONS CABLING GUIDELINES FOR WIRELESS

ACCESS POINTS

ANSI/NECA/BICSI 568 : STANDARD FOR INSTALLING COMMERCIAL BUILDING

TELECOMMUNICATIONS CABLING

NFPA 70 : NATIONAL ELECTRICAL CODE (NEC)

NFPA 75 : STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY

EQUIPMENT

NFPA 76 : STANDARD FOR THE FIRE PROTECTION OF TELECOMMUNICATIONS

FACILITIES

MIL-HDBK-232A : RED/BLACK ENGINEERING-INSTALLATION GUIDELINES

MIL-HDBK-1012/3 : TELECOMMUNICATIONS PREMISES DISTRIBUTION PLANNING,

DESIGN AND ESTIMATING

USASOC INFORMATION TECHNOLOGY (IT) TECHNICAL DESIGN GUIDE

TM 5-853-4 CORPS OF ENGINEERS ELECTRONIC SECURITY SYSTEMS TECHNICAL

MANUAL

IC-TECH SPEC ICD/ICS 705, ICS-705-1, ICS-705-2

CoSC ISP INSTALLATION STANDARDS VERSION 1.0, 16 MAY 2011

UFC 4-020-04A : ELECTRONIC SECURITY SYSTEMS : SECURITY ENGINEERING

AR 380-5 - DEPARTMENT OF THE ARMY INFORMATION SECURITY PROGRAM

AR 380-27 - (FOUO) CONTROL OF COMPROMISING EMANATIONS

AR 380-40 - SAFEGUARDING AND CONTROLLING COMMUNICATIONS SECURITY

MATERIAL

VA PHYSICAL SECURITY DESIGN MANUAL - LIFE SAFETY PROTECTED FACILITIES

MIL-HDBK-419A : GROUNDING, BONDING AND SHIELDING FOR ELECTRONIC

EQUIPMENT AND FACILITIES

MIL-STD-188-124B – (U) GROUNDING, BONDING, AND SHIELDING FOR

COMMON LONG-HAUL/TACTICAL COMMUNICATIONS SYSTEMS, INCLUDING

GROUND BASED COMMUNICATION ELECTRONICS FACILITIES FOR

EQUIPMENT

1. THIS IS A STANDARD LEGEND SHEET. NOT ALL SYMBOLS OR ABBREVIATIONS MAY APPEAR ON

DRAWINGS.

2. REFER TO DIVISION 26, 27, 28 AND 33 SPECIFICATIONS FOR TELECOMMUNICATION SYSTEM

ITEMS.

3. MOUNTING DEVICES AND EQUIPMENT PE SPECIFICATIONS UNLESS OTHERWISE NOTED.

4. MOUNTING HEIGHTS UNLESS OTHERWISE NOTED, ARE TO CENTER LINE OF DEVICE.

5. THE CONTRACTOR SHALL DETERMINE EXACT ROUTING OF RACEWAYS.

6. THE CONTRACTOR SHALL COORDINATE ALL RACEWAY PENETRATIONS AND PROVIDE

FIREPROOFING AS APPLICABLE.

7. THE MAXIMUM PERMANENT HORIZONTAL LINK DISTANCE SHALL BE 295' AND THE MAXIMUM

HORIZONTAL CHANEL ( LINK PLUS WORKSTATION CABLES AND PATCH CORDS) SHALL BE 328'.

8. ALL HORIZONTAL VOICE AND DATA CABLING SHALL BE CAT 6A INSTALLED IN A MINIMUM 1"

CONDUIT UNLESS NOTED OTHERWISE FROM TELECOMMUNICATION OUTLET LOCATIONS TO THE

CABLE TRAY.

9. ALL HORIZONTAL AND BACKBONE CABLING SHALL BE PLENUM RATED WITH THE EXCEPTION OF

CABLING INSTALLED IN UNDERGROUND CONDUITS. SEE NOTE 23 FOR CABLES INSTALLED IN

UNDERGROUND CONDUITS.

10. CAT 6A CABLING SHALL BE TERMINATED ON 8-PIN, 8-CONDUCTOR (RJ-45) CONNECTORS USING

PIN/PAIR ASSIGNEMENTS IN ACCORDANCE WITH T568A PIN-OUT SEQUENCE.

11. CAT 6A JACKS SHALL BE THE SAME COLOR AS CORRESPONDING HORIZONTAL VOICE AND DATA

CABLING. CAT 6A JACKS SHALL BE THE SAME MANUFACTURER AS THE PATCH PANELS.

12. PROVIDE CAT 6A, 8-PIN, 8-CONDUCTOR MODULAR TO 8-PIN, 8-CONDUCTOR MODULAR, PATCH

CABLES IN QUANTITIES AND LENGTHS SUCH THAT ALL WORKSTATION CABLES ARE CONNECTED.

13. PROVIDE CAT 6A, 8-PIN, 8-CONDUCTOR MODULAR TO 1-PAIR 110 CLIP, PATCH CABLES IN

QUANTITIES AND LENGTHS FOR CONNECTION FROM VOICE PATCH PANELS TO RACK MOUNTED

110 BLOCKS.

14. OPTICAL FIBER CABLES SHALL BE TERMINATED WITH DUPLEX SC-TYPE CONNECTORS.

15. THE USE OF J-HOOKS SHALL BE LIMITED. WHEN USED, J-HOOKS SHALL BE CAT 6A RATED AND

SPACES AT INTERVALS N OT TO EXCEED 5'. J-HOOKS SHALL NOT EXCEED 24 CABLES OR 50%

FILL, WHICHEVER IS LESS. WHEN J-HOOKS ARE USED TO SPAN FORM CONDUIT STUB UPS TO

CABLE TRAY A BONDING BUSHING SHALL BE INSTALLED ON THE CONDUIT STUB UPS AND A

MINIMUM # 6 AWG. GROUND CONDUCTOR SHALL BE INSTALLED FROM THE BONDING BUSHING

TO THE CABLE TRAY, EFFECTIVELY BONDING THE METALLIC RACEWAYS TOGETHER.

16. ALL TELECOMMUNICATIONS RACKS AND SUPPORTING STRUCTURES ( CABLE TRAYS, LADDER

RACKS, CONDUITS, AND BASKETS) WITHIN A TR MUST BE BONDED TO THE TR SIGNAL GROUND

RING OR BUS BAR (TGB OR TMGB) AS DEFINED IN ANSI/TIA-569-C AND IN ANSI/TIA-607-B.

17. CABLE TRAY SHALL BE WALL MOUNTED (PREFERABLE) OR TRAPEZE MOUNTED. CENTER HUNG

CABLE TRAY IS NOT ALLOWED. CABLE TRAY SHALL NOTE BE USED TO SUPPORT OTHER ITEMS,

CONDUIT, CABLE TRAY, PIPING OF UTILITITES. CABLE TRAY SUPPORTS SHALL BE PER NEMA

STANDARDS PUBLICATION VE 2 - METAL CABLE TRAY INSTALLATION GUIDELINES.

18. PROVIDE ACCES PANELS IN NON LAY-IN CEILINGS SUCH THAT NO POINT IN THE CABLE TRAY

SYSTEM IS MORE THAN 20' FROM AN ACCESS POINT.

19. PROVIDE A MINIMUM OF 12" OF CLEARANCE ABOVE THE TOP OF CABLE TRAYS AND A MINIMUM

OF 3" CLEARANCE BELOW CABLE TRAYS.

20. PROVIDE RECTANGULAR, MODULAR, FIRE RATED WALL PENETRATION ASSEMBLIES USING

EITHER INTEGRAL, SLIDING COVERS OR REMOVABLE PLUGS.

21. COMPLY WITH ANSI/TIA-569-C TELECOMMUNICATION PATHWAYS AND SPACES.

22. USE ONLY COPPER CONDUCTORS FOR GROUND CONNECTIONS. THE USE OF ALUMINUM

CONDUCTORS IS NOT ALLOWED.

23. PROVIDE CABLE INSTALLED IN UNDERGROUND CONDUITS LISTED FOR USE IN WET LOCATIONS.

PLENUM RATED CABLE SHALL NOT BE INSTALLED IN ANY UNDERGROUND CONDUIT.

24. PROVIDE OSP CABLES RATED FOR OUTDOOR USE, FILLED WITH A WATER BLOCKING

COMPOUND.

25. LABEL ALL CABLE TERMINATIONS AND BOTH ENDS OF ALL CABLES IN ACCORDANCE WITH UFC

3-580-01 AND ANSI/TIA-606-B.

26. PROVIDE AS-BUILT DOCUMENTATION INCLUDING COMPLETE TEST RESULT REPORTS, FLOOR

PLANS SHOWING USER WORKSTATIONS WITH CABLING LABELING, AND BACKBONE CABLE

SCHEMATIC AND LABELING IN AN ELECTRONIC FORMAT (PDF) OR OTHER APPROVED FORMAT

AND A PRINTED HARDCOPY. TEST RESULTS SHALL BE SUPPLIED ELECTRONICALLY TO THE

PROJECT RCDD AND CORPS PROJECT ENGINEER/ARCHITECT IN THE TEST PROGRAM NATIVE

FORMAT.

27. ANY MOTOR, TRANSFOMER, OR OTHER ELECTRICAL DEVICE GREATER THAN 5 KVA SHALL HAVE

A MINIMUM OF A 4' BUFFER FROM ANY WALL OF THE EF, TER, OR TR(S).

28. THE CONTRACTOR SHALL INITIATE THE APPLICATION FOR TELEPHONE SERVICE AND ASSIST THE

GOVERNMENT IN COMPLETING THE APPLICATION FOR SERVICE; ACCEPTING INSTALLATION OF

SERVICE; START-UP OF SERVICE; AND ACTIVATION OF SPECIFIC TELEPHONE NUMBERS AND

DEDICATED (POTS) LINES FOR FIRE ALARM, ENTRY CONTROL AND ELEVATOR PANELS.

29. MOVING INSTALLED COPPER OR FIBER OPTIC CABLE AND STORING IT, COILED, FOR REUSE IS NOT ADVISABLE. REINSTALLED COPPER U/UTP CABLE SHALL REQUIRE RE-CERTIFICATION PRIOR

TO BEING PLACED BACK INTO SERVICE. THE SAME IS TRUE FOR OPTICAL FIBER CABLE.

HANDLING COPPER U/UTP CABLE BY THOSE UNFAMILIAR WITH TELECOMUNICATION PRACTICES

MAY ALTER THE PHYSICAL GEOMETY OF THESE CABLES RENDERING THEM UNSERVICEABLE.

MOST TELECOMMUNICATIONS CONTRACTORS WILL NOT WARRANTEE REINSTALLED CABLE

WHEREAS FACTORY FRESH CABLE INSTALLED INTO THE PLANT MAY BE WARRANTED FOR UP TO

FIFTEEN YEARS. THIS NEW CONSTRUCTION IS AN IDEAL TIME TO UPGRADE TO CATEGORY-6A

U/UTP FOR THE CABLE PLANT.

30. OSP CABLES SHALL NOT BE EXTENDED INTO A PLENUM OR RATED SPACE. CONTRACTOR SHALL

PROVIDE A 6A RATED TRANSITION BLOCK ALONG WITH A RATED ENCLOSURE FOR

TRANSITIONING THE CABLES FROM OSP-RATED TO A CABLE WITH A RATING COMMENSURATE

WITH THE SPACE.

VIDEO OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.

MODIFIIERS FOR VIDEO:

H = HDMI = 68" AFF

SBB

SCH

SECONDARY BONDING BUSBAR

SCHEDULE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

c h a re n g s rv

\s e rv e rf o ld e r\ p ro je c ts

\4

V

A M

C C o lu m b ia R e n o v a te B f o r E

H R

M A d m in

T ra in in g \1

R e f\

C E

C e n tr a l M o d e l.

rv t

/1

/2

:2

:5

A

M

E002

ELECTRICAL - SYMBOLS, NOTES, &

DRAWING INDEX (2 OF 2)

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

ARCHITECTURAL

CEILING GRID

ACOUSTICAL

CEILING TILE

(TYP)

HANGER WIRE AND

MOUNTING CHANNEL

ATTACHED TO STRUCTURE

REFER TO SPECIFICATION

SECTION 26 51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

JUNCTION BOX

LOCKING

SQUARE

WASHER & NUT

6.35mm (1/4") SCREW

ARCHITECTURAL

CEILING

WIRE TIE THROUGH

MOUNTING CHANNEL &

CROSS BEAM, TYP.

FIXTURE WHIP FROM

JUNCTION BOX (1829mm

(6') LONG MAX)

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS

AND USING THE RECOMMENDED MOUNTING HARDWARE.

EXIT SIGN MOUNTING - LAY-IN CEILING

GRID

ACOUSTICAL CEILING TILE (TYP)

ARCHITECTURAL

CEILING

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND

USING THE RECOMMENDED MOUNTING HARDWARE.

LUMINAIRE MOUNTING - LAY-IN CEILING

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION 26 51 00

3 TWIST MINIMUM

(TYP)

FIXTURE WHIP FROM JUNCTION

BOX (1829mm (6') LONG MAX.)

LUMINAIRE. REFER

TO SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING HARDWARE. REFER TO

SPECIFICATION SECTION 26 51 00

CEILING CROSS

BEAM

LUMINAIRE. REFER TO SCHEDULE

GRID

DEVICE MOUNTING DETAIL

TOP PLATE

STUDS

JUNCTION BOX ABOVE

CEILING MOUNTED ON

BRACKET, TOP PLATE,

OR BY THREADED

ROD FROM STRUCTURE.

HOMERUN

IN EMT.

EMT

CADDY STRAP.

MOUNT TO

STUDS ON BOTH

SIDES.

SWITCH OR

RECEPTACLE.

FEATURES

PATTERN: 360 DEGREES

COVERAGE: 46-186 SQ M (500-2000SF)

TIME DELAY: ADJUSTABLE 30 SECONDS TO 30 MINUTES

OPTIONS

PROVIDE DUAL RELAY IN SPACES WITH MULTIPLE SWITCHING.

CONTROL: MANUAL OFF, DUAL TECHNOLOGY LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: IMPACT RESISTANT INJECTION MOLDED ABS

MOUNTING: CEILING BETWEEN 2440-3050 mm (8'-10') H

ELECTRICAL: 24 VOLT DC (FROM POWER PACK), 120 OR 277

VOLT AC

INPUT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 121 mm X 102 mm (4 3/4" DIA X 4"D)

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

7FCL-37FCL-1

DEVICE LABELING DETAIL

PROVIDE ALL WIRING DEVICES WITH A SELF-

ADHESIVE METALLIC LABEL WITH BLACK

LETTERING INDICATING PANEL AND CIRCUIT

NUMBER SERVING THE DEVICE. THE LABEL

SHALL MATCH THE CURRENT FACILITY'S

STANDARDS FOR NORMAL AND EMERGENCY

BRANCH CIRCUITS. 1

4 " MINIMUM LETTERING

HEIGHT.

GENERAL DETAIL NOTES:

A. COORDINATE LABELING WITH OWNER PRIOR TO INSTALLATION.

NTS

NTS

NTS

NTS

NTS

RECEPTACLE GROUNDING BOX DETAIL

METALLIC

BOXCONDUIT

CONDUIT

BUSHING

GROUNDING

SCREW

"GREEN"

GROUNDING

WIRE

NTS

PLASTIC

THROAT

BUSHING

GROUNDING WIRE

EXIT

12" OR 24" ABOVE DOOR,

WHICHEVER IS LOWER.

CEILING

FLOOR

WALL MOUNTED

TELEPHONE

2" TO

TOP OF

COUNTER OR

BACKSPLASH

18"

RECEPTACLE

LIGHT SWITCH

OR DIMMER

ALIGN WHERE

POSSIBLE

TELEPHONE OR

VOICE DATA OUTLET

TV OUTLET

OR CLOCK

OUTLET

FIRE ALARM DEVICES

A B

O V

E F

L O

O R

T O

B O

T T

O M

O F

D E

V

IC

E

O N

C O

L U

M N

S

MOUNTING HEIGHTS OF DEVICES

FOR WALL MOUNTED UNITS:

BOTTOM

OF DEVICE

N O

T T

O E

X C

E E

D

T O

B O

T T

O M

GENERAL DETAIL NOTES:

A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF DEVICES.

WHEREVER DEVICES, ON THIS SHEET OR OTHER SHEETS, ARE SHOWN AT

GIVEN LOCATION WITH DIFFERENT MOUNTING HEIGHTS THEY SHALL BE

ALIGNED VERTICALLY. IF THEY ARE SHOWN AT THE SAME MOUNTING HEIGHT

THEY SHALL BE ALIGNED HORIZONTALLY. REFER TO THE ARCHITECTURAL

PLANS, ELEVATIONS AND DETAILS. COORDINATE WITH ARCHITECT PRIOR TO

ROUGH-IN.

B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS INDICATED

OTHERWISE.

C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN,

COORDINATE WITH ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS. IF A

CONFLICT OCCURS, REQUEST CLARIFICATION FROM ARCHITECT/ENGINEER

PRIOR TO ROUGH-IN.

6"

NTS

DEVICE LEGEND:

LIGHT SWITCH

RECEPTACLE

VOICE/DATA OUTLET

NTS

2-PORT FACE PLATED DETAIL

BASKET TRAY WITH TRAPEZE HANGER DETAIL 8

NTS

NTS

FINISHED FLOOR

MOUNTING HEIGHT AS

SHOWN IN DRAWINGS

4-11/16" SQ. BY 2-1/2"

DEEP BOX WITH SINGLE

GANG 5/8" TILE RING.

1" CONDUIT WITH

COMMUNICATIONS

WIRING

WALL

CORRIDORROOM

6"

NYLON BUSHING

COORDINATE WITH DUCTWORK

EXTEND CONDUIT TO ABOVE

FINISHED ACCESSIBLE

CEILING IN CORRIDOR TO

CABLE TRAY UNLESS NOTED

OTHERWISE.

SUSPENDED LAY-

IN

CEILING

CABLE TRAY

TELE/DATA OUTLET INSTALLATION DETAIL

NTS

TRAINING ROOM DATA DETAIL 12

NTS

(1) 2-PORT FACE PLATE

PER WORKSTATION.

EMERGENCY LIGHTING AUTOMATIC LOAD CONTROL RELAY DETAIL 11

NTS

POKE - THRU DETAIL 14

FINISHED

FLOOR

MONITOR POWER AND DATA OUTLET INSTALLATION DETAIL

NTS

PLYWOOD BACKING

HDMI

84" AFF

5-20R QUAD

RECEPTACLE 84" AFF

CAT 6A

DATA OUTLET

TO SERVICE

LOOP ABOVE

CEILING

BACK TO

RACK IN OIT

RM 320A

HDMI

24" AFF

NTS

1" CONDUIT ROUTED

INSIDE WALL

CEILING

MONITOR

MOUNTING

BRACKET

NOTE: FIELD COORDINATE

LOCATION OF DEVICES

BEHIND MONITOR SO THEY

ARE NOT VISIBLE AND DO

NOT INTERFERE WITH THE

MONITOR MOUNTING

BRACKET.

EMERGENCY LIGHTING AUTOMATIC LOAD CONTROL RELAY - THREE WAY DETAIL 13

NTS

8" POKE-THRU DEVICE WITH 5 GANGS OF CAPACITY (3 5-20 RECEPTACLES AND 2 6-PORT TELECOM OUTLETS), LOW PROFILE METAL DIE-CAST ALUMINUM COVER (COLOR SELECTED BY ARCHITECT), MEETS UL SCRUB WATER EXCLUSION REQUIREMENTS FOR CARPET FLOORS, UL FIRE RATED FOR UP TO 2-HOUR FIRE CLASSIFIED FLOORS.

SEE ACHITECTURAL PLANS

FINISHED FLOOR

SLAB (VARIES)

POKE-THRU

INSTALL SELF-SEALING POKE-THRU PER

MANUFACTURER'S RECOMMENDATIONS

AND REQUIREMENTS.

SIDE VIEW

TOP VIEW

POKE-THRU

DEVICE(S) BY

CONFERENCE

TABLE IN SAME

ROOM

1" CONDUIT

ROUTED

UNDER FLOOR

FOR CONFERENCE

ROOMS 312B, 320B,

AND 351.

LABEL

LABEL

LABEL

LABELLABEL

LABELLABEL

LABEL

LABEL LABEL

LABELLABEL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

c h a re n g s rv

\s e rv e rf o ld e r\ p ro je c ts

\4

V

A M

C C o lu m b ia R e n o v a te B f o r E

H R

M A d m in

T ra in in g \1

R e f\

C E

C e n tr a l M o d e l.

rv t

/1

/2

:2

:3

A

M

E003

ELECTRICAL - DETAILS EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

c h a re n g s rv

\s e rv e rf o ld e r\ p ro je c ts

\4

V

A M

C C o lu m b ia R e n o v a te B f o r E

H R

M A d m in

T ra in in g \1

R e f\

C E

C e n tr a l M o d e l.

rv t

/1

/2

:2

:1

A

M

E004

ELECTRICAL - PANEL SCHEDULES EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 NGE ERF

1. ALL CIRCUIT ARE EXISTING TO REMAIN. UNLESS OTHERWISE NOTED.

2. UTILIZE SPARE BREAKER AND PROVIDE NEW CIRCUIT AS SHOWN.

Notes:

Total Est. Demand: 4 A

Total Conn.: 3 A

Total Est. Demand: 3361 VA

Other 25 VA 100.00% 25 VA Total Conn. Load: 2694 VA

Lighting 2670 VA 125.00% 3337 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

3 A 2 A 4 A

Total Load: 0.9 kVA 0.6 kVA 1.2 kVA

PHASE A PHASE B PHASE C

41 SPARE 1 20 0.0 0.0 -- -- -- 42

39 SPARE 1 20 0.0 0.0 -- -- -- 40

37 SPARE 1 20 0.0 0.0 30 3 TVSS UNIT 38

35 SPARE 1 20 0.0 0.0 20 1 SPARE 36

33 SPARE 1 20 0.0 0.0 20 1 SPARE 34

31 SPARE 1 20 0.0 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 0.0 20 1 SPARE 24

21 SPARE 1 20 0.0 0.0 20 1 SPARE 22

19 SPARE 1 20 0.0 0.0 20 1 SPARE 20

17 SPARE 1 20 0.0 0.0 20 1 SPARE 18

15 SPARE 1 20 0.0 0.0 20 1 SPARE 16

13 SPARE 1 20 0.0 0.5 20 1 EXISTING GENERAL LIGHTING 14

11 SPARE 1 20 0.0 0.0 20 1 SPARE 12

9 SPARE 1 20 0.0 0.0 20 1 SPARE 10

7 LGHT - MECH RM 312C 2 12 12 2 ¾ 1 20 0.1 0.0 20 1 SPARE 8

5 LGHT - RMS 320 - 320G 2 12 12 2 ¾ 1 20 1.2 0.0 20 1 SPARE 6

3 LGHT - RM 330 2 12 12 2 ¾ 1 20 0.6 0.0 20 1 SPARE 4

1 LGHT - RMS 312A/B & 351A/B 2 12 12 2 ¾ 1 20 0.3 0.0 20 1 SPARE 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1

Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: 3BHDP Phases: 3 Mains Type: MLO

Location: ELECTRICAL 348 Volts: 480/277 Wye A.I.C. Rating: 22,000A

Branch Panel: 3BHA (EXISTING)

1. PROVIDE NEW DEVICE TO MATCH EXISTING IN ALL CHARACTERISTICS.

2. REFER TO POWER RISER DIAGRAM FOR CONDUCTOR AND RACEWAY SIZE AND QUANTITY.

3. ALL CIRCUIT ARE EXISTING TO REMAIN, UNLESS OTHERWISE NOTED.

Notes:

Total Est. Demand: 118 A

MISCELLANEOUS 8760 VA 100.00% 8760 VA Total Conn.: 146 A

Receptacle 30200 VA 66.56% 20100 VA Total Est. Demand: 42360 VA

Power 7300 VA 100.00% 7300 VA Total Conn. Load: 52460 VA

HVAC 6200 VA 100.00% 6200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

184 A 123 A 133 A

Total Load: 21.9 kVA 14.8 kVA 15.8 kVA

PHASE A PHASE B PHASE C

41 SPARE 1 20 0.0 0.0 20 1 SPARE 42

39 SPARE 1 20 0.0 0.0 20 1 SPARE 40

37 SPARE 1 20 0.0 0.0 20 1 SPARE 38

35 SPARE 1 20 0.0 0.0 20 1 SPARE 36

33 SPARE 1 20 0.0 0.0 20 1 SPARE 34

31 SPARE 1 20 0.0 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 0.0 20 1 SPARE 24

21 SPARE 1 20 0.0 0.0 20 1 SPARE 22

19 REC- REF. 351A 1 12 12 2 ¾ 1 20 1.0 2.1 -- -- -- 20

17 REC - BREAK ROOM 351A 1 12 12 2 ¾ 1 20 0.6 2.1 25 2 ¾ 2 10 10 1 EWH-1 18

15 REC - MICROWAVE 351A 1 12 12 2 ¾ 1 20 1.0 0.0 20 1 GFI WOMEN'S BATH 16

13 REC - COFFEE 351A 1 12 12 2 ¾ 1 20 1.0 0.0 20 1 SPARE 14

11 -- -- -- 11.9 0.0 20 1 VAV UNIT 12

9 -- -- -- 12.4 0.0 20 1 SENSET BATHROOM 10

7 PANELBOARD 3BLA-3 1, 2 3 100 15.2 0.0 20 1 WATER FOUNTAIN 8

5 RECEPTACLES ROOM 308 1 20 1.2 0.0 20 1 GFI MEN'S BATHROOM 6

3 SPARE 1 20 0.0 1.4 20 1 REC - COMM ROOM 307 4

1 ATTIC AREA RECEPTACLES 1 20 1.3 1.4 20 1 REC - COMM ROOM 307 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: XFMR T3BLA Phases: 3 Mains Type: MCB

Location: ELECTRICAL 348 Volts: 120/208 Wye A.I.C. Rating: 10,000A

Branch Panel: 3BLA-1 (EXISTING)

Notes:

Total Est. Demand: 32 A

Total Conn.: 32 A

Receptacle 1400 VA 100.00% 1400 VA Total Est. Demand: 11600 VA

Power 10200 VA 100.00% 10200 VA Total Conn. Load: 11600 VA

Equipment 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

36 A 34 A 28 A

Total Load: 4.2 kVA 4.0 kVA 3.4 kVA

PHASE A PHASE B PHASE C

41 -- -- -- 0.0 0.0 -- -- -- 42

39 -- -- -- 0.0 0.0 -- -- -- 40

37 ETC SMARTPACK 3 50 0.0 0.0 30 3 TVSS UNIT 38

35 PATHWAY REPEATER 1 20 0.0 3.4 -- -- -- 36

33 SPARE 1 20 0.0 4.0 -- -- -- 34

31 SPARE 1 20 0.0 4.2 100 3 1, 2 PANELBOARD 3BLA-4 32

29 SPARE 1 20 0.0 0.0 20 1 SPARE 30

27 SPARE 1 20 0.0 0.0 20 1 SPARE 28

25 SPARE 1 20 0.0 0.0 20 1 SPARE 26

23 SPARE 1 20 0.0 0.0 20 1 SPARE 24

21 SPARE 1 20 0.0 0.0 20 1 SPARE 22

19 SPARE 1 20 0.0 0.0 20 1 SPARE 20

17 SPARE 1 20 0.0 0.0 20 1 SPARE 18

15 SPARE 1 20 0.0 0.0 20 1 SPARE 16

13 SPARE 1 20 0.0 0.0 20 1 SPARE 14

11 SPARE 1 20 0.0 0.0 20 1 SPARE 12

9 SPARE 1 20 0.0 0.0 20 1 SPARE 10

7 SPARE 1 20 0.0 0.0 20 1 SPARE 8

5 SPARE 1 20 0.0 0.0 20 1 ATTIC 6

3 SPARE 1 20 0.0 0.0 20 1 ATTIC 4

1 SPARE 1 20 0.0 0.0 20 1 ATTIC REC 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: NEMA 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: XFMR T3BLA Phases: 3 Mains Type: MLO

Location: ELECTRICAL 348 Volts: 120/208 Wye A.I.C. Rating: 10,000A

Branch Panel: 3BLA-2 (EXISTING)

Notes:

Total Est. Demand: 82 A

MISCELLANEOUS 1600 VA 100.00% 1600 VA Total Conn.: 110 A

Receptacle 29600 VA 66.89% 19800 VA Total Est. Demand: 29700 VA

Power 2100 VA 100.00% 2100 VA Total Conn. Load: 39500 VA

HVAC 6200 VA 100.00% 6200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

127 A 104 A 99 A

Total Load: 15.2 kVA 12.4 kVA 11.9 kVA

PHASE A PHASE B PHASE C

41 SPARE 1 20 0.0 0.0 20 1 SPARE 42

39 SPARE 1 20 0.0 0.0 20 1 SPARE 40

37 -- -- -- 2.6 0.0 20 1 SPARE 38

35 SSCU-1/ SSEU-1 8 10 2 1 2 40 2.6 1.2 20 1 ¾ 2 12 12 REC - CERNER ARCH. 330 36

33 VAV CONTROLS 12 12 2 ¾ 1 20 1.0 1.0 20 1 ¾ 2 12 12 VAV CONTROLS 34

31 AHU-09 CONTROLS & REC 12 12 2 ¾ 1 20 1.6 0.0 20 1 SPARE 32

29 SPARE 1 20 0.0 0.1 15 1 ¾ 2 12 12 HUH-1 - MECHANICAL 312C 30

27 SPARE 1 20 0.0 1.2 20 1 ¾ 2 12 12 REC - CONFERENCE 351B 28

25 REC - CONFERENCE 312A 12 12 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 12 12 REC - CONF/ VISIT 312B/ 312A 26

23 REC - PRINTER 312A 12 12 2 ¾ 1 20 0.2 0.8 20 1 ¾ 2 12 12 REC - PRINTER 330 24

21 REC - PRINTER 320C 10 10 2 ¾ 1 20 0.8 1.2 20 1 ¾ 2 12 12 REC - CON. RM/ ADHOC 312B 22

19 REC - CERNER CTLR WRK 320 12 12 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 10 10 REC - CERNER CTLR WRK 320 20

17 REC - CERNER CTLR WRK 320 10 10 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 12 12 REC - CERNER ARCH. 330 18

15 REC - CERNER ARCH. 330 12 12 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 12 12 REC - CERNER ARCH. 330 16

13 REC - CERNER ARCH. 330 12 12 2 ¾ 1 20 1.2 0.8 20 1 ¾ 2 12 12 REC - CERNER ARCH. 330 14

11 REC - CERNER ARCH. 330 12 12 2 ¾ 1 20 1.0 1.2 20 1 ¾ 2 12 12 REC - CERNER ARCH. 330 12

9 REC - CERNER ARCH. 330 12 12 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 12 12 REC - TRAIN RM 320G 10

7 REC - TRAIN RM 320E 12 12 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 12 12 REC - TRAIN RM - 320F 8

5 REC-TV/MONITOR RM 320B 10 10 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 12 12 REC - TRAIN RM 320D 6

3 REC - BRIEF CENTER 320B 10 10 2 ¾ 1 20 1.2 1.2 20 1 ¾ 2 10 10 REC - BRIEFING CENTER 320B 4

1 FLR REC - BRIEF CENTER... 12 12 2 ¾ 1 20 0.9 0.9 20 1 ¾ 2 12 12 FLOOR REC - BRIEF CNTR... 2

CIR DESCRIPTION NOTE G... SIZE # C P AMP A B C A B C AMP P C # SIZE G... NOTE DESCRIPTION CIR Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: 3BLA-1 Phases: 3 Mains Type: MLO

Location: ELECTRICAL 348 Volts: 120/208 Wye A.I.C. Rating: 10,000A

Branch Panel: 3BLA-3 (NEW)

1. PROVIDE NEW DEVICE TO MATCH EXISTING IN ALL CHARACTERISTICS.

2. ALL CIRCUIT ARE EXISTING TO REMAIN, UNLESS OTHERWISE NOTED.

Notes:

Total Est. Demand: 20 A

Total Conn.: 20 A

Other 25 VA 100.00% 25 VA Total Est. Demand: 16948 VA

Lighting 2670 VA 125.00% 3337 VA Total Conn. Load: 16296 VA

HVAC 13676 VA 100.00% 13676 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

20 A 19 A 21 A

Total Load: 5.4 kVA 5.1 kVA 5.7 kVA

PHASE A PHASE B PHASE C

29 SPACE ONLY 1 -- -- -- -- 1 SPACE ONLY 30

27 SPACE ONLY 1 -- -- -- -- 1 SPACE ONLY 28

25 SPACE ONLY 1 -- -- -- -- 1 SPACE ONLY 26

23 SPACE ONLY 1 -- -- 1.3 -- -- -- 24

21 SPACE ONLY 1 -- -- 1.3 -- -- --…