This document is a comprehensive set of final design drawings for the P-1102 Weapons Magazine & Ordnance Operations Facility, specifically a Containerized Long Weapons Storage (CLWS) magazine located at Naval Submarine Base New London in Groton, Connecticut. The drawings are dated June 23, 2025, and were prepared by Jacobs for the Naval Facilities Engineering Systems Command (NAVFAC) Mid-Atlantic.
The facility design includes structural elements such as reinforced concrete magazines with 24-inch thick roof slabs, earth-covered storage areas with waterproofing membranes, and a blast door system capable of storing up to 500,000 lbs of Hazard Division 1.1 explosives. Key structural components include six individual magazines (CLWS-001 through CLWS-006) with varying dimensions, security pilasters, trench covers with plow systems, and a bridge crane system (25-ton capacity, double-girder, CMAA Class D service). The design incorporates mechanical systems including dual redundant air handling units with dehumidification capability, natural ventilation options, and electric heating; mechanical ductwork with fire dampers and honeycomb security devices; and plumbing systems with floor drains, foundation drains, and perforated drain piping. Electrical systems include bonding and grounding requirements, lighting, and controls. The design has been site-adapted from NAVFAC's standard CLWS drawings (NAVFAC Drawing Numbers 12877610-12877660) approved by the Department of Defense Explosives Safety Board on March 20, 2023, to meet specific geotechnical and loading conditions at the Naval Submarine Base location. Construction specifications reference ACI 318 for reinforced concrete, AISC standards for structural steel, and ASTM standards for materials, with concrete strengths of 4,000-5,000 PSI specified for various applications.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTAINERIZED LONG WEAPONS STORAGE (CLWS)
SITE OF CLWS MAGAZINE
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
VISITOR
ENTRANCEPROJECT SITE
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
DEPARTMENT OF DEFENSE EXPLOSIVES SAFETY BOARD (DDESB) APPROVAL NOTES
DO NOT REMOVE THESE NOTES WHEN PREPARING CONSTRUCTION DRAWINGS FOR SITE ADAPTION.
1. THIS STANDARD IS APPROVED BY THE DEPARTMENT OF DEFENSE EXPLOSIVE SAFETY BOARD
(DDESB) AS A 7-BAR EARTH COVERED MAGAZINE AND MAY BE SITED AS AN EXPOSED SITE
MAGAZINE FROM OTHER POTENTIAL EXPLOSION SITES STORING UP TO 500,000 LBS HAZARD
DIVISION 1.1 EXPLOSIVES.
2. THE DESIGN AND DETAILING OF THIS STANDARD MAGAZINE FOR BLAST LOADING IS THE SOLE
RESPONSIBILITY OF THE GOVERNMENT. THE GOVERNMENT IS THE ENGINEER OF RECORD FOR
THE BLAST DOOR.
3. ANY DEVIATION FROM THESE STANDARD DRAWINGS, EXCEPT FOR FOUNDATION MODIFICATIONS, WITHOUT THE WRITTEN APPROVAL FROM THE DEPARTMENT OF DEFENSE EXPLOSIVE SAFETY
BOARD (DDESB) MAY REQUIRE THE MAGAZINE TO BE CONSIDERED AN UNDEFINED MAGAZINE AND
MAY SEVERELY RESTRICT THE ALLOWABLE STORAGE CAPACITY.
GENERAL PROJECT SYMBOLS
A1 VIEW TITLE
PLAN TITLE
0 8'4' 16'
0 8'4' 16'A1
G
EN
ER
AL
N O
TE
S
- 1
JAF SFF TPH
NONE
12894246
S-001
NEK
THE CONTRACT STRUCTURAL DRAWINGS REPRESENT THE FINISHED
STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHOD OF
CONSTRUCTION. PROVIDE ALL MEASURES NECESSARY TO PROTECT THE
STRUCTURE, WORKERS OR OTHER PERSONS DURING CONSTRUCTION. SUCH
MEASURES MUST INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR
CONSTRUCTION EQUIPMENT, SHORING FOR THE BUILDING, FORMS,
SCAFFOLDING, PLANKING, SAFETY NETS, ETC.
THE CONTRACTOR MUST ENGAGE PROPERLY QUALIFIED PERSONS TO
DETERMINE WHERE AND HOW TEMPORARY PRECAUTIONARY MEASURES MUST
BE USED DURING CONSTRUCTION. THE CONTRACTOR MUST ALSO PROVIDE
THEIR OWN THIRD-PARTY INSPECTOR TO REVIEW AND VERIFY INSTALLATION OF
ALL TEMPORARY PRECAUTIONARY MEASURES
CONSTRUCTION PROCEDURES &
SAFETY REQUIREMENTS:
THE CONTRACTOR MUST COMPLY WITH ALL APPLICABLE CITY, COUNTY, STATE,
FEDERAL, AND INTERNATIONAL LAWS, INCLUDING THE OCCUPATIONAL SAFETY
AND HEALTH ACT (OSHA) AND REGULATIONS ADOPTED PURSUANT THERETO.
THE CONTRACTOR MUST SUPERVISE AND DIRECT THE WORK SO AS TO MAINTAIN
RESPONSIBILITY FOR COORDINATING THE WORK OF ALL TRADES AND THE
CHECKING OF ALL DIMENSIONS. ALL DISCREPANCIES MUST BE CALLED TO THE
ATTENTION OF THE CONTRACTING OFFICER AND MUST BE RESOLVED BEFORE
PROCEEDING WITH THE WORK.
CONSTRUCTION LOADS INCLUDING MATERIALS MUST NOT EXCEED THE DESIGN
LIVE LOAD. PROVIDE ADEQUATE SHORING, RESHORING AND/OR BRACING
WHERE REQUIRED.
EQUIPMENT PENETRATION OPENINGS AND LOCATIONS WHEN INDICATED ON
DRAWINGS ARE FOR INFORMATION ONLY AND MUST BE VERIFIED WITH THE
APPROPRIATE DRAWING AND/OR EQUIPMENT SUPPLIER BEFORE CONSTRUCTION.
THE STRUCTURAL DRAWINGS SHOW ONLY THE BASIC STRUCTURAL SYSTEM.
REFER TO OTHER DRAWINGS FOR ORNAMENTS, GROOVES, CLIPS, GROUNDS,
SLAB DEPRESSIONS, CURBS, EQUIPMENT PADS, PENETRATIONS, NON-BEARING
WALLS AND OTHER NON-STRUCTURAL ITEMS.
GENERAL NOTES AND STANDARD DETAILS MUST BE USED WHERE APPLICABLE,
UNLESS NOTED OTHERWISE. NOTES AND DETAILS ON THE DRAWINGS MUST
TAKE PRECEDENCE OVER GENERAL NOTES AND STANDARD DETAILS. WHERE
CONFLICTS ARISE BETWEEN DRAWINGS AND SPECIFICATIONS, MOST STRINGENT
WILL GOVERN. CONTACT THE CONTRACTING OFFICER IN WRITING FOR
CLARIFICATION BEFORE PROCEEDING WITH WORK.
ALL OMISSIONS AND/OR CONFLICTS BETWEEN VARIOUS ELEMENTS OF THE
CONTRACT DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE
CONTRACTING OFFICER IN WRITING BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
DIMENSIONS MUST NOT BE SCALED FROM THE PLANS, SECTIONS AND/OR
DETAILS OF THE STRUCTURAL DRAWINGS.
ALL MATERIALS AND WORKMANSHIP MUST CONFORM TO THE DRAWINGS AND
SPECIFICATIONS.
SEE STRUCTURAL AND ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF ALL
OPENINGS REQUIRED FOR DUCT WORK, PIPES AND PIPE SLEEVES.
OPENINGS OR POCKETS LARGER THAN 6 INCHES NOT INDICATED IN
STRUCTURAL DRAWINGS MUST NOT BE PLACED WITHOUT WRITTEN
NOTIFICATION OF THE CONTRACTING OFFICER.
1.
2.
3.
4.
5.
DESIGN CRITERIA:
7.
6.
5.
4.
3.
2.
B.
A.
FOUNDATIONS:
ALL ROUGHENED SURFACES IN CONCRETE MUST BE MADE WITH A MINIMUM
AMPLITUDE OF 1/4 INCH.
CONDUIT OR PIPE SIZE (O.D.) MUST NOT EXCEED 30 PERCENT OF SLAB
THICKNESS AND MUST BE PLACED BETWEEN THE TOP AND BOTTOM
REINFORCING UNLESS SPECIFICALLY DETAILED OTHERWISE. CONCENTRATIONS
OF CONDUITS OR PIPES MUST BE AVOIDED EXCEPT WHERE DETAILED OPENINGS
ARE PROVIDED.
PROVIDE SLEEVES FOR ELECTRICAL OPENINGS IN CONCRETE BEFORE PLACING.
DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN CONCRETE IS
NOT PERMITTED EXCEPT AS SHOWN. NOTIFY THE STRUCTURAL ENGINEER AND
CONTRACTING OFFICER IN ADVANCE IF THE FIELD CONDITIONS DO NOT REFLECT
THE CONDITIONS SHOWN ON THE DRAWINGS.
PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., MUST BE FORMED
WITH 3/4 INCH CHAMFER, UNLESS OTHERWISE NOTED.
ALL STRUCTURAL CONCRETE:
CHLORIDES OR CHLORIDE SALTS ARE NOT ALLOWED IN THE CONCRETE MIXES.
CONCRETE AGGREGATES
CAST-IN-PLACE CONCRETE:
CONCRETE MUST ATTAIN THE FOLLOWING 28-DAY COMPRESSIVE STRENGTHS,
UNLESS OTHERWISE INDICATED;
MATERIAL MUST CONFORM TO ALL OF THE FOLLOWING STANDARD
SPECIFICATIONS, LATEST EDITION:
THE DESIGN AND CONSTRUCTION OF REINFORCED CONCRETE MUST CONFORM
TO THE ACI BUILDING CODE (ACI 318) AND THE FOLLOWING CODES AND
STANDARD SPECIFICATIONS:
ALL REINFORCING STEEL DETAILING AND PLACEMENT MUST CONFORM TO THE
ACI DETAILING MANUAL PUBLICATION SP-66, "BUILDING CODE REQUIREMENTS
FOR REINFORCED CONCRETE" ACI-318, AND THE "MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" ACI-315.
PROVIDE ADEQUATE BOLSTERS, HI-CHAIRS, SUPPORT BARS, ETC., TO MAINTAIN
SPECIFIED COVER FOR THE ENTIRE LENGTH OF ALL REINFORCING. SECURE ALL
REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS IN
POSITION PRIOR TO PLACING CONCRETE.
12.
11.
10.
9.
8.
A.
WELDED WIRE FABRIC
REINFORCING STEEL
PORTLAND CEMENT
CONCRETE PLACEMENT
CONCRETE MIXING
D.
C.
B.
A.
B.
A.
1.
5.
3.
2.
7.
5,000 PSI
ASTM A615 DEFORMED
BARS (GRADE 60)
ASTM A1064
ASTM C33
ASTM C150, TYPE I OR II
ASTM C304
ASTM C94
B. LEAN CONCRETE:
COORDINATE WITH THE CONTRACTING OFFICER FOR PROCUREMENT AND
INSTALLATION OF INTERNAL LOCKING DEVICE (ILD), BOLTWORKS, AND THE
DISTRIBUTION OF KEY SETS FOR EACH MAGAZINE DOOR. THE ILD MUST BE
PROCURED WITH TWO UNIQUE KEYS IN ORDER TO OPERATE THE BOLTWORKS.
CONTACT THE DoD LOCK PROGRAM FOR DIRECTIONS ON HOW TO PROCURE THE
INTERNAL LOCKING DEVICE (ILD), BOLTWORKS, AND A LIST OF RECOMMENDED
MANUFACTURERS FOR MAGAZINE DOORS:
A. DoD LOCK PROGRAM: https://navfac.navy.mil/go/locks B. EMAIL: ILD_Field_Support@navy.mil
C. ILD SUPPORT HOTLINE: 805-982-5625.
D. DoD LOCK PROGRAM TECHNICAL SUPPORT HOTLINE: 800-290-7607 OR 805-982-1212.
COORDINATE WITH THE CONTRACTING OFFICER FOR THE CONNECTION OF THE
BALANCED MAGNETIC SWITCH (BMS) ON THE DOOR AND THE ILD, WHICH MUST
BE INSTALLED AND CONNECTED TO THE INTRUSION DETECTION SYSTEM (IDS) BY
NAVY INFORMATION WARFARE CENTER.
8.
3,000 PSI
SEE SHEET S-002 FOR LIGHTWEIGHT CONCRETE MIX DESIGN FOR HIGH
SECURITY MAGAZINE DOOR.
D.
C.
A. 3 INCH
B. 2 INCH
2 INCH
2 INCH
MINIMUM CONCRETE PROTECTION (COVER) FOR REINFORCEMENT MUST BE
PROVIDED AS FOLLOWS UNLESS SPECIFICALLY CALLED OUT OTHERWISE IN
PLANS AND DETAILS:
CONCRETE PLACED AGAINST EARTH.
CONCRETE PLACED AGAINST FORM AND
LATER EXPOSED TO EARTH OR WEATHER.
COLUMNS AND BEAMS (FROM TIE OR STIRRUP).
SLAB EXPOSED TO WEATHER OR GROUND.
E. 3/4 INCHSLABS AND WALLS (NOT EXPOSED
TO WEATHER OR GROUND).
NEAR SIDE
FAR SIDE
STRUCTURAL ABBREVIATIONS:
TOP OF SLAB, TOP OF STEEL
UNLESS NOTED OTHERWISE
VERTICAL
HORIZONTAL
JOINT
INTERMEDIATE
INFORMATION WITH
COMPLETE JOINT PENETRATION
ANCHOR BOLT
GAUGE
FOOT OR FEET
FINISH FLOOR
FINISH
FLOOR
EXTERIOR
EACH SIDE
EQUAL
EACH FACE
EACH
DRAWING
DIMENSION
DIAMETER
DETAIL
DOUBLE
CONTINUOUS
CONSTRUCTION
CONNECTION
CONCRETE
COLUMN
CLEAR (ANCE)
CAST-IN-PLACE
BOTTOM
BEAM
ARCHITECTURAL
APPROXIMATE
ALTERNATE
MINIMUM
ON CENTER
REQUIRED
SCHEDULE
SECTION
STANDARD
THROUGH
STIFFENER
MISCELLANEOUS
NOT IN CONTRACT
NOT TO SCALE
OPPOSITE HAND
REINFORCEMENT
SPECIFICATIONS
STRUCTURAL
TYPICAL
RADIUS
SHEET
SIMILAR
SQUARE
OPENING
PLATE
MAXIMUM
LONGITUDINAL
LONG LEG VERTICAL
LONG LEG HORIZONTAL
MANUFACTURER
TEMPERATURE STEEL
NS
FS
VERT, (V)
HORIZ, (H)
JT
INTERM
INFO W/
GA
FT
FIN FL
FIN
FL
EXT
ES
EQ
EF
EA
DWG
DIM
DIA
DET
DBL
CONT
CONSTR
CJP
CONN
CONC
COL
CLR
CIP
BOT
BM
ARCH
APPROX
ALT
AB
UNO
TYP
TOS
THRU
STRUCT
STIFF
STD
SQ
SPECS
SIM
SHT
SECT
SCHED
REQ'D
REINF
RAD
PL
OPNG
OH
OC
NTS
NIC
MISC
MIN
MANUF, MFR
MAX
LONGIT
LLV
LLH
TEMP
EJ EXPANSION JOINT
OF OUTSIDE FACE
ADDITIONALADD'L
CONSTRUCTION JOINTCJ
MECHANICALMECH
PANEL JOINTPJ
HSS HOLLOW STRUCTURAL SECTION
SLAB-ON-GRADESOG
DEFORMED BAR ANCHORDBA
HEADED ANCHOR STUDHAS
DISTANCEDIST
IF INSIDE FACE
THICKTHK
SPACESPA
PART NUMBERPN
GENERAL:
CONTROL JOINTCLJ
9.
10.
(SHEET TYPE, ROLL
TYPE NOT ACCEPTABLE)
4.
STRUCTURAL STEEL:
GALVANIZED IRONGI
TOPT
FOOTINGFTG
7. UNLESS OTHERWISE NOTED WELD ALL SHOP CONNECTIONS AND BOLT ALL FIELD
CONNECTIONS. THE FABRICATOR IS RESPONSIBLE FOR THE DESIGN OF ALL CONNECTIONS,
UNLESS OTHERWISE DETAILED.
8. DO NOT CUT OR BURN HOLES IN STRUCTURAL STEEL WITHOUT THE APPROVAL OF THE
CONTRACTING OFFICER.
9. SPLICING OF STRUCTURAL STEEL IS NOT PERMITTED UNLESS APPROVED IN WRITING BY
THE CONTRACTING OFFICER.
10. GROUT BELOW BASE PLATES WITH NON-SHRINK GROUT WITH COMPRESSIVE STRENGTH,
f'c = 5,000 PSI.
11. COAT ALL STRUCTURAL STEEL EXPOSED TO SOIL WITH TWO COATS OF COAL TAR EPOXY.
EPOXY MUST MEET THE REQUIREMENTS OF PAINT SPECIFIC SSPC-PAINT 16.
12. BLAST DOOR AND COMPONENTS MUST MEET THE FOLLOWING TOLERANCES.
A. BLAST DOOR MUST HAVE A TOTAL MAX FLATNESS TOLERANCE OF ±1/4" VERTICALLY
AND HORIZONTALLY.
B. TRENCHES AND DOOR GUIDE RAIL MUST HAVE A ±1/4" MAX DIFFERENTIAL
TOLERANCE PER EVERY 37'-0".
C. SECURITY PILASTER AND ALL OTHER VERTICAL AND HORIZONTAL DOOR BEARING
SURFACES MUST HAVE A ±1/4" MAX TOTAL TOLERANCE.
STRUCTURAL STEEL (CONT):
FOUNDATIONFDN
OPENINGS OR PENETRATIONS OF ANY SIZE IN BLAST-RESISTING STRUCTURAL
COMPONENTS (BLAST DOOR, HEADER BEAM, HEADWALL, PILASTERS, ROOF
PANEL, SIDE WALLS, REAR WALL) THAT ARE UNPLANNED OR NOT SHOWN IN THE
DRAWINGS ARE NOT PERMITTED TO BE CONSTRUCTED WITHOUT PRIOR
APPROVAL FROM THE CONTRACTING OFFICER.
C.
6. WELDING OF REINFORCING STEEL IS PROHIBITED.
SS STAINLESS STEEL
THESE CONSTRUCTION DOCUMENTS ARE CONSTRUCTION STANDARDS FOR THE
NAVY CLWS DOUBLE BAY STANDARD MAGAZINES AND HAVE BEEN SITE ADAPTED
BY THE DOR.
1.
TBD TO BE DETERMINED
ASTM A706 GRADE 60 IS NOT EQUIVALENT AND IS NOT ACCEPTABLE.
ORIGINAL STANDARD DRAWING IS NAVFAC DRAWING NUMBER 12877611 SHT 2 OF 51
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DN
AN
CE
O
PE
RA
TIO
NS
FA
CI
LIT
Y
CL
W
S M
AG
AZ
IN
E
SMS/CWJ
JWJ
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
SCALE:
CONSTR. CONTR. NO.
NAVFAC DRAWING NO.
EPROJECT NO.:
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
6/3/2025
THESE DRAWINGS ARE AN EXACT REPLICA OF THE STANDARD MAGAZINE TYPE
"CLWS" PROVIDED BY NAVFAC. THE DESIGN WILL BE SITE ADAPTED AND MODIFIED
TO MEET THE SPECIFIC GEOTECHNICAL AND LOADING CONDITIONS SPECIFIC TO
NAVAL SUBMARINE BASE NEW LONDON, GROTON, CONNECTICUT.
1. THE STRUCTURAL DESIGN AND CONSTRUCTION MUST COMPLY WITH THE
FOLLOWING GOVERNMENT STANDARDS:
· UFC 1-200-01, "DESIGN: GENERAL BUILDING REQUIREMENTS"
· FC 1-300-09N, "NAVY AND MARINE CORPS DESIGN PROCEDURES"
2. DESIGN LOADS:
THE FOLLOWING LOADS WERE USED AS BASIS OF DESIGN:
A. DEAD LOADS: ACTUAL WEIGHT
a. SOIL: 110 PCF
B. LIVE LOADS:
a. CANOPY ROOF: 20 PSF
b. ROOF: 100 PSF
c. MAGAZINE FLOOR: 32K (HS 20-44 AXLE)
70.5K (SIDELOADER AXLE)
15K (FORKLIFT AXLE)
31K (CPS CONTAINER EACH)
2,000 PSF (UNIFORM)
d. MECHANICAL ROOM FLOOR: 150 PSF (UNIFORM)
3. WIND DESIGN DATA:
A. DESIGN WIND SPEED: 210 MPH
B. EXPOSURE: "C"
C. RISK CATEGORY: III
4. SEISMIC DESIGN DATA:
A. RISK CATEGORY: III
B. IMPORTANCE FACTOR: 1.25
C. SEISMIC DESIGN CATEGORY: D
D. SITE SEISMICITY: SS = 2.79g
S1 = 0.68g
E. SITE CLASS: D
5. SNOW DESIGN DATA:
A. GROUND SNOW LOAD: 45
B. EXPOSURE FACTOR: 1.0 PSF
C. IMPORTANCE FACTOR: 1.10
D. THERMAL FACTOR: 1.2
6. EXPLOSIVE SAFETY DESIGN LOADS:
A. EXPLOSIVE SAFETY DESIGN LOADS FOR DOOR AND ROOF OF MAGAZINES
ARE PRESCRIBED BY NAVFAC EXWC. DESIGN GUIDANCE IS PROVIDED BY
UFC 3-340-02 2008.
B. TRIANGULAR PULSE LOAD VALUES BASED ON NAVFAC EXWC - DESIGNED
CRITERIA: CONTAINERIZED LONG WEAPONS STORAGE EARTH COVERED
MAGAZINES, DATED NOVEMBER 2019:
C. APPROVED LOCATION AND STORAGE CAPACITY OF EACH ECM MUST BE
DETERMINED BY THE SAFETY OFFICER BASED ON ORIENTATION AND
PROXIMITY RELATIVE TO NEARBY FACILITIES/MAGAZINES.
MEMBER PEAK PRESSURE IMPULSE DURATION
HEAD WALL AND DOOR 301 PSI 2,119 PSI-MS 14.08 MS ROOF
176.3 PSI 1,640 PSI-MS 18.60 MS
1. THE FOUNDATIONS HAVE BEEN DESIGNED USING THE FOLLOWING ALLOWABLE
BEARING PRESSURES:
A. DEAD PLUS LIVE LOAD: 4,000 PSF
B. TOTAL DESIGN LOAD (INCLUDING WIND OR SEISMIC, TRANSIENT LOAD
FACTOR = 1.33): 5,300 PSF
C. BLAST DESIGN LOAD (DYNAMIC INCREASE FACTOR = 2.5): 10,000 PSF
2. EARTH COVER MATERIAL TO BE USED AS MAGAZINE COVER AND WITHIN THE
EMBANKMENT IS TO BE NON-EXPANSIVE, FREE OF DELETERIOUS MATERIAL AND
MEET THE FOLLOWING CHARACTERISTICS:
A. ALLOWABLE WET SOIL DENSITY: 110 - 120 PCF.
B. ASTM D2487 CLASSIFICATION: SM, SM-SC, SC.
C. ASTM D1140 MATERIAL FINER THAN #200 SIEVE (0.075MM) -MIN. 25%: MAX. 50%.
D. MAXIMUM PARTICLE SIZE: 1 INCH
E. ASTM D4318: MAX LIQUID LIMIT = 35, MAX PLASTICITY INDEX = 12.
F. REQUIREMENTS FOR EARTH COVER ECMS IN ACCORDANCE WITH DEFENSE
EXPLOSIVES SAFETY REGULATION (DESR) 6055.09.
3. RETAINING WALLS HAVE BEEN DESIGNED USING THE FOLLOWING CRITERIA.
A. PASSIVE EQUIVALENT FLUID PRESSURE: 300 PSF/FT
B. AT-REST LATERAL PRESSURE w/ 2:1 BACKFILL (RESTRAINED):
· WITHOUT SEISMIC: 32 PSF/ FT
· WITH SEISMIC: 68 PSF/ FT
C. CANTILEVERED WALL LATERAL PRESSURE (UNRESTRAINED):
· WITHOUT SEISMIC: 40 PSF/ FT
· WITH SEISMIC: 102 PSF/ FT
D. FRICTION FACTOR BETWEEN SOIL AND CONCRETE PLACED AGAINST SOIL:
0.35
E. FRICTION FACTOR BETWEEN SOIL AND CONCRETE PLACED AGAINST
FORMWORK: 0.25
F. MINIMUM SOIL COHESIVE STRENGTH: 500 PSF
4. SAND MATERIAL USED AS A FREE-DRAINING LAYER AT THE EXTERIOR CONCRETE
SURFACES AT THE ROOF PANEL, ENDWALL, AND SIDEWALLS MUST MEET
MINIMUM REQUIREMENTS FOR ECMS IN ACCORDANCE WITH DEFENSE
EXPLOSIVES SAFETY REGULATION (DESR) 6055.09.
5. STRUCTURAL DRAWINGS INDICATE GENERAL SOG AND FOUNDATION
PREPARATION. SEE PROJECT SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
6. ALL FILLING, BACKFILLING AND COMPACTING MUST BE PER PROJECT
SPECIFICATION. COMPACTION OF SOILS ON TOP OF MAGAZINE MUST BE
PERFORMED WITH HAND COMPACTION TOOLS ONLY.
7. EXPANSIVE SOILS MUST NOT BE USED FOR BACKFILL OR FILL. BACKFILL AT
RETAINING WALLS MUST CONFORM TO THE PROJECT SPECIFICATIONS.
8. ALL EXCAVATIONS MUST BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL
BEHIND RETAINING WALLS BEFORE CONCRETE HAS ATTAINED FULL DESIGN
STRENGTH. CONTRACTOR MUST BRACE OR PROTECT ALL BUILDING AND PIT
WALLS BELOW GRADE FROM LATERAL LOADS UNTIL ATTACHING FLOORS ARE
COMPLETELY IN PLACE AND HAVE ATTAINED FULL STRENGTH. CONTRACTOR
MUST PROVIDE FOR DESIGN, PERMITS AND INSTALLATION OF SUCH BRACING.
9. CONTRACTOR MUST PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM
SURFACE WATER, GROUND WATER AND SEEPAGE.
10. CONTRACTOR MUST PROVIDE FOR DESIGN AND INSTALLATION OF ALL CRIBBING,
SHEETING, AND SHORING REQUIRED TO SAFELY RETAIN THE EARTH BANKS.
11. EXCAVATION FOR FOUNDATIONS MUST BE APPROVED BY THE CONTRACTING
OFFICER PRIOR TO PLACING THE REINFORCING AND CONCRETE.
12. SHALLOW FOOTING FOUNDATIONS MUST BE PLACED AND INSTALLED IN
ACCORDANCE WITH THE CONSTRUCTION DRAWINGS AND SPECIFICATIONS
PREPARED FOR THE PROJECT.
13. FOUNDATION BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA
MUST BE MECHANICALLY COMPACTED IN LAYERS PER THE SPECIFICATIONS TO
THE APPROVAL OF THE CONTRACTING OFFICER. FLOODING WILL NOT BE
PERMITTED.
14. NEW FOUNDATIONS MUST BEAR ON APPROVED, UNDISTURBED, NATURAL
SUBGRADE SOILS OR ON PROPERLY COMPACTED AND APPROVED FILL
MATERIALS PLACED DIRECTLY ABOVE APPROVED SUBGRADES AS INDICATED IN
CONSTRUCTION DRAWINGS AND SPECIFICATIONS.
1. DETAIL, FABRICATE, AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE "AISC
SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDINGS," LATEST EDITION.
2. CONTRACTOR MUST REVIEW AND APPROVE STRUCTURAL STEEL SHOP DRAWINGS PRIOR TO
SUBMITTAL TO THE CONTRACTING OFFICER. DO NOT BEGIN FABRICATION PRIOR TO THE
COMPLETION OF THE SHOP DRAWING REVIEW PROCESS.
3. FURNISH STRUCTURAL STEEL THAT IS NEW, CLEAN, STRAIGHT, AND CONFORMING TO THE
FOLLOWING STANDARD SPECIFICATION, LATEST EDITION:
A. STRUCTURAL STEEL WIDE FLANGE: ASTM A992
B. STRUCTURAL STEEL CHANNELS, ANGLES, S-SHAPES, AND PLATES: ASTM A992 OR ASTM
A572, GRADE 50
C. HOLLOW STRUCTURAL STEEL SECTIONS: ASTM A500, GRADE C
D. ANCHOR BOLTS: ASTM F1554 (GRADE SPECIFIED AS REQUIRED)
E. HIGH STRENGTH BOLTS: ASTM F3125 GRADE A325
F. HEADED STUD ANCHORS: ASTM A29 (TYPE B)
G. SUBSTITUTIONS OF STEEL SHAPES IS NOT PERMITTED.
4. STRUCTURAL STEEL MUST CONFORM TO THE FOLLOWING PROPERTIES OR COATINGS:
A. ALL WELDMENT AND EMBEDMENTS FABRICATED FOR THE DOOR JAMB, HEAD, LOCKING
PILASTER, AND TRENCH MUST BE MADE OF TYPE 304 STAINLESS STEEL PER ASTM A240.
B. ALL DOOR STRUCTURAL STEEL MUST BE PRIMED AND PAINTED AFTER FABRICATION.
REFER TO DOOR COATINGS NOTES ON S-003.
C. ALL OTHER STRUCTURAL STEEL INCLUDING CANOPY FRAMING MUST BE HOT DIP
GALVANIZED PER ASTM A123 AND COATED A MINIMUM DRY FILM THICKNESS (DFT) OF 12
MILS IN ACCORDANCE WITH THE FOLLOWING REQUIREMENTS:
a. PRIMER COAT: SOLVENT-BASED TWO COMPONENT EPOXY ANTI-CORROSIVE PRIMER
(3-5 MILS), MPI (THE MASTER PAINTERS INSTITUTE) #101.
b. INTERMEDIATE COAT: HIGH SOLIDS EPOXY COATING (3-5 MILS). MPI #108.
c. TOP COAT: HIGH SOLIDS POLYURETHANE COATING (3-5 MILS). MPI #72.
D. GALVANIZE STRUCTURAL STEEL AFTER FABRICATION WHERE PRACTICAL. REPAIR
DAMAGED GALVANIZED COATING USING ASTM A780 ZINC-RICH PAINT. FIELD CUTTING OF
ANY HOT-DIP GALVANIZED HARDWARE IS NOT PERMITTED.
5. REPAIR ABRADED AND RUSTED SHOP PAINT WITH SAME PAINT AS SPECIFIED IN STRUCTURAL
STEEL NOTE 4C.
6. WELDING MUST COMPLY WITH THE “STRUCTURAL WELDING CODE - STEEL” (AWS D1.1) AND
THE "STRUCTURAL WELDING CODE - STAINLESS STEEL" (AWS D1.6). WELD ELECTRODES MUST
BE E70XX FOR STEEL AND E308L FOR STAINLESS STEEL. PASSIVATION OF STAINLESS STEEL
WELDS MUST BE PERFORMED PER ASTM A380. UNLESS OTHERWISE NOTED, MINIMUM WELD
SIZE MUST BE 1/4 INCH CONTINUOUS FILLET WELD.
ABOVE FINISHED GRADEAFG
CAST IRONCI
PARTIAL CONTROL JOINTPCJ
S-002
1. ALL COATINGS AND INSTALLATION OF COATINGS MUST COMPLY WITH:
A. UFGS - 09 97 13.27.
B. SHOP COATINGS: SSPC (THE SOCIETY OF PROTECTIVE COATINGS) QP3.
C. FIELD COATINGS: SSPC QP1 + QS1.
D. COLOR: LIGHT GRAY.
2. SURFACE PREPARATION:
A. REMOVE SLAG FROM ALL WELDING SURFACES PRIOR TO CLEANING IN ACCORDANCE WITH NACE
SP0178.
B. SOLVENT CLEAN SURFACE TO BE COATED PRIOR TO ABRASIVE BLASTING IN ACCORDANCE WITH
SSPC SP1.
C. DRY ABRASIVE BLAST TO NEAR WHITE FINISH IN ACCORDANCE WITH SSPC SP10. BLAST PROFILE
MUST BE 1-3 MILS TOOTH HEIGHT.
3. PAINT SYSTEMS:
A. TOTAL COATING DRY FILM THICKNESS (DFT): 12 MILS.
B. PRIMER COAT: ABRASION RESISTANT INORGANIC ZINC SILICATE PRIMER (3-5 MILS). SSPC PAINT
20, TYPE IC, LEVEL 1, WITH AT LEAST 85% ZINC IN DRY FILM.
C. INTERMEDIATE COAT: HIGH SOLIDS EPOXY COATING (3-5 MILS). MPI #108.
D. TOP COAT: HIGH SOLIDS POLYURETHANE COATING (3-5 MILS). MPI #72.
4. ALL SURFACES OF ALL DOOR COMPONENTS MUST BE SOLVENT CLEANED, DRY ABRASIVE BLASTED, AND ZINC RICH PRIMER COATED. PRIOR TO FULLY ASSEMBLING OR FABRICATING DOOR, CLEAN AND
PRIMER SURFACES THAT WILL BECOME INACCESSIBLE AFTER DOOR IS ASSEMBLED. THE DOOR
MUST NOT BE GALVANIZED. EPOXY INTERMEDIATE AND POLYURETHANE TOP COATS MUST BE
APPLIED TO ALL EXTERIOR SURFACES OF THE FULLY-ASSEMBLED DOOR.
DOOR COATINGS:
1. ALL STEEL LOUVERS, VENTILATORS, DOORS AND FRAMES MUST BE ELECTRICALLY BONDED
TO THE MAGAZINE REINFORCING CAGE.
2. ALL STRUCTURAL AND MISCELLANEOUS ITEMS EMBEDDED IN CONCRETE MUST BE
ELECTRICALLY BONDED TO THE REINFORCING CAGE BY WIRE TIES.
3. THE REINFORCING CAGE MUST BE MADE ELECTRICALLY CONTINUOUS BY WIRE TIES AT A
MINIMUM OF 48 INCH ON CENTERS IN EVERY DIRECTION, REFER TO DETAIL A1 ON DRAWING
E-504.
4. ALL WALLS AND CONSTRUCTION JOINTS MUST BE ELECTRICALLY BONDED. SEE THE
ELECTRICAL DRAWINGS FOR DETAILS.
5. ALL STRUCTURAL STEEL AND REINFORCING STEEL MUST BE GROUNDED TO THE
SECONDARY GROUND. SEE THE ELECTRICAL DRAWINGS FOR DETAILS.
6. BURIED OR EMBEDDED ITEMS MUST BE DOCUMENTED WITH PHOTOS AT INTERVALS OF
20 FEET.
ELECTRICAL BONDING & GROUNDING
SPECIAL INSPECTION SCHEDULE/ VERIFICATION
ITEM EXTENT OF
INSPECTION1 REFERENCE COMMENT/ SCOPE
CONCRETE CONSTRUCTION
REINFORCING STEEL PLACEMENT P ACI 318: 26.6.2
INSPECT SIZE, SPACING, COVER, POSITIONING AND GRADE OF REINFORCING STEEL. VERIFY THAT REINFORCING BARS ARE FREE OF FORM OIL OR OTHER DELETERIOUS MATERIALS. INSPECT BAR LAPS AND MECHANICAL SPLICES. VERIFY THAT BARS ARE ADEQUATELY TIED AND SUPPORTED ON CHAIRS OR BOLSTERS. WELDING OF REINFORCEMENT IN STRUCTURAL CONCRETE IS NOT
ALLOWED WITHOUT APPROVAL
CONCRETE PLACEMENT C AC1 318: 26.5.2 INSPECT PLACEMENT OF CONCRETE. VERIFY THAT CONCRETE CONVEYANCE AND DEPOSITING AVOIDS SEGREGATION OR
CONTAMINATION. VERIFY THAT CONCRETE IS PROPERLY CONSOLIDATED.
SAMPLING AND TESTING OF CONCRETE C
ASTM C 172
ASTM C 31
ACI 318: 26.12
TEST CONCRETE COMPRESSIVE STRENGTH, SLUMP, AIR-CONTENT AND TEMPERATURE
CURING AND PROTECTION P ACI 318: 26.5.3-26.5.5 INSPECT CURING, COLD WEATHER PROTECTIONS AND HOT WEATHER PROTECTION PROCEDURES.
FORMWORK P ACI 318: 26.11 INSPECT FLATWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED.
DOOR CONSTRUCTION
FABRICATOR CERTIFICATION/ QUALITY CONTROL
PROCEDURES S REVIEW OF FABRICATOR'S QUALITY CONTROL PROCEDURES OR AISC CERTIFICATION.
FABRICATION INSPECTION P INSPECT IN-PLACE FABRICATION, OR REVIEW FABRICATOR'S APPROVED INDEPENDENT INSPECTION AGENCY'S REPORTS
SHOP DEMONSTRATION C SEE BLAST DOOR NOTES
SPECIAL ITEMS RELATED TO THE OTHER EXPLOSIVES
SAFETY RELATED ITEMS
REBAR FARADAY-SHIELD P DWG E-102A; E-501;
E-504
INSPECT REINFORCING STEEL TO ENSURE ELECTRICAL CONTINUITY BETWEEN THE CAP, WALLS, SLAB AND FOUNDATION THROUGH CRIMPED CONNECTIONS. DOCUMENT CONNECTIONS WITH PHOTOS AND CONTINUITY TEST. ALL CRIMPED CONNECTIONS MUST BE
INSPECTED PRIOR TO CONCRETE PLACEMENT.
ECM GROUNDING P DWGS E-102A; E-501;
E-504 VISUALLY INSPECT TO ENSURE ECM FOUNDATION IS BONDED TO THE GROUNDING SYSTEM. DOCUMENT WITH PHOTOS.
GROUNDING SYSTEM P
DWGS E-102A; E-501;
E-504, DA PAM 385-64,
17-27.
VISUALLY INSPECT GROUNDING SYSTEM CONDUCTORS TO ENSURE NO DAMAGE, BREAKAGE, OR CORROSION HAS OCCURED TO
THE CONDUCTORS DURING INSTALL AND BEFORE EARTH BURIAL DOCUMENT WITH PHOTOS.
INDIVIDUAL BONDS P
DWGS E-102A; E-501;
E-504, NFPA 780, 8.9
DA PAM 385-64, 17.27.
INSPECT ALL BONDS FOR LOOSE CONNECTIONS THAT MIGHT RESULT IN HIGH-RESISTANCE CONNECTIONS.
LPS COMPONENTS P NFPA 780, 8.9
DA PAM 385-64, 17-27
INSPECT LPS COMPONENTS FOR SECURE MOUNTING AND PROTECTION AGAINST ACCIDENTAL MECHANICAL DISPLACEMENT AND TO
ENSURE NO DAMAGE, BREAKAGE, OR CORROSION HAS OCCURRED.
LPS TESTING S NFPA 780, 8.9
DA PAM 385-64, 17-28 PERFORM BONDING TEST ACROSS EACH BOND, AND AN EARTH ELECTRODE TEST OF THE LPS.
EARTH COVER P DWGS S-301 INSPECT DEPTH GAUGES ON ROOF PRIOR TO EARTH COVER PLACEMENT FOR SIZE AND STABILITY. INSPECT EARTH COVER DEPTH
AND SLOPE TO ENSURE A 2'-0" MINIMUM IS PROVIDED ABOVE STRUCTURE.
DOOR LAPS C DWGS S-504 INSPECT DOOR LAPS AT TOP AND BOTTOM OF DOOR FRAME
MISCELLANEOUS EMBEDDED AND ATTACHED ITEMS (DOORS,
FRAMES, TRENCHES, ETC) P INSPECT EMBEDDED AND ATTACHED ITEMS TO ENSURE THEY ARE BONDED TO THE GROUNDING SYSTEM. DOCUMENT WITH
PHOTOS.
SPECIAL INSPECTION NOTES:
1. INSPECTION INTERVALS ARE AS FOLLOWS:
C - CONTINUOUS: THE FULL-TIME OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.
P - PERIODIC: THE PART-TIME OR INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS BEING
PERFORMED AND AT THE COMPLETION OF THE WORK.
S - SUBMITTAL
2. STRUCTURAL TEST AND SPECIAL INSPECTIONS ARE BASED ON CHAPTER 17 OF THE IBC.
3. CONTRACTOR MUST HIRE A QUALIFIED INSPECTIONS AND TESTING AGENCY TO PERFORM SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH THE IBC. SUBMIT INSPECTION REPORTS TO THE CONTRACTING OFFICER FOR
EACH DAY SPECIAL INSPECTIONS AND TESTING ARE PERFORMED.
4. THE SPECIAL INSPECTIONS LISTED IN THIS TABLE ARE TO BE USED IN CONJUNCTION WITH ALL SPECIAL INSPECTION REQUIREMENTS PER THE IBC SHOWN BELOW.
5. THE CONTRACTOR MUST EMPLOY ONE OR MORE APPROVED AGENCIES TO PERFORM INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED UNDER SECTION 1705 OF THE IBC REQUIRING VERIFICATION AND INSPECTION. THE CONTRACTING OFFICER MUST ATTEND ALL OBSERVATIONS. THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS DEFINED IN SECTION 110. THE INSPECTING AGENCY MUST PROVIDE REPORTS OF THE
SPECIAL INSPECTIONS DIRECTLY TO THE GOVERNMENT.
THE FOLLOWING IS A LIST OF INSPECTIONS THAT MUST BE PERFORMED IN ACCORDANCE WITH CHAPTER 17 OF THE IBC.
· STEEL CONSTRUCTION: 1705.2
· CONCRETE CONSTRUCTION: 1705.3
· SOILS: 1705.6
· DRIVEN DEEP FOUNDATIONS: 1705.7
· CAST-IN-PLACE DEEP FOUNDATIONS: 1705.8
· HELICAL PILE FOUNDATIONS: 1705.9
· FABRICATED ITEMS: 1705.10
· SPECIAL INSPECTIONS FOR WIND RESISTANCE: 1705.11
· SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE: 1705.12
· TESTING FOR SEISMIC RESISTANCE: 1705.13
· TOLERANCES: SEE SPECS
MATERIAL AMOUNT
LIGHTWEIGHT AGGREGATE 1530
0.70
TOTAL VOLUME 27
UNIT SPECIFIC
GRAVITY
SYNTHETIC FIBERS - TYPE III
CEMENT TYPE II
WATER
SILICA FUME
SUPERPLASTICIZER - TYPE A
lb lb lb lb oz* lb ft3
1.38
3.15
2.2
1.27
0.855
ASTM
C331
C150
C1602
C1240
C494
C1116
LIGHTWEIGHT CONCRETE MIX DESIGN
oz*/ 100lb OF CEMENTITIOUS MATERIAL
PROPERTY AMOUNT
SLUMP 2 + 1/4
UNIT
MINIMUM DENSITY - UNIT WEIGHT
STRENGTH (28 DAY MINIMUM)
in lb/ ft3 psi
LIGHTWEIGHT CONCRETE MATERIAL PROPERTY REQUIREMENTS
ASTM
C143
C138
C78
1. THE FOLLOWING MIX DESIGN AND CONCRETE MATERIAL PROPERTIES MUST BE
USED FOR THE LIGHTWEIGHT CONCRETE LAYER IN THE HIGH SECURITY DOOR:
LIGHTWEIGHT CONCRETE:
2. LIGHTWEIGHT AGGREGATES MUST BE DRY.
3. ADJUST WATER AMOUNT TO +/- 0.5 lb SO THAT MIX HOLDS SHAPE WHEN FORMED INTO A
BALL IN THE HAND.
4. MIX CAN BE SPLIT FOR VOLUME NEEDED.
5. MIX PROCEDURE:
A. WEIGH OUT ALL MATERIALS.
B. IN A SEPARATE CONTAINER, COMBINE AND MIX HALF OF WATER, PLASTICIZER AND ALL
FIBERS.
C. IN ANOTHER SEPARATE CONTAINER, COMBINE AND MIX SILICA FUME AND CEMENT.
D. POUR WATER WITH PLASTICIZER AND ALL FIBERS INTO MIXER.
E. POUR LIGHTWEIGHT FINE AGGREGATE INTO MIXER.
F. SLOWLY ADD SILICA FUME AND CEMENT TO MIXER.
G. ADD REMAINING WATER ADJUSTING AS NECESSARY (NOTE 3).
H. ALLOW TO MIX FOR AT LEAST 10 MINUTES.
I. WHEN MIX IS READY, POUR INTO DOOR CAVITIES OVER REBAR, TO PRESCRIBED DEPTH,
ENSURE MIX FILLS ALL AREAS BEHIND REBAR, VIBRATE AS NECESSARY, NO VOIDS
ALLOWED.
6. ALLOW CONCRETE TO CURE FOR 14 DAYS BEFORE MOVING DOOR AND 28 DAYS BEFORE
WELDING FRONT PANELS ONTO DOOR.
7. QUESTIONS CAN BE REFERRED TO NAVFAC EXWC DOD LOCK PROGRAM, AND SECURITY,
ENGINEERING DIV SH22.
PLUMBING MATERIALS
1. LOUVERS MUST BE CONSTRUCTED OF 16 GAUGE GALVANIZED STEEL WITH 4" DEEP FRAME.
BLADES MUST BE 16 GAGE GALVANIZED STEEL POSITIONED AT APPROXIMATELY 37.5
DEGREES DOWN FROM THE HORIZONTAL AND SPACED APPROXIMATELY 6" ON CENTER.
SCREEN MUST BE 19 GAUGE GALVANIZED 1/4" MESH. APPROXIMATELY 50% FREE AREA.
2. VENTILATORS MUST BE CONSTRUCTED OF MINIMUM 24 GAUGE GALVANIZED STEEL AND
MUST BE DESIGNED FOR A SUSTAINED WIND SPEED OF 132 MPH.
3. FIRE DAMPER FUSIBLE LINKS MUST HAVE A MELTING POINT OF 160 TO 165 DEGREES
FAHRENHEIT. BREAKING STRENGTH MUST BE SUITABLE FOR LOADS IMPOSED BY
COUNTERWEIGHTS.
4. PIPE FLANGE GASKETS MUST BE OF NON-ASBESTOS MATERIAL IN ACCORDANCE WITH
ASME B16.21. GASKETS MUST BE FLAT, 1/16 INCH THICK, AND CONTAIN ARAMID FIBERS
BONDED WITH STYRENE BUTADIENE RUBBER. FLANGE FASTENERS MUST BE TYPE 316
STAINLESS STEEL.
MECHANICAL MATERIALS
STEEL DECK:
1. THE DESIGN, FABRICATION, ERECTION OF METAL DECKING MUST BE IN ACCORDANCE WITH
THE CURRENT EDITION OF THE SDI SPECIFICATIONS AND THE SDI DIAPHRAGM MANUAL
2. STEEL ROOF DECK AND SIDING IS 1 1/2" x 18 GAUGE FACTORY-FINISHED DESIGNED FOR THE
DEAD AND LIVE LOADS INDICATED.
3. STEEL ROOF DECK AND SIDING MUST BE ATTACHED TO SUPPORTS WITH #14 STAINLESS
STEEL SCREWS AND WASHERS AT EA VALLEY (MINIMUM 5 PER PANEL). USE 1/4-INCH BUTYL
TAPE TO SEAL LAPS.
4. THE PLANS INDICATE DECK SPAN DIRECTION.
5. SUSPENDED CEILINGS, LIGHT FIXTURES, DUCTS, AND OTHER UTILITIES MUST NOT BE
SUPPORTED FROM THE STEEL DECK.
6. STEEL DECK MUST CONFORM TO THE COATINGS FOR STRUCTURAL STEEL PROVIDED ON
SHEET S-001.
BLAST DOOR NOTES:
ORIGINAL STANDARD DRAWING IS NAVFAC DRAWING NUMBER 12877612 SHT 3 OF 51
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DN
AN
CE
O
PE
RA
TIO
NS
FA
CI
LIT
Y
CL
W
S M
AG
AZ
IN
E
SMS/CWJ
JWJ
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
SCALE:
CONSTR. CONTR. NO.
NAVFAC DRAWING NO.
EPROJECT NO.:
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
6/3/2025
THESE DRAWINGS ARE AN EXACT REPLICA OF THE STANDARD MAGAZINE TYPE
"CLWS" PROVIDED BY NAVFAC. THE DESIGN WILL BE SITE ADAPTED AND MODIFIED
TO MEET THE SPECIFIC GEOTECHNICAL AND LOADING CONDITIONS SPECIFIC TO
NAVAL SUBMARINE BASE NEW LONDON, GROTON, CONNECTICUT.
9. THE PLOW/TRENCH COVER ASSEMBLY ALONG WITH THE WHEEL/MOTOR ASSEMBLY ARE
NOTIONAL AND SHOWN FOR BIDDING PURPOSES AND MAY VARY BASED ON THE DOOR
MANUFACTURER'S APPROVED DESIGN.
8. BLAST DOOR MANUFACTURER MUST PROVIDE A COMPLETE BLAST DOOR MANUAL THAT
INCLUDES MAINTENANCE AND STEP BY STEP INSTRUCTIONS OF WHEEL REMOVAL.
7. PROVIDE A HAND RELEASE ON THE DESIGNED BRAKING SYSTEM TO RELEASE THE BRAKE
WHEN IT BECOMES NECESSARY TO MANUALLY MOVE THE DOOR. PROVIDE AN AUTOMATIC
RESET TYPE HAND RELEASE SO THAT THE BREAK WILL BE OPERABLE DURING SUBSEQUENT
ELECTRICAL OPERATIONS OF THE DOOR.
6. THE GENERAL CONTRACTOR MUST SELECT A SINGLE SUPPLIER TO PROVIDE A COMPLETE
BLAST DOOR SYSTEM INCLUDING BUT NOT LIMITED TO THE BLAST DOOR AND ALL OF ITS
ASSOCIATED COMPONENTS AND HARDWARE, RAIL, TRENCH, TRENCH COVER ASSEMBLY,
PLOW AND EMBEDDED PLATES.
5. PROVIDE STEEL PLATE BOTTOM WHEELS HAVING A MINIMUM TREAD DIAMETER AS
REQUIRED FOR THE ACTUAL WHEEL LOADING. CONSTRUCTION WHEEL ASSEMBLES TO
PERMIT REMOVAL OF THE WHEEL WITHOUT REMOVING THE DOOR LEAF FOR ITS POSITION
ON THE RAIL.
4. THE BLAST DOOR MANUFACTURER MUST HAVE A MINIMUM OF 10 YEARS OF EXPERIENCE IN
THE DESIGN, CONSTRUCTION AND INSTALLATION OF DOORS WEIGHING A MINIMUM OF 30
KIPS, CONSISTING OF BOTTOM ROLLING DOORS AND LARGE HEAVY DOORS SUCH AS
MAGAZINE BLAST DOORS AND/OR NUCLEAR CONTAINMENT DOORS. THE BLAST DOOR
MANUFACTURER MUST SUBMIT PROOF OF EXPERIENCE TO THE CONTRACTING OFFICER
FOR APPROVAL BY NAVFAC EXWC AND NAVFAC ATLANTIC. A MINIMUM OF 5 EXAMPLES
MUST BE SUBMITTED.
3. THE DOOR MANUFACTURER MUST COMMENCE A FIELD DEMONSTRATION OF EACH DOOR IN
THE PRESENCE OF A GOVERNMENT OFFICIAL, CONSISTING OF A SUCCESSFUL CYCLE OF
OPENING AND CLOSING THE DOOR BY CONTROLS, OPENING AND CLOSING OF TRENCH
PLATES BY DOOR PLOWS, LOCKING AND UNLOCKING DOOR, AND ALIGNMENT OF DOOR IN
SECURITY PILASTER.
2. THE DOOR MANUFACTURER MUST COMMENCE A SHOP DEMONSTRATION OF EACH DOOR IN
THE PRESENCE OF A GOVERNMENT OFFICIAL, CONSISTING OF A SUCCESSFUL CYCLE OF
OPENING AND CLOSING THE DOOR BY CONTROLS, OPENING AND CLOSING OF TRENCH
PLATES BY DOOR PLOWS AND ALIGNMENT OF DOOR IN SECURITY PILASTER.
DEMONSTRATION MUST BE A MINIMUM OF HALF THE LENGTH OF THE DOOR TRAVEL.
DEMONSTRATION MUST ALSO INCLUDE MANUAL OPERATION OF BLAST DOOR IN BOTH
DIRECTIONS.
1. THE BLAST DOOR MANUFACTURER MUST BE SOLELY RESPONSIBLE FOR INSTALLATION AND
ERECTION OF THE BLAST DOOR.
3. PREFABRICATED TRENCH DRAINS MUST BE 6" WIDE, SHALLOW, PRECAST POLYESTER
CONCRETE CHANNEL OF INTERLOCKING DESIGN. 3" OUTLETS. DUCTILE IRON EDGE RAIL
AND EXTRA HEAVY DUTY, DIN19580 LOAD CLASS E DUCTILE IRON SLOTTED TOP GRATE
FASTENED TO RAIL. GRATE SLOTS MUST BE NO WIDER THAN 1/4" OR PROVIDE STAINLESS
STEEL MESH SCREEN FASTENED TO BOTTOM OF GRATES. MESH OPENINGS MUST BE NO
LARGER THAN 1/4" TO MITIGATE RODENT ENTRY.
2. UNDERGROUND DRAINAGE PIPING MUST CONSIST ASTM D2665 SCH 40 PVC SOLID CORE
PIPING WITH DWV PATTERN FITTINGS. PERFORATED DRAIN PIPING MUST INCLUDE 1/2"
HOLES SPACED 5" O.C. IN TWO ROWS 120 DEGREES APART PER ASTM D2729. ALL
PERFORATED DRAIN PIPING MUST BE INSTALLED WITH HOLES FACING DOWN.
1. FLOOR DRAIN FIXTURES MUST CONSIST OF A CAST IRON BODY, NICKEL BRONZE
ADJUSTABLE TOP, 6" ROUND STRAINER, FLASHING COLLAR, SURFACE MEMBRANE CLAMP,
AND DEEP SEAL TRAP. PROVIDE WITH BARRIER-TYPE TRAP SEAL PROTECTION DEVICE
CONFORMING TO ASSE 1072 WHERE CONNECTING TO SANITARY SEWER SYSTEM.
10. MANUFACTURER TO DESIGN AND FURNISH DOOR STOPS AT TRAILING AND LEADING EDGES
OF DOOR.
SCALE: NONE
EXTRA REINFORCING AROUND OPENINGSB4
(2) #5 x 4'-0" EACH FACE
TYP 4 LOCATIONS
ADDITIONAL REINF
SEE NOTE 1
D/2 +
LAP LENGTH
TYP
CL
SYM ABOUT
OPNG
D /2
LA
P
LE
N G
TH
TY
P D
CL
SYM ABOUT
OPNG
L/
L/
W /2
LA
P
LE
N G
TH
TY
P
W/2
L/2 +
LAP LENGTH
TYP
RECTANGULAR OPNG DETAIL
CIRCULAR OPNG DETAIL
NOTES:
1. PROVIDE ADDITIONAL REINFORCING THE SAME SIZE AS DISCONTINUOUS REINFORCEMENT AT OPENING. QUANTITY OF REINFORCING IN EACH DIRECTION MUST BE EQUAL TO OR ONE GREATER THAN THE NUMBER OF DISCONTINUOUS BARS. PLACE 1/2 OF ADDITIONAL REINFORCING BARS EACH SIDE OF OPENING, PLACE ADDITIONAL REINFORCEMENT AT 3" OC (TYPICAL BOTH DIRECTIONS AND ALL LAYERS OF REINFORCEMENT). START FIRST BAR 2" CLEAR TO OPENING.
2. EXTEND ADDITIONAL REINFORCING BEYOND EDGE OF OPENING AS SHOWN ABOVE. ADDITIONAL BARS MAY TERMINATE AT THE END OF THE WALL WITH A STANDARD HOOK WHERE THE LENGTH OF THE WALL WILL NOT PERMIT BARS TO
EXTEND AS SHOWN ABOVE.
3. TYPICAL WALL OR SLAB REINFORCING NOT SHOWN FOR CLARITY. TERMINATE TYPICAL REINFORCING 2" CLEAR TO
OPENING.
4. ADDITIONAL REINFORCING AS SHOWN ABOVE IS REQUIRED IN ANY CASE FOR SLABS, WALLS, AND FOUNDATIONS WHERE THE OPENING SIZE IS GREATER THAN THE SPACING OF REINFORCING IN EITHER DIRECTION MINUS 4" OF
CONCRETE COVER (2" COVER EACH SIDE OF OPENING).
CL
SYM ABOUT
OPNG
MINIMUM TENSION LAP
SPLICE LENGTHS ("1.3 ")
BAR
SIZE
f' c = 5,000 PSI
TOP BARS OTHER BARS
31.2 31.2
36.9 31.2
46.1 35.5
55.4 42.6
80.7 62.1
92.3 71.0
104.1 80.1
117.2 90.1
130.1 100.1
MINIMUM EMBEDMENT LENGTHS
FOR STANDARD END HOOKS (" ")
BAR SIZE f' c > 5,000 PSI dh d
4" MIN
D = FINISHED INSIDE BEND DIAMETER
TIE OR STIRRUP
NOTES:
6d OR d
PRINCIPAL REINFORCING
D D
90° HOOK
D d D
4d OR
2 1/2" MIN
180° HOOK
MAX OFFSET BEND
d d d = BAR DIAMETER
135° HOOK
A
A O
R G
HOOK
A OR G
90° HOOK
#5
#4
#6
#7
#8
#10
#9
#11
#3
DIMENSIONS OF STANDARD
180-DEG HOOKS, ALL GRADE
A OR G J D
DIMENSIONS OF STANDARD
90-DEG HOOKS, ALL GRADE
A OR G D
135° SEISMIC HOOK
5.25
4.5
2.5
1.5
A OR GBAR SIZE
2.5
5.25
4.5
3.75
4.5
5.5
D APPROX H
STIRRUP HOOKS
6 610.5
O R
G
H
#5
#4
#6
#7
#8
#3 #5
#4
#6
#7
#8
#10
#9
#11
#3
#5
#4
#6
#7
#8
#10
#9
#11
#3
SEISMIC HOOP
CLOSED TIE DETAIL
REINFORCEMENT
SPLICE SCHEDULE
3" M
AX
BAR
SIZE
6d (T
YP
1/
2" M
IN
d O
R
6, 7, B
AR
S
SCALE: NONEC1 SCALE: NONEC2 STIRRUP AND TIE HOOK DIMENSIONS
SCALE: NONEB2
NOTE:
1. PLACE DEPTH GAUGE ABOVE WATERPROOFING
MEMBRANE SYSTEM.
NOTES:
1. IF CONCRETE COVER IS NOT GREATER THAN THE DIAMETER OF THE BAR OR THE CENTER TO
CENTER SPACING IS NOT GREATER THAN (3) BAR DIAMETERS, THEN VALUES MUST BE
INCREASED BY 50%. ALL LAPS ARE TYPICAL TENSION LAP SPLICES U.N.O. ON PLANS OR DETAILS.
2. "TOP BARS" ARE HORIZONTAL BARS WITH MORE THAN 12 INCH DEPTH OF CONCRETE CAST
BELOW THEM.
3. IF CONCRETE COVER IS NOT GREATER THAN 2 1/2 INCH AND THE END COVER OF HOOK IS NOT
GREATER THAN 2 INCH, THEN VALUES MUST BE INCREASED BY 43%.
4. LAPS SPLICES AND EMBEDMENT LENGTHS SHOWN IN THIS DETAIL ARE BASED ON A DYNAMIC
INCREASE FACTOR = 1.29. LAPS FOR REINFORCEMENT IN STRUCTURAL COMPONENTS NOT
RELATED TO BLAST DESIGN (WING WALLS, FOUNDATIONS, SLAB-ON-GRADE) MAY BE REDUCED BY
THE DYNAMIC INCREASE FACTOR. LAP SPLICES FOR REINFORCEMENT IN BLAST COMPONENTS
(HEADER BEAM, HEADWALL, ROOF SLAB, SIDE/ END WALLS, PILASTERS) MAY NOT BE REDUCED BY
THE DYNAMIC INCREASE FACTOR.
5. PER UFC 3-340-02, FOR BLAST COMPONENTS SPLICES OF CONCRETE REINFORCEMENT MUST BE STAGGERED ON OPPOSITE FACES AND SPLICES OF ADJACENT PARALLEL BARS WITHIN THE SAME
LAYER MUST BE STAGGERED.
ALTERNATE 90 DEG HOOK ON
CONSECUTIVE CROSSTIES
NOTE:
1. THIS IS A GENERAL DETAIL
ONLY, UNO, AND THE STIRRUPS
FOR THE HEADER BEAM
PILASTER, HEADWALL AND
ROOF MUST BE BENT AS
SHOWN IN THEIR
CORRESPONDING DETAILS.
2. USING A U STIRRUP WITH A
CROSS-TIE INSTEAD OF A
CLOSED TIE IS ACCEPTABLE
FOR BEAMS ONLY, PER ACI
318-19 PARAGRAPH 9.7.7.
EXTENSION TO BE
THE GREATER OF
6 BAR DIAMETERS
AND 3 INCHES
PIPE
TO BASE
1' -0
BASE PLATE FOR
MOUNTING TO CONCRETE
EDGE OF
CONCRETE
HOLE FOR
FASTENERS
1 1/4"
TYPICAL
CL POST
VERTICAL POST
BASE PLATESIDE VIEW
ALUMINUM GUARDRAIL
POST DETAIL
SCALE: NONEB1
6"
6"
1/2" THK BP
(4) 1/2" DIA POST
INSTALLED EPOXY
ANCHORS w/ 4" MIN
EMBED. EACH EPOXY
ANCHOR MUST HAVE
A MIN 5,000 LB
TENSILE CAPACITY
SCALE: NONEA2
1 1/2" WIDE
CONT KEYWAY CONT REINF THRU
CONST JT
CONT REINF
THRU CONST JT
ROUGHEN SURFACE
LAP SOIL WHERE
APPLICABLE
EQ
EQ
EQ
NOTES:
1. TO BE USED ONLY WHERE CALLED FROM IN THE CONTRACT
DOCUMENTS, OR AS PERMITTED BY THE CONTRACTING OFFICER.
ROUGHEN CONSTRUCTION JOINT (CJ)
KEYED CONSTRUCTION JOINT (KCJ)
T/ CONC
EL= SEE PLAN
60°
"D 1"
LAP
LAP
CONC FTG/
GRADE BEAM
LAP
FOOTING/GRADE
BEAM REINF
NOTES:
1. FOR FOOTING ELEVATION DEPTH AND
REINFORCING, SEE PLAN AND OTHER
STANDARD AND COMMON DETAILS.
2. MAXIMUM INDIVIDUAL STEP = 2'-0" ("D2" - "D1").
"D 2"
WALL REINFORCEMENT AT
CORNERS AND INTERSECTIONS
STD HOOK
LAP SPLICE + 6"
STD HOOK
NOTES:
1. ALL HOOKS MUST BE STD 90 DEGREE HOOKS UNO.
2. SEE DRAWINGS FOR ADDITIONAL HORIZONTAL BARS.
STAGGER BETWEEN TYPICAL REINF SPACING, EXTEND
TO 1/5 OF DISTANCE TO NEAREST ADJACENT WALL IN
EACH DIRECTION, UNO.
0"
0"
SCALE: NONEA3
SCALE: NONEA1
CONSTRUCTION JOINTTYPICAL MISCELLANEOUS
HOUSEKEEPING PAD (INTERIOR)
SCALE: NONEA5
TYPICAL BOTTOM
STEP FOOTING/GRADE BEAM
LAP
SCALE: NONEA4 DEPTH GAUGE DETAIL
1/
2" C
LR
DO NOT DAMAGE
SLAB/GRADE BM
REINF WHEN
DRILLING HOLES
6"
(MIN)
INTENTIONALLY
ROUGHEN TO 1/4"
AMPLITUDE, DAMPEN
SURFACE PRIOR TO PAD
PLACEMENT SAME AS PERIM
DWLS 2FTx2FT
NOMINAL INTERIOR
SPACING
CONC SLAB
EDGE OF EQUIPMENT,
SEE OTHER DRAWINGS
FOR SIZE AND
LOCATIONS
#4@8 EW
4" M
IN
/8
" M
AX
U N
LE
SS
N O
TE
D
O
TH
ER
W
IS
E
#4@8" OC EPOXY
DWLS W/ 4" MIN
EMBED
NOTE:
1. PLACE DEPTH GAUGE ABOVE WATERPROOFING MEMBRANE SYSTEM.
1' -3
2' -0
0"
2"
REMOVABLE CAP
MARK AND LABEL PIPE IN 1"
INCREMENTS TO INDICATE
HEIGHT ABOVE TOP OF
CONCRETE
3" DIA PVC PIPE BONDED TO
FIBERGLASS PLATE. PAINT PIPE
BRIGHT ORANGE
18"x18"x3/8" FIBERGLASS
PLATE
6" SAND MATERIAL
TOP OF ROOF
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DN
AN
CE
O
PE
RA
TIO
NS
FA
CI
LIT
Y
CL
W
S M
AG
AZ
IN
E
SMS/CWJ
JWJ
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
SCALE:
CONSTR. CONTR. NO.
NAVFAC DRAWING NO.
EPROJECT NO.:
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
6/3/2025
S-003ORIGINAL STANDARD DRAWING IS NAVFAC DRAWING NUMBER 12877613 SHT 4 OF 51
THESE DRAWINGS ARE AN EXACT REPLICA OF THE STANDARD MAGAZINE TYPE
"CLWS" PROVIDED BY NAVFAC. THE DESIGN WILL BE SITE ADAPTED AND MODIFIED
TO MEET THE SPECIFIC GEOTECHNICAL AND LOADING CONDITIONS SPECIFIC TO
NAVAL SUBMARINE BASE NEW LONDON, GROTON, CONNECTICUT.
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DN
AN
CE
O
PE
RA
TIO
NS
FA
CI
LIT
Y
CL
W
S M
AG
AZ
IN
E
SMS/CWJ
JWJ
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
6/3/2025
G
EN
ER
AL
N O
TE
S
- 3
SB JC LAP
NONE
12894249
S-004S
NEK
SITE SPECIFIC DATA*:
1. SITE SPECIFIC WIND DATA:
A. SITE SPECIFIC ULTIMATE WIND SPEED: 136 MPH
B. EXPOSURE: "C"
C. RISK CATEGORY: III
2. SITE SPECIFIC SEISMIC DATA:
A. RISK CATEGORY: III
B. IMPORTANCE FACTOR: 1.25
C. SEISMIC DESIGN CATEGORY: B
D. SITE SEISMICITY: SS = 0.19g
S1 = 0.052g
E. SITE CLASS: D
3. SNOW DESIGN DATA:
A. GROUND SNOW LOAD: 30 PSF
B. EXPOSURE FACTOR: 1.0
C. IMPORTANCE FACTOR: 1.10
D. THERMAL FACTOR: 1.2
4. ENVIRONMENTAL SEVERITY CLASSIFICATION.
A. ESC C4
* - SITE SPECIFIC DATA INCLUDED FOR INFORMATION
ONLY. REFER TO S-001 FOR PARAMETERS USED IN
THE DESIGN AND DEVELOPMENT OF THE STANDARDIZED
DRAWINGS
SITE SPECIFIC GEOTECHNICAL DATA:
1. FOUNDATION DESIGN IS IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEERING
REPORT PREPARED BY JACOBS, DATED 07 FEBRUARY 2025.
2. FOUNDATION SYSTEMS:
CLWS-001, CLWS-002, CLWS-003, CLWS-004, CLWS-005:
PLACE FOUNDATIONS ON REINFORCED AND COMPACTED
ENGINEERED FILL OVER CEMENTITIOUS RIGID INCLUSIONS
(GROUND IMPROVEMENT SYSTEM), REFER TO CIVIL PLANS
SHEET B-101, GROUND IMPROVEMENT PLANS FOR
ADDITIONAL REQUIREMENTS. GROUND IMPROVEMENT
SYSTEM MUST CREATE A FOUNDATION SUBGRADE WITH THE
MINIMUM BEARING CAPACITY AS NOTED ON S-001 AND A
MAXIMUM ALLOWABLE SETTLEMENT OF 3/4 INCH.
CLWS-006
PLACE FOUNDATIONS ON OVEREXCAVATED AREA USING
CRUSHED AGGREGATE OVER BEDROCK. REFER TO CIVIL
PLANS SHEET B-101 FOR ADDITIONAL INFORMATION.
3. PROVIDE MEASURES TO PREVENT WATER, FROST OR ICE
FROM PENETRATING FOOTING OR SLAB SUBGRADE BEFORE
PLACING CONCRETE. FOOTINGS, MUD SLABS, OR BUILDING
SLABS MUST NOT BE PLACED INTO OR AGAINST SUBGRADE
CONTAINING FREE WATER, FROST OR ICE.
4. CONCRETE FOUNDATIONS OR A 3" THICK CONCRETE MUD
MAT (LEAN CONCRETE) MUST BE PLACED THE SAME DAY THE
SUBGRADE IS INSPECTED. IF THE GROUND SURFACE IS
DISTURBED BEFORE CONCRETE IS PLACED, THE SUBGRADE
MUST BE RE-INSPECTED BY THE CONTRACTOR'S
GEOTECHNICAL ENGINEER AT NO ADDITIONAL COST.
5. DESIGN, PROVIDE AND MAINTAIN DEWATERING SYSTEMS,
EARTH RETENTION SYSTEMS, BRACING. PROTECT EXISTING
STRUCTURES AND UTILITIES DURING CONSTRUCTION.
6. WHEN FILLING AGAINST OPPOSITE SIDES OF A WALL OR
STRUCTURE, BACKFILL IN LIFTS THAT MAINTAIN LEVEL
ELEVATIONS WITHIN 12" ON BOTH SIDES TO BALANCE THE
LATERAL PRESSURE.
7. EARTHWORK, INCLUDING FOUNDATION SUBGRADE, FILL AND
BACKFILL MUST BE INSPECTED AND APPROVED BY THE
CONTRACTOR'S GEOTECHNICAL ENGINEER.
8. WHERE EXCAVATION WOULD BE BELOW A LINE EXTENDING
UPWARD AT A 1.0H TO 1.0V SLOPE FROM THE BOTTOM OF A
FOUNDATION OR UTILITY, PROVIDE SHEETING, SHORING, AND
BRACING. DO NOT UNDERMINE EXISTING CONSTRUCTION.
CODES AND STANDARDS:
American Concrete Institute (ACI) 301 (2016) Specifications for Structural Concrete 318 (2014) Building Code Requirements for Structural Concrete
American Institute of Steel Construction (AISC) 360 (2016) Specification for Structural Steel Buildings
American Society for Testing and Materials (ASTM) A29 (2020) Standard Specification for General Requirements for Steel Bars, Carbon and Alloy, Hot-Wrought A500 (2020) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes A572 (2018) Standard Specification for High-Strength Low-Alloy Columbium-Vanadium Structural Steel A615 (2020) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement A992 (2020) Standard Specification for Structural Steel Shapes A1064 (2018) Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete F1554 (2018) Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength F3125 (2020) Standard Specification for High Strength Structural Bolts and Assemblies, Steel and Alloy Steel, Heat Treated, Inch Dimensions 120 ksi and 150 ksi Minimum Tensile Strength, and Metric Dimensions 830 MPa and 1040 MPa Minimum Tensile Strength
American Society of Civil Engineers (ASCE) 7-16 (2016) Minimum Design Loads and Associated Criteria for Buildings and Other Structures
American Society Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE)
62.1 (2016) Ventilation for Acceptable Indoor Air Quality F16 (2017) Fundamentals Chapter 16 – Ventilation and Infiltration
Department of Defense (DoD)
5100.76 (2012) Physical Security of Sensitive Conventional Arms, Ammunition, and Explosives
International Code Council (ICC) IBC (2018) International Building Code IMC (2018) International Mechanical Code IPC (2018) International Plumbing Code
National Fire Protection Association (NFPA) 70 National Electrical Code 780 Stand
SCALE: 1" = 30'
HEADWALL ELEVATIONB1
57'-8" 40'-0"
2'-0"
16'-8" 26'-8" 16'-8" 16'-8" 25'-4" 14'-2"
2'-0"
SCALE: 1" = 30'
OVERALL PLANC1
C
LW
S-
F.
F.
E.
=8 2.
C
LW
S-
F.
F.
E.
=8 2.
C
LW
S-
F.
F.
E.
=8 3.
C
LW
S-
F.
F.
E.
=8 3.
C
LW
S-
F.
F.
E.
=8 3.
C
LW
S-
F.
F.
E.
=8 4.
22'-8" TYP
1' -4
40'-0" 16'-8" 26'-8" 16'-8" 40'-0" 16'-8" 26'-8" 16'-8" 40'-0" 16'-8" 26'-8" 16'-8" 40'-0" 16'-8" 26'-8" 16'-8" 40'-0"
1' -4
1' -4
1' -4
1' -4
1' -4
1' -4
1' -4
1' -4
1' -4
1' -4
T/WALL
EL. 113.92'
T/WALL
EL. 104.25'
T/WALL
EL. 114.25'
T/WALL
EL. 104.58'
T/WALL
EL. 114.58'
T/WALL
EL. 104.92'
T/WALL
EL. 114.92'
T/WALL
EL. 105.25'
T/WALL
EL. 115.25'
T/WALL
EL. 105.58'
T/WALL
EL. 115.58'
T/WALL
EL. 105.92'
'-6
36'-0" 64'-0" 36'-0" 64'-0" 36'-0" 64'-0" 36'-0" 64'-0" 36'-0" 64'-0" 36'-0"
18'-8" 18'-8" 18'-8" 18'-8" 18'-8"
T/
FT
G
2.
T/
FT
G
2.
T/
FT
G
2.
T/
FT
G
3.
T/
FT
G
3.
T/
FT
G
3.
T/
FT
G
3.
T/
FT
G
3.
T/
FT
G
3.
T/
FT
G
4.
61'-8" 60'-2"
NTS
SECTIONA1
A1
O
VE
R
AL
L
PL
AN
SI
TE
A D
AP
TE
D
AS NOTED
S-010S
1. SEE SHEET S-001, S-002, S-003, AND S-004S FOR GENERAL
NOTES.
SHEET NOTES
GRAPHIC SCALE:
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DI
NA
NC
E
OP
ER
AT
IO
NS
FA
CI
LIT
Y
CL
W S
M
AG
AZ
IN
E
SMS/CWJ
EJA
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
A1
C1 S-521S
B1 S-521S
A1 S-521S
EP
D
M C
O
VE
R L
AY
O
U T
- S
IT
E
AD
AP
TE
D
AS NOTED
S-011S
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DI
NA
NC
E
OP
ER
AT
IO
NS
FA
CI
LIT
Y
CL
W S
M
AG
AZ
IN
E
SMS/CWJ
EJA
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
1'=30'-0"
OVERALL PLAN - EPDM COVERAGEA1
S-301S C1
C1
S-201AS
95'-6"
30'-0"
'-0
SE
E
S-
0S , S
-2
AS
, S
-2
BS
, S
-2
C S
SE
E
S-
0S , S
-2
AS
, S
-2
BS
, S
-2
C S
1'-4"
1' -4
1' -4
'-0
'-0
VA
R
IE
S
'-8
C
LW
S-
'-0
'-2
VA
R
IE
S
'-0
1/ 4"
C
LW
S-
2' -0
FT
G
EX
TE
N
SI
O
N (T
YP
EDGE OF FOOTING
R
ET
AI
N
IN
G
W
AL
L, SE
E S-
3, S -4
S
R
ET
AI
N
IN
G
W
AL
L, SE
E S-
3, S -4
S
36" THK CONC
SLAB-ON-GRADE,
UNO
C J
C J
'-0
2' -0
(T
YP
'-8
30"x30"
VENTILATION
DUCT
24"Ø HONEYCOMB
SECURITY DEVICE AT
MAGAZINE WALL (TYP. 2).
REF: A3/M-706
BLAST DOOR
AND TRENCH
S-302 A1
SCALE: 3/32" = 1'-0"
FOUNDATION/ FLOOR PLANA2
3' -5
/4
FOOTING STEP
AT CJ (BOT)
MECH ROOM
DOOR POCKET
PILASTER
5' -0
5'-6"
2'-0"
5'-0"
5'-0"
2'-0"
5'-6" 29'-0"
29'-0"
3'-0"
4'-2"
63'-6"
105'-0"
12'-6"
63'-6"
S-301S
A1 FLOOR DRAIN
TRENCH DRAIN, (TYP)
T/ SLAB EL = 0'-0" @
PERIMETER, (TYP)
T/ FTG EL = 0'-0", (TYP)
A1 S-401
C5 S-704
LONGITUDINAL
FLEXURAL REINF:
#9@8" OC, TOP & BOT
TRANSVERSE FLEXURAL REINF:
#9@8" OC TOP, #10@8" OC BOT
#8@8" OC ADDL TOP REINF,
STAGGER W/ TRANSVERSE
FLEXURAL REINF
30'-9"30'-9" 2'-0"
FTG STEP
(BOT)
CJ
A1
S-201AS
A1 S-202
C1 S-401
A4
S-502 TYP
24"Ø PIPE THRU MECH
ROOM WALL W/SLEEVE
(TYP. 2). REF: B3/M-706
SLOPE
SLOPE
SL
O
PE
SL
O
PE
2'-8"
T/ DRAIN EL @
LP = -0'-4" (TYP)
CLWS-001
C1
S-201BS
CLWS-002
THRU 005
C1
S-201CS
CLWS-006
A1
S-201BS
A1
S-201CS
CLWS-001
CLWS-002
THRU 005 CLWS-006
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
DES DRW
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
CHK
OF
EPROJECT NO.:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
- M
ID
-A
TL
AN
TI
C
MI
D-
AT
LA
NT
IC
NA
VA
L S
TA
TI
ON
NO
RF
OL
K, V A
NA
VA
L
SU
BM
AR
IN
E
BA
SE
N
EW
L O
ND
O
N G
RO
TO
N, C
O
NN
EC
TI
CU
T
P-
W
EA
PO
NS
M
AG
AZ
IN
E
OR
DN
AN
CE
O
PE
RA
TIO
NS
FA
CI
LIT
Y
CL
W
S M
AG
AZ
IN
E
SMS/CWJ
JWJ
HPN
1667770
APPROVED BY LCDR PETE
FOVARGUE NAVFAC FEAD
DIRECTOR - NLON, VIA EMAIL
SCALE:
CONSTR. CONTR. NO.
NAVFAC DRAWING NO.
EPROJECT NO.:
FAX: 571.218.1600
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
6/3/2025
S-101S
1. ALL ELEVATIONS ARE IN REFERENCE TO A DATUM
ELEVATION OF 0'-0" FOR THE MAGAZINE FINISHED FLOOR
ELEVATION. SEE CIVIL DRAWINGS FOR ACTUAL
ELEVATIONS.
2. SEE SHEETS S-001, S-002, S-003, AND S-004S FOR GENERAL
NOTES.
3. ALL REINFORCING STEEL MUST BE CONTINUOUSLY
BONDED AND GROUNDED PER S-002 AND A1/E-504S
4. SLAB-ON-GRADE MUST BE MOIST CURED FOR A MINIMUM
OF 14 DAYS.
5. SLAB-ON-GRADE CONSTRUCTION JOINTS ARE INDICATED
AS "CJ" ON PLAN. SEE STANDARD DETAIL ON S-003 FOR
CONSTRUCTION JOINT DETAILS.
6. BLAST DOOR IS NOT SHOWN FOR CLARITY.
7. SEE SHEET S-302 FOR ARRANGEMENT OF SLAB
REINFORCEMENT AND FOR SIDEWALL REINFORCEMENT
SIZE, SPACING, AND ARRANGEMENT.
8. SEE SHEET S-104 FOR FOUNDATION DRAINAGE FLOOR
PLAN.
9. SEE CIVIL FOR EXTENTS OF RIGID…