A&E 15021.00 MAMMOTH HOT SPRINGS HOTEL REHABILITATION – PHASE 1
MAMMOTH HOT SPRINGS
YELLOWSTONE NATIONAL PARK, WYOMING
THERMAL INSULATION 072100 - 1
SECTION 072100 - THERMAL INSULATION
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Extruded polystyrene foam-plastic board.
2. Polyisocyanurate foam-plastic board.
3. Mineral-wool blanket.
4. Mineral-wool board.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Sustainable Design Submittals:
1. Product Data: For recycled content, indicating postconsumer and preconsumer recycled content and cost.
2. Product Data: For adhesives, indicating VOC content.
3. Laboratory Test Reports: For adhesives, indicating compliance with requirements for low-emitting materials.
4. Laboratory Test Reports: For Insulation, indicating compliance with requirements for low-emitting materials.
1.3 INFORMATIONAL SUBMITTALS
A. Product test reports.
B. Research reports.
PART 2 - PRODUCTS
2.1 GENERAL
A. Glass-fiber insulation shall not be utilized.
2.2 EXTRUDED POLYSTYRENE FOAM-PLASTIC BOARD – UNDER SLAB, FOUNDATION WALL
A. Extruded polystyrene boards in this article are also called "XPS boards."
B. Extruded Polystyrene Board, Type IV: ASTM C 578, Type IV, 25-psi minimum compressive strength; unfaced; maximum flame-spread and smoke-developed indexes of 25 and 450, respectively, per ASTM E 84.
THERMAL INSULATION 072100 - 2
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. DiversiFoam Products.
b. Dow Chemical Company (The).
c. Owens Corning.
d. Pactiv Corporation.
2. Fire Propagation Characteristics: Passes NFPA 285 testing as part of an approved assembly.
2.3 POLYISOCYANURATE FOAM-PLASTIC BOARD – LOW SLOPE ROOFING
A. Polyisocyanurate Board, Foil Faced: ASTM C 1289, foil faced, Type I, Class 1 or 2.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Atlas Roofing Corporation.
b. Dow Chemical Company (The).
c. Hunter Panels.
d. Rmax, Inc.
2. Fire Propagation Characteristics: Passes NFPA 285 testing as part of an approved assembly.
2.4 MINERAL-WOOL BLANKETS – FRAME WALL AND CEILING CAVITIES
A. Recycled Content: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.
B. Mineral-Wool Blanket, Unfaced: ASTM C 665, Type I (blankets without membrane facing);
consisting of fibers; with maximum flame-spread and smoke-developed indexes of 25 and 50, respectively, per ASTM E 84; passing ASTM E 136 for combustion characteristics.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Industrial Insulation Group, LLC (IIG-LLC).
b. Roxul Inc.
c. Thermafiber Inc.; an Owens Corning company.
C. Mineral-Wool Blanket, Reinforced-Foil Faced: ASTM C 665, Type III (reflective faced), Class A (faced surface with a flame-spread index of 25 or less per ASTM E 84); Category 1 (membrane is a vapor barrier), faced with foil scrim, foil-scrim kraft, or foil-scrim polyethylene.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
THERMAL INSULATION 072100 - 3
a. Thermafiber, Inc.; an Owens Corning company.
2.5 MINERAL-WOOL BOARD
A. Recycled Content: Postconsumer recycled content plus one-half of preconsumer recycled content not less than 25 percent.
B. Mineral-Wool Board, Types IA and IB: ASTM C 612, Types IA and IB; unfaced, with maximum flame-spread and smoke-developed indexes of 15 and zero, respectively, per ASTM E 84;
passing ASTM E 136 for combustion characteristics. Nominal density of 4 lb/cu. ft..
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Industrial Insulation Group, LLC.
b. Roxul Inc.
c. Thermafiber, Inc.; an Owens Corning company.
2.6 VAPOR RETARDERS
A. Reference Section 072600 “Vapor Retarders” for information.
2.7 ACCESSORIES
A. Insulation for Miscellaneous Voids:
1. Spray Polyurethane Foam Insulation: ASTM C 1029, Type II, closed cell, with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, per ASTM E 84.
B. Insulation Anchors, Spindles, and Standoffs: As recommended by manufacturer.
C. Adhesive for Bonding Insulation: Product compatible with insulation and air and water barrier materials, and with demonstrated capability to bond insulation securely to substrates without damaging insulation and substrates.
1. Adhesives shall have a VOC content of 70 g/L or less.
D. Eave Ventilation Troughs: Preformed, rigid fiberboard or plastic sheets designed and sized to fit between roof framing members and to provide ventilation between insulated attic spaces and vented eaves.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Comply with insulation manufacturer's written instructions applicable to products and applications.
THERMAL INSULATION 072100 - 4
B. Install insulation that is undamaged, dry, and unsoiled and that has not been left exposed to ice, rain, or snow at any time.
C. Extend insulation to envelop entire area to be insulated. Fit tightly around obstructions and fill voids with insulation. Remove projections that interfere with placement.
D. Provide sizes to fit applications and selected from manufacturer's standard thicknesses, widths, and lengths. Apply single layer of insulation units unless multiple layers are otherwise shown or required to make up total thickness or to achieve R-value.
3.2 INSTALLATION OF SLAB INSULATION
A. On vertical slab edge and foundation surfaces, set insulation units as indicated in the drawings using manufacturer's recommended adhesive according to manufacturer's written instructions.
B. On horizontal surfaces, loosely lay insulation units as indicated in the drawings and according to manufacturer's written instructions. Stagger end joints and tightly abut insulation units.
3.3 INSTALLATION OF FOUNDATION WALL INSULATION
A. Butt panels together for tight fit.
B. Anchor Installation: Install board insulation on concrete substrates by adhesively attached, spindle-type insulation anchors.
C. Adhesive Installation: Install with adhesive or press into tacky waterproofing or dampproofing according to manufacturer's written instructions.
3.4 INSTALLATION OF CAVITY-WALL INSULATION
A. Foam-Plastic Board Insulation: Install pads of adhesive spaced approximately 24 inches o.c.
both ways on inside face and as recommended by manufacturer. Fit courses of insulation between wall ties and other obstructions, with edges butted tightly in both directions. Press units firmly against inside substrates.
1. Supplement adhesive attachment of insulation by securing boards with two-piece wall ties designed for this purpose and specified in Section 042000 "Unit Masonry."
3.5 INSTALLATION OF INSULATION IN FRAMED CONSTRUCTION
A. Blanket Insulation: Install in cavities formed by framing members according to the following requirements:
1. Use insulation widths and lengths that fill the cavities formed by framing members. If more than one length is required to fill the cavities, provide lengths that will produce a snug fit between ends.
2. Place insulation in cavities formed by framing members to produce a friction fit between edges of insulation and adjoining framing members.
3. Maintain 3-inch clearance of insulation around recessed lighting fixtures not rated for or protected from contact with insulation.
THERMAL INSULATION 072100 - 5
4. Attics: Install eave ventilation troughs between roof framing members in insulated attic spaces at vented eaves.
5. For metal-framed wall cavities where cavity heights exceed 96 inches, support unfaced blankets mechanically and support faced blankets by taping flanges of insulation to flanges of metal studs.
B. Miscellaneous Voids: Install insulation in miscellaneous voids and cavity spaces where required to prevent gaps in insulation using the following materials:
1. Glass-Fiber Insulation: Compact to approximately 40 percent of normal maximum volume equaling a density of approximately 2.5 lb/cu. ft..
2. Spray Polyurethane Insulation: Apply according to manufacturer's written instructions.
3.6 INSTALLATION OF VAPOR RETARDERS
A. Reference Section 072600 “Vapor Retarders” for information.
END OF SECTION 072100