LEJU NH180 2012 NATIONAL INTREPID CENTER OF EXCELLENCE.pdf
PDF 26 MB Posted
- Solicitation number
- N4008526R9042
About this file
This file contains construction contract documents for the National Intrepid Center of Excellence (NICoE) facility at Camp Lejeune, North Carolina, consisting of architectural and structural drawings dated August 29, 2012. The project involves a one-story, fully sprinklered medical office building (Group B occupancy) with a total actual square footage of 24,665 square feet, designed to provide outpatient rehabilitation services including physical therapy, speech therapy, occupational therapy, and counseling for military service members suffering from traumatic brain injuries.
The structural documents specify a Type IIB noncombustible construction with driven timber piles (20-ton capacity, 8-inch minimum tip diameter) extending to -40 feet elevation, reinforced concrete pile caps and grade beams, a two-way flat plate concrete floor system on grade with 4,500 psi concrete at perimeter and 3,000 psi interior concrete, and structural steel framing with wide-flange beams, hollow structural sections for bracing, and steel joists. Key design criteria include 2009 International Building Code, 2011 National Electrical Code, NFPA standards, and UFC (Unified Facilities Criteria) requirements. The construction drawings reference multiple design disciplines including acoustic, MEP (mechanical, electrical, plumbing), fire protection, telecommunications, landscape, and structural engineering, with seals from structural engineers Cagley & Associates and MEP firm SmithGroup MidAtlantic. The project includes site details with concrete walks, planting plans, and utility enclosures, and establishes specific reinforcement schedules, connection details, and construction joint requirements throughout the structural documentation.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PROJECT NORTH
Miller, Beam & Paganelli
ACOUSTICS
12040 South lakes Drive #104 Reston, Virginia 20191 703.506.0005
Pl ot
D at e:
MARINE CORPS BASE CAMP LEJEUNE
NORTH CAROLINA
CAMP LEJEUNE
KJWW
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Cagley & Associates
STRUCTURAL
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
901 K STREET NW
SUITE 400
WASHINGTON, DC 20001
202.842.2100 www.smithgroupjjr.com
SmithGroup MidAtlantic, Inc.
MEPFP
901 K Street NW Suite 400 Washington, DC 20001 202.842.2100
SMITHGROUP, PLLC
8/
/2
7:
:2
PM
COVER SHEET
G0.1 28300.000
NATIONAL INTREPID CENTER OF EXCELLENCE
CAMP LEJEUNE, NORTH CAROLINA
CONTRACT DOCUMENTS
29 AUGUST 2012
FOUNDATION AND STEEL CONSTRUCTION 13 JUN 2012
CURTAIN WALL PACKAGE 11 JUL 2012
MEP BID PACKAGE 2 09 AUG 2012
CONTRACT DOCUMENTS 4 29 AUG 2012
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PROJECT NORTH
Miller, Beam & Paganelli
ACOUSTICS
12040 South lakes Drive #104 Reston, Virginia 20191 703.506.0005
Pl ot
D at e:
MARINE CORPS BASE CAMP LEJEUNE
NORTH CAROLINA
CAMP LEJEUNE
KJWW
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Cagley & Associates
STRUCTURAL
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
901 K STREET NW
SUITE 400
WASHINGTON, DC 20001
202.842.2100 www.smithgroupjjr.com
SmithGroup MidAtlantic, Inc.
MEPFP
901 K Street NW Suite 400 Washington, DC 20001 202.842.2100
SMITHGROUP, PLLC
8/
/2
7:
:3
PM
LOCATION PLAN
G0.2 28300.000
AREA OF MAP BELOW
CLINIC LOCATION VICINITY MAP
PROJECT SITE
PROJECT SITE
NICOE SATELLITE
FOUNDATION AND STEEL CONSTRUCTION 13 JUN 2012
DRAWING INDEX
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PROJECT NORTH
Miller, Beam & Paganelli
ACOUSTICS
12040 South lakes Drive #104 Reston, Virginia 20191 703.506.0005
Pl ot
D at e:
MARINE CORPS BASE CAMP LEJEUNE
NORTH CAROLINA
CAMP LEJEUNE
KJWW
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Cagley & Associates
STRUCTURAL
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
901 K STREET NW
SUITE 400
WASHINGTON, DC 20001
202.842.2100 www.smithgroupjjr.com
SmithGroup MidAtlantic, Inc.
MEPFP
901 K Street NW Suite 400 Washington, DC 20001 202.842.2100
SMITHGROUP, PLLC
12" = 1'-0"
8/
/2
7:
:2
PM
DRAWING INDEX
G0.3 28300.000
A Series Architectural Drawings
● ● ● ● A0.1 ARCHITECTURAL ABBREVIATIONS AND SYMBOLS
● ● ● A0.2 ARCHITECTURAL DIMENSIONING CONVENTIONS
● ● A1.1 ARCHITECTURAL SITE PLAN
● ● A1.2 SITE ENCLOSURES PLANS AND ELEVATIONS
● A1.3 SITE ENCLOSURE DETAILS
● ● ● A2.1A GROUND FLOOR SLAB EDGE PLAN
● ● ● ● ● ● A2.1B GROUND FLOOR PLAN
● ● ● ● ● A2.1C GROUND FLOOR DIMENSION PLAN
● ● ● A2.RA ROOF DECK PLAN
● ● ● A2.RB ROOF PLAN
● ● A3.1 REFLECTED CEILING PLAN
● ● ● ● ● A4.1.1 EXTERIOR ELEVATIONS
● ● ● ● A4.1.2 EXTERIOR ELEVATIONS
● ● ● ● A4.2.1 BUILDING SECTIONS
● ● ● ● A4.3.1 3D VIEWS
● ● ● ● A4.4.1 ENLARGED ELEVATIONS AND SECTIONS
● ● A4.4.2 ENLARGED ELEVATIONS
● ● ● ● A5.1.1 PLAN DETAILS
● ● A5.1.2 PLAN DETAILS
● ● ● ● A5.2.1 SECTION DETAILS
● ● A5.2.2 SECTION DETAILS
● ● A5.2.3 SECTION DETAILS
● A5.3.1 ROOFING DETAILS
● ● A5.4.1 CANOPY DETAILS
● ● ● A7.1.1 ENLARGED FLOOR PLANS - COMMON AREAS
● ● ● A7.1.2 ENLARGED PLANS AND RCP - TOILET ROOMS
● ● ● A7.2.1 GROUND FLOOR FINISH PLAN
● A7.2.2 GROUND FLOOR WALL FINISH PLAN
● A8.1.1 TYPICAL MOUNTING HEIGHTS AND CLEARANCES
● ● ● A8.1.2 TYPICAL TOILET ROOM MOUNTING HEIGHTS AND CONFIGURATIONS
● A8.1.3 TYPICAL RULES FOR DETERMINING MOUNTING HEIGHTS AND LOCATIONS
● A8.1.4 TYPICAL REFLECTED CEILING PLAN LOCATIONS AND CONFIGURATIONS
● ● A8.2.1 INTERIOR ELEVATIONS - COMMON AREAS
● ● A8.2.2 INTERIOR ELEVATIONS - CENTRAL PARK
● A8.2.3 INTERIOR ELEVATIONS - TOILET ROOMS
● ● A8.3.1 INTERIOR ELEVATIONS - CLINICAL SPACES
● ● ● A9.1.1 ROOM FINISH SCHEDULE
● ● ● ● A9.2.1 PARTITION DETAILS
● A9.2.2 PARTITION DETAILS
● A9.2.3 PARTITION DETAILS
● ● ● ● ● A9.3.1 DOOR SCHEDULE
● A9.3.2 FRAME AND OPENING DETAILS
● A9.3.3 FRAME AND OPENING DETAILS
● A9.4.1 INTERIOR DETAILS
● A9.4.2 INTERIOR DETAILS
● A9.4.4 INTERIOR CEILING DETAILS
● A9.4.5 INTERIOR CEILING DETAILS
● A9.4.6 INTERIOR CEILING DETAILS
● A9.5.1 MODULAR CASEWORK DETAILS
● A9.6.1 ARCHITECTURAL WOODWORK DETAILS
● A9.6.2 ARCHITECTURAL WOODWORK DETAILS
● A9.7.1 SIGNAGE SCHEDULE
E Series Electrical Drawings
● ● ● ● ● E0.01 SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES
● ● ● ● E1.01 ELECTRICAL SITE PLAN
● ● ● ● E2.00 ELECTRIC FOUNDATION PLAN
● ● ● E2.01 ELECTRICAL POWER PLAN - GROUND FLOOR
● ● ● E2.02 ELECTRICAL POWER PLAN - ROOF
● ● ● E3.01 ELECTRICAL LIGHTING PLAN - GROUND FLOOR
● ● ● ● E5.01 ELECTRICAL PARTIAL POWER PLANS AND POWER RISER DIAGRAM
● ● E6.01 ELECTRICAL DETAILS
● ● ● E7.01 LIGHTING FIXTURE SCHEDULE
● ● ● E7.02 MECHANICAL EQUIPMENT SCHEDULE
● ● ● E7.03 ELECTRICAL PANEL SCHEDULES
● ● ● E7.04 ELECTRICAL PANEL SCHEDULES
A
PR
SC
H
EM
AT
IC
D
ES
IG
N
J
U N
D
ES
IG
N D
EV
EL
O
PM
EN
T
J
U N
FO
U N
D
AT
IO
N
A N
D S
TE
EL
C O
N
ST
R U
C
TI
O N
J
U L
C U
R
TA
IN
W
AL
L
PA
C
KA
G
E
J
U L
A D
D
EN
D U
M B
A
U G
C
C D
A
U G
M
EP
B
ID
P
AC
KA
G E
A
U G
C
C D
A
U G
C
O N
TR
AC
T D
O C
U M
EN
TS
M Series Mechanical Drawings
● ● ● ● ● M0.1 MECHANICAL ABBREVIATIONS AND SYMBOLS
● ● ● ● M2.1 HVAC SYSTEMS LEGEND
● ● ● ● M2.2 HVAC ZONES LEGEND
● ● ● ● M2.3 GROUND FLOOR AIR TERMINAL PLAN
● ● ● M2.4 GROUND FLOOR HVAC DUCT PLAN
● ● ● M2.5 HVAC ROOF PLAN
● ● ● M2.6 OVERALL 3D VIEW
● ● ● ● M3.1 GROUND FLOOR HVAC PIPING PLAN
● ● ● ● M4.1 MECHANICAL ROOM ENLARGED PIPING AND DUCT PLANS
● ● ● ● M4.2 MECHANICAL ROOM SECTIONS
● ● ● M4.3 MECHANICAL ROOM 3D VIEWS
● ● ● ● M4.4 MECHANICAL ROOM PIPING PART PLAN
● ● M4.5 BUILDING SECTIONS
● ● M4.6 BUILDING SECTIONS
● ● M4.7 BUILDING SECTIONS
● ● ● M5.1 HOT WATER AND CHILLED WATER PIPING DIAGRAMS
● ● ● ● M6.1 MECHANICAL DETAILS
● ● ● ● M6.2 MECHANICAL DETAILS
● ● ● M6.3 MECHANICAL DETAILS
● M6.4 MECHANICAL DETAILS
● ● ● M7.1 SCHEDULES
● ● ● M7.2 SCHEDULES
● ● ● M7.3 SCHEDULES
● ● ● M8.1 CONTROLS
● ● ● M8.2 CONTROLS
● ● ● M8.3 CONTROLS
● ● ● M8.4 CONTROLS
● ● ● M8.5 CONTROLS
A
PR
SC
H
EM
AT
IC
D
ES
IG
N
J
U N
D
ES
IG
N D
EV
EL
O
PM
EN
T
J
U N
FO
U N
D
AT
IO
N
A N
D S
TE
EL
C O
N
ST
R U
C
TI
O N
J
U L
C U
R
TA
IN
W
AL
L
PA
C
KA
G
E
J
U L
A D
D
EN
D U
M B
A
U G
C
C D
A
U G
M
EP
B
ID
P
AC
KA
G E
A
U G
C
C D
A
U G
C
O N
TR
AC
T D
O C
U M
EN
TS
G Series General Drawings
● ● ● ● ● ● G0.1 COVER SHEET
● ● ● ● G0.2 LOCATION PLAN
● ● ● ● ● ● G0.3 DRAWING INDEX
L Series Landscape Drawings
● ● L1.0 LAYOUT, MATERIALS AND GRADING PLAN
● L1.1 SITE DETAILS
● ● ● L2.0 PLANTING PLAN
● L2.1 PLANTING DETAILS
P Series Plumbing Drawings
● ● ● ● ● P0.1 PLUMBING SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
● ● ● ● P2.00 PLUMBING FOUNDATION PLAN
● ● ● ● ● P2.01 PLUMBING GROUND FLOOR PLAN
● ● ● ● P2.02 PLUMBING ROOF PLAN
● ● ● ● P5.01 SANITARY WASTE & VENT RISER DIAGRAM
● ● ● ● P5.02 DOMESTIC WATER RISER DIAGRAM
● ● ● ● P5.03 STORM WATER & GAS RISER DIAGRAM
● ● ● ● P7.01 PLUMBING SCHEDULES
● ● ● ● G1.0 PROJECT CODE SUMMARY
● ● ● ● G1.1 LIFE SAFETY PLAN
F Series Fire Protection Drawings
● ● ● ● F0.1 FIRE PROTECTION ABBREVIATIONS AND SYMBOLS
● ● ● ● F2.1 FIRST LEVEL FIRE PROTECTION PLAN
FA Series Fire Alarm Drawings
● ● ● ● FA0.1 FIRE ALARM ABBREVIATIONS AND SYMBOLS
● ● ● ● FA2.0 FIRE ALARM FLOOR PLAN
AQ Series Equipment and Furniture
● ● AQ1 GROUND FLOOR EQUIPMENT REFERENCE PLAN
● ● AQ1.A GROUND FLOOR EQUIPMENT PLAN - AREA A
● ● AQ1.B GROUND FLOOR EQUIPMENT PLAN - AREA B
● ● AQ1.C GROUND FLOOR EQUIPMENT PLAN - AREA C
● ● AQ1.D GROUND FLOOR EQUIPMENT PLAN - AREA D
S Series Structural Drawings
● ● ● S1.0 GENERAL NOTES
● ● ● S2.1 GROUND FLOOR FOUNDATION PLAN
● ● ● ● S2.2 ROOF FRAMING PLAN
● S2.3 UTILITY ENCLOSURE PLANS AND DETAILS
● ● ● S3.1 TYPICAL FOUNDATION DETAILS
● ● ● S3.2 TYPICAL FOUNDATION DETAILS
● ● ● S4.1 TYPICAL FRAMING DETAILS
● ● ● S4.2 TYPICAL FRAMING DETAILS
● ● ● S4.3 TYPICAL FRAMING DETAILS
● ● ● S4.4 BRACED FRAME ELEVATIONS AND DETAILS
T Series Telecommunications Drawings
● ● ● T0.1 COVER SHEET - TECHNOLOGY
● ● ● T2.0 GROUND FLOOR PLAN - TECHNOLOGY
● ● ● T2.1 ENLARGED PLANS - TECHNOLOGY
● ● ● T3.0 DETAILS - TECHNOLOGY
● ● ● T4.0 RISER DIAGRAMS - TECHNOLOGY
● ● ● T5.0 SCHEDULES - TECHNOLOGY
FOUNDATION AND STEEL CONSTRUCTION 13 JUN 2012
CURTAIN WALL PACKAGE 11 JUL 2012
MEP BID PACKAGE 2 09 AUG 2012
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PROJECT NORTH
Miller, Beam & Paganelli
ACOUSTICS
12040 South lakes Drive #104 Reston, Virginia 20191 703.506.0005
Pl ot
D at e:
MARINE CORPS BASE CAMP LEJEUNE
NORTH CAROLINA
CAMP LEJEUNE
KJWW
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Cagley & Associates
STRUCTURAL
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
901 K STREET NW
SUITE 400
WASHINGTON, DC 20001
202.842.2100 www.smithgroupjjr.com
SmithGroup MidAtlantic, Inc.
MEPFP
901 K Street NW Suite 400 Washington, DC 20001 202.842.2100
SMITHGROUP, PLLC
8/
/2
7:
:4
PM
PROJECT CODE
SUMMARY
G1.0 28300.000
CODE SUMMARY
NATIONAL INTREPID CENTER OF EXCELLENCE
CAMP LEJEUNE, NORTH CAROLINA
FIRE PROTECTION CODE SUMMARY
DESIGN CRITERIA:
2009 ed. IBC The 2009 International Building Code by the International Code Council
2009 ed. IPC The 2009 International Plumbing Code by the International Code Council
2009 ed. IMC The 2009 International Mechanical Code by the International Code Council
2011 ed. NEC The 2011 National Electrical Code by the National Fire Protection Association
The ABA Accessibility Standard for Department of Defense Facilities as adopted by the Deputy Secretary of Defense on October 31, 2008
Applicable National Fire Codes by the National Fire Protection Association as referenced by UFC 1-200-01 including but not limited to:
NFPA 1, 2012 ed. - Fire Code NFPA 10, 2010 ed. - Standard for Portable Fire Extinguishers NFPA 13, 2010 ed. - Automatic Sprinkler Systems NFPA 14, 2010 ed. - Standard for the Installation of Standpipe and Hose Systems NFPA 24, 2007 ed. - Installation of Private Fire Service Mains and Their Appurtenances NFPA 54, 2012 ed. - National Fuel Gas Code NFPA 70, 2011 ed. - National Electrical Code NFPA 72, 2010 ed. - National Fire Alarm Code NFPA 80, 2010 ed. - Standard for Fire Doors and Other Opening Protectives NFPA 80A, 2012 ed. - Recommended Practice for Protection of Buildings from Exterior Fire Exposures NFPA 90A, 2012 ed. - Installation of Air Conditioning and Ventilating Systems NFPA 90B, 2012 ed. - Standard for the Installation of Warm Air Heating and Air-Conditioning Systems NFPA 101, 2012 ed. - The Life Safety Code NFPA 110, 2010 ed. - Standard for Emergency and Standby Power Systems NFPA 1963, 2009 ed. - Fire Hose Connections
UFC 1-200-01, CHANGE 2 - GENERAL BUILDING REQUIREMENTS
CORE UNIFIED FACILITIES CRITERIA:
UFC 3-101-01 - ARCHITECTURE
UFC 3-201-01 - CIVIL ENGINEERING
UFC 3-301-01 - STRUCTURAL ENGINEERING
UFC 3-400-10N - MECHANICAL ENGINEERING
UFC 3-410-01FA - HEATING, VENTILATING AND AIR CONDITIONING
UFC 3-420-01 - PLUMBING SYSTEMS
UFC 3-501-01 - ELECTRICAL ENGINEERING
UFC 3-600-01 - FIRE PROTECTION ENGINEERING FOR FACILITIES
UFC 4-010-01 - DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS
BUILDING DESCRIPTION
THE NATIONAL INTREPID CENTERS OF EXCELLENCE (NICoE) ARE A SERIES OF FACILITIES
BEING CONSTRUCTED THROUGHOUT THE UNITED STATES TO SPECIALIZE IN THE
REHABILITATION OF MILITARY SERVICEMEN AND WOMEN SUFFERING FROM TRAUMATIC
BRAIN INJURIES. THE NICoE - CAMP LEJEUNE SITE WILL BE ONE STORY IN HEIGHT AND
PROVIDE OUTPATIENT SERVICES EXCLUSIVELY. ANTICIPATED SERVICES INCLUDE PHYSICAL
THERAPY, SPEECH THERAPY, OCCUPATIONAL THERAPY AND COUNSELING. AS SUCH, THE
PROPOSED FACILITY WILL BE CONSIDERED A BUSINESS OCCUPANCY.
BUILDING DESCRIPTION
OCCUPANCY CLASSIFICATION:
MEDICAL OFFICE BUILDING: FULLY SPRINKLERED
GROUP B BUSINESS - DOCTOR'S OFFICES, ADMINISTRATIVE AREAS
CLASSROOMS AND ASSEMBLY ROOMS < 750 SF IN AREA
CONSTRUCTION TYPE:
TYPE IIB NONCOMBUSTIBLE
ALLOWABLE AREA/FLOOR(SqFt) B
BASIC ALLOWABLE: 23,000 IBC TABLE 503
SPRINKLER INCREASE: 69,000 IBC SECTION 506.3
TOTAL ALLOWABLE PER FLOOR: 92,000
ACTUAL SQUARE FOOTAGE (SqFt): 24,665
ALLOWABLE BUILDING HEIGHT: B IBC TABLE 503
STORIES: 4 IBC 503, 504 (FULLY SPRINKLERED)
HEIGHT: 75 IBC 503, 504 (FULLY SPRINKLERED)
ACTUAL STORIES: 1
ACTUAL HEIGHT: 17 FT
BUILDING ELEMENTS - MINIMUM FIRE RESISTIVE REQUIREMENTS
BUILDING ELEMENT TYPE IIB IBC TABLE 601
STRUCTURAL FRAME 0 HOUR
BEARING WALLS
EXTERIOR 0 HOUR
INTERIOR 0 HOUR
NONBEARING WALLS/PARTITIONS
EXTERIOR 0 HOUR
INTERIOR 0 HOUR
FLOOR CONSTRUCTION 0 HOUR
ROOF CONSTRUCTION 0 HOUR
INCIDENTAL RATINGS
FIRE BARRIERS: THE FOLLOWING INCIDENTAL AREAS ARE TO BE ENCLOSED WITH 1-HOUR FIRE
RESISTANCE RATED CONSTRUCTION WITH 45-MINUTE DOORS:
- MECHANICAL ROOM
- ELECTRICAL ROOM
- COMMUNICATIONS ROOM
SMOKE RESISTIVE: THE FOLLOWING ARE TO BE ENCLOSED WITH SMOKE RESISTIVE CONSTRUCTION:
- STORAGE ROOM(S) > 100 SqFt.
CORRIDORS
PROTECTION: 0-HOUR FIRE RESISTANCE RATING (FULLY SPRINKLERED)
WIDTH (MIN): CORRIDORS IN ALL AREAS ARE REQUIRED TO BE 44 INCHES MINIMUM
(SERVING UP TO 220 OCCUPANTS), AND 36 INCHES WHEN SERVING 50
OCCUPANTS OR LESS
DEAD END CORRIDORS
OR HALLWAY: MAXIMUM LENGTH OF 50 FEET IN BUSINESS OCCUPANCIES
OCCUPANT LOAD CALCULATION
GROSS FLOOR AREA: 24,665 SqFt.
BUSINESS 16,6158 SqFt. / 100 SqFt. PER PERSON = 162
ASSEMBLY
UNCONCENTRATED 3,178 SqFt. / 15 SqFt. PER PERSON = 212 CLASSROOM 426 SqFt. / 20 SqFt. PER PERSON = 22 FITNESS 2,008 SqFt. / 50 SqFt. PER PERSON = 41 STORAGE/MECHANICAL 2,894 SqFt. / 300 SqFt. PER PERSON = 10
TOTAL OCCUPANCY = 447
EXITS
NUMBER OF EXITS
1. FROM FLOROS OR SPACES MIN. OF 2 EXITS SERVING 1 TO 500 OCCUPANTS
MIN. OF 3 EXITS SERVING 501 TO 1000 OCCUPANTS
MIN. OF 4 EXITS SERVING OVER 1000 OCCUPANTS
2. FROM ROOMS MIN OF 2 EXIT ACCESS DOORS REQUIRED WHEN:
A. COMMON PATH > 100 FT
B. OCCUPANT LOAD > 50 PEOPLE
EXITS REQUIRED: 2
EXITS PROVIDED: 6
EXIT SEPARATION: AT LEAST TWO EXITS FROM THE BUILDING MUST BE
SEPARATED BY A LINEAR DISTANCE NO LESS THAN 1/3
OF THE LONGEST DIAGONAL DIMENSION OF THE
BUILDING REQUIRING TWO EXITS.
TRAVEL DISTANCE TO
AN EXIT (MAX.):
1. MAXIMUM TRAVEL: 300 FEET
2. MAXIMUM COMMON PATH: 100 FEET
3. MAXIMUM DEAD END: 50 FEET
EXIT DOORS
1. EGRESS WIDTH FACTOR: 0.2 INCHES PER PERSON
2. WIDTH (MAX.): 48 INCHES (SWINGING LEAF)
(MIN.): 32 INCHES MINIMUM CLEAR WIDTH
EXIT WIDTH REQUIRED: 86 INCHES
EXIT WIDTH PROVIDED: 285 INCHES
FIRE SUPPRESSION SYSTEMS
AUTOMATIC SYSTEMS
1. SPRINKLERS REQUIRED THROUGHOUT. SPRINKLERS UTILIZED
THROUGHOUT ARE TO BE QUICK-RESPONSE TYPE TO THE
GREATEST EXTENT PRACTICABLE
2. DESIGN CODE/STANDARD NFPA 13 - 2010 EDITION; INSTALLATION OF SPRINKLER SYSTEMS
MANUAL SYSTEMS
PORTABLE FIRE
EXTINGUISHERS: REQUIRED IN ACCORDANCE WITH NFPA 1 FIRE CODE
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM: FULL FIRE ALARM SYSTEM COVERAGE THROUGHOUT, WITH ADA
COMPLIANT VISUAL APPLIANCES
AUTOMATIC FIRE
DETECTION SYSTEM: PARTIAL
EXIT SIGNAGE
EXIT SIGNS: ILLUMINATED WITH DIRECTIONAL SIGNS, PLACED TO CLEARLY MARK
DIRECTION TO AN EXIT, 100 FT. OR LESS TO NEAREST SIGN WITHIN
CORRIDORS, SPACES REQUIRING TWO OR MORE MEANS OF EGRESS AND
AT EXIT DOORS.
EMERGENCY EGRESS
ILLUMINATION: AVERAGE OF 1.0 FOOTCANDLES AT EGRESS PATHS WITH A MIN. OF 0.1
FOOTCANDLE AT ANY POINT
POWER SUPPLY: MEANS OF EGRESS ILLUMINATION NORMAL POWER IS TO BE PROVIDED BY
PREMISE'S ELECTRICAL SYSTEM
1 2 3 4 5 6 7 8
G
F
E
D
C
B
A
GROUP THERAPY
CLASSROOM
NICOE LIAISON
ADMIN CUBICLES
NICOE DIRECTOR
MANAGEMENT
ANALYST
VESTIBULE
MECHANICAL
WAITING
CENTRAL PARK
LOUNGE
REC THERAPY
SPEECH O/E
NEUROPSYCH O/E
IN-TAKE
CASE MNGR
RECEPTION
CASE MNGR
CASE MNGR
IN-TAKE
SPEECH O/E
PSYCH TEST PSYCH TEST
VESTIBULAR
TESTING
NEUROPSYCH O/E
PSYCH TEST
COMM
ELECT
TEAM ROOM
PAT TLT
PAT TLT
CONSULT
SPEECH O/E
OT TREATMENT
EQUIP / STORAGE
CLEAN UTILITY
NEUROPSYCH O/E
BH CONSULT
PSYCH TEST
BIO FEEDBACK
TEAM ROOM SOILED UTILITY
JC
STAFF TLT
OT EVAL
CONSULT
TEAM ROOM
RN EDUCATOR
OFFICERN CLINIC MNGR
NICOE DIRECTOR
REGIONAL
COORDINATOR
OT EVAL
CONSULT
PT EVAL
OT TREATMENT
BH CONSULT
BH CONSULT
FAMILY THERAPIST
(CHAPLAIN)
TREATMENT
TREATMENT
TREATMENT
TREATMENT
TREATMENT
SPEECH O/E
PT EVAL
OT TREATMENT
OT EVAL
PT EVAL
NEUROPSYCH
CLERK
MAXIMUM DIAGONAL = 262FT 6IN
EX
IT
R
EM
OT
EN
ES
S
8F T
0I N
(8 7F
T 6I
N
RE
Q' D)
MAXIMUM DEAD END = 34FT 11IN
M
AX
IM
UM
T
RA
VE
L
DI
ST
AN
CE
FT
IN
2'8"
4'9"
5'6"
2'8" 2'8"
2'8" 1'4"
1" 80
80 81
OCCUPANT LOAD LEGEND
BUSINESS
ASSEMBLY-
UNCONCENTRATED
CLASSROOM
FITNESS/
LOCKER ROOMS
STORAGE/
MECHANICAL
15,967
3,370
2,008
2,894
OCCUPANCY
USE GROUP
HATCHING
PATTERN AREA
OCCUPANT
LOAD
FACTOR
TOTAL 24,665
CALCULATED
OCCUPANT
LOAD
LIFE SAFETY LEGEND
MAXIMUM DEAD END
MAXIMUM COMMON PATH
MAXIMUM TRAVEL DISTANCE
X Y Z
X = ANTICIPATED NUMBER OF USERS
Y = ACTUAL WIDTH OF PROVIDED EGRESS COMPONENT
Z = REQUIRED WIDTH OF EGRESS COMPONENT
CONFERENCE
ROOM
FEMALE TOILET
TOILET / SHOWER
CHANGING
LOCKER ROOM
AUDIO VISUAL
SUPPLY ROOM
MALE TOILET
COMM
ELECT
PATIENT TLT
STORAGE
STORAGE
JC
TREATMENT
CUBICLES
PT CORRIDOR
A.2
0.7A
0.2A 0.4A
D.7
4.2
2'8"
1"
2'8"
1"
5'6" 10"
1'4"
1'4"
1'4" 1'5"
2'8"
1"
M
AX
IM
UM
C
OM
M
ON
P
AT
H
FT
IN
DRAWING NUMBER
PROJECT NUMBER
SCALE
DRAWING TITLE
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR REV DATE
PROJECT NORTH
Miller, Beam & Paganelli
ACOUSTICS
12040 South lakes Drive #104 Reston, Virginia 20191 703.506.0005
Pl ot
D at e:
MARINE CORPS BASE CAMP LEJEUNE
NORTH CAROLINA
CAMP LEJEUNE
KJWW
ELECTRONIC SECURITY / TELECOMMUNICATIONS
2882 106th Street Suite 100 Des Moines, Iowa 50322 515.334.9906
Cagley & Associates
STRUCTURAL
6141 Executive Boulevard Rockville, Maryland 20852 301.881.9050
901 K STREET NW
SUITE 400
WASHINGTON, DC 20001
202.842.2100 www.smithgroupjjr.com
SmithGroup MidAtlantic, Inc.
MEPFP
901 K Street NW Suite 400 Washington, DC 20001 202.842.2100
SMITHGROUP, PLLC
1/8" = 1'-0"
8/
/2
7:
:5
PM
LIFE SAFETY PLAN
G1.1 28300.000
S x
21.42
21.42
21.56
21.93
21.58
21.90
21.58
21.98
21.98
21.98
21.98
21.98
21.86
21.86
21.76
21.60
21.94
21.94
21.98
21.67
21.34
21.34
21.34
21.67
21.98
21.94
21.67
21.39
21.35
RIM 20.80
RIM 20.80
RIM 19.00
RIM 21.30
RIM 21.50
RIM 21.30
RIM 21.30
R
I
M
RIM 21.30
RIM 19.90
B
C
21.82
21.76
21.67
21.67
21.67
21.67
21.90
21.92
21.32
36.00'
24.00' 4.00'
8.00'
15.14'
32.00'
16.00'
12.00' 16.00'
33.05'
5.00'
6.00'
6.00' 6.00'
4.00'
13.62'
2.00'
R16.19' R18.23'
R25.00'
R33.00'
R42.50'
R54.00' 6.75'
5.65'
5.54'
6.00'
50.32'
17.65'
6.00'
32.67'
20.00'
35.33'
37.78'
R14.00'
R14.00'
R65.72'
43.10'
43.10'
21.62
21.69
21.69
21.89
21.45
21.45 21.51
21.64
21.94
21.90
19.22
19.17
20.31
20.26
PLANTING BED
CHAIR (TYP)
CONCRETE WALK
PLANTER (TYP)
ALTERNATE TERRAIN
REHABILITATION AREA
(TYP)
CONCRETE WALK
CONCRETE WALK
CONCRETE WALK
ACCESSIBLE CURB RAMP
CONCRETE WALK
B
C
FLUSH CURB
TRANSITION FROM FLUSH
CURB TO STANDARD
CURB OVER 10'
TRANSITION FROM FLUSH CURB
TO STANDARD CURB OVER 10'
21.69
21.43
21.98
21.98
21.67
21.67
12.00'
8.00'
BICYCLE HOOP
TYP, 3 EQUALLY SPACED
4.0' x 4.0' CONCRETE PAD
AT DOOR, TYP
8.00' 16.00'
3.00'
PLANTING BED
PLANTING BED
BENCH (TYP)
16.00'
9.05'
8.00'
21.74
21.58
21.62
21.62
21.4
21.6
21.58
PAVEMENT JOINTING
ON 4' X 8' GRID
6" PERF CORRUGATED
HDPE UNDERDRAIN WITH
FABRIC (SOCK) WRAP
IN PLANTER AREA
6" SOLID CORRUGATED HDPE DRAIN PIPE
FIELD ROUTE TO PICK UP TERRAIN DRAINS CONNECT HDPE DRAIN
TO STORM STRUCTURE
(SEE CIVIL DRAWINGS)
AT IE 17.50
6" UNDER DRAIN IE 19.00
INSTALL CLEAN OUT ON END
SLOPE DRAIN PIPE UNIFORMLY FROM
PLANTER AREA TO STORM STRUCTURE.
L1.1
4" CONCRETE PLAZA PAVEMENT
(REAR PLAZA)
L1.1
4" CONCRETE PLAZA PAVEMENT
(FRONT PLAZA)
L1.1
THICKENED SLAB
L1.1
L1.1
CONTROL JOINT
L1.1
EXPANSION JOINT
L1.1
FLAG POLE
L1.1
ACCESSIBLE
CURB RAMP
THICKENED SLAB
L1.1
[Drawing Title Text]
[A0.0]
DD
L1.0
LAYOUT, MATERIALS
AND GRADING PLAN
NOTES:
1. THIS PLAN IDENTIFIES SITE ELEMENTS,
CRITICAL DIMENSIONS AND GRADES OF
SIDEWALKS AND PLAZAS.
2. REFER TO CIVIL DRAWING FOR GEOMETRIC
PLANS OF ROADS, PARKING AREAS AND CURB
LINES.
3. REFER TO CIVIL DRAWINGS FOR UTILITY PLANS
AND ADDITIONAL SITE GRADING.
4. REFER TO CIVIL DRAWINGS FOR CONCRETE
WALK, ACCESSIBLE RAMP AND CURB AND
GUTTER DETAILS.
5. COORDINATE THE INSTALLATION OF
CORRUGATED HDPE DRAIN PIPE SHOWN ON
THIS DRAWING WITH THE CIVIL ENGINEERING
GRADING AND DRAINAGE DRAWING.
1/4"
M
I N
4" 4"
CONCRETE FOOTING
COMPACTED SUBGRADE
COMPACTED AGGREGATE
CONCRETE WALK
8"Ø CAST-IN-PLACE
BLACK VINYL COATED
GALVANIZED STEEL; 2 3/8"
O.D. SCHEDULE 40 PIPE
3/8" x 6" STEEL ANCHOR RODS
SUBMIT PRODUCT
LITERATURE FOR REVIEW
AND APPROVAL
1'-11
" 1'-11
" 1'-11
" 1'-11
8'-0"
SLOPE CONCRETESLOPE CONCRETE
ALUMINUM GRATE PANEL WIDTH
BE
AR
IN
G
BA
R
DI
RE
CT
IO
N
3" DRAIN
CONCRETE
WALK
L13 4" x 13
4" x 14" PERIMETER
PANEL SEAT ANGLE
PLAN
1'-10
" 1'-10
" 1'-10
" 1'-10
8'-0"
SLOPE CONCRETESLOPE CONCRETE
ALUMINUM GRATE PANEL WIDTH
BE
AR
IN
G
BA
R
DI
RE
CT
IO
N
3" DRAIN
CONCRETE
WALK
L13 4" x 13
4" x 14" PERIMETER
PANEL SEAT ANGLE
PLAN - TERRAIN AREA ADJACENT TO PAVEMENT EDGE
6"
EDGE OF CONCRETE
LAWN AREA
ALUMINUM BAR GRATING
PLAY SAND
LAWN AREA
1 2
6"
3 4
6" AGGREGATE
FILTER FABRIC
SECTION B-B
2" CHAMFER
CONCRETE
PEA STONE
SLOPE CONCRETE
TO DRAIN
SEAT ANGLE
A
A
A
A
B B
ALUMINUM BAR GRATING
4 " D. x 3'-111
4" L. PANELS
15-SGI-4 AS MANUFACTURED
BY DIRECT METALS, OR APPROVED EQUAL
2" DEEP PLAY SAND OR STONE
24" SQUARE OF FILTER FABRIC
CENTERED OVER DRAIN3" DIA RISER PIPE
6" DIA DRAIN
3" DROP IN GRATE
ADS #0330SDS OR
APPROVED EQUAL
4" CONCRETE WALK
1 2
6"
4'-0"
3'-8"
2"
2"
1 2
AGGREGATE
FILTER FABRIC
2"x11 2"x1
4" 6061T6 ALUMINUM PERIMETER
SEAT ANGLE WITH 3
8"x3" LONG ANCHORS
@ 18" O.C. TYP.
NOTE:
RISER PIPE AND DRAIN PIPE TO BE
SINGLE WALL CORRUGATED HDPE
SOLID WALL TUBING.
SECTION A-A
WASHED PEA STONE
NOTE:
ONE TERRAIN AREA TO HAVE PLAY SAND SURFACE
ONE TERRAIN AREA TO HAVE WASHED STONE SURFACE
WASHED STONE GRADATION TO BE 11
2" TO 3 4".
2"x11 2"x1
4" ALUMINUM
SEAT ANGLE
CONCRETE
ALUMINUM BAR GRATE
ALUMINUM ANCHOR BLOCK
ALUMINUM TREADED INSERT
STAINLESS STEEL BOLT WITH WASHER
4 x 20 UNC x 11
4" LONG (NOTE 2)
NOTES:
1. ALUMINUM ANCHOR BLOCK INSTALLED BY GRATING
MANUFACTURER.
2. COORDINATE BOLT AND TREADED INSERT SIZE WITH
ANCHOR BLOCK.
3. THREADED INSERT TO HAVE KNURLED EXTERIOR
SURFACE.
4. SUPPLY PLASTIC REMOVABLE PLUGS FOR INSERTS. COLOR
TO BE SILVER.
5. FIELD LOCATE, DRILL AND PLACE THREADED
INSERTS. EPOXY THREADED INSERTS INTO CONCRETE.
SECTION AT ANCHOR BLOCK
4" CONCRETE PLAZA PAVEMENT1
SECTION NTS
CONTROL JOINT3
SECTION NTS
EXPANSIONL JOINT4
SECTION NTS
BICYCLE HOOP5
SECTION NTS
FLAG POLE6
SECTION NTS
THICKENED SLAB2
SECTION NTS
ALTERNATE TERRAIN REHABILITATION AREAS7
PLAN AND SECTION NTS
L1.1
SITE DETAILS
x
S
S x
425 HEUCHERA 'ELECTRA'
4 CORNUS FLORIDA 'CHEROKEE BRAVE'
140 CAMPANULA GARGANICA 'DICKSON'S GOLD'
3 CORNUS FLORIDA 'CHEROKEE BRAVE'
540 PACHYSANDRA TERMINALIS
320 THYMUS PRAECOX 'COCCINEUS'
50 DELOSPERMA 'MESA VERDE'
70 DELOSPERMA 'MESA VERDE'
365 CAMPANULA GARGANICA 'DICKSON'S GOLD'
1550 PACHYSANDRA TERMINALIS
9 AMELANCHIER ARBOREA
5 PINUS TAEDA
3 QUERCUS SHUMARDII
2 ULMUS PARVIFOLIA 'DYNASTY'
200 DELOSPERMA 'MESA VERDE'
16 JUNIPERUS CHINENSIS 'SEA GREEN'
105 NEPETA X FAASSENII 'WALKER'S LOW'
185 HEMEROCALLIS 'HAPPY RETURNS'
135 HEMEROCALLIS 'HAPPY RETURNS'
4 QUERCUS PHELLOS
2 ULMUS PARVIFOLIA 'DYNASTY'
4 QUERCUS PHELLOS
4 ULMUS PARVIFOLIA 'DYNASTY'
1 MAGNOLIA GRANDIFLORA
3 PINUS TAEDA
2 MAGNOLIA GRANDIFLORA
1 QUERCUS SHUMARDII
205 DELOSPERMA
'MESA VERDE'
LAWN
LAWN
LAWN
LAWN (ALL PARKING
LOT ISLANDS EXCEPT
AS SHOWN)
LAWN (ALL PARKING LOT
ISLANDS EXCEPT AS SHOWN)
275 DELOSPERMA 'MESA
VERDE'
30 HEMEROCALLIS 'RUBY
STELLA'
12 CORNUS KOUSA
'GREENSLEEVES'
METAL EDGING TYP.
METAL EDGING TYP.
METAL EDGING TYP.
18" UNPLANTED MULCH
BORDER BACK OF CURB
82 HEMEROCALLIS 'HAPPY RETURNS'
72 NEPETA X FAASSENII 'WALKER'S LOW'
120 CAMPANULA GARGANICA
'DICKSON'S GOLD'
155 HEUCHERA 'ELECTRA'
MAINTENANCE
EDGE, TYP
METAL
EDGING
MAINTENANCE
EDGE, TYP
METAL
EDGING
[Drawing Title Text]
[A0.0]
DD
L2.0
PLANTING PLAN
PLANT LIST:
NOTES:
1. THE CONTRACTOR IS RESPONSIBLE FOR INDEPENDENTLY DETERMINING THE PLANT MATERIAL QUANTITIES
REQUIRED BY THE PLANS.
2. NO PLANT SHALL BE INSTALLED BEFORE ROUGH GRADING AND THE ADDITION OF TOPSOIL HAS BEEN
FINISHED AND APPROVED BY THE OWNER'S REPRESENTATIVE.
3. THE LAYOUT OF ALL PLANTING BEDS, TREES, AND SHRUBS SHALL BE STAKED BY THE CONTRACTOR PRIOR
TO ANY PLANT INSTALLATION FOR REVIEW BY THE OWNER'S REPRESENTATIVE. INTERNAL BED LAYOUT
SHALL ALSO INCLUDE PERENNIAL GROUPINGS BY SPECIES. FLAGGING, STAKES, OR PAINT MAY BE USED
TO DELINEATE LOCATIONS AS SCALED FROM THE PLANS. THE OWNER'S REPRESENTATIVE WILL REVIEW
THESE LOCATIONS WITH THE CONTRACTOR BEFORE ANY PLANTS ARE INSTALLED AND MAKE MINOR
ADJUSTMENTS AS NECESSARY. SUCH ADJUSTMENTS SHALL BE AT NO ADDITIONAL COST TO THE OWNER.
4. SPACING OF PLANT MATERIALS SHALL BE AS SHOWN ON PLANS AND AS INDICATED IN PLANT LISTS. THE
OWNER'S REPRESENTATIVE SHALL REVIEW THE PLACEMENT OF PLANT MATERIAL AFTER INSTALLATION, AND RESERVES THE RIGHT TO ADJUST LAYOUT TO ACCOMMODATE SITE CONDITIONS AND DESIGN INTENT.
5. ALL PLANT MATERIALS SHALL CONFORM TO PLANT SCHEDULES. SIZES SHALL BE THE MINIMUM STATED ON
THE PLANT LIST OR LARGER. ALL MEASUREMENTS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION
OF THE A.A.N. "STANDARDS FOR NURSERY STOCK".
6. ALL AREAS DISTURBED DURING CONSTRUCTION ARE TO RECEIVE 4" MINIMUM TOPSOIL AND SOD UNLESS
NOTED FOR OTHER PLANT MATERIAL INSTALLATION ON THE PLAN.
7. PROVIDE 4" MINIMUM TOPSOIL FOR ALL SODDED AREAS.
8. ALL PLANTING BED AREAS SHALL RECEIVE A MINIMUM 12" DEPTH OF TOPSOIL.
9. ALL PARKING LOT ISLANDS AND LANDSCAPE BEDS SHALL BE CROWNED TO DRAIN. FLAT BEDS WILL NOT BE
PERMITTED. FINAL GRADE AFTER COMPACTION SHALL BE NO LOWER THAN 1" FROM TOP OF CURB.
10. INSTALL CONTINUOUS METAL EDGING TO SEPARATE ALL PLANT BEDS FROM LAWN.
11. CONTRACTOR SHALL CONFIRM THAT TREE PITS DO NOT HOLD WATER FOR A TIME PERIOD LONGER THAN
12 HOURS. CONTRACTOR SHALL CONTACT OWNER'S REPRESENTATIVE PRIOR TO PLANTING TREES IF
TREE PITS HOLD WATER LONGER THAN SPECIFIED PERIOD FOR FURTHER DIRECTION.
12. TREES SHALL HAVE CLEAR, SINGLE, UNBROKEN CENTRAL LEADERS. TREES WITHOUT SINGLE CENTRAL
LEADERS WILL BE REJECTED.
13. THE CONTRACTOR SHALL LOCATE AND VERIFY THE EXISTENCE OF ALL UTILITIES PRIOR TO STARTING
WORK.
14. ALL DEBRIS ASSOCIATED WITH PLANTING SHALL BE LEGALLY DISPOSED. CONTRACTOR IS RESPONSIBLE
FOR DISPOSAL.
NOTE:
NEVER CUT CENTRAL LEADERS. PRUNE ONLY TO REMOVE DEAD OR BROKEN BRANCHES.
UP TO 6' TALL
6' - 12' TALL
> 12' TALL
SCHEDULES
SIZE
DOUBLE STAKE
TRIPLE STAKE
TRIPLE GUY
STAKING / GUYING
4' MIN. OR 2' WIDER THAN TREE CANOPY AT GROUND LEVEL
5' MIN. OR 2' WIDER THAN TREE CANOPY AT GROUND LEVEL
8' MIN. OR 2' WIDER THAN TREE CANOPY AT GROUND LEVEL
MULCH SAUCER DIMENSION
TOP OF STAKES AND GUYS
TO BE SET 1/2 TO 2/3 UP TREE
SET STAKES VERTICAL AND AT
SAME HEIGHT
GUYING CABLE 3 GUYS
PER TREE
TURNBUCKLE
REMOVE BURLAP FROM
TOP 1/3 OF BALL
2" OF MULCH
MOUND TO FORM SAUCER
UNDISTURBED GROUND
PLANTING BACKFILL
AS SPECIFIED
SCARIFY TO 4" DEPTH
AND RECOMPACT
STAKES TO EXTEND 12"
BELOW TREE PIT IN
UNDISTURBED GROUND
GUYS
BETWEEN
ANGLE 30°- 45°
12" MIN.
TOP OF STAKES AND GUYS TO BE
SET ABOVE FIRST BRANCHES
GUYING CABLE, 3 GUYS
PER TREE
REMOVE BURLAP FROM TOP
1/3 OF BALL
STAKES TO EXTEND 12" BELOW
TREE PIT IN UNDISTURBED GROUND
COMPACTED PLANTING BACKFILL
LEVELING COURSE DEPTH AS REQUIRED
SCARIFY SIDES OF TREE PIT
PLANTING BACKFILL AS SPECIFIED
2x4 WOOD OR #3/LF METAL
FENCE POST ANCHOR STAKE
DRIVEN BELOW FINISH GRADE
MIN. LENGTH TO BE 24"
NOTES:
GUY ALL TREES 4" CAL. AND OVER. TRIPLE
STAKE TREES BETWEEN 2" AND 4" CAL. SET
STAKES VERTICAL AND AT SAME HEIGHT.
NEWER CUT CENTRAL LEADERS PRUNE
ONLY TO THIN CANOPY AND REMOVE DEAD
OR DAMAGED BRANCHES.
SET CROWN OF BALL AT FINISH GRADE
2" DEEP COMPOSTED BARK MULCH
DO NOT PLACE MULCH AGAINST
COLLAR OF TREE
MOUND PLANTING BACKFILL
TO FORM SAUCER AROUND
PLANT PIT. SET SAUCER
OUTSIDE OF GUY STAKES
12" MIN. FOR UP TO 3" CAL.
18" MIN. FOR 3" CAL. & LARGER
30°- 45°
MULCH SAUCER DIMENSION -
SEE SCHEDULE
2" CAL. & SMALLER
BETWEEN 2.5" & 3.5" CAL.
4" CAL. - 6" CAL.
SCHEDULES
SIZE
DOUBLE STAKE
TRIPLE STAKE
TRIPLE GUY
STAKING / GUYING
4' DIA.
5' DIA.
MIN. 8' DIA.- EXTEND OUTSIDE DIAMETER
TO INCLUDE GUYING STAKES
MULCH SAUCER DIMENSION
TURNBUCKLE
TREE WRAP
UNDISTURBED GROUND
NOTES:
NEVER CUT CENTRAL LEADERS. PRUNE ONLY TO THIN AND REMOVE DEAD, AND DAMAGED BRANCHES. SET
TREE STAKES VERTICAL AND AT SAME HEIGHT.
UP TO 2" CAL.
2" CAL. AND LARGER
SCHEDULES
SIZE
DOUBLE STAKE
TRIPLE STAKE
STAKING
4' DIA.
5' DIA.
MULCH SAUCER DIMENSION
STAKE TREE ABOVE FIRST
BRANCHES, MIN. 1/2 UP TREE
TREE WRAP
2" OF MULCH
MOUND TO FORM SAUCER
REMOVE BURLAP FROM
TOP 1/3 OF BALL
PLANTING BACKFILL
AS SPECIFIED
SCARIFY TO 4" DEPTH
AND RECOMPACT
STAKES TO EXTEND 12" BELOW
TREE PIT IN UNDISTURBED
GROUND
12" MIN.
STAKING/GUYING LOCATION PLAN
STAKING DETAILGUYING CABLE DETAIL PLAN
NOTES:
ORIENT STAKING/GUYING TO PREVAILING WINDS AND SLOPES,
EXCEPT ON SLOPES GREATER THAN 3:1 ORIENT TO SLOPE.
USE SAME STAKING/GUYING ORIENTATION FOR ALL PLANTS
WITHIN EACH GROUPING OR AREA.
NOTE TO SPECIFIER:
INCLUDE THIS DETAIL WITH ALL TREE STAKING DETAILS
DELETE NON-APPLICABLE INFORMATION
1/2" DIA. RUBBER HOSE
CHAFING GUARD 2-PLY,
COLOR BLACK
3/16"- SEVEN STRAND
GUYING CABLE SECURED
W/CLAMPS
TURNBUCKLE
WITH 6" OPENING
1/2" DIA. RUBBER HOSE
CHAFING GUARD 2-PLY,
COLOR BLACK
DOUBLE STRAND
#14 GAUGE GALV.
WIRE, NEATLY TWISTED
NOTCH POSTS TO
SET STAKE WIRE
STAKES AS SPECIFIED
3 PER TREE
NOTE:
CONTAINER PLANTS: REMOVE POTS AND
SEPERATE POT BOUND ROOTS AS
SPECIFIED.
2" DEEP COMPOSTED
BARK MULCH
SPACING AS SHOWN
PLANTING BACKFILL
AS SPECIFIED
SUBGRADE
ON PLANS AND ON
PLANT LIST
1'- 0"
M
IN
NOTES:
REMOVE BURLAP FROM TOP 1/3 OF BALL,
OR, WITH CONTAINER PLANTS, REMOVE
POTS AND SEPERATE POT BOUND ROOTS
AS SPECIFIED.
DO NOT PRUNE EVERGREEN SHRUB
EXCEPT TO REMOVE DEAD OR BROKEN
BRANCHES
SET CROWN OF BALL
AT FINISHED GRADE
2" DEEP COMPACTED
BARK MULCH. LIMITS SHALL
BE AS SHOWN ON PLANS
PLANTING BACKFILL
AS SPECIFIED.
SCARIFY SIDES OF
PLANT PIT.
COMPACTED PLANTING BACKFILL
LEVELING COURSE. DEPTH AS
REQUIRED
SUBGRADE
BALLED AND BURLAPPED
SHRUBS
BARE ROOT OR
CONTAINER SHRUBS
1'- 0"
M
IN
SPACING AS SHOWN ON PLANS
AND ON PLANT LIST
D=DIMENSION OF PLANT SPACING (SHRUB, GROUNDCOVER OR PERENNIAL)
AS INDICATED ON PLANS.
"D"
"D" "D"
SECTION
ELEVATION
NOTE TO SPECIFIER:
REVIEW WITH CLIENT THE COLOR & TYPE OF EDGING TO BE USED
EDGING NEEDS TO BE SPECIFIED UNDER SECTION 02930 , AND IS CURRENTLY AND INCORRECTLY SPECIFIED
UNDER SECTION 02870 - SITE FURNISHINGS
THE TERM METAL IS GENERIC FOR STEEL OR ALUMINUM. SPECIFY THE DESIRED FINISH, COLOR, MATERIAL, THICKNESS AND HEIGHT.
FLUSH OVERLAP JOINT ASSEMBLY
METAL EDGING AS SPECIFIED
VA
RI
ES
PUNCHED SLOTS
METAL STAKES
GROUNDCOVER
FINISHED GRADE
LAWN OR STONE MULCH
METAL EDGING
PLANTING BACKFILL
AS SPECIFIED
SUBGRADE
METAL STAKES - SET
ON INSIDE EDGE OF
PLANT BED
2" DEEP MULCH TO
BE FLUSH WITH TOP
OF EDGING
1" MAX.
VARIES
SEE LAYOUT PLAN
TOPSOIL
SUBGRADE
STAKES
BUILDING FACE
LAWN
METAL EDGING
FILTER FABRIC
FINISHED GRADE
DECIDUOUS TREE PLANTING1
SECTION NTS
EVERGREEN TREE PLANTING2
SECTION NTS
FLOWERING TREE PLANTING - SINGLE STEM3
SECTION NTS
TREE STAKING AND GUYING - SINGLE STEM4
NTS
SHRUB PLANITNG - BED5
SECTION NTS
GROUNDCOVER / PERENNIAL PLANTING6
SECTION NTS
TYPICAL PLANT SPACINIG7
PLAN NTS
METAL LANDSCAPE EDGING8
ELEVATION / SECTION NTS
MAINTENANCE EDGE9
\ ELEVATION / SECTION NTS
L2.1
PLANTING DETAILS
GENERAL STRUCTURAL AND CONSTRUCTION NOTES
THESE NOTES SUPPLEMENT THE SPECIFICATIONS, WHICH SHALL BE REFERRED TO
FOR ADDITIONAL REQUIREMENTS.
A. CODES AND STANDARDS
1. THE FOLLOWING CODES AND STANDARDS, INCLUDING ALL SPECIFICATIONS
REFERENCED WITHIN, SHALL APPLY TO ALL WORK PERFORMED ON THE PROJECT.
USE THE LATEST EDITIONS UNLESS NOTED OTHERWISE.
a. "THE INTERNATIONAL BUILDING CODE - 2009", INTERNATIONAL CODE COUNCIL.
b. "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES" (ASCE 7), AMERICAN SOCIETY OF CIVIL ENGINEERS.
c. "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, ACI 318", AMERICAN CONCRETE INSTITUTE.
d. “STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIALS”, ACI 117, AMERICAN CONCRETE INSTITUTE.
e. “SPECIFICATIONS FOR STRUCTURAL CONCRETE, ACI 301”, AMERICAN
CONCRETE INSTITUTE.
f. “STANDARD SPECIFICATION FOR COLD WEATHER CONCRETING, ACI 306.1”, AMERICAN CONCRETE INSTITUTE.
g. "MANUAL OF STANDARD PRACTICE", CONCRETE REINFORCING STEEL INSTITUTE.
h. "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530/ASCE
5/TMS 402)", AMERICAN CONCRETE INSTITUTE, AMERICAN SOCIETY OF CIVIL
ENGINEERS, AND THE MASONRY SOCIETY.
i. "SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1/ASCE 6/TMS 602)", AMERICAN CONCRETE INSTITUTE, AMERICAN SOCIETY OF CIVIL ENGINEERS, AND
THE MASONRY SOCIETY.
j. "STEEL CONSTRUCTION MANUAL", THIRTEENTH EDITION, 2005, AMERICAN
INSTITUTE OF STEEL CONSTRUCTION INCLUDING ANSI/AISC 360-05
SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, SPECIFICATION FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, AND AISC 303-05 CODE
OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES.
k. "DETAILING FOR STEEL CONSTRUCTION", AMERICAN INSTITUTE OF STEEL
CONSTRUCTION.
l. "STRUCTURAL WELDING CODE ANSI/AWS D1.1" AMERICAN WELDING SOCIETY.
m. "STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-SERIES", STEEL
JOIST INSTITUTE.
n. "DESIGN MANUAL FOR FLOOR DECKS AND ROOF DECKS", STEEL DECK
INSTITUTE.
o. UFC 1-200-01 "GENERAL BUILDING REQUIREMENTS"
p. UFC 3-310-01 "STRUCTURAL LOAD DATA"
q. UFC 3-310-02A "STRUCTURAL DESIGN CRITERIA FOR BUILDINGS"
r. UFC 4-010-01 "DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS"
B. DESIGN DATA
1. GRAVITY - SUPERIMPOSED DEAD LOADS
C. FOUNDATIONS / GEOTECHNICAL REPORT
1. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE
RECOMMENDATIONS INCLUDED IN THE GEOTECHNICAL REPORT PREPARED BY
FROEHLING & ROBERTSON, INC., DATED APRIL 24, 2012, PROJECT NO. 66N-0204. SEE
THAT REPORT FOR ADDITIONAL RECOMMENDATIONS.
2. TREATED TIMBER PILES: 20 TON CAPACITY WITH AN 8 INCH MINIMUM TIP
DIAMETER.
3. MAXIMUM ALLOWABLE TENSION LOAD USED IN DESIGN FOR PILES: 14 KIPS.
D. MATERIALS
THE FOLLOWING ASTM STANDARDS AND DESIGN STRESSES SHALL BE USED FOR
THE APPROPRIATE MATERIALS USED IN THE CONSTRUCTION OF THIS PROJECT.
1. CEMENT:
ASTM C150; TYPE I OR III
ASTM C150; TYPE II FOR CONCRETE IN CONTACT WITH EARTH
2. BLENDED HYDRAULIC CEMENT (CEMENT SUBSTITUTES):
ASTM C595, TYPE IS (LIMIT TO 35% MAX OF CEMENTITIOUS
CONTENT BY WEIGHT)
3. AGGREGATES:
ASTM C33 (NORMAL WEIGHT)
4. ADMIXTURES:
AIR ENTRAINING ADMIXTURES ASTM C260
CHEMICAL ADMIXTURES ASTM C494
5. CONCRETE:
a. CONCRETE MIXES SHALL BE DESIGNED BASED ON THE MINIMUM 28-DAY
COMPRESSIVE STRENGTH (f’c), MAXIMUM WATER-CEMENT (W/C) RATIO, EXPOSURE CATEGORY, AND AIR ENTRAINMENT REQUIREMENTS OF THE
“CONCRETE MIX DESIGN TABLE”, DETAIL 1/S1.1.
b. CONCRETE SHALL BE NORMAL WEIGHT UNLESS SPECIFIED OTHERWISE.
NORMAL WEIGHT CONCRETE SHALL HAVE A UNIT WEIGHT OF 145 PCF ± 5 PCF.
6. REINFORCEMENT:
DEFORMED REINFORCING BARS ASTM A615, GRADE 60
WELDED WIRE REINFORCEMENT (WWF) ASTM A185
ADHESIVE REINFORCING BAR HILTI HIT HY-150 MAX
DOWELING SYSTEMS SYSTEM OR EQUAL
7. MASONRY
a. LOAD BEARING CONCRETE MASONRY UNITS: LIGHTWEIGHT, HOLLOW ASTM
C90. MINIMUM COMPRESSIVE STRENGTH OF CONCRETE MASONRY UNITS =
1900 PSI. MINIMUM COMPRESSIVE STRENGTH ON NET AREA = 1500 PSI.
b. MORTAR: ASTM C270 - TYPE M (BELOW GRADE) / TYPE S (ABOVE GRADE)
e. GROUT: ASTM C476; MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS = 2000 PSI
f. HORIZONTAL JOINT REINFORCING: ASTM A951; 9 GAGE LADDUR-TYPE
GALVANIZED REINFORCEMENT
9. STEEL
WIDE FLANGE SHAPES AND TEES ASTM A992
SQUARE OR RECTANGULAR HOLLOW ASTM A500, GRADE B, FY=46 KSI
STRUCTURAL SHAPES
BASE PLATES AND RIGID FRAME ASTM A572, GRADE 50
CONTINUITY PLATES
OTHER STRUCTURAL SHAPES AND ASTM A36
PLATES
HIGH STRENGTH BOLTS ASTM A325-N OR ASTM F1852
ANCHOR RODS ASTM F1554, GRADE 36
WELDING ELECTRODES AWS A5.1 OR A5.5, E70XX WITH MIN. CVN
TOUGHNESS OF 20 FT-LBF AT 20%%D F
EXPANSION BOLTS ITW RAMSET/REDHEAD TRU-BOLT WEDGE
ANCHOR, HILTI KWIK-BOLT III OR APPROVED
EQUAL
ADHESIVE ANCHORING SYSTEM ITW RAMSET/REDHEAD EPCON SYSTEM,
HILTI HVA OR HIT HY-150 MAX SYSTEM
GALVANIZED STEEL ROOF DECK ASTM A653 SS, GRADE 33, G-90
GROUT ASTM C1107, NON-SHRINK, NON-METALLIC
F'c = 5000 PSI
E. CONSTRUCTION
1. GENERAL
a. DO NOT SCALE DRAWINGS.
b. THESE DRAWINGS REPRESENT THE COMPLETED PROJECT WHICH HAS BEEN
DESIGNED FOR THE WEIGHTS OF THE MATERIALS INDICATED ON THE DRAWINGS
AND FOR THE SUPERIMPOSED LOADS INDICATED IN THE DESIGN DATA. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO DETERMINE ALLOWABLE CONSTRUCTION
LOADS AND PROVIDE PROPER DESIGN AND CONSTRUCTION OF FALSEWORK,
FORMWORK, STAGINGS, BRACING, SHEETING AND SHORING, ETC. CONTRACTOR
HAS SOLE RESPONSIBILITY FOR MEANS AND METHODS, SEQUENCES AND
PROCEDURES OF CONSTRUCTION. THE STRUCTURE IS STABLE ONLY IN ITS
COMPLETED FORM.
c. IMPLEMENTING JOB SITE SAFETY AND CONSTRUCTION PROCEDURES IS SOLELY
THE RESPONSIBILITY OF THE CONTRACTOR.
d. STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR THE DESIGN
OF SYSTEMS NOT SHOWN ON THE STRUCTURAL DOCUMENTS, INCLUDING BUT
NOT LIMITED TO STEEL STAIRS, HANDRAILS, CURTAINWALL/WINDOW WALL
SYSTEMS, OR COLD-FORMED METAL FRAMING. SUCH SYSTEMS SHALL BE
DESIGNED, FURNISHED, AND INSTALLED BY OTHERS. REVIEW OF SHOP
DRAWINGS FOR SUCH SYSTEMS BY THE STRUCTURAL ENGINEER OF RECORD
SHALL BE FOR GENERALCONFORMANCE WITH THE PROJECT PARAMETERS AS
INDICATED ON THE DRAWINGS AND IN THE GENERAL NOTES.
e. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND CIVIL
DRAWINGS FOR SIZE AND LOCATIONS OF OPENINGS, SLEEVES, CONCRETE
HOUSEKEEPING PADS, INSERTS, EMBEDS, CURBS, RAMPS, DRAINS, DEPRESSIONS,
ETC. NOTIFY STRUCTURAL ENGINEER OF ANY DISCREPANCIES. REFER TO ARCHITECTURAL
DRAWINGS FOR DIMENSIONS NOT SHOWN.
f. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILED
INFORMATION REGARDING FINISHES, FIREPROOFING, WATERPROOFING, ETC.
g. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF MASONRY AND
DRYWALL NON-LOAD BEARING PARTITIONS, INCLUDING BUILDING EXTERIOR
WALLS. PROVIDE SLIP CONNECTIONS THAT ALLOW VERTICAL MOVEMENT AT THE
HEADS OF SUCH PARTITIONS. DESIGN CONNECTIONS TO SUPPORT THE TOP OF
THE WALLS LATERALLY FOR THE CODE-REQUIRED LATERAL LOAD. PROVIDE
COMPRESSIBLE FIRESAFING AT TOP OF WALL IN ACCORDANCE WITH
ARCHITECTURAL DRAWINGS.
h. IN CASE OF CONFLICT WITHIN THE CONTRACT DOCUMENTS, INCLUDING
DRAWINGS AND SPECIFICATIONS, THE MOST RIGID REQUIREMENTS GOVERN.
i. REPRODUCTION OF ANY PORTION OF THE STRUCTURAL CONTRACT DRAWINGS
FOR RESUBMITTAL AS SHOP DRAWINGS IS PROHIBITED. SHOP DRAWINGS
PRODUCED IN SUCH A MANNER WILL BE REJECTED AND RETURNED.
2. GRAVITY - FLOOR LIVE LOADS
LIVE LOADS ON FOUNDATIONS, COLUMNS, BEAMS, ETC. ARE REDUCIBLE IN
ACCORDANCE WITH THE BUILDING CODE. UNREDUCIBLE LOADS ARE FOLLOWED
BY [U].
j. SUBMIT DIMENSIONED SHOP DRAWINGS AT ALL LEVELS LOCATING FLOOR AND
ROOF EDGES, SLEEVES, AND OPENINGS REQUIRED BY ALL TRADES FOR REVIEW
BY THE ARCHITECT AND STRUCTURAL ENGINEER OF RECORD PRIOR TO
EXECUTION OF WORK. ADDITIONAL OPENINGS NOT SHOWN ON SHOP DRAWINGS
WILL REQUIRE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD.
k. PAY ALL COSTS, INCLUDING INVESTIGATION AND/OR REDESIGN, DUE TO
CONTRACTOR MISLOCATION OF STRUCTURAL ELEMENTS OR OTHER LACK OF
CONFORMANCE WITH THE CONTRACT DOCUMENTS TO BRING WORK IN
COMPLIANCE WITH THE CONTRACT DOCUMENTS.
2. INSPECTION AND TESTING
a. THE OWNER WILL ENGAGE AN APPROVED TESTING AGENCY TO PROVIDE
SERVICES AS INDICATED IN THE PROJECT SPECIFICATIONS. SUBMIT REPORTS TO
THE STRUCTURAL ENGINEER OF RECORD AND CODE OFFICIAL (AS APPLICABLE).
F. FOUNDATIONS & STRUCTURAL EARTHWORK
1. GENERAL
a. REFER TO PROJECT SPECIFICATIONS AND GEOTECHNICAL REPORT
RECOMMENDATIONS FOR EXCAVATION AND PREPARATION OF THE FOUNDATION
AND SLAB-ON-GRADE SUBGRADES, INCLUDING COMPACTION PROCEDURES.
RECOMMENDATIONS CONTAINED IN THE GEOTECHNICAL REPORT ARE PART OF
THIS WORK.
b. VERIFY ALL EXISTING FIELD CONDITIONS THAT MAY AFFECT THE INSTALLATION
OF THE FOUNDATION SYSTEM AS SHOWN PRIOR TO STARTING WORK.
c. FIELD VERIFY SIZE, LOCATION, AND DEPTH OF EXISTING UTILITIES SHOWN ON
THE CIVIL DRAWINGS.
d. REFER TO PLUMBING DRAWINGS FOR PERIMETER DRAIN AND UNDERFLOOR
DRAINAGE SYSTEM.
e. DO NOT PLACE UTILITY LINES THROUGH OR BELOW FOUNDATIONS UNLESS
SHOWN OTHERWISE ON THE STRUCTURAL DRAWINGS.
f. BEAR ALL FOUNDATIONS ON UNDISTURBED SOIL OR COMPACTED STRUCTURAL
FILL. BEARING ELEVATIONS ARE ESTIMATED FROM SOIL BORING DATA INDICATED
IN THE GEOTECHNICAL REPORT. DETERMINATION OF FINAL BEARING ELEVATIONS
AND FIELD VERFICATION OF ALLOWABLE BEARING PRESSURE SHALL BE MADE BY
AN EXPERIENCED, QUALIFIED GEOTECHNICAL ENGINEER PRIOR TO PLACING
FOUNDATIONS. NOTIFY STRUCTURAL ENGINEER OF RECORD WHEN ADDITIONAL
EXCAVATION IS REQUIRED TO REACH SUITABLE BEARING MATERIAL.
g. BEAR FOUNDATIONS A MINIMUM OF 12 INCHES BELOW GRADE UNLESS
OTHERWISE INDICATED. IN CASE OF CONFLICT, NOTIFY THE ARCHITECT AND
STRUCTURAL ENGINEER OF RECORD IN ADVANCE OF ANY CONSTRUCTION TO
ALLOW FOR ADJUSTMENT.
h. DO NOT USE EARTH CUTS AS FORMS FOR VERTICAL SURFACES.
i. PLACE CONCRETE FOR FOUNDATIONS OR MUD SLABS ON THE SAME DAY
SUBGRADE APPROVAL IS GIVEN BY THE GEOTECHNICAL ENGINEER.
j. PROTECT CONCRETE FOUNDATIONS FROM FREEZING DURING PLACING AND
FOR A PERIOD OF NOT LESS THAN 5 DAYS THEREAFTER.
2. DRIVEN PILES
a. PERFORM PILE LOAD TESTS IN ACCORDANCE WITH PROJECT SPECIFICATIONS
AND ASTM D1143.
b. PRE-AUGER PILES WHEN SPECIFIED OR RECOMMENDED BY THE
GEOTECHNICAL ENGINEER TO REDUCE VIBRATIONS. DRIVE PILES TO
COMPLETION IMMEDIATELY AFTER PRE-AUGERING OF EACH PILE LOCATION, AND
PRIOR TO ANY FURTHER PRE-AUGERING.
c. SUBMIT AS-BUILT PILE LOCATION PLAN AND ELEVATION DATA WITHIN THREE
DAYS OF DRIVING. REPORT ANY DEVIATION IN PILE LOCATIONS OR ELEVATIONS
THAT EXCEEDS STANDARD TOLERANCES IMMEDIATELY TO THE STRUCTURAL
ENGINEER OF RECORD. ALL RE-DESIGN COSTS DUE TO PILE MISLOCATION SHALL
BE AT THE CONTRACTOR'S EXPENSE.
3. BACKFILL:
a. USE BACKFILL MATERIAL CONSISTING OF BANK RUN GRAVEL, CRUSHED STONE
AND/OR MATERIAL APPROVED BY THE GEOTECHNICAL ENGINEER, WITH OPTIMUM
MOISTURE CONTENT FOR COMPACTING AND FREE OF ANY DEBRIS.
b. WHERE THE FINAL GRADE ELEVATIONS ARE APPROXIMATELY EQUAL ON BOTH
SIDES OF A WALL, BACKFILL IN LIFTS TO MAINTAIN LEVEL ELEVATIONS WITHIN
12-INCHES ON BOTH SIDES AT ANY TIME TO PREVENT LATERAL MOVEMENT
AND/OR OVERTURNING.
4. STRUCTURAL FILL:
a. THE FOUNDATION SYSTEM AS SHOWN REQUIRES THE PLACEMENT OF
STRUCTURAL FILL ON PORTIONS OF THE SITE. REFER TO SPECIFICATIONS AND
GEOTECHNICAL REPORT RECOMMENDATIONS FOR COMPACTED STRUCTURAL
FILL. LOCATION AND EXTENT OF AREAS TO RECEIVE STRUCTURAL FILL SHALL BE
PER THE GEOTECHNICAL REPORT UNLESS OTHERWISE DIRECTED BY A QUALIFIED
GEOTECHNICAL ENGINEER.
b. INSPECTION OF THE PLACEMENT OF COMPACTED STRUCTURAL FILL SHALL BE
BY AN EXPERIENCED, QUALIFIED GEOTECHNICAL ENGINEER.
G. CONCRETE
1. CAST-IN-PLACE:
a. COMPLY WITH REQUIREMENTS OF "SPECIFICATIONS FOR STRUCTURAL
CONCRETE" (ACI 301) EXCEPT AS MODIFIED BY THESE NOTES AND
PROJECT SPECIFICATIONS.
b. PROVIDE MINIMUM CLEAR COVER FOR REINFORCING AS FOLLOWS UNLESS
OTHERWISE NOTED:
CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH 3"
CONCRETE EXPOSED TO EARTH AND WEATHER:
#6 BARS AND LARGER 2"
#5 BARS AND SMALLER 1½”
CONCRETE NOT EXPOSED TO WEATHER OR IN
CONTACT WITH GROUND:
SHEAR WALL VERTICAL BARS 1½”
SLABS, WALLS, JOISTS
#11 BARS AND SMALLER ¾”
BEAMS, COLUMNS:
PRIMARY REINFORCEMENT, TIES,
STIRRUPS, SPIRALS 1½”
c. SPLICE REINFORCEMENT AS DETAILED. MAKE BARS CONTINUOUS AROUND
CORNERS. SPLICES SHALL BE MADE BY CONTACT TENSION LAP SPLICES, UNLESS
OTHERWISE NOTED.
d. WELDING OF REINFORCING IS NOT PERMITTED UNLESS OTHERWISE NOTED.
e. FIELD BENDING OF REINFORCING PARTIALLY EMBEDDED IN CONCRETE IS NOT
PERMITTED UNLESS OTHERWISE NOTED.
f. FURNISH ALL ACCESSORIES, CHAIRS, SPACE BARS, SUPPORTS, ETC.
NECESSARY TO SECURE REINFORCING.
g. PROVIDE PLASTIC TIPPED BOLSTERS AND CHAIRS AT ALL LOCATIONS WHERE
THE CONCRETE SURFACE IN CONTACT WITH THE BOLSTERS OR CHAIRS IS
EXPOSED.
3. GRAVITY - ROOF LIVE LOADS
ROOF LIVE LOAD - 30 PSF MINIMUM (PONDING OR SNOW LOAD IS USED WHEN
GREATER THAN 30 PSF).
SNOW LOADS:
GROUND SNOW LOAD, Pg: 10 PSF
SNOW EXPOSURE FACTOR, Ce: 1.0
SNOW LOAD IMPORTANCE FACTOR, Is: 1.0
THERMAL FACTOR, Ct: 1.0
FLAT ROOF SNOW LOAD, Pf: 0.7CeCtIPg = 7 PSF PLUS UNBALANCED, DRIFTING AND SLIDING SNOW WHERE APPLICABLE.
4. WIND LOADS
a. MAIN WIND FORCE RESISTING SYSTEM
BASIC WIND SPEED (3 SECOND GUST): 130 MPH
SITE EXPOSURE CATEGORY: C
WIND IMPORTANCE FACTOR, Iw: 1.0
INTERNAL PRESSURE COEFFICIENT: +/- 0.18
b. ROOF OVERHANGS: COMPLY WITH SECTION 6.5.11.4 OF ASCE 7
5. SEISMIC LOADS
a. STRUCTURAL DESIGN REQUIREMENTS
SEISMIC IMPORTANCE FACTOR, Ie: 1.0
OCCUPANCY CATEGORY: II
MAPPED SHORT PERIOD SPECTRAL RESPONSE ACCELERATION, Ss: 0.21
MAPPED 1-SECOND PERIOD SPECTRAL RESPONSE ACCELERATION, S1: 0.08
SHORT PERIOD DESIGN SPECTRAL RESPONSE COEFFICIENT, Sds: 0.35
1-SECOND PERIOD DESIGN SPECTRAL RESPONSE COEFFICIENT, Sd1: 0.187
SOIL SITE CLASS: E
SEISMIC DESIGN CATEGORY: C
BASIC SEISMIC FORCE RESISTING SYSTEM: STEEL SYSTEMS NOT SPECIFICALLY
DESIGNED FOR SEISMIC RESISTANCE
RESPONSE MODIFICATION FACTOR, R:3
SEISMIC RESPONSE COEFFICIENT, Cs: 0.117
DESIGN BASE SHEAR: 106 KIPS
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
b. ARCHITECTURAL, MECHANICAL AND ELECTRICAL COMPONENTS AND SYSTEMS:
DESIGN COMPLETE SYSTEM IN ACCORDANCE WITH CHAPTER 13 OF ASCE 7 AND
ABOVE INFORMATION.
h. PLACE SLAB-ON-GRADE ON A VAPOR RETARDER OR VAPOR BARRIER OVER A
MINIMUM 4” LAYER OF CLEAN, WELL-GRADED GRAVEL OR CRUSHED STONE
OVER COMPACTED SUBGRADE, UNLESS OTHERWISE NOTED. REINFORCE WITH
6X6 W2.0Xw2.0 WELDED WIRE REINFORCEMENT, UNLESS OTHERWISE NOTED.
i. PROVIDE ADDITIONAL BARS AT RE-ENTRANT CORNERS AND AROUND ALL WALL
AND SLAB OPENINGS AS INDICATED IN DETAILS. PROVIDE A MINIMUM OF
2#5 x 6’-0” AT EACH CORNER.
j. CAST IN PLACE INSERTS AND SLEEVES WHENEVER FEASIBLE.
k. PLACING SLEEVES THROUGH CONCRETE ELEMENTS IS NOT PERMITTED
UNLESS SHOWN ON THE STRUCTURAL DRAWINGS OR APPROVED SLEEVING SHOP
DRAWINGS, OR AUTHORIZED IN WRITING BY THE STRUCTURAL ENGINEER OF
RECORD.
l. LOCATE CONSTRUCTION JOINTS AS NOT TO IMPAIR THE STRENGTH OF THE
STRUCTURE.
m. LOCATE CONSTRUCTION JOINTS FOR MILD-REINFORCED CONCRETE WITHIN
THE MIDDLE THIRD OF THE SPANS OF SLABS AND GRADE BEAMS. SUBMIT
SHOP DRAWINGS INDICATING PROPOSED JOINT LOCATIONS. MAKE STOPS IN
CONCRETE PLACEMENT WITH VERTICAL BULKHEADS AND HORIZONTAL KEYS,
UNLESS OTHERWISE SHOWN. ALL REINFORCING TO BE CONTINUOUS THROUGH JOINTS.
REFER TO DETAILS FOR ADDITIONAL REINFORCING AT JOINTS.
n. LOCATING JOINTS IN HORIZONTAL PLANE OF FOUNDATIONS, PILE CAPS, SLABS AND GRADE BEAMS IS NOT PERMITTED, UNLESS OTHERWISE SHOWN.
o. FINISH SHORED CONCRETE SLABS FLAT AND LEVEL WITHIN TOLERANCE, TO
THE ELEVATION INDICATED ON THE DRAWINGS. PROVIDE ADDITIONAL CONCRETE
REQUIRED DUE TO FORMWORK AND FRAMING DEFLECTION TO ACHIEVE THIS
FINISHED TOP OF SLAB ELEVATION.
p. CORE DRILLING FOUNDATIONS, BEAMS, SLABS, COLUMNS OR ANY
MEMBERS IS NOT PERMITTED UNLESS OTHERWISE NOTED.
q. CHAMFER EXPOSED CONCRETE COLUMNS, ¾”x ¾” MINIMUM, UNLESS
OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
r. POWER DRIVEN FASTENERS PERMITTED WHEN PROVEN TO THE SATISFACTION
OF THE STRUCTURAL ENGINEER OF RECORD THAT THE FASTENERS WILL NOT
SPALL THE CONCRETE AND HAVE THE SAME CAPACITY AS CAST-IN-PLACE
INSERTS. TAKE MEASURES AS NEEDED TO AVOID DRILLING EXISTING
REINFORCING AND DESTRUCTION OF CONCRETE.
s. WHEN INSTALLING EXPANSION BOLTS OR ADHESIVE ANCHORS, TAKE
MEASURES TO AVOID DRILLING OR CUTTING OF EXISTING REINFORCING AND
DESTRUCTION OF CONCRETE. BLOW HOLES CLEAN PRIOR TO PLACING BOLTS OR
ADHESIVE ANCHORS.
H. MASONRY
1. SUBMIT GROUT MIX DESIGN AND MASONRY UNIT CERTIFICATIONS FOR
APPROVAL.
2. PROVIDE ADEQUATE BRACING AND SUPPORT OF MASONRY UNTIL PERMANENT
CONSTRUCTION IS IN PLACE.
3. WALL SECTIONS AND PIERS LESS THAN 0.2 SQUARE METERS IN CROSS-
SECTIONAL AREA TO BE FULLY GROUTED OR OF 100% SOLID MASONRY UNITS.
4. IN GROUTED AND/OR REINFORCED MASONRY WALLS, USE MASONRY UNITS WITH
CORES THAT ALIGN VERTICALLY AND PROVIDE CONTINUOUS UNOBSTRUCTED
CELLS FOR GROUTING AND REINFORCING STEEL PLACEMENT.
5. LAP SPLICES FOR DEFORMED REINFORCING BARS USED IN MASONRY
CONSTRUCTION TO BE 50 BAR DIAMETERS.
6. PROVIDE STANDARD WEIGHT GALVANIZED HORIZONTAL JOINT REINFORCEMENT
IN ALL WALLS AND PARTITIONS AT 16” O.C. UNLESS OTHERWISE NOTED. PROVIDE
ONE PIECE PREFABRICATED UNITS AT 8” O.C. AT ALL WALL CORNERS AND
INTERSECTIONS.
7. ANCHOR OR BOND PIERS AND PARTITIONS TO ADJACENT MASONRY WALLS.
8. PROVIDE BOND BEAMS WITH 2-#4 HORIZONTAL REINFORCEMENT CONTINUOUS
IN ALL MASONRY WALLS AT EACH FRAMING LEVEL.
9. REFER TO SPECIFICATIONS AND DETAILS FOR GENERAL EXPANSION JOINT AND
CONTRACTION JOINT REQUIREMENTS FOR ALL WALLS.
10. PROVIDE LINTELS OF LOOSE STEEL ANGLES, PRECAST CONCRETE, OR
REINFORCED CONCRETE BLOCK (CONTRACTOR'S OPTION UNLESS SHOWN
OTHERWISE ON THE DRAWINGS) FOR NON-LOAD BEARING WALLS AND
PARTITIONS AS FOLLOWS:
STEEL LINTELS: PROVIDE HOT-DIP GALVANIZED FINISH AT EXTERIOR
CONDITIONS UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
FOR EACH 4" THICKNESS OF WALL
UP TO A 12" THICK WALL (MAX.) BEARING LENGTH
OPENING < 4'-0": L3½x3½x5/16 6"
4'-0" < OPENING < 6'-0": L4x3½x5/16 (LLV) 6"
6'-0" < OPENING < 8'-0": L5x3½x5/16 (LLV) 6"
8'-0" < OPENING < 10'-0": W8x15 WITH 5/16” SUSP PL 6"
REINFORCED CMU LINTELS: PROVIDE MINIMUM 8" BEARING EACH END.
OPENING < 4'-0": LINTEL SIZE = WALL THICKNESS x 8" DEEP
REINFORCE WITH 2 #4 BOTTOM BARS UP TO 8" THICK
REINFORCE WITH 3#4 BOTTOM OVER 8"
4'-0" < OPENING < 8'-0": LINTEL SIZE = WALL THICKNESS x 16" DEEP
REINFORCE WITH 2 #5 BOTTOM BARS UP TO 8" THICK
REINFORCE WITH 3#5 BOTTOM & #3 STIRRUPS AT 6" O.C. OVER 8" THICK
PRECAST CONCRETE LINTELS: PROVIDE MINIMUM 8” BEARING EACH END.
OPENING < 4'-0": LINTEL SIZE = WALL THICKNESS x 8" DEEP
REINFORCE WITH 2 #4 BOTTOM BARS.
4'-0" < OPENING < 8'-0": LINTEL SIZE = WALL THICKNESS x 16" DEEP
REINFORCE WITH 2 #5 BOTTOM BARS.
11. VERIFY ALL OPENINGS BELOW LINTELS INDICATED ARE ADEQUATE TO ACCEPT
DOOR FRAMES, LOUVERS, ETC. AS SHOWN ON THE ARCHITECTURAL AND
MECHANICAL DRAWINGS. NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER OF
RECORD OF ANY DISCREPANCIES OR CONFLICTS PRIOR TO LINTEL INSTALLATION.
12. DO NOT PLACE OPENINGS ABOVE ANY LINTEL WITHIN A HEIGHT LESS THAN OR
EQUAL TO THE WIDTH OF THE CLEAR OPENING BELOW THE LINTEL, UNLESS
SPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS.
I. STRUCTURAL STEEL
1. SUBMIT CERTIFIED COPIES OF MILL TEST REPORTS TO THE STRUCTURAL
ENGINEER OF RECORD.
2. PROVIDE ACCESS FOR INSPECTION OF ALL SHOP AND FIELD CONNECTIONS FOR
PROPER MATERIALS AND WORKMANSHIP.
3. MAINTAIN CURRENT EVIDENCE OF WELDERS PASSING THE APPROPRIATE AWS
QUALIFICATION TESTS. SUCH EVIDENCE MAY BE REQUESTED AT ANY TIME DURING
THE PROJECT.
4. PERMANENT FRAMING AND FINAL CONNECTION DETAILS ARE SHOWN ON THE
DRAWINGS. THE FABRICATOR AND ERECTOR ARE RESPONSIBLE FOR THE DESIGN
OF TEMPORARY BRACING AND RECOMMENDED ERECTION PROCEDURES.
5. SELECT CONNECTIONS FOR REACTIONS SHOWN ON PLANS AND AS DETAILED
AND SCHEDULED.
a. IF NO REACTION IS SHOWN, DETAIL SIMPLE SHEAR CONNECTIONS FOR 3/4 OF
THE ALLOWABLE UNIFORM LOAD TABULATED IN THE AISC "STEEL CONSTRUCTION
MANUAL: ASD". NO CONNECTION SHALL CONSIST OF LESS THAN TWO 3/4" DIA.
HIGH STRENGTH BOLTS AND/OR WELDS DEVELOPING A MINIMUM OF 10,000
POUNDS. MINIMUM WELDS FOR ALL CONNECTIONS SHALL BE 3/16" FILLET.
b. ALTERNATE SIMPLE SHEAR CONNECTIONS DETAILED IN ACCORDANCE WITH
THE CONNECTION TABLES IN THE AISC "STEEL CONSTRUCTION MANUAL" SHALL
BE PERMITTED WITH PRIOR APPROVAL OF THE STRUCTURAL ENGINEER OF
RECORD.
c. SIMPLE SHEAR CONNECTIONS SHALL HAVE A MINIMUM CONNECTION DEPTH
OF ONE-HALF THE T-DIMENSION OF THE BEAM TO BE SUPPORTED (EXCLUDING
BEAM SEAT CONNECTIONS.)
d. ALTERNATE CONNECTIONS THAT ARE NOT TABULATED IN THE AISC "STEEL
CONSTRUCTION MANUAL" SHALL ONLY BE…
This is the start of the file's text. The full file is on GovTribe.