This document is a Technical Amendment (Number 0008) for a dental clinic replacement project at the Marine Corps Recruit Depot in Parris Island, South Carolina. The amendment modifies several technical specifications across multiple sections, including sterilizers and associated equipment, medical and dental equipment, healthcare casework, and elevator systems.

Key changes include updates to the chemistry delivery system for washer/disinfectors, addition of a wall-mounted dental utility center, deletion of specifications for dental prosthetics casework, and modifications to elevator parameters such as load capacity and plunger type. The amendment specifies technical details for equipment like sterilizers, loading cars, washer/disinfectors, cabinets, and elevator components, ensuring precise requirements for the dental clinic replacement project. The technical amendment is dated 21 April 2025 and is associated with solicitation number N62470-19-D-5015.

View the file

Other files

File Type Posted
AMD 0010 - WD SC20250008.pdf PDF
N4008525R2500 AMD 0010.pdf PDF
N4008525R2500 AMD 0009.pdf PDF
USMC ESS_Standard Equip List-v6.1.xlsx XLSX spreadsheet
N4008525R2500 AMD 0008.pdf PDF
N4008525R2500 AMD 0007.pdf PDF
AMD 0006 - Technical Amendment 0008 Continuation Sheet.pdf PDF
N4008525R2500 AMD 0006.pdf PDF
AMD 0005 - Technical Amendment 0007 Continuation Sheet.pdf PDF
AMD 0005 - 21-54-23019_CP CPT-2-PPD.xls XLS spreadsheet
AMD 0005 - CPT-1_forAPILE.xls XLS spreadsheet
AMD 0005 - 21-54-23019_SP CPT-1-PPD.xls XLS spreadsheet
AMD 0005 - Technical Amendment 0007.pdf PDF
AMD 0005 - 21-54-23019_CP CPT-2-BSC.XLS XLS spreadsheet
AMD 0005 - 21-54-23019_SP CPT-1 - VsResults.xlsx XLSX spreadsheet
N4008525R2500 AMD 0005.pdf PDF
AMD 0005 - 21-54-23019_SP CPT-1-BSC.XLS XLS spreadsheet
AMD 0005 - 21-54-23019 P-7889 Dental Clinic Replacment - Full Report.pdf PDF
N4008525R2500 AMD 0004.pdf PDF
Geo Tech portion P-7889 MCRD PARRIS ISLAND CORRECTED FINAL BASIS OF DESIGN - 26 AUGUST 2024.pdf PDF
674002.PDF PDF
3 of 23 Foundation Plan Building P-88-A (602).pdf PDF
602001.PDF PDF
4 of 23 Foundation Details Building P-88-A (602).pdf PDF
602002.PDF PDF
674001.PDF PDF
602003.PDF PDF
674003.PDF PDF
Technical Amendment 0006 Continuation Sheet.pdf PDF
100 Corrected Final Haz Mat Report B602 and B674 Parris Island - March 2024.pdf PDF
N4008525R2500 AMD 0003.pdf PDF
P7889 VISIT SITE SIGN IN SHEET.pdf PDF
N4008525R2500 AMD 0002.pdf PDF
Technical Amendment 0003.pdf PDF
Technical Amendment 0002.pdf PDF
Attachment C - Price Proposal Form REVISED.docx DOCX document
N4008525R2500 AMD 0001.pdf PDF
Technical Amendment 0004.pdf PDF
Attachment H - Small Business Subcontracting Plan.docx DOCX document
1686626dwg04of14_LANDSCAPE.pdf PDF
1686626dwg11of14_ELECTRICAL.pdf PDF
Attachment D - Construction Experience Data Sheet.docx DOCX document
1686626dwg12of14_AUDIOVISUAL.pdf PDF
Attachment G - Small Business Participation Commitment Document (SBPCD).docx DOCX document
1686626dwg08of14_PLUMBING.pdf PDF
Attachment B - PIEE Vendor Access Instructions.pdf PDF
1686626dwg07of14_GENERAL SERIES.pdf PDF
Attachment C - Price Proposal Form.docx DOCX document
1686626dwg10of14_GENERAL SERIES.pdf PDF
1686626dwg02of14_LIFESAFETY.pdf PDF
Show 40 more

Latest 50 of 63 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NAVFAC ATLANTIC

TECHNICAL AMENDMENT 0008

Solicitation: N62470-19-D-5015 Title: PROJECT P7889 DENTAL CLINIC REPLACEMENT

MARINE CORPS RECRUIT DEPOT

PARRIS ISLAND – BEAUFORT, SC

Date: 21 April 2025

SECTION 11 71 00 – STERILIZERS AND ASSOCIATED EQUIPMENT

Paragraph 2.4.3 S0295, Loading Car and Transfer Carriage

FROM:

Sterilizer load car with fixed base shelf and two adjustable shelves, stainless steel. Load car transfer carriage with swivel casters, load car locking mechanisms, stainless steel. Load car and carriage shall be provided to match and as accessories to Item S0237, Sterilizer. Provide connection to UL301.

TO:

Sterilizer load car with fixed base shelf and two adjustable shelves, stainless steel. Load car transfer carriage with swivel casters, load car locking mechanisms, stainless steel. Load car and carriage shall be provided to match and as accessories to Item S0237, Sterilizer. Provide connection to UL301.

Paragraph 2.4.8 US960, Chemistry Delivery System

FROM:

Chemistry delivery system capable of providing automated solution for delivering Prolystica Ultra Concentrate Chemistries to Washer/Disinfectors. Pump must maintain accurate delivery of solution from 1/40 to 1/10 oz/gal. Provide system compatible with selected washer disinfectors item S0960E.

TO:

Chemistry delivery system capable of providing automated solution for delivering Prolystica Ultra Concentrate Chemistries to Washer/Disinfectors. Pump must maintain accurate delivery of solution from 1/40 to 1/10 oz/gal. Provide system compatible with selected washer disinfectors item S0960E. Chemistry delivery system capable of providing automated bulk chemistry solutions to Washer/Disinfector (JSN S0960E); must provide and maintain accurate delivery of solution as required per Washer/Disinfector manufacturer's instructions.

SECTION 11 72 13 – MEDICAL AND DENTAL EQUIPMENT

Paragraph 2.2.13 D7090, Utility Center, Dental, Floor Mounted

FROM:

Surface floor mounted dental utility box with removable cover. Verify required utilities as indicated in the drawings. Coordinate to function with the dental delivery system, item D8250.

TO:

Surface floor mounted dental utility box with removable cover. Verify required utilities as indicated in the drawings. Coordinate to function with the dental delivery system, item D8250.

Add Paragraph

2.2.14 D7090R, Utility Center, Dental, Wall Mounted

Surface wall mounted dental utility box with removable cover. Verify required utilities as indicated in the drawings.

SECTION 12 35 70 – HEALTHCARE CASEWORK

Paragraph 2.1.3 Dental Prosthetics Casework

DELETE THE FOLLOWING PARAGRAPHS IN THEIR ENTIRITY

Provide dental prosthetics casework of baked enamel carbon steel. Color of finish selected by the Contracting Officer from the manufacturer's standard colors.

Baked enamel carbon steel must contain a minimum of 40 percent recycled steel content.

Provide data identifying percentage of recycled content for baked enamel carbon steel dental prosthetics casework.

SECTION 14 24 23 METAL WALL PANELS

Paragraph 2.1.1.1. Elevator No. 1CE1 and 1CE2

FROM:

a. Type: In-Ground Direct Plunger

b. Rated load: 4500 lb.

TO:

a. Type: In-Ground Direct Plunger Twinpost above ground 1-stage

b. Rated load: 4500 4000 lb.

Paragraph 2.1.1.2. Elevator No. 1FE3

FROM:

a. Type: In-Ground Direct Plunger

TO:

a. Type: In-Ground Direct Plunger Twinpost above ground 1-stage

-- End of Technical Amendment 0008 --

P7889 Dental Clinic Replacement Marine Corps Recruit Depot Parris Island - Beaufort, South Carolina

SECTION 11 71 00

STERILIZERS AND ASSOCIATED EQUIPMENT

05/20

PART 1 GENERAL

1.1 RELATED REQUIREMENTS

The requirements of Section 11 70 00 GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT apply to this Section.

1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

ASME B16.18 (2021) Cast Copper Alloy Solder Joint Pressure Fittings

ASME B16.22 (2021) Standard for Wrought Copper and Copper Alloy Solder Joint Pressure Fittings

ASME BPVC SEC II-C (2017) BPVC Section II-Materials Part C-Specifications for Welding Rods Electrodes and Filler Metals

ASME BPVC SEC VIII D1 (2019) BPVC Section VIII-Rules for Construction of Pressure Vessels Division 1

ASTM INTERNATIONAL (ASTM)

ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel

ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip

ASTM A240/A240M (2020a) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications

ASTM A264 (2012; R 2019) Standard Specification for Stainless Chromium-Nickel Steel-Clad Plate

ASTM A265 (2012) Standard Specification for Nickel and Nickel-Base Alloy-Clad Steel Plate

ASTM A269/A269M (2015; R 2019) Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service

SECTION 11 71 00 Page 1

ASTM A285/A285M (2017) Standard Specification for Pressure Vessel Plates, Carbon Steel, Low- and Intermediate-Tensile Strength

ASTM A312/A312M (2019) Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes

ASTM A515/A515M (2017) Standard Specification for Pressure Vessel Plates, Carbon Steel, for Intermediate- and Higher-Temperature Service

ASTM A568/A568M (2019a) Standard Specification for Steel, Sheet, Carbon, Structural, and High-Strength, Low-Alloy, Hot-Rolled and Cold-Rolled, General Requirements for

ASTM B32 (2020) Standard Specification for Solder Metal

ASTM B39 (1979; R 2008) Standard Specification for Nickel

ASTM B42 (2020) Standard Specification for Seamless Copper Pipe, Standard Sizes

ASTM B43 (2020) Standard Specification for Seamless Red Brass Pipe, Standard Sizes

ASTM B88 (2022) Standard Specification for Seamless Copper Water Tube

ASTM B88M (2020) Standard Specification for Seamless Copper Water Tube (Metric)

ASTM B127 (2019) Standard Specification for Nickel-Copper Alloy (UNS N04400) Plate, Sheet, and Strip

ASTM B135/B135M (2017) Standard Specification for Seamless Brass Tube

ASTM B163 (2019) Standard Specification for Seamless Nickel and Nickel Alloy Condenser and Heat-Exchanger Tubes

ASTM B164 (2003; R 2014) Standard Specification for Nickel-Copper Alloy Rod, Bar, and Wire

ASTM B165 (2019) Standard Specification for Nickel-Copper Alloy (UNS N04400)* Seamless Pipe and Tube

ASTM B166 WARNING: Text in tags exceeds the maximum length of 300 characters

ASTM B167 WARNING: Text in tags exceeds the maximum

SECTION 11 71 00 Page 2 length of 300 characters

ASTM B339 (2019) Standard Specification for Pig Tin

ASTM B348/B348M (2019) Standard Specification for Titanium and Titanium Alloy Bars and Billets

INTERNATIONAL CODE COUNCIL (ICC)

ICC IPC (2021; TIA 20-1) International Plumbing Code

1.3 SUBMITTALS

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Submit approved detail drawings for each item of equipment listed above that interfaces with other items of equipment or construction.

SD-03 Product Data

Equipment Submit catalog numbers, trade names, literature, data sheets, diagrams and other pertinent data for each item of equipment listed above to evaluate performance, function, materials, dimensions and appearance.

SD-06 Test Reports

Field Tests and Inspections Submit field tests and inspection reports for each item of equipment listed above signed by authorized official responsible for field tests and inspections.

SD-10 Operation and Maintenance Data

Operations and Maintenance Data ; G Training ; G Submit Data Package 3, including training requirements, for each item of equipment listed above in accordance with requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA. In addition, provide hard copies consisting of two Operator's Manuals and two Service Manuals.

1.4 WARRANTY

Provide warranties as specified in this Section. Refer to Article WARRANTY in Section 11 70 00 GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT for additional requirements.

SECTION 11 71 00 Page 3

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Carbon Steel

ASTM A36/A36M, ASTM A285/A285M , ASTM A515/A515M , or ASTM A568/A568M , cold rolled sheets, commercial bright finish.

2.1.2 Nickel

ASTM B39. Nickel-copper alloy or stainless steel or white metal.

2.1.3 Nickel and Nickel-Alloy Clad Steel

ASTM A265. Nickel or nickel-copper alloy and steel for pressure vessels, mill-rolled under heat and pressure until integrally bonded over entire interface.

2.1.4 Nickel-Copper Alloy (Monel Metal)

ASTM B127, ASTM B163, ASTM B164, or ASTM B165 plate sheet and strip.

2.1.5 Stainless Steel

ASTM A167, Type 301 or 316L; Class 304L for welded construction and Class 302 or 304 for construction formed without welding. Exposed surfaces of stainless steel to have satin finish.

2.1.6 Stainless Steel Bars and Rods

ASTM B166.

2.1.7 Stainless Steel for Pressure Vessels

ASTM A240/A240M .

2.1.8 Stainless Steel Clad

ASTM A264 for pressure vessels.

2.1.9 Tin

ASTM B339.

2.1.10 Titanium

For construction of products used in contact with distilled water, ASTM B348/B348M , Grade 2.

2.2 PIPING AND TUBING

Seamless, annealed, and ground smooth. Welded tubing to be thoroughly heat treated and properly quenched to eliminate carbide precipitation, drawn true to size and roundness. Provide piping and tubing conforming to the following:

SECTION 11 71 00 Page 4

2.2.1 Steam Supply and Return Condensate Lines

Copper pipe must conform to ASTM B42; brass pipe must conform to ASTM B43;

brass tube must conform to ASTM B135/B135M , Alloy 230. Include strainer, shut-off valve and pressure gage suitable for steam pressure up to 80 psig .

In return line include steam trap, check valve, and hand shut-off valves.

2.2.2 Gaseous Sterilant Lines

Brass pipe must conform to ASTM B43, Alloy 230; stainless steel tube must conform to ASTM A269/A269M , ASTM A312/A312M , or ASTM B167 as applicable.

2.2.3 Water and Waste Lines

Copper tube must conform to ASTM B88M, ASTM B88 Type K, hard-drawn or annealed for bending; brass tube must conform to ASTM B135/B135M , Alloy 230 or C23000.

2.2.4 Pipe Fittings

Wrought copper or wrought bronze, brazing or solder joint type in accordance with ASME B16.18 and ASME B16.22 . Use ASTM B32,Alloy Sb5 tin-antimony solder to make joints for copper tubing.

2.2.5 Pressure Vessels

Design, construction, materials, and testing of each pressure vessel, including doors, must comply with applicable provisions of ASME BPVC SEC VIII D1 . Submit a signed copy of ASME Form U-1 or U-1A, as shown in ASME BPVC SEC VIII D1 Appendix W, with each sterilizer, as applicable.

2.2.6 Welding Materials

Welding Materials must comply with ASME BPVC SEC II-C . Welding equipment, electrodes, welding wire, and fluxes must be capable of producing satisfactory welds when used by a qualified welder or welding operator using qualified welding procedures.

2.2.7 Connections to Equipment

Prewire and prepipe each unit of equipment complete with trim and fittings. Equipment includes fittings to prevent backflow of polluted water or waste into water supply system or equipment in accordance with ICC IPC . Provide reduced pressure or atmospheric type backflow preventer.

2.3 ELECTRICAL WORK

Provide electric motor-driven equipment complete with motors, motor starters, and controls. Provide electrical equipment and wiring in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Electrical characteristics are as specified herein or as indicated. Provide motor starters complete with thermal overload protection and other components necessary for the motor control specified. Provide each motor of sufficient size to drive the equipment at the specified capacity without exceeding the nameplate rating of the motor. Provide manual or automatic control, protective or signal devices required for the operation specified, and any control wiring required for controls and devices specified.

SECTION 11 71 00 Page 5

2.4 EQUIPMENT

2.4.1 S0237, Sterilizer, ELEC, VAC, 2DO, RCSD 1WLL, 20x20x38

Prevacuum/gravity steam sterilizer for healthcare application. Chamber dimensions: 20 inch by 20 inch by 38 inch deep. In-wall, recessed unit with 2 power doors. Includes S0290 Rack and S0295 Loading car and transfer carriage accessories. Microcomputer monitors and controls operations. Printer recorder for documentation of each cycle performance. For general purpose pre-vacuum or gravity steam sterilization of hospital and laboratory supplies at temperatures in the range from 230 degrees F to 275 degrees F and a liquid cycle with temperatures in the range from 212 degrees F to 250 degrees F. Provide electric unit with on board carbon steel steam generator which receives "treated" make-up water from UL296. Unit shall operate with a minimum feed water conductivity of 38 - 500 microSiemens per centimeter. Steam generator includes an automatic flush and drain system. All other utility requirements as indicated on drawings.

2.4.2 S0290, Rack, 2 Shelves

Sterilizer load rack with two extendible shelves, stainless steel.

Provide to match and as an accessory to Item S0237, Sterilizer.

2.4.3 S0295, Loading Car and Transfer Carriage

Sterilizer load car with fixed base shelf and two adjustable shelves, stainless steel. Load car transfer carriage with swivel casters, load car locking mechanisms, stainless steel. Load car and carriage shall be provided to match and as accessories to Item S0237, Sterilizer. Provide connection to UL301.

2.4.4 S0960E, Washer/Disinfector,ELEC,2DO,RCSD1WLL,26X24X24 CHMBR

A recessed mounted (through one wall), double door (vertical sliding with tempered glass window), multi-level, mechanical, washer/disinfector, minimum chamber size 26x24x24. The unit is controlled by a microcomputer that monitors and controls all unit operations and documents and records each cycle performance. Processing Cycles are pre-programmed with pre-wash, wash/cleaning, rinse, and thermal rinse/disinfection.

Electric-heated "non-vented" unit. Units that require direct connection to exhaust system are not allowed. Sliding power door. For use in health care facilities and laboratories where reusable items (instruments, utensils, anesthesia/respiratory goods, and glass ware) are handled for decontamination purposes. Provide electric unit with "treated" water final rinse. "Treated" water supplied by UL296. Provide unit with sampling valve option on all supply water connections. Utility requirements as indicated in drawings.

2.4.5 S0965, Washer/Disinfector, Dental

Dental thermal disinfector, two-level chamber, general dentistry basket/insert package, oral surgery basket/insert package, direct injection rotary cleaning mechanism. Provide unit with optional drain water cool-down kit to reduce discharge temperature to <140 degrees F .

Unit nominal dimensions: 35 inches H. by 24 inches W. by 24 inches D.

Utility requirements as indicated in drawings.

SECTION 11 71 00 Page 6

2.4.6 S1900A, Window, Pass-Thru, Automated

The Automated Pass-Through Window is an inline vertical lift window with a single operable (movable) panel, and a single non-operable (fixed) panel, an integral continuous stainless steel shelf extending 24 inches on each side with a microwave no-touch sensor plate for opening and closing.

Overall window size is 28 inches wide by 45 inches high. 16 gauge Type 304 satin finish stainless steel, pass-through door windows of tempered safety glass. Window is designed to help maintain negative air pressure in soiled areas. Utility requirements as indicated on drawings.

Interlock Operation Note: Provide a combination controller and power supply that monitors window between 2D01 and 2D02. The interlock system shall function as follows: When window between rooms 2D01 and 2D02 is in the open position, close and disable the window between 2D02 and 2D03 from opening.

2.4.7 S1900E, Window, Pass-Thru, Automated

The Automated Pass-Through Window is an inline vertical lift window with a single operable (movable) panel, and a single non-operable (fixed) panel, an integral continuous stainless steel shelf extending 24 inches on one side and 4 inches on the other side with a microwave no-touch sensor plate for opening and closing. Overall window size is 28 inches wide by 45 inches high. 16 gauge Type 304 satin finish stainless steel, pass-through door windows of tempered safety glass. Window is designed to help maintain negative air pressure in soiled areas. Utility requirements as indicated on drawings.

Interlock Operation Note: Provide a combination controller and power supply that monitors window between 2D03 and 2DC1. The interlock system shall function as follows: When window between rooms 2D03 and 2DC1 is in the open position, close and disable the window between 2D02 and 2D03 from opening.

2.4.8 US960, Chemistry Delivery System

Chemistry delivery system capable of providing automated solution for delivering Prolystica Ultra Concentrate Chemistries to Washer/Disinfectors. Pump must maintain accurate delivery of solution from 1/40 to 1/10 oz/gal. Provide system compatible with selected washer disinfectors item S0960E. Chemistry delivery system capable of providing automated bulk chemistry solutions to Washer/Disinfector (JSN S0960E);

must provide and maintain accurate delivery of solution as required per Washer/Disinfector manufacturer's instructions.

PART 3 EXECUTION

3.1 EXAMINATION

After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing the work.

3.2 INSTALLATION

Install equipment at locations indicated in accordance with manufacturer's printed installation instructions, Section 11 70 00 GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT, and approved detail drawings . Submit

SECTION 11 71 00 Page 7 detail drawings specifically prepared to illustrate required work for each item of equipment that interfaces with other items of equipment or construction, including, but not limited to, installation layout, coordination of equipment services, drain piping connections, complete electrical wiring and control diagrams, and details of construction and rough-in requirements. Furnish and install necessary items such as framing, mounting hardware and trim as required for the type of equipment furnished.

3.3 ADJUSTING

Following installation, adjust flows, timers, levelers, and similar components and operation devices as appropriate. After testing, and before acceptance, examine equipment to ensure that adjustments are correct and that any additional adjustments deemed necessary during product testing have been incorporated.

3.4 UTILITIES

3.4.1 Service Runs

Connect service runs from equipment to building services as indicated.

3.4.2 Dissimilar Metal Connectors

Provide connections between ferrous and nonferrous metallic pipe with dielectric waterways and flanges. Provide dielectric waterways with temperature and pressure rating equal to or greater than that specified for the connecting piping. Provide waterways with metal connections on both ends suited to match connecting piping. Internally line dielectric waterways with an insulator specifically designed to prevent current flow between dissimilar metals. Dielectric flanges must meet the performance requirements described herein for dielectric waterways.

3.5 MANUFACTURER'S FIELD SERVICES

Provide the services of a manufacturer's representative, in addition to the Government's Biomedical Equipment Technician, who is experienced in the installation, adjustment, and operation of the equipment specified, and responsible for supervising the installation, adjustment, and testing of the equipment.

3.6 FIELD TESTS AND INSPECTIONS

3.6.1 Before Testing

Clean pipes, equipment and components of grease, dirt, stains, and other foreign materials.

3.6.2 Testing

Perform testing in accordance with manufacturer's written instructions.

Unless otherwise approved by the Contracting Officer, test all items of equipment to ensure that they are operational and installation conforms to specification requirements. Hydrostatically test piping system at pressure of 1.5 times system operating pressure with water at temperature not exceeding 100 degrees F . Before test, remove or isolate gage traps and apparatus that may be damaged by that pressure. Install calibrated test gage in system to observe any loss of pressure. Close off system and

SECTION 11 71 00 Page 8 maintain test pressure for not less than one hour. Inspect joints and equipment connections for leaks. Retest and make repair until no further leaks are observed. Each test report must indicate compliance with specified performance criteria and the final position of controls.

3.6.3 Inspection

Examine each item for visual defects and conformance to specifications.

3.7 CLEANING

3.7.1 For Final Acceptance

Remove labels, fingerprints, and clean all surfaces both inside and out.

Tightly cover and protect fixtures and equipment against rust, dirt, water, and chemical or mechanical injury.

3.7.2 Marred Surfaces Exposed-to-View

Refinish marred exposed surfaces that affect appearance, such as both interior and exterior cabinet finishes, to match the adjacent finishes, like new; replace components that cannot be refinished in this manner.

3.7.3 Concealed Marred Surfaces

Refinish marred surfaces exposed to atmosphere, where such surfaces do not affect product's appearance but do affect resistance to elements, such as galvanized pipes and insulation, to equal resistance performance as the unmarred surfaces.

3.8 TRAINING

3.8.1 Training Course

Conduct training course for operation and maintenance staff as designated by the Contracting Officer. Start the training period, for a total of 8 hours of normal working time, after systems are functionally complete but prior to final acceptance. The field instructions must include all of the items contained in the approved operations and maintenance data , as well as demonstrations of routine maintenance operations. Notify Contracting Officer at least 14 days prior to date of the training course.

3.8.1.1 Government's Biomedical Equipment Technician Training

Include operator's training for one Biomedical Equipment Technician (BMET) for each procured equipment item.

-- End of Section --

SECTION 11 71 00 Page 9

SECTION 11 72 13

MEDICAL AND DENTAL EQUIPMENT

05/20

PART 1 GENERAL

1.1 RELATED REQUIREMENTS

The requirements of Section 11 70 00 GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT apply to this Section.

1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM A1008/A1008M (2021a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable

ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM B221M (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

ANSI/NEMA LD 3 (2005) Standard for High-Pressure Decorative Laminates

1.3 SUBMITTALS

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Schedule of Equipment ; G

Submit detail drawings listed above for each item of equipment that interfaces with other items of equipment or construction.

SD-03 Product Data

All specified Equipment in this section.

Submit catalog numbers, trade names, literature, data sheets, SECTION 11 72 13 Page 1 diagrams and other pertinent data for each item of equipment listed above to evaluate performance, function, materials, dimensions and appearance.

SD-06 Test Reports

All specified Equipment in this section.

Submit field tests and inspections report for each item of equipment listed above signed by authorized official responsible for field tests and inspections.

SD-10 Operation and Maintenance Data

All specified Equipment in this section.

Submit Data Package 3, including training requirements, for each item of equipment listed above in accordance with requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA. In addition, provide hard copies consisting of two Operator's Manuals and two Service Manuals.

1.4 WARRANTY

Provide warranties as specified in this Section. Refer to Article WARRANTY in Section 11 70 00 GENERAL REQUIREMENTS FOR MEDICAL AND DENTAL EQUIPMENT for additional requirements.

PART 2 PRODUCTS

2.1 MATERIALS

Items not specified otherwise must conform to the following requirements:

a. Aluminum alloy: Equivalent in ultimate tensile, yield, and shear strengths to Alloy 6063-T5 or 6063-T6; conforming to ASTM B221M, ASTM B221.

b. Carbon steel: ASTM A1008/A1008M .

c. Laminated plastic: ANSI/NEMA LD 3 ; colors and patterns as selected by the Contracting Officer from the manufacturer's standard colors and patterns.

d. Stainless steel: Type 301, 302, or 304. Provide satin finish or a minimum No. 3 polished finish for exposed surfaces.

2.2 EQUIPMENT

Provide Shop drawings and a schedule of equipment for all the following items:

2.2.1 D0680, Console, Accessory/Side, Dental Operatory

Dental treatment side console with sink, air operated knee activated faucet, drawers, double doors, waste drop; 32 inches high by 86 inches wide by 20 inches deep; left or right unit as required by operatory layout; verify sink location before fabrication; finish as indicated in the drawings. Provide solid surface countertop. Cabinet shell and

SECTION 11 72 13 Page 2 components are 5/8 inch thick 45# industrial grade particleboard. Door and drawer fronts covered with high pressure V32 laminate (HPDL). Exposed edges are finished with 3mm thick rigid PVC. Sub base with leveling feet made from 14- gauge cold rolled steel with powder coat and stainless steel fasteners.

2.2.2 D0682, Cabinet, Dispensing, Dental Operatory, Wall Mounted

Dental dispensing cabinet, 29 inches wide by 24 inches high by 9 inches deep . Dispenses gloves, tissues, cups, towels and other disposable items.

Cabinet shell and components are 5/8 inch thick 45# industrial grade particleboard. Door and drawer fronts covered with high pressure V32 laminate (HPDL). Exposed edges are finished with 3mm thick rigid PVC.

2.2.3 D0685, Cabinet, Storage, Dental Operatory, Wall Mounted

Dental upper wall mounted storage cabinet, two adjustable shelves, 34 inches wide by 24 inches high by 12 inches deep . Cabinet shell and components are 5/8 inch thick 45# industrial grade particleboard. Door and drawer fronts covered with high pressure V32 laminate (HPDL).

Includes 2 adjustable shelves. Exposed edges are finished with 3mm thick rigid PVC.

2.2.4 D0755, Tank Assembly, Boilout/Curing, Double

Two basin washout and boil-out tank assembly, stainless steel tanks, gas heating elements. Included a vented cabinet with internal shield, recirculating pump, wax trap, drain valve; base cabinet mounted; 35 inches wide by 24 inches deep.

2.2.5 D0760, Guard, Casting Machine

Casting Well, approximately 14 inches high by 19 inches diameter.

Stainless steel construction with a rim to match the guard to the casting cabinet working surface. Designed for use in dental laboratories as an insert in a cabinet to preclude casting material from becoming a projectile if hte casting equipment fails.

2.2.6 D0900, Workstation, Dental Lab, Receiving

Modular workstation for receiving supplies in a dental laboratory. The unit stands on the floor and consists of a 24 inch wide base cabinet with 4 drawers, a 24 inch wide single or double door base cabinet unit with an adjustable shelf and a 74 inch wide laminate counter supported by the two base cabinets. The working space between the two cabinets contains an under counter single drawer unit. Steel construction cabinets with powder coating. See drawings for configuration.

2.2.7 D0904, Workstation, Tech, Dental Lab, Single Station

Dental laboratory technician workstation, overhead task lighting(approximately 3000 lux), integrated gas for bunsen burner, integrated dust collection system, air for air gun, and electrical lines for accessory equipment, 46 inches wide by 24 inches deep by 78 inches high .

The workstation also includes a dust extraction system with filtration, a minimum of 4 drawers for storage, an air gun, a gas valve for a Bunsen burner and electrical outlets for accessory equipment. Desktop is made from heat, abrasion, and chemical resistant material. Steel construction cabinets with powder coating. Workstation must accommodate power feed from

SECTION 11 72 13 Page 3 rear.

2.2.8 D0925A, Hood, Fume, Dental Acrylic, Floor Standing

Dental fume hood, 1/3hp blower, vapor proof light, 115V, 60 Hz, tempered safety glass counterbalanced sash, epoxy-coated 16 gauge steel cabinet, 47 inches wide by 25 inches deep by 53 inches high. Include minimum of 3 GFCI 120V 20 amp electrical receptacles, water, gas, and air valves with serrated hose connectors, cupsink with 6" x 3" inside dimension. All internal utilities must be pre-piped and pre-wired. Acid storage fume hood base cabinet fabricated from steel and designed for the storage of corrosive chemicals.

2.2.9 D0930, Workstation, Dental Lab, Casting

Dental lab casting workstation, aluminum frame, adjustable legs, pullout casting ring cooling drawer, ceramic tile countertop, overhead stainless steel ventilation canopy, 48 inch by 16 inch furnace shelf, 73 inches wide by 34 inches high by 29 inches deep.

2.2.10 D0942, Workstation, Dental Lab, Microblasting

Dental lab workstation to include micro-abrasive blaster and dust collector work station. Blaster: 10 to 125 psi air pressure, inlet air pressure 10 to 145 psi, 1 liter powder capacity. Work Station: down-draft design, HEPA filter, blow-off gun, spent abrasive storage hopper, desiccant air dryer, free standing, 2.2 Cubic feet, tempered glass opening. Utilities indicated on drawing are for basis of design model.

2.2.11 D6150, Light, Dental, Operating, Dual, Ceiling Mounted

Dual ceiling column mount with each head on a cantilever arm, variable intensity control. Dimmable levels between 50-100%. Minimum of 100,000 lux. Approximate color temperature of 4300K. 67 inches high by 58 inches wide by 116 inched deep, 200 lbs.

2.2.12 D6155, Light, Dental, Operating, Ceiling, Column

Single head, ceiling column mounted with a variable intensity controller on the head of the dental operating light. Dimmable levels between 50-100%. Minimum of 30,000 lux. Approximate color temperature of 5000K.

Utility Characteristics stated are for basis of design model; verify with substituted equipment manufacturer: 100-240V, 50/60Hz, 1.25A

2.2.13 D7090, Utility Center, Dental, Floor Mounted

Surface floor mounted dental utility box with removable cover. Verify required utilities as indicated in the drawings. Coordinate to function with the dental delivery system, item D8250.

2.2.14 D7090R, Utility Center, Dental, Wall Mounted

Surface wall mounted dental utility box with removable cover. Verify required utilities as indicated in the drawings.

2.2.15 M2010, Cabinet, Storage, Acid, Undercounter

Steel dual-wall, epoxy-coated steel cabinet with three point locking, self closing doors, adjustable interior shelf. Approximate exterior dimensions

SECTION 11 72 13 Page 4

35"H x 35"W x 22"D.

2.2.16 UL225: Snorkel Exhaust, Ceiling Mounted

Anodized aluminum section with three adjustable composite friction joints, 360 degree rotation, transparent combi hood, ceiling cover, duct connector, all necessary mounting brackets and hardware.

2.2.17 X3150, Rack, Apron/Gloves, Wall Mounted

Painted steel apron/gloves rack, 16 inches high by 28 inches wide by 8 inches deep .

PART 3 EXECUTION

3.1 EXAMINATION

After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing the work.

3.2 INSTALLATION

Install equipment at locations indicated in accordance with manufacturer's printed installation instructions, Section 11 70 00 GENERAL REQUIREMENTS

FOR MEDICAL AND DENTAL EQUIPMENT, 25 05 11 CYBERSECURITY FOR

FACILITY-RELATED CONTROL SYSTEMS, and approved detail drawings . Submit detail drawings specifically prepared to illustrate required work for each item of equipment that interfaces with other items of equipment or construction, including, but not limited to, installation layout, coordination of equipment services, drain piping connections, complete electrical wiring and control diagrams, and details of construction and rough-in requirements. Furnish and install necessary items such as framing, mounting hardware and trim shall be furnished and installed as required for the type of equipment furnished.

3.3 ADJUSTING

Following installation, adjust flows, timers, levelers, and similar components and operation devices as appropriate. After testing, and before acceptance, examine equipment to ensure that adjustments are correct and that any additional adjustments deemed necessary during product testing, have been incorporated.

3.3.1 Ceiling Mounted Patient-Life Systems

Install tracks level and plumb, according to manufacturer's written instructions.

a. Support track directly from overhead supplementary framing using manufacturer's standard supports, anchors, and fasteners at intervals required by lifting capacity indicated, but not less than 36 inches o.c.

b. Brace direct-to-structure track supports where distance between suspended ceiling and anchors is more than 18 inches .

c. Provide supports at each track end, splice, and tangent point of each corner.

SECTION 11 72 13 Page 5

d. Install track accessories, splices, end caps, connectors, coupling and joining devices, and other accessories as required for a secure and operational installation.

3.4 UTILITIES

3.4.1 Service Runs

Connect service runs from equipment to building services as indicated.

3.4.2 Dissimilar Metal Connectors

Provide connections between ferrous and nonferrous metallic pipe with dielectric waterways and flanges. Provide dielectric waterways with temperature and pressure rating equal to or greater than that specified for the connecting piping. Provide waterways with metal connections on both ends suited to match connecting piping. Internally line dielectric waterways with an insulator specifically designed to prevent current flow between dissimilar metals. Dielectric flanges meet the performance requirements described herein for dielectric waterways.

3.5 MANUFACTURER'S FIELD SERVICES

Provide the services of a manufacturer's representative, in conjunction with the Government's Biomedical Equipment Technician, who is experienced in the installation, adjustment, and operation of the equipment specified, and responsible for supervising the installation, adjustment, and testing of the equipment.

3.6 FIELD TESTS AND INSPECTIONS

3.6.1 Before Testing

Clean pipes, equipment and components of grease, dirt, stains, and other foreign materials.

3.6.2 Testing

Perform testing in accordance with manufacturer's written instructions.

Unless otherwise approved by the Contracting Officer, test all items of equipment to ensure that they are operational and installation conforms to specification requirements. Hydrostatically test piping system at pressure of 1.5 times system operating pressure with water at temperature not exceeding 100 degrees F . Before test, remove or isolate gage traps and apparatus that may be damaged by that pressure. Install calibrated test gage in system to observe any loss of pressure. Close off system and maintain test pressure for not less than one hour. Inspect joints and equipment connections for leaks. Retest and make repair until no further leaks are observed. Each test report must indicate compliance with specified performance criteria and the final position of controls.

3.6.3 Inspection

Examine each item for visual defects and conformance to specifications.

SECTION 11 72 13 Page 6

3.7 CLEANING

3.7.1 For Final Acceptance

Remove labels, fingerprints, and clean all surfaces both inside and out.

Tightly cover and protect fixtures and equipment against rust, dirt, water, and chemical or mechanical injury.

3.7.2 Marred Surfaces Exposed-to-View

Refinish marred exposed surfaces that affect appearance, such as both interior and exterior cabinet finishes, to match the adjacent finishes, like new; replace components that cannot be refinished in this manner.

3.7.3 Concealed Marred Surfaces

Refinish marred surfaces exposed to atmosphere, where such surfaces do not affect product's appearance but do affect resistance to elements, such as galvanized pipes and insulation, to equal resistance performance as the unmarred surfaces.

3.8 TRAINING

3.8.1 Training Course

Conduct training course for operation staff as designated by the Contracting Officer. Start the training period, for a total of 8 hours of normal working time, after systems are functionally complete but prior to final acceptance. The field instructions must include all of the items contained in the approved operations and maintenance data, as well as demonstrations of routine maintenance operations. Notify Contracting Officer at least 14 days prior to date of the training course.

3.8.1.1 Government's Biomedical Equipment Technician Training

Include operator's training for one Biomedical Equipment Technician (BMET) for each procured equipment item.

SECTION 11 72 13 Page 7

SECTION 12 35 70

HEALTHCARE CASEWORK

08/16, CHG 2: 11/18

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants

U.S. DEPARTMENT OF DEFENSE (DOD)

MIL-STD-1691 (1994; Rev F) Construction and Material Schedule for Military Medical and Dental Facilities

1.2 SUBMITTALS

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Detail Drawings ; G

SD-03 Product Data

Casework

Recycled Content for Baked Enamel Carbon Steel Medical Casework ; S

Recycled Content for Baked Enamel Carbon Steel Dental Prosthetics Casework ; S

SD-04 Samples

Casework ; G

Wall Hung Cabinets ; G

Floor Mounted Cabinets ; G

SD-08 Manufacturer's Instructions

Installation

SECTION 12 35 70 Page 1

1.3 DELIVERY, STORAGE, AND HANDLING

Deliver casework to the jobsite in the original individual containers, complete with screws, keys, and instructions. Mark each container with the manufacturer's name and catalog number. Store casework in an adequately ventilated, dry location that is free of dust, water, or other contaminates and in a manner to permit access for inspection and handling. Handle casework carefully to prevent damage to the surfaces.

Replace damaged items that cannot be restored to like-new condition.

PART 2 PRODUCTS

2.1 CASEWORK

Submit for approval Drawings showing layout of casework at 3/4 inch equals one foot scale. Indicate details of construction and rough-in requirements. Verify job condition affecting the work and obtain accurate field measurements for incorporation into drawings. Locate structural members, required utilities and services provided by other sections of this specification. Submit details and information necessary for fabrication and installation , manufacturer's printed data, catalog cuts, and instructions for installation and cleaning. Provide casework as scheduled on the detail drawings . Factory fabricate of manufacturer's standard sizes and finishes and conform to MIL-STD-1691 , and the requirements specified below. Casework items are identified on drawings with numbers preceded by the letters "C" and "D". These numbers are Joint Schedule Numbers in MIL-STD-1691 .

2.1.1 Medical Casework

Provide medical casework of baked enamel carbon steel. Color of finish in accordance with color schedule as indicated.

2.1.1.1 Recycled Content

Baked enamel carbon steel must contain a minimum of 40 percent recycled content. Provide data identifying percentage of recycled content for baked enamel carbon steel medical casework .

2.1.2 Dental Casework

Provide dental operator casework of carbon steel covered with laminated plastic sheets. Pattern, color and finish of decorative laminated plastic for exteriors of casework selected by the Contracting Officer from the manufacturer's standard color and woodgrain samples.

2.1.3 Dental Prosthetics Casework

Provide dental prosthetics casework of baked enamel carbon steel. Color of finish selected by the Contracting Officer from the manufacturer's standard colors.

Baked enamel carbon steel must contain a minimum of 40 percent recycled steel content. Provide data identifying percentage of recycled content for baked enamel carbon steel dental prosthetics casework .

2.1.2 Countertops

Provide countertops as specified in Section 12 36 00 COUNTERTOPS and

SECTION 12 35 70 Page 2

06 61 16 SOLID SURFACE FABRICATIONS

2.2 PLUMBING FIXTURES

Provide faucet, trap and drain fittings, gas, air and vacuum cocks as required. Provide connection conforming to the requirements specified in Section 22 00 70 PLUMBING, HEALTHCARE FACILITIES.

PART 3 EXECUTION

3.1 INSTALLATION

Install casework in a manner that does not damage the work of other trades. Secure the casework in place in true alignment, level, and plumb. Secure units with screws through backs to cleats that have been anchored to building structure with toggle or expansion bolts.

Do not install building construction materials that show visual evidence of biological growth.

3.1.1 Wall Hung Cabinets

Install wall-hung cabinets to support the weight of the cabinets plus the normally expected weight of the contents of the cabinets. Space fasteners 12 inch on center using at least three bolts in each 3 or 4 foot unit width. Join adjacent cabinets in an assembly together at top and bottom with inconspicuous bolts or clips. Seal joints between the casework and wall surfaces which are not larger than the joints between casework sections with sealant conforming to ASTM C920, Type M, Grade NS, Class 25, Use NT. Close larger joints with filler strips of the same material and finish as adjacent casework. Cut filler strips to the contour of the wall surface and secure to the casework with concealed nails or screws. Use filler strips no wider than 6 inch .

3.1.2 Floor Mounted Cabinets

Set floor-mounted metal cabinets on a common metal base or integral base, in assemblies up to 6 feet in length in rooms having concrete or resilient flooring. Bolt cabinets to bases at cabinet corners. Face metal bases with resilient material to match wall base in space where the cabinets are located. Fasten together adjoining cabinets at top and bottom of front and back with bolts placed inconspicuously inside cabinets. Set metal cabinets in rooms having terrazzo or ceramic-tile floors on concrete or masonry bases with exposed faces finished the same as other bases in the room. Seal flush openings between cabinet and wall surfaces, due to irregularity of surfaces, with Type S or M, Grade NS, Class 12.5, use NT, conforming to ASTM C920. Close exposed-to-view openings larger than joints in tile work with filler or scribing strip of the same material and finish as adjacent casework. Cut filler to contour of wall surface and secure to casework with concealed sheet-metal screws. Use minimum width and number of fillers consistent with need and in no case shall filler exceed 6 inch in width.

3.1.3 Countertops

Height of counter tops as indicated. Where required, toe space at front of cabinets shall be provided by installing front face of cabinets 3 inch in front of face of base. Where toe space is not required, face of base and cabinets shall be flush. Bases must have a height of approximately 4

SECTION 12 35 70 Page 3 inch . Install all items as required for proper operation in accordance with the manufacturer's directions.

3.2 INSPECTION AND CLEANING

Inspect placed items for proper location, fastening, connection to utilities, operation, and for damage which may have occurred during installation. Put each item into service to prove proper operation.

Correct defects disclosed during inspection. Clean cabinets and countertops in accordance with manufacturer's instructions.

SECTION 12 35 70 Page 4

SECTION 14 24 23

HYDRAULIC PASSENGER ELEVATORS

05/16

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

ASME A17.1/CSA B44 (2019) Safety Code for Elevators and Escalators

ASME A17.2 (2017) Guide for Inspection of Elevators, Escalators, and Moving Walks Includes Inspection Procedures for Electric Traction and Winding Drum Elevators, Hydraulic Elevators, and Escalators and Moving Walks

ASME B16.9 (2018) Factory-Made Wrought Buttwelding Fittings

ASME B16.11 (2022) Forged Fittings, Socket-Welding and Threaded

AMERICAN WELDING SOCIETY (AWS)

AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel

ASTM INTERNATIONAL (ASTM)

ASTM A53/A53M (2022) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

ASTM A106/A106M (2019a) Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits

INTERNATIONAL CODE COUNCIL (ICC)

ICC IBC (2021) International Building Code

SECTION 14 24 23 Page 1

NATIONAL ELEVATOR INDUSTRY, INC. (NEII)

NEII-1 (2000; R thru 2017) Building Transportation Standards and Guidelines, including the Performance Standards Matrix for New Elevator Installation

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2023; ERTA 4 2023) National Electrical Code

NFPA 70E (2021) Standard for Electrical Safety in the Workplace

NFPA 72 (2022) National Fire Alarm and Signaling Code

NFPA 101 (2021) Life Safety Code

U.S. DEPARTMENT OF DEFENSE (DOD)

UFC 3-560-01 (2017, with Change 2, 2019) Operations and Maintenance: Electrical Safety

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines

1.2 RELATED REQUIREMENTS

Division 25 Sections, Cybersecurity for Facility-Related Control Systems, applies to this section, with the additions and modifications specified herein, for Elevator Equipment capably of connecting to an Information System/Platform and/or Local Area Networks. Equipment meeting this requirement must have Authority to Operate (ATO). Coordinate with NAVFAC CIO and the Authorizing Official (AO) to obtain the ATO. The Default Requirements for Control System Devices in Division 25 Sections, Cybersecurity for Facility-Related Control Systems, applies to this section.

Section 25 08 11.00 20 RISK MANAGEMENT FRAMEWORK FOR FACILITY-RELATED

CONTROL SYSTEMS

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING.

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-02 Shop Drawings

Elevator System; G

SECTION 14 24 23 Page 2

Elevator Components ; G

Elevator Machine ; G

Elevator Controller ; G

Wiring Diagrams ; G

SD-03 Product Data

Elevator and Accessories; G

Elevator Components ; G

Data Sheets ; G

Elevator Microprocessor Controller ; G

SD-05 Design Data

Emergency Power Systems

Heat Loads

Reaction Loads

SD-07 Certificates

Elevator Parts and Components Price Lists ; G

Warranty

Endorsement Letter

Welders' Qualifications

Elevator Controller Certification ; G

SD-10 Operation and Maintenance Data

Elevator , Data Package 4; G

Maintenance Control Program (MCP) ; G

Software and Documentation ; G

Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA and 01 78 24.05 20 FACILITY OPERATION AND

MAINTENANCE SUPPORT INFORMATION.

1.3.1 Shop Drawing Requirements

Provide assembly and arrangement of elevators, accessories, and elevator components . Show location of elevator machine in elevator machine room (MR) or machinery space (MS). Show location of elevator controller in elevator machine room or elevator control room (CR). Provide details for materials and equipment, including but not limited to operating and signal fixtures, doors, door and car frames, car enclosure, controllers, motors, SECTION 14 24 23 Page 3 guide rails and brackets, layout of hoistway in plan and elevation, and other layout information and clearance dimensions.

1.3.2 Product Data Requirements

Provide manufacturers' product data for all elevator components , including but not limited to the following: elevator controller, hydraulic pump unit, hydraulic pump and motor, hydraulic cylinder, hydraulic piping and fittings, car and hall fixture buttons and switches, cab and machine room or control room communication devices, door operator, door protection system, car roller guides, and buffers. For data sheets , provide document identification number or bulletin number, published or copyrighted prior to the date of contract bid opening. Provide controller manufacturer's published procedures for performance of each and all testing required by

ASME A17.1/CSA B44 .

1.3.3 Design Data

1.3.3.1 Reaction Loads

Provide…