About this file

This document is a set of plumbing construction drawings and specifications for a renovation project at the U.S. Department of Veterans Affairs (VA) facility in Columbia, South Carolina. The project involves renovating Building B3 for Emergency Health and Resource Management (EHRM) Administration and Training purposes. The drawings are part of 100% Bid Documents for Construction and were prepared by GMK Associates, Inc. (Architect), with Charlotte Engineers, LLP as the consultant, and Odell International as the Program Manager.

The specifications detail plumbing fixture requirements including a stainless steel ADA-accessible sink (P-40) measuring 19"x18"x5.5" deep with an 8" gooseneck faucet, laminar flow delivery at 2.2 GPM, and vandal-proof wristblade handles. All faucets, valves, and equipment must be lead-free with NSF 61 approval. Additional fixtures include an electric tankless water heater (EWH-1) requiring 4160W at 208V/20A, floor drains with trap guards, cleanout schedules with cast iron bodies and stainless steel components, and a water supply box (P-90) with lead-free 1/4-turn valves and spill-resistant vacuum breaker. The documents include plumbing legends, connection specifications for waste, vent, and water piping, and detailed notes regarding contractor responsibilities for verification, coordination with other trades, compliance with local and national codes, and field adaptations to site conditions. The drawings cover new sanitary waste connections (3" line to existing 4" riser) and domestic water installations across Level 03 of the facility.

View the file

Other files

File Type Posted
S06 - Amendment 0006-Att 2-Tech Questions-Columbia.pdf PDF
S06-Amendment 0006-Att 1-SF30-Columbia.pdf PDF
S06 - Amendment 0005-Att 1-Tech Questions-Columbia.pdf PDF
S06-Amendment 0005-Att 2-SF30-Columbia.pdf PDF
S06-Amendment 0004-Att 3-HL100.pdf PDF
S06-Amendment 0004-Att 1- BLDG 3 EHRM - DIV 23 Specs Combined.pdf PDF
S06 -Amendment 0004-Att 4- Tech Questions-Columbia.pdf PDF
S06-Amendment 0004-Att 2 - Lim. AB LBP Report - Bld3 EHRM.pdf PDF
S06-Amendment 0004-Att 5- SF30-Columbia.pdf PDF
S06-36C77626R0032-Amendment 0003.pdf PDF
S04- Pre Bid Conference - Columbia.pptx PPTX presentation
S06-36C77626R0032 Amendment 0002.pdf PDF
S06-36C77626R0032 0001.pdf PDF
S06-Site Visit Sign-In Sheet 03062026-Columbia.pdf PDF
S02-RFP Attachment 12-Specifications-Columbia_Part2.pdf PDF
S06-RFP Attachment 17-Spce Update for 01321615-2025-12.pdf PDF
S02-RFP Attachment 15-Specifications-Columbia_Part5.pdf PDF
S02-RFP Attachment 8- Fire Sup Drawings-COL.pdf PDF
S02-RFP Attachment 5- ARCH Drawings-COL.pdf PDF
S02-RFP Attachment 4-Campus Map-Columbia.pdf PDF
S02-36C77626R0032-Columbia.pdf PDF
S02-RFP Attachment 13-Specifications-Columbia_Part3.pdf PDF
S02-RFP Attachment 11-Specifications-Columbia_Part1.pdf PDF
S02-RFP Attachment 9- Mechanical Drawings-COL.pdf PDF
S02-RFP Attachment 6- Electrical Drawings-COL.pdf PDF
S02 - RFP Attachment 3 - Limitations on Subcontracting - Columbia.docx DOCX document
S02-RFP Attachment 1-Wage Rates-Col.txt TXT text file
S02-RFP Attachment 16-Final SOW-Col.pdf PDF
S02-RFP Attachment 14-Specifications-Columbia_Part4.pdf PDF
S02-RFP Attachment 7- Fire Alarm Drawings-COL.pdf PDF
S02-RFP Attachment 2 Site Visit Information-Columbia.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REMARKSSPECIFICATIONS

PLUMBING FIXTURE SCHEDULE

DESCRIPTIONSYMBOL

CONNECTIONS

VW CW HW

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND

PERFORMS EQUAL TO THE SPECIFIED PRODUCT.

GENERAL NOTES:

1. PROVIDE INSULATING SAFETY COVERS FOR ADA ACCESSIBLE SINKS WITH

EXPOSED HOT AND COLD WATER SUPPLIES, DRAINS, AND P-TRAPS. COLOR SHALL MATCH THE

FIXTURE. COORDINATE WITH PROJECT ARCHITECT.

2. ALL FAUCETS, VALVES, AND EQUIPMENT SHALL BE LEAD FREE, BEARING NFS 61 APPROVAL

P-40 2"2" 1/2" 1/2"STAINLESS STEEL-

SINGLE BOWL SINK -

ADA -

SINK - 19"X18"X5.5" DEEP TOP MOUNT, FULLY UNDERCOATED, 18

GA. TYPE 304 STAINLESS STEEL SINK.

FAUCET- DECK MOUNTED 8" FIXED

CENTER 8"GOOSENECK, 2.2 GPM LAMINAR FLOW, 4" VANDAL PROOF WRISTBLADE

HANDELS, AND CERAMIC 1/4TURN OPERATING CARTRIDGE.

ANGLE STOP - LOOSE KEY ANGLE STOP 1/2" IPS FEMALE INLET AND

3/8"x12" LONG CHROME PLATED FLEXIBLE TUBE. PROVIDE WITH CHROME PLATED OR

STAINLESS STEEL LOOSE KEY CAP.

P-TRAP - 1-1/2" x1-1/2" P-TRAP WITH ESCUTCHEON.

DRAIN - FLAT GRID STRAINER WITH 1-1/2"X4" TAILPIECE.

CLEANOUT TEE, DURA-COATED CAST IRON BODY, NO-HUB CONNECTION, GAS AND WATERTIGHT TAPERED THREADED ABS PLUG AND SMOOTH STAINLESS STEEL WALL ACCESS

COVER WITH VANDAL RESISTANT FASTNERS. LOCATE 18" OR LESS ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. LOCATE IN ACCESSIBLE LOCATION.

WCO

RESEMBLES AND PERFORMS EQUAL TO THE SPECIFIED PRODUCT.

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY

CLEANOUT SCHEDULE

DESCRIPTIONSYMBOL

FD-A FLOOR DRAIN, DURA COATED CAST IRON BODY, COMBINATION INVERTIBLE MEMBRANE CLAMP/ADJUSTABLE COLLAR, 6" DIAMETER MEDIUM DUTY VERTICALLY

ADJUSTABLE SATIN FINISH VANDAL PROOF TOP, AND FIXED STAINLESS STEEL STRAINER. PROVIDE TRAP GUARD IN LIEU OF TRAP PRIMER FOR EACH FLOOR DRAIN.

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND PERFORMS EQUAL TO THE

SPECIFIED PRODUCT.

* NOTE: SET ALL FLOOR DRAINS A MINIMUM OF 3/4" BELOW FINISHED FLOOR TO ALLOW FOR FLOOR SLOPE.*

FLOOR DRAIN SCHEDULE

SYMBOL DESCRIPTION

HWR

HW

DN

ABBREVIATIONS

CO

CW

CONNECT TO EXISTING

BALL VALVE

PIPE CONTINUES

ELBOW UP

ELBOW DN

GENERAL

PIPING

HOT WATER

HOT WATER RETURN

DOWN

COLD WATER

CLEANOUT

ABOVE FINISHED FLOOR AFF

HOSE BIBB HB

VENT V

SHOCK ARRESTOR & PDI SIZE SA-A

(E)EXISTING

WASTE W

DEMO TO EXISTING

SANITARY WASTE BELOW FINISHED FLOOR

SANITARY VENT ABOVE FINISHED CEILING

COLD WATER ABOVE FINISHED CEILING

HOT WATER ABOVE FINISHED CEILING

BFFBELOW FINISHED FLOOR

ABOVE FINISHED CEILING AFC

PUMP DISCHARGE PD

VENT THROUGH ROOF VTR

PLUMBING LEGEND

HOT WATER RETURN ABOVE FINISHED CEILING

EWH-1 0.5

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND PERFORMS EQUAL TO THE

SPECIFIED PRODUCT.

ELECTRIC TANKLESS WATER HEATERS

SYMBOL

RECOVERY @

57°F RISE (G.P.M.)

POWER REQUIREMENTS

WATTS/VOLTAGE/AMPS

4160W/208V/20A

REMARKS

CHRONOMITE ELECTRIC TANKLESS POINT OF USE WATER HEATER WITH PRE-WIRED DISCONNECT. CONCEALED IN WALL NEAR

SINK.

NTS

NTS

FLOOR DRAIN DETAIL

NO-HUB BAND

DRAIN BODY

MEMBRANE CLAMP

FLOOR SLAB

RECESSED GRATE

FINISHED FLOOR

PIPE AS SCHEDULED

WATER PROOF

MEMBRANE

PROVIDE WATER

TIGHT SEAL

NTS

FLOOR CLEANOUT DETAIL 3

TYPE 1 CLEVIS HANGER

NTS

4 TYPICAL SS SINK

FINISHED FLOOR

ROUND SCORIATED

STAINLESS STEEL

TOP

CAULK INSIDE

AIR TIGHT SEAL WITH

TAPERED THREAD

BRASS PLUG

INSULATE AS REQD

ATTACH TO

STRUCTURE

TYPE 1 CLEVIS HANGER

WITH PROTECTIVE

SADDLE OR SHIELD

FINISHED FLOOR

ESCUTCHEON

TRAP PARALLEL

TO WALL

OFFSET WASTE

LOOSE KEY

STOP

LAMINAR FLOW

FAUCET

SEE SCHEDULE

CONTROL DEVICE

5 1/2"

MAX

8 " (200 MM)

(4

M

M

APRON. REFER TO

REMOVABLE ANGLED

ARCH'S DETAILS.

WALL CLEANOUT WALL CLEANOUT

SEE SCHEDULE

NOTE: SINK DEPTH AND LOCATION TO BE CONFIRMED BY PC WITH GC AND

MILLWORK VENDOR PRIOR TO ORDERING.

NOTES:

1. PROVIDE WITH TRAP GUARD

P-90 -- 1/2" -WATER SUPPLY BOX - WALL BOX - POWDER COATED STEEL WALL BOX. VALVES TO BE LEAD FREE 1/4 TURN. PROVIDE WATER SUPPLY WITH

SPILL RESISTANT VACUUM

BREAKER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:4

A

M

P001

PLUMBING - SYMBOLS, NOTES,

DETAILS AND DRAWING INDEX

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

PLUMBING - DRAWING INDEX

Sheet

Number Sheet Name

P001 PLUMBING - SYMBOLS, NOTES, DETAILS AND DRAWING

INDEX

PP100 PLUMBING - LEVEL 03 - NEW WORK - SANITARY

PP101 PLUMBING - LEVEL 03 - NEW WORK - DOMESTIC

Rev. No. Revisions: Date:

P-40

3"W

"W

2"V

2"V

BRIEFING CENTER

320B

OIT

320A

STORAGE

320C

PRIVATE OFFICE

320D

PRIVATE OFFICE

320E

PRIVATE OFFICE

320F

PRIVATE OFFICE

320G

CERNER ARCHITECTS

MECHANICAL

312C

CONFERENCE ROOM/ADHOC

WORK AREA

WOMENS

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

FD-A

WCO

"W

3"W

2"V

RECEPTION

312A

CONFERENCE ROOM/ADHOC

WORK AREA

312B

MENS

ELECTRICAL

ELEVATOR

EV01

PIPE CLOSET

330A

COMM.

Room

320QQ

A2

A3

A4 A5

A6 A7 A8 A9 A10 A11

A12 A13 A14

A15

A. THE PLUMBING CONTRACTOR SHALL VERIFY AND

COORDINATE THE INSTALLATION OF THE PLUMBING

SYSTEMS WITH OTHER TRADES PRIOR TO

INSTALLATION TO AVOID CONFLICTS ABOVE CEILING

AND BELOW FLOORS.

B. THE PLUMBING CONTRACTOR SHALL VERIFY ALL

WASTE AND WATER REQUIREMENTS AND LOCATIONS

FOR CONNECTING OWNERS EQUIPMENT PRIOR TO

INSTALLATION. PROVIDE ALL NECESSARY MATERIALS

AND COMPONENTS. VERIFY AND INSTALL PER

MANUFACTURES WRITTEN SPECIFICATIONS,

INSTRUCTIONS, AND ALL LOCAL AND NATIONAL CODES.

C. PLUMBING CONTRACTOR SHALL COORDINATE WITH

ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED

BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL

NATIONAL CODES.

D. PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-

OFF VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS

ARE TO BE INSTALLED. WHERE VALVES DO OCCUR, A

2’X2’ ACCESS PANEL SHALL BE INSTALLED. ARCHITECT

SHALL BE NOTIFIED BEFORE PANEL IS INSTALLED.

E. THE PLUMBING CONTRACTOR SHALL VERIFY AND

COORDINATE ALL PIPING INVERTS WITH EXISTING

CONDITIONS PRIOR TO NEW INSTALLATIONS. PLUMBING

DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT

INTENDED TO INCLUDE EVERY ASPECT OF THE

REQUIRED WORK. PLUMBING CONTRACTOR SHALL

ENSURE A COMPLETE AND WORKING SYSTEM IS

INSTALLED.

F. FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE,

VENT, STORM, AND WATER PIPING RISERS PRIOR TO

ANY DEMOLITION AND RELOCATION. CONTACT

ENGINEER ONCE PIPING SYSTEMS HAVE BEEN

UNCOVERED/EXPOSED.

G. ALL DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR TO

PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE

WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS

REQUIRED DUE TO FIELD CONDITIONS ARE THE

RESPONSIBILITY OF THE CONTRACTOR.

GENERAL NOTES

CONNECT NEW 3" SANITARY WASTE LINE TO EXISTING

4" SANITARY WASTE RISER BELOW FINISHED FLOOR.

VERIFY EXISTING LOCATION OF EXISTING SANITARY

WASTE RISER AND EXACT TIE IN POINT PRIOR TO

PERFORMING ANY WORK.

NEW WORK KEYED NOTES

CONNECT NEW 2" VENT LINE TO EXISTING 4" VENT

STACK ABOVE CEILING. VERIFY EXISTING LOCATION

OF EXISTING VENT STACK AND EXACT TIE IN POINT

PRIOR TO PERFORMING ANY WORK.

FD-A SHALL BE PROVIDED WITH TRAP GUARD IN LIEU

OF TRAP PRIMER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:4

A

M

PP100

PLUMBING - LEVEL 03 - NEW WORK

- SANITARY

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

1/8" = 1'-0"

PLUMBING - LEVEL 03 - NEW WORK - SANITARY

GRAPHIC SCALE

( in Feet )

1 inch = 8 ft.

8 84 16 32

CERNER ARCHITECTS

CONFERENCE ROOM/ADHOC

WORK AREA

MECHANICAL

312C

CERNER CONTROL

CENTER/WORK SPACES

BRIEFING CENTER

320B

STORAGE

320C

PRIVATE OFFICE

320D

PRIVATE OFFICE

320E

PRIVATE OFFICE

320F

PRIVATE OFFICE

320G

OIT

320A

P-40

1/2"CW

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

P-90

RECEPTION

312A

CONFERENCE ROOM/ADHOC

WORK AREA

312B

WOMENS

MENS

Room

320II

ELECTRICAL

COMM.

ELEVATOR

EV01

PIPE CLOSET

330A

A2

A3

A4 A5

A6 A7 A8 A9 A10 A11

A12 A13 A14

A15

A. THE PLUMBING CONTRACTOR SHALL VERIFY AND

COORDINATE THE INSTALLATION OF THE PLUMBING

SYSTEMS WITH OTHER TRADES PRIOR TO

INSTALLATION TO AVOID CONFLICTS ABOVE CEILING

AND BELOW FLOORS.

B. THE PLUMBING CONTRACTOR SHALL VERIFY ALL

WASTE AND WATER REQUIREMENTS AND LOCATIONS

FOR CONNECTING OWNERS EQUIPMENT PRIOR TO

INSTALLATION. PROVIDE ALL NECESSARY MATERIALS

AND COMPONENTS. VERIFY AND INSTALL PER

MANUFACTURES WRITTEN SPECIFICATIONS,

INSTRUCTIONS, AND ALL LOCAL AND NATIONAL CODES.

C. PLUMBING CONTRACTOR SHALL COORDINATE WITH

ARCHITECTURAL PLANS ALL FIRE OR SMOKE RATED

BARRIERS, WALLS, OR PARTITIONS, AND ALL LOCAL

NATIONAL CODES.

D. PLUMBING CONTRACTOR SHALL NOT INSTALL SHUT-

OFF VALVES ABOVE WHERE ANY SHEET ROCK CEILINGS

ARE TO BE INSTALLED. WHERE VALVES DO OCCUR, A

2’X2’ ACCESS PANEL SHALL BE INSTALLED. ARCHITECT

SHALL BE NOTIFIED BEFORE PANEL IS INSTALLED.

E. THE PLUMBING CONTRACTOR SHALL VERIFY AND

COORDINATE ALL PIPING INVERTS WITH EXISTING

CONDITIONS PRIOR TO NEW INSTALLATIONS. PLUMBING

DOCUMENTS ARE DIAGRAMMATIC AND ARE NOT

INTENDED TO INCLUDE EVERY ASPECT OF THE

REQUIRED WORK. PLUMBING CONTRACTOR SHALL

ENSURE A COMPLETE AND WORKING SYSTEM IS

INSTALLED.

F. FIELD VERIFY EXACT LOCATION AND SIZE OF WASTE,

VENT, STORM, AND WATER PIPING RISERS PRIOR TO

ANY DEMOLITION AND RELOCATION. CONTACT

ENGINEER ONCE PIPING SYSTEMS HAVE BEEN

UNCOVERED/EXPOSED.

G. ALL DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR TO

PROVIDE COORDINATION DOCUMENTS IN ACCORDANCE

WITH THE SPECIFICATIONS. ADDITIONAL TRANSITIONS

REQUIRED DUE TO FIELD CONDITIONS ARE THE

RESPONSIBILITY OF THE CONTRACTOR.

GENERAL NOTES

1/2" CW DOWN AND 1/2" HW UP FROM EWH-1. EWH-1 TO

BE MOUNTED UNDERNEATH SINK IN ACCESSIBLE

LOCATION.

NEW WORK KEYED NOTES

CONNECT NEW 1/2" CW TO EXISTING CW LINE ABOVE

CORRIDOR CEILING.

1/2"CW LINE DOWN TO P-90 TO SERVE COFFEE MAKER

AND ICE MAKER AT REFRIGERATOR.

1/2"CW

1/2"CW

1/2"CW

1/2"HW

1/2"CW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

100% BID DOCUMENTS

FOR CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT

GMK Associates, Inc.

1201 Main Street, Suite 2100 Columbia, SC 29201 803-256-0000 Thomas M. Weiland, AIA

STAMPPROGRAM MANAGER

321 4 5 6 7 8 9 10

Odell International 129 Fast Lane, Suite 200 Mooresville, NC 28117 704-401-2040 C. Harmon Reed, Jr. AIA

CONSULTANT

Charlotte Engineers, LLP 5838 Monroe Road Charlotte, NC 28212 704-531-3000 Michael Eaves FULLY SPRINKLERED

Approved:

U A

C a lla h a n \L o c a l R e v it \R

\4

C

E C e n tr a l M o d e l.

rv t

/9 /2

:3

:4

A

M

PP101

PLUMBING - LEVEL 03 - NEW WORK

- DOMESTIC

EHRM - RENOVATE B3 FOR EHRM

ADMIN AND TRAINING

COLUMBIA, SC

544-22-703

B3

07/15/2025 GAT CAS

1/8" = 1'-0"

PLUMBING - LEVEL 03 - NEW WORK - DOMESTIC WATER

GRAPHIC SCALE

( in Feet )

1 inch = 8 ft.

8 84 16 32

EWH-1

PLUMBING - DOMESTIC - ISOMETRIC

EWH-1 1

1/2"HW AND 1/2"CW SERVING

NEW P-40 SINK

1/2"CW SERVING P-90

WATER SUPPLY BOX

BALL VALVE

P001 - PLUMBING - SYMBOLS, NOTES, DETAILS AND DRAWING INDEX
PP100 - PLUMBING - LEVEL 03 - NEW WORK - SANITARY
PP101 - PLUMBING - LEVEL 03 - NEW WORK - DOMESTIC

File details come from the government source that posted it. Updated .