POWER PANELBOARDS & EQUIPMENT
SD
PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP. SEE PANELBOARD
SCHEDULE.
PANELBOARD, FLUSH MOUNTED AT 72" AFF TO TOP. SEE PANELBOARD
SCHEDULE.
DISTRIBUTION PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP. SEE
PANELBOARD SCHEDULE.
- TYPICAL LIGHTING APPLIANCE PANELBOARD NAMING SCHEME -
N21C3
FIRST EQ - EQUIPMENT BRANCH OF ESSENTIAL POWER SYSTEM
POSITION (1-2 (EMERGENCY)
CHARACTERS) LS - LIFE SAFETY BRANCH OF ESSENTIAL POWER SYSTEM
(EMERGENCY)
N - NORMAL POWER SYSTEM
SECOND POSITION 4 - 480Y/277 VOLT
(1-3 CHARACTERS) 2 - 208Y/120 VOLT
COM - COMMUNICATIONS PANEL, 208Y/120V
THIRD POSITION 1 - FIRST FLOOR
(1 CHARACTER) 2 - SECOND FLOOR
FOURTH POSITION A - ELECTRICAL ROOM 'A'
(1 CHARACTER) B - ELECTRICAL ROOM 'B'
FIFTH POSITION 1 - PANEL #1
(1 CHARACTER) 2 - PANEL #2
3 - PANEL #3
- TYPICAL DISTRIBUTION PANELBOARD NAMING SCHEME -
DP-480-EQ
FIRST
POSITION (2 DP - DISTRIBUTION PANELBOARD
CHARACTERS)
SECOND POSITION 480 - 480Y/277 VOLT
(3 CHARACTERS) 208 - 208Y/120 VOLT
THIRD POSITION EQ - EQUIPMENT BRANCH OF ESSENTIAL POWER SYSTEM
(1-3 CHARACTERS) (EMERGENCY)
LS - LIFE SAFETY BRANCH OF ESSENTIAL POWER SYSTEM
(EMERGENCY)
N - NORMAL POWER SYSTEM
1B - ELECTRIC ROOM '1B'
- MISCELLANEOUS PANELBOARD NAMING SCHEME -
4HVAC1 - 480Y/277V HVAC PANEL
2HVAC1 - 208Y/120V HVAC PANEL
4STER - 480Y/277V STERILIZATION SUITE PANEL
4DENT - 480Y/277V DENTAL EQUIPMENT PANEL
DISCONNECT SWITCH, FUSIBLE, IF DISCONNECT SIZE AND FUSING IS NOT
SHOWN ON PLAN, REFER TO POWER SINGLE LINE DIAGRAM ON SHEETS EP6xx THRU EP6xx.
FUSE SIZE (FM - FUSE PER MANUFACTURER'S RECOMMENDATION; NF - NON
FUSED)
DISCONNECT AMP RATING
# OF POLES
SAME AS ABOVE EXCEPT MOUNTED ON UNISTRUT STAND.
INTEGRAL SAFETY DISCONNECT SWITCH FURNISHED WITH EQUIPMENT. IF
EQUIPMENT IS SHOWN WITH DISCONNECT BUT MANUFACTURER DOES NOT
PROVIDE ONE, CONTRACTOR IS RESPONSIBLE FOR PROVIDING DISCONNECT
OF REQUIRED SIZE AND TYPE. COORDINATE WITH APPROPRIATE TRADE
INVOLVED.
DRY TYPE TRANSFORMER. PARAMETERS AS SHOWN ON PLANS. NAMING
SCHEME FOLLOWS PANELBOARD TYPICAL NAMING SCHEMES.
LIGHTING INVERTER. SEE SINGLE LINE DIAGRAM FOR ELECTRICAL
CHARACTERISTICS.
SURGE PROTECTIVE DEVICE. SEE SPECIFICATIONS.
ELECTRIC METER.
ENCLOSED CIRCUIT BREAKER. SURFACE MOUNTED UON.
GENERATOR SET REMOTE ALARM PANEL.
T-XXX
LI-X
T
SPD
M
B
GAP
N21A:1,3,5
BRANCH CIRCUITS
1"
10'S
INDICATES CONCEALED OVERHEAD OR IN WALLS.
INDICATES CONCEALED IN OR BELOW FLOOR SLAB OR BELOW ROOF. SEE
SPECIFICATIONS FOR RESTRICTIONS. CONDUIT BELOW SLAB ON GRADE
MUST BE PVC COATED RIGID CONDUIT.
INDICATES EXPOSED CONDUIT.
CONDUIT TERMINATION, (C) CAPPED, (B) BUSHED, (G) GROUND BUSHING.
BRANCH CIRCUIT WIRING IN CONDUIT. TICK MARKS INDICATE THE NUMBER
OF #12 AWG PHASE & NEUTRAL CONDUCTORS IN 3/4" CONDUIT UNLESS
OTHERWISE NOTED. PROVIDE A #12 AWG GROUND CONDUCTOR IN ALL
CONDUIT UON. ARROWHEADS INDICATES NUMBER OF CIRCUITS UP TO
THAT POINT (DEVICE, LUMINAIRE, ETC.). EXAMPLE SHOWN, ONE
ARROWHEAD/CIRCUIT TO RECEPTACLE.
HOMERUN TO PANELBOARD. PANELBOARD AND CIRCUIT DESIGNATIONS AS
INDICATED.
INDICATES SIZE OF CONDUIT OTHER THAN 3/4". 1" CONDUIT SHOWN HERE.
INDICATES SIZE OF ALL CIRCUIT CONDUCTORS INCLUDING GROUND IF
OTHER THAN #12 AWG. SHOWN, #10 AWG CONDUCTORS.
GENERAL RECEPTACLES
SUBSCRIPT MODIFIER LEGEND FOR BASIC RECEPTACLE TYPES:
NOTE: VERIFY WITH CONTRACTING OFFICER THE HEIGHT OF ALL COUNTER
TOPS, BACKSPLASHES, TABLE TOPS OR SINKS WHICH AFFECT THE MOUNTING
HEIGHT OF RECEPTACLES. MOUNTING HEIGHTS GIVEN ARE TO CENTER OF
DEVICE BOX UON.
CRG - TAMPER RESISTANT GFI RECEPTACLE MOUNTED 4" ABOVE COUNTER
TOP, BACKSPLASH OR SINK.
CT - RECEPTACLE MOUNTED 4" ABOVE COUNTER TOP, BACKSPLASH OR
TABLE TOP.
CTG - GFI RECEPTACLE MOUNTED 4" ABOVE COUNTER TOP, BACKSPLASH
OR SINK.
CTR - SAFETY TYPE, TAMPER RESISTANCE RECEPTACLE MOUNTED 4") ABOVE
COUNTER TOP OR BACKSPLASH.
CW - RECEPTACLE MOUNTED IN CASEWORK 4" ABOVE COUNTER TOP UON.
EWC - GFI RECEPTACLE FOR ELECTRIC WATER COOLER. COORDINATE
LOCATION AND HEIGHT WITH PLUMBING. REFER TO GENERAL NOTE 24.
GFI - GROUND FAULT INTERRUPTER TYPE RECEPTACLE.
HG - HOSPITAL GRADE RECEPTACLE.
HGC - HOSPITAL GRADE RECEPTACLE MOUNTED 4" ABOVE COUNTER TOP OR
BACKSPLASH.
HGG - GFI TYPE, HOSPITAL GRADE RECEPTACLE MOUNTED 4" ABOVE
COUNTER TOP OR BACKSPLASH.
SR - SAFETY TYPE, TAMPER RESISTANT RECEPTACLE.
SRG - SAFETY TYPE, TAMPER RESISTANT GFI.
SW - RECEPTACLE SWITCHED BY AUTOMATIC MEANS. MARK RECEPTACLE
PER NFPA 70, 406.3(E).
TVF - RECEPTACLE FOR FLAT SCREEN TV. COORDINATE MOUNTING HEIGHTS
OF RECEPTACLES AND ASSOCIATED DATA OUTLETS WITH BLOCKING IN
WALL AS WELL AS WITH TV BRACKET LOCATION. REFER TO
ARCHITECTURAL DETAILS FOR ADDITIONAL INFORMATION.
WP - WATER AND/OR WEATHER RESISTANT.
WPG - WEATHER RESISTANT GFI RECEPTACLE WITH WEATHERPROOF "IN USE"
COVER.
WTG - WEATHER RESISTANT & TAMPER RESISTANT GFI RECEPTACLE WITH
WEATHERPROOF "IN USE" COVER.
SIMPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R, SWITCHED BY
AUTOMATIC MEANS. RECEPTACLE MUST BE MARKED PER NFPA 70. SEE DETAIL
A1/EP502.
STUB-UP THRU FLOOR WITH DIE CAST FSD BOX MOUNTED 6" ABOVE FLOOR WITH
DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
DOUBLE DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R (RED
COLOR). SEE DETAIL A2/EP502.
EMERGENCY DOUBLE DUPLEX RECEPT, 20A, 125V, 2P-3 WIRE, NEMA 5-20R (RED
COLOR).
DUPLEX RECEPTACLE, CEILING MOUNTED, RECESSED, SUPPORT FROM CEILING
SUSPENSION SYSTEM, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
DUAL CHANNEL, SURFACE METAL RACEWAY AS SPECIFIED. TOP CHANNEL FOR
VOICE/DATA OUTLETS, AND BOTTOM CHANNEL FOR POWER RECEPTACLES.
MOUNT 4" ABOVE COUNTERTOP OR BACKSPLASH, UNLESS OTHERWISE NOTED.
LOCATE RECEPTACLES AT 18" ON CENTER.
X
X
SPECIAL RECEPTACLES
SPECIAL SIMPLEX RECEPTACLE - NEMA CONFIGURATION GIVEN BY SUBSCRIPT
'X', WHERE 'X' EQUALS ONE OF THE LETTERS BELOW. NEMA CONFIGURATION
SHOWN ON PLANS ARE FOR BID PURPOSES ONLY. ACTUAL NEMA
CONFIGURATION REQUIRED IN EACH CASE MAY VARY DEPENDING UPON
SPECIFIC MANUFACTURER OF EQUIPMENT BEING SUPPLIED. VERIFY NEMA
CONFIGURATION WITH CONTRACTING OFFICER AND/OR MANUFACTURER.
SPECIAL RECEPTACLE (EMERGENCY POWER).
NEMA CONFIGURATION SUBSCRIPT LEGEND:
NOTE: SUBSCRIPT MODIFIER LEGEND FOR BASIC RECEPTACLE TYPES MAY ALSO BE
APPLIED TO SPECIAL RECEPTACLES.
A - 125V, 30A, 1Ø (NEMA 5-30R)
B - 125V, 30A, 1Ø (NEMA L5-30R) LOCKING RECEPTACLE
C - 208V, 15A, 1Ø (NEMA 6-15R)
D - 208V, 20A, 3Ø (NEMA L15-20R) LOCKING RECEPTACLE
E - 208V, 20A, 1Ø (NEMA 6-20R)
F - 208V, 20A, 1Ø (NEMA L6-20R) LOCKING RECEPTACLE
G - 208V, 20A, 1Ø (NEMA 14-20R)
H - 208V, 20A, 3Ø (NEMA L21-20R) LOCKING RECEPTACLE
J - 208V, 30A, 1Ø (NEMA 6-30R)
K - 208V, 30A, 1Ø (NEMA L6-30R) LOCKING RECEPTACLE
L - 208V, 40A, 1Ø (NEMA 6-50R) ON 40A/2P CIRCUIT BREAKER
M - 208V, 50A, 1Ø (NEMA 14-50R)
N - 208V, 50A, 1Ø (NEMA L14-50R) LOCKING RECEPTACLE
P - 208V, 50A, 3Ø (NEMA 15-50R)
Q - 208V, 60A, 1Ø (NEMA L14-60R) LOCKING RECEPTACLE
S - 125V, 20A, 1Ø (NEMA L5-20R) LOCKING RECEPTACLE
J
J
J
J
WP
MF
JUNCTION BOXES
JUNCTION BOX IN OR ABOVE CEILING.
WEATHERPROOF DIE CAST BOX WITH WEATHERPROOF COVER.
JUNCTION BOX IN WALL - MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.
SAME AS ABOVE EXCEPT WITH FLEXIBLE CONNECTION TO EQUIPMENT. CL =
MOUNTED ABOVE CEILING. MF = MODULAR FURNITURE, PRE-WIRED
(COORDINATE WITH MANUFACTURER SO THAT THE FURNITURE CONNECTOR
WIRING MATCHES THE NUMBER OF BRANCH CIRCUITS BEING PROVIDED AT THE
JUNCTION BOX). SEE DETAIL C4/EP502.
BLANK (NON-RECEPTACLE TYPE) GFCI MODULE, 125VAC, 20A, HEAVY DUTY FOR
PROVIDING GFCI PROTECTION FOR RECEPTACLE WHICH IS NOT READILY
ACCESSIBLE. ROUTE BRANCH CIRCUIT THRU GFCI DEVICE. MOUNT 18"AFF
UNLESS OTHERWISE NOTED. PROVIDE MICARTA LABEL WITH 1/4" HIGH BLACK
LETTERS ON WHITE BACKGROUND AND MOUNT ABOVE THE FACE PLATE.
LETTERING MUST READ 'GFCI PROTECTION FOR (EQUIPMENT NAME)". EXAMPLE -
GFCI PROTECTION FOR ELECTRIC WATER COOLER. BASIS OF DESIGN = HUBBELL
#813R516 OR APPROVED EQUAL.
J
GFCI
CONTROLS & MECHANICAL EQUIPMENT
M
VFD
COMBINATION DISCONNECT & MOTOR CONTROLLER (STARTER). WITH NO
SUBSCRIPT, PROVIDE MAGNETIC TYPE WITH THERMAL OVERLOAD PROTECTION.
"VFD" SUBSCRIPT INDICATES VARIABLE FREQUENCY DRIVE (AKA ADJUSTABLE
SPEED DRIVE) WITH INTEGRAL DISCONNECTING MEANS. COORDINATE EXACT
LOCATION WITH MECHANICAL. FOR ALL HVAC EQUIPMENT: REFER TO GENERAL
NOTES. FOR ALL OTHER EQUIPMENT: DISCONNECT AND MOTOR CONTROLLER
PROVIDED (FURNISHED AND INSTALLED) BY ELECTRICAL.
MOTOR RATED TOGGLE SWITCH, MAXIMUM 20 AMP RATING, 120/277V, 1-POLE. 'M2'
OR 'M3' SUBSCRIPT INDICATES 2-POLE OR 3-POLE MANUAL MOTOR
CONTROLLER/SWITCH, RESPECTIVELY WITH 30A RATING MAXIMUM.
FLOOR RECEPTACLES & OTHERS
MULTI SERVICE, HAND ACCESS, REACH-IN TYPE, FLUSH, FLOOR BOX WITH
ACTIVATION COVER PLATE AS DESCRIBED IN THE SPECIFICATIONS. FIRE RATED
WHERE APPLICABLE. PROVIDE WITH ONE OR 2 DUPLEX RECEPTACLES, 20A, 125V,
2P-3 WIRE, NEMA 5-20R PER THE SYMBOLOGY. SEE SUBSCRIPT MODIFIER LEGEND
UNDER GENERAL RECEPTACLES. SEE TELECOMMUNICATIONS PLANS FOR
VOICE/DATA REQUIREMENTS AND NOTES.
SW
LUMINAIRES
SURFACE MOUNTED OR SUSPENDED 4'-0" STRIP OR PENDANT TYPE LUMINAIRE.
SURFACE MOUNTED OR SUSPENDED 4'-0" STRIP OR PENDANT TYPE LUMINAIRE
(EMERGENCY POWER)
2' X 4' LUMINAIRE - MOUNTING AND TYPE SHOWN IN LUMINAIRE SCHEDULE
2' X 2' LUMINAIRE - MOUNTING AND TYPE SHOWN IN LUMINAIRE SCHEDULE
1' X 4' LUMINAIRE - MOUNTING AND TYPE SHOWN IN LUMINAIRE SCHEDULE
2' X 4' LUMINAIRE (EMERGENCY POWER) - MOUNTING AND TYPE SHOWN IN
LUMINAIRE SCHEDULE. SUBSCRIPT 'NL' INDICATES NIGHT LIGHT
2' X 2' LUMINAIRE (EMERGENCY POWER) - MOUNTING AND TYPE SHOWN IN
LUMINAIRE SCHEDULE. SUBSCRIPT 'NL' INDICATES NIGHT LIGHT
1' X 4' LUMINAIRE (EMERGENCY POWER) - MOUNTING AND TYPE SHOWN IN
LUMINAIRE SCHEDULE
WALL MOUNTED LUMINAIRE - MOUNTING AND TYPE SHOWN IN LUMINAIRE
SCHEDULE
WALL MOUNTED LUMINAIRE (EMERGENCY POWER) - MOUNTING AND TYPE
SHOWN IN LUMINAIRE SCHEDULE
RECESSED DOWN LIGHT LUMINAIRE
RECESSED DOWN LIGHT LUMINAIRE (EMERGENCY POWER). SUBSCRIPT 'NL'
INDICATES NIGHT LIGHT
EXIT SIGN, WALL MOUNTED WITH 90 MINUTE BATTERY PACK UNIT. SHADED
PORTION DENOTES FACE(S). DIRECTIONAL ARROWS AS INDICATED ON LIFE
SAFETY PLAN.
EXIT SIGN, CEILING MOUNTED WITH 90 MINUTE BATTERY PACK UNIT. SHADED
PORTION DENOTES FACE(S). DIRECTIONAL ARROWS AS INDICATED ON LIFE
SAFETY PLAN.
LUMINAIRE WITH 90 MINUTE BATTERY PACK.
LUMINAIRE WITH 90 MINUTE BATTERY PACK AND CONNECT TO EMERGENCY
POWER SYSTEM.
ANNOTATIONS ASSOCIATED WITH LUMINARIES:
UPPER CASE = LUMINAIRE MARK (REFER TO LUMINAIRE
ALPHANUMERIC (ex. F02) SCHEDULE
LOWER CASE LETTER = INDICATES WHICH CONTROL DEVICE
(SWITCH, SENSOR CONTROLLER) IS
CONTROLLING THE LUMINAIRE
NUMBER = CIRCUIT TO WHICH THE LUMINAIRE IS
CONNECTED
NL = NIGHT LIGHT
F02
12 c
NL
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:0
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
1/8" = 1'-0"
E-001
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
L E
G E
N D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909482
MLB RMA MBA
JAS
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
PROFESSIONAL
E RN G I N E E
ABBREVIATIONS
A AMPERES
AC ALTERNATING CURRENT OR AIR CONDITIONING
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAGE
BAS BUILDING AUTOMATION SYSTEM
BFG BELOW FINISHED GRADE
BPI BYPASS ISOLATION
C CONDUIT OR CONDUCTOR
CB CIRCUIT BREAKER
CCT CORRELATED COLOR TEMPERATURE
CIRC CIRCUIT
CKT CIRCUIT
CL CEILING MOUNTED
COMM COMMUNICATIONS
CRI COLOR RENDERING INDEX
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DDP DDC POWER PANEL
DIA DIAMETER
DISC DISCONNECT
DIV DIVISION
DPW DEPARTMENT OF PUBLIC WORKS
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EGC EQUIPMENT GROUND CONDUCTOR
ELEV ELEVATOR
EMT ELECTRIC METALLIC TUBING
EWC ELECTRIC WATER COOLER
EX EXISTING TO REMAIN
EXD EXISTING TO BE DEMOLISHED
FCU FAN COIL UNIT
FLA FULL LOAD AMPERE
FM FUSE BY MANUFACTURER
GA GAGE
GALV GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HP HORSEPOWER RATING
IES ILLUMINATING ENGINEERING SOCIETY
IMC INTERMEDIATE METAL CONDUIT
K KILO (THOUSAND) OR DEGREES KELVIN
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY
KCMIL THOUSAND CIRCULAR MILS
KV KILO-VOLT
KVA KILO-VOLT-AMPERE
KW KILO-WATT
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LSI LONG, SHORT, INSTANTANEOUS (TRIPPING)
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MF MODULAR FURNITURE
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRIC CODE, NFPA 70
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEU NEUTRAL
NF NON-FUSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTR NEUTRAL
NTS NOT TO SCALE
OC ON CENTER
P POLE
PF POWER FACTOR
PH PHASE
PNL PANEL
PVC POLYVINYLCHLORIDE
RECPT RECEPTACLE
RF RETURN FAN
ROHS RESTRICTION OF HAZARDOUS SUBSTANCES
SD SAFETY DISCONNECT
SF SUPPLY FAN OR SQUARE FOOT
SLD SINGLE LINE DIAGRAM
SP SUMP PUMP
SPD SURGE PROTECTION DEVICE
SS STAINLESS STEEL
ST SHUNT TRIP
SW SWITCHED
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UV ULTRA-VIOLET
V VOLT
VFD VARIABLE FREQUENCY DRIVE
W WIRE OR WATT
WP RAINTIGHT (NEMA 3R CLASSIFICATION)
XFMR TRANSFORMER
SWITCHES & LIGHTING CONTROLS
WALL SWITCHES
1-POLE, 20A, 120/277V AC ONLY, QUIET TYPE.
2-POLE, SINGLE THROW, 20A, 120/277V AC ONLY, MOTOR RATED, QUIET TYPE.
3-WAY, 20A, 120/277V AC ONLY, QUIET TYPE.
4-WAY, 20A, 120/277V AC ONLY, QUIET TYPE.
CONTROLS LUMINAIRE WITH SUBSCRIPT "a" ETC.
SOLID STATE DIMMER, FULL RANGE, LINE VOLTAGE TYPE.
SOLID STATE THREE WAY DIMMER, FULL RANGE, LINE VOLTAGE TYPE.
LOW VOLTAGE SWITCH. 'LV' DENOTES LOW VOLTAGE ON/OFF, 'LVD' (SHOWN)
DENOTES LOW VOLTAGE ON/OFF WITH 0-10V DIMMING.
LOW VOLTAGE SWITCH. NUMBER (SHOWN '2') DENOTES NUMBER OF BUTTONS.
SEE CONTROL WIRING DIAGRAM INDICATED ON PLANS FOR CONTROL
STRATEGY.
SWITCHES UNDER A COMMON COVER.
MULTI-ZONE SWITCHING. ANNOTATIONS INDICATE WHICH LUMINAIRE TO BE
CONTROLLED, OR WHICH SET OF LUMINARIES TO BE CONTROLLED. SHOWN -
SUBSET "b" IS CONTROLLED BY 3 WAY SWITCHING.
OCCUPANCY AND LIGHT LEVEL SENSORS
WALL MOUNTED, LINE VOLTAGE, DUAL TECHNOLOGY TYPE OCCUPANCY
SENSOR.
WALL MOUNTED, LOW-VOLTAGE, DUAL TECHNOLOGY OCCUPANCY SENSOR.
WALL MOUNTED INTERIOR DAYLIGHT SENSOR/PHOTOCELL.
CEILING MOUNTED, DUAL TECHNOLOGY, 360 DEGREE COVERAGE, OCCUPANCY
SENSOR. IN CORRIDORS, SUBSCRIPTS (ie. 'b') ARE PROVIDED TO INDICATE
WHICH SENSOR(S) CONTROL LUMINARIES WITH THE SAME SUBSCRIPT.
WIRING DIAGRAM WD01. REFER TO SHEETS EL612 THRU EL618.
ROOF MOUNTED PHOTOCELL.
DAYLIGHT PHOTO SENSORS
DIGITAL, CEILING MOUNTED, INTERIOR DAYLIGHT SENSOR. SUBSCRIPT
INDICATES SWITCH LEG(S) BEING CONTROLLED (WHEN PRESENT).
LOCAL AREA CONTROLLERS
SINGLE OR MULTI-RELAY LOCAL AREA CONTROLLER. MOUNT IN JUNCTION BOX
ABOVE ACCESSIBLE CEILING OR MOUNT ON DIN RAIL ENCLOSURE AS
INDICATED ON LIGHTING CONTROL WIRING DIAGRAMS ON SHEETS EL612
THROUGH EL618. IN SPACES WITH NO ACCESSIBLE CEILING, PROVIDE AN
ACCESS PANEL ADJACENT TO THE LOCAL AREA CONTROLLER. WHEN LOCATED
ABOVE ACCESSIBLE CEILING, PROVIDE LAMINATED LABEL STATING "LIGHTING
CONTROL ROOM CONTROLLER" ON CEILING GRID DIRECTLY BELOW DEVICE
LOCATION. PROVIDE SEPARATE RELAY FOR EACH SWITCH LEG. SUPERSCRIPT
'15' INDICATES CIRCUIT IN PRE-WIRED MODULAR FURNITURE TO BE
CONTROLLED.
'R' DENOTES USE FOR SWITCHED RECEPTACLES. 'L' DENOTES USE FOR
LIGHTING. NUMBER (SHOWN '1') INDICATES NUMBER OF RELAYS.
a b a
D
LVD
DT
DT
WD01
PC
a
DS
L1
LAC
- TYPICAL AUTOMATIC LIGHTING CONTROL PANELBOARD NAMING SCHEME -
FIRST LCP - LIGHTING CONTROL PANEL
POSITION
SECOND 1 - FIRST FLOOR
POSITION 2 - SECOND FLOOR
(1 CHARACTER)
THIRD POSITION A - ELECTRICAL ROOM 'A'
(1 CHARACTER) B - ELECTRICAL ROOM 'B'
LCP-1B
PS
DT
LV2
D b
SITE LEGEND
T
P
EUP
EUP
UP
EXISTING UTILITY POLE.
EXISTING SITE LIGHT.
EXISTING SITE LIGHT TO BE DEMOLISHED.
POLE LIGHT (SEE LUMINARIES SCHEDULE).
WALL MOUNTED LUMINAIRE (SEE LUMINARIES
SCHEDULE).
INDICATES CIRCUIT INSTALLED BELOW GRADE.
EXISTING PAD MOUNT TRANSFORMER.
PAD MOUNT TRANSFORMER (HEAVY LINE INDICATES
FRONT OF EQUIPMENT).
EXISTING POWER MANHOLE.
EXISTING POWER MANHOLE TO BE DEMOLISHED.
POWER MANHOLE.
EXISTING COMMUNICATIONS MANHOLE.
EXISTING COMMUNICATIONS MANHOLE TO BE
DEMOLISHED.
COMMUNICATIONS MANHOLE.
POWER OR LIGHTING HANDHOLE
EXISTING UNDERGROUND PRIMARY TO BE
DEMOLISHED. SEE DRAWING NOTES AND SINGLE LINE
DIAGRAM FOR ADDITIONAL DIRECTION.
EXISTING UNDERGROUND PRIMARY.
UNDERGROUND PRIMARY.
EXISTING UNDERGROUND SECONDARY TO BE
DEMOLISHED.
EXISTING UNDERGROUND SECONDARY.
UNDERGROUND SECONDARY.
EXISTING UNDERGROUND COMMUNICATIONS
DUCTBANK TO BE DEMOLISHED.
EXISTING UNDERGROUND COMMUNICATIONS
DUCTBANK.
UNDERGROUND COMMUNICATIONS DUCTBANK.
EXISTING OVERHEAD COMMUNICATIONS CABLES TO
BE DEMOLISHED.
EXISTING OVERHEAD COMMUNICATIONS CABLES.
T
EX
EUS
US
EUS
P
EXD
P
T
EX
T
EXD
T
EUC
UC
EUC
EX
EX
EXD
HH
EOC
EOC
SINGLE LINE DIAGRAM
EXISTING CABLING AND/OR AND CONDUIT TO REMAIN.
EXISTING UNDERGROUND PRIMARY TO BE DEMOLISHED.
EXISTING UNDERGROUND PRIMARY TO REMAIN.
UNDERGROUND PRIMARY.
UNDERGROUND SECONDARY.
WATT-HOUR DEMAND METER.
PANELBOARD.
STEP-DOWN TRANSFORMER WITH GROUNDING SHOWN. REFER TO
GROUNDING DIAGRAM ON SHEET EP701.
TRANSFORMER WINDINGS.
FUSE.
SWITCH.
METER.
CURRENT TRANSFORMER.
DIGITAL, SOLID STATE, ELECTRONIC, DRAW-OUT CIRCUIT BREAKER WITH
ADJUSTABLE LSIG TRIP SETTINGS. GFP=GROUND FAULT PROTECTION.
MOLDED CASE CIRCUIT BREAKER WITH ADJUSTABLE SOLID STATE
ELECTRONIC TRIP (LSI FUNCTIONS).
MOLDED CASE CIRCUIT BREAKER (THERMAL MAGNETIC).
CIRCUIT BREAKER TAG. 3=NUMBER OF POLES/ 50AT=TRIP SETTING OF THE
BREAKER/ 100AF=FRAME SIZE OF THE BREAKER.
CIRCUIT BREAKER IN NEMA 1 ENCLOSURE - SURFACE MOUNTED, 22,000AIC
SHOWN. 'LSI' INDICATES ADJUSTABLE ELECTRONIC TRIP BREAKER WITH LSI
FUNCTIONS. SEE CIRCUIT BREAKER TAG ABOVE.
DISCONNECT SWITCH.
SURGE PROTECTION DEVICE.
FEEDER REFERENCE, SEE SHEET EP607 FOR DESCRIPTION.
AUTOMATIC TRANSFER SWITCH. REFER TO SPECIFICATIONS AND CALLOUT
IN SINGLE LINE DIAGRAM FOR MORE INFORMATION.
ENGINE/GENERATOR SET.
GENERATOR ALARM PANEL.
GENERATOR SET REMOTE ALARM PANEL.
T
XXXX
EUP
EUP
UP
US
WHD
M
B22KAIC
GFP
SPD
NE
GE
GAP
RAP
50AT
100AF
LSI
50AT
100AF
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:0
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
1/8" = 1'-0"
E-002
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
L E
G E
N D
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909483
MLB RMA MBA
JAS
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
DEMOLITION NOTES
1. IT IS STRONGLY RECOMMENDED THAT THE CONTRACTOR VISIT THE SITE PRIOR TO BIDDING TO ASCERTAIN EXISTING CONDITIONS AS HE WILL BE RESPONSIBLE FOR EXISTING CONDITIONS AS
REQUIRED IN OTHER NOTES.
2. REMOVED EQUIPMENT NOT DESIRED BY THE OWNER MUST BE DISPOSED OF OFF SITE BY THE CONTRACTOR AT NO ADDITIONAL COST. WIRE AND CONDUIT WILL BECOME PROPERTY OF THE
CONTRACTOR AND MUST BE DISPOSED OF OFF SITE.
3. CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF PCB-CONTAINING FLUORESCENT BALLASTS AND MERCURY CONTAINING FLUORESCENT LAMPS FROM ALL DEMOLISHED LUMINARIES. BALLAST
MUST BE DELIVERED FOR DISPOSAL BY THE GOVERNMENT.
GENERAL NOTES
1. PROVIDE ALL ELECTRICAL WORK AND MATERIAL AS NEW UNLESS INDICATED OTHERWISE.
2. MAINTAIN NEC MINIMUM CLEARANCE IN FRONT OF ALL SWITCHGEAR, SWITCHBOARDS, SAFETY SWITCHES, PANELBOARDS, TRANSFER SWITCHES, TRANSFORMERS, AND OTHER ELECTRICAL
EQUIPMENT. DETERMINE PROPER CLEARANCE BEFORE INSTALLATION. DIMENSIONS OF EQUIPMENT SHOWN ARE BASED ON A PARTICULAR MANUFACTURER. IF DIMENSIONS OF EQUIPMENT FURNISHED DIFFER FROM THOSE ON THE DRAWINGS, ENSURE THAT ALL EQUIPMENT FITS IN THE ROOM OR SPACE ALLOCATED WITH PROPER CLEARANCE.
3. PROVIDE ALL CIRCUIT BREAKERS RATED 1200A OR LARGER WITH ARC ENERGY REDUCTION. PROVIDE ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL STATUS INDICATOR.
4. PRIOR TO ROUGH-IN, PROVIDE SCALED WALL ELEVATIONS WHERE ALL ALARM CABINETS, SIGNAL CABINETS, ETC. ARE INSTALLED IN OTHER THAN MECHANICAL AND ELECTRICAL ROOMS FOR
APPROVAL.
5. PROVIDE AN ARC FLASH STUDY AND COORDINATION ONCE THE ELECTRICAL (AS-BUILT SYSTEM) IS IN PLACE THAT WILL YIELD THE REQUIRED ARC FLASH WARNING LABELS, IN ACCORDANCE WITH NEC
110.16 (A) AND NFPA 72E, AS WELL AS THE FINAL ADJUSTABLE TRIP ELECTRONIC CIRCUIT BREAKER SETTINGS.
6. PROVIDE ALL SWITCHBOARDS AND PANELBOARDS WITH A PERMANENT SIGN TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS AND THAT PERSONNEL PROTECTIVE
EQUIPMENT (PPE) IS REQUIRED. LOCATE THE MARKING SO THAT IT IS CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE SERVICING THE EQUIPMENT. PROVIDE LABEL IN ACCORDANCE WITH NFPA 110.16.
7. PROVIDE A LAMINATED PLASTIC LABEL ON THE SERVICE SWITCHBOARD TO INDICATE THE MAXIMUM AVAILABLE FAULT CURRENT AT THE SERVICE AND THE DATE THE FAULT CALCULATION WAS
PERFORMED IN ACCORDANCE WITH NEC 110.24. SEE SINGLE LINE DIAGRAMS FOR DATA.
8. PROVIDE SIGNAGE AT THE SERVICE SWITCHBOARD INDICATING THE LOCATION OF THE GENERATOR SET.
9. COORDINATE WITH PANELBOARD MANUFACTURER AND PROVIDE CIRCUIT BREAKERS IN THE PANELBOARD SUBMITTAL THAT WILL COORDINATE TO 0.1 SECONDS FROM THE SERVICE SWITCHBOARD TO
ALL DOWNSTREAM CIRCUIT BREAKERS (INCLUDING BRANCH PANEL CIRCUIT BREAKERS).
10. PROVIDE RECESSED MOUNTED PANELBOARDS MUST HAVE FOUR (4) 3/4" EMPTY CONDUITS STUBBED UP ABOVE THE CEILING UNLESS OTHERWISE NOTED ON THE PANELBOARD SCHEDULE.
11. PROVIDE A MINIMUM #10 INSULATED CONTINUOUS COPPER GROUNDING CONDUCTOR TO BOND THE GROUNDING BUSSES IN ALL PANELBOARDS WITH BRANCH CIRCUITS SERVING THE SAME PATIENT
CARE AREA.
12. PROVIDE ENGRAVED LAMINATED MELAMINE TYPE LABELS DESCRIBING THE LOAD SERVED FOR EACH CIRCUIT BREAKER IN MAIN SWITCHBOARD AND ALL DISTRIBUTION TYPE PANELBOARDS. ALSO
PROVIDE SAME FOR EACH DISCONNECT SWITCH.
13. PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUITS WITH SUITABLE FITTINGS FOR FLEXIBLE CONDUITS WHICH ARE INSTALLED OUT-OF-DOORS, IN ANY MECHANICAL EQUIPMENT ROOM, OR IN
NORMALLY WET AREAS.
14. PROVIDE FLEXIBLE CONDUIT FOR ALL CONDUITS PASSING THROUGH EXPANSION JOINTS. SEE ARCHITECTURAL DRAWINGS FOR EXPANSION JOINT LOCATIONS.
15. PROVIDE MINIMUM OF AWG #12 COPPER CONDUCTOR AND 3/4" CONDUIT FOR BRANCH CIRCUITS AND HOMERUNS UNLESS OTHERWISE NOTED. PROVIDE A DEDICATED NEUTRAL FOR EACH PHASE IN
SINGLE PHASE BRANCH CIRCUITS. PROVIDE SEPARATE DEDICATED GROUNDING CONDUCTOR (#12 MINIMUM) IN EACH CONDUIT. DO NOT USE ALUMINUM CONDUCTORS.
16. DO NOT INSTALL MORE THAN THREE PHASE CONDUCTORS IN ONE CONDUIT UNLESS NOTED OTHERWISE.
17. DO NOT ROUTE CONDUIT THROUGH ELEVATOR HOIST WAY OR MACHINE ROOM UNLESS IT SPECIFICALLY SERVES EQUIPMENT IN THAT ROOM.
18. PROVIDE SEALING FOR ALL UNDERGROUND CONDUIT RUNS ENTERING THE BUILDING AND IN MANHOLES TO PREVENT THE ENTRANCE OF MOISTURE AND GASES.
19. ROUTE CONDUIT FOR RECEPTACLE CIRCUITS AND OTHER POWER BRANCH CIRCUIT WIRING AS WELL AS COMMUNICATION SYSTEMS CONDUITS OVERHEAD UNLESS NOTED OTHERWISE.
20. PROVIDE CONDUIT FOR DEVICE BOXES AS REQUIRED FOR THERMOSTATS. THERMOSTATS ARE SHOWN ON MECHANICAL DRAWINGS
21. IN ALL ROOMS WITHOUT FINISHED CEILINGS INSTALL ALL ELECTRICAL CONDUITS AS CLOSE TO THE STRUCTURAL CEILING AS POSSIBLE.
22. UNLESS NOTED OTHERWISE, THE CONDUIT SIZES SHOWN ON THE DRAWINGS FOR POWER AND LIGHTING ARE BASED ON THHN/THWN-2 CONDUCTORS. IF A DIFFERENT TYPE OF CONDUCTOR
INSULATION IS USED RATHER THAN TYPE THHN/THWN-2, NOTIFY THE CONTRACTING OFFICER, INCLUDING ANY INSTANCES WHERE AN INCREASE IN CONDUIT SIZE WILL BE REQUIRED.
23. PROVIDE ALL REQUIRED LUGS IN ELECTRICAL EQUIPMENT TO MATCH THE NUMBER OF CONDUCTORS PER PHASE, NEUTRAL AND GROUND FOR PARALLEL RUNS. PROVIDE ALL RUNS IN A PARALLEL
RUN SO THAT THEY ARE THE SAME PHYSICAL LENGTH.
24. PROVIDE ALL INTERIOR CONDUIT CONCEALED UNLESS SPECIFICALLY SHOWN TO BE EXPOSED. PROVIDE ALL CONDUIT SERVING DEVICES AND EQUIPMENT ON THE EXTERIOR OF THE BUILDING
CONCEALED IN WALLS OR COLUMNS. NO CONDUITS ARE ALLOWED TO BE EMBEDDED HORIZONTALLY WITHIN THE THICKNESS OF CONCRETE SLABS AND CONCRETE FILL ON METAL DECK.
25. DO NOT USE METAL CLAD CABLE 'MC' OR ARMORED CABLE 'AC' ON THIS PROJECT.
26. PROVIDE ELECTRIC WATER COOLER GFI RECEPTACLES (INDICATED BY "EWC" ON PLANS ) ADJACENT TO THE WATER COOLER ASSEMBLY. COORDINATE WITH PLUMBING TRADE. IF RECEPTACLE IS
REQUIRED TO BE INSIDE THE HOUSING OF THE WATER COOLER, USE STANDARD RECEPTACLE AND PROVIDE A GROUND FAULT INTERRUPTING DEVICE ADJACENT TO WATER COOLER TO MAINTAIN
REQUIRED ACCESSIBILITY FOR THE TEST SWITCH.
27. MECHANICAL TRADE FURNISHES MOTOR CONTROL DEVICES, ELECTRICAL TRADE MAKES ELECTRICAL CONNECTIONS FOR SAME.
28. COORDINATE WITH ALL MECHANICAL AND PLUMBING TRADES FOR SPACE REQUIREMENTS IN MECHANICAL ROOMS, CORRIDORS, SHAFTS, ABOVE CEILING, ETC. THIS INCLUDES SPACE ABOVE PANELS
WHERE DUCTS AND PIPING ARE PROHIBITED. SEE MECHANICAL PLANS FOR EXACT LOCATIONS OF MECHANICAL EQUIPMENT.
29. PROVIDE ENCLOSURES LISTED FOR ENVIRONMENT (CORROSIVE ATMOSPHERES, COASTAL AREAS, ETC.) IN ACCORDANCE WITH APPLICABLE DESIGN CRITERIA.
30. WHERE WALL SWITCHES AND CONTROL DEVICES SUCH AS THERMOSTATS ARE SHOWN AT THE SAME LOCATION IN PLAN VIEW (CONTROL DEVICES SUCH AS THERMOSTATS ARE SHOWN ON THE
MECHANICAL DRAWINGS), PROVIDE THE CONTROL DEVICE DIRECTLY IN LINE ABOVE THE SWITCH.
31. THE LOCATION OF LUMINAIRES IN MECHANICAL ROOMS, ELECTRICAL ROOMS MACHINE ROOMS, ETC. ARE SHOWN FOR BID PURPOSES ONLY. PROVIDE LUMINAIRES SO AS TO COORDINATE WITH ALL
TRADES AND ARRANGED FOR MAXIMUM LIGHTING DISTRIBUTION OF THE AREA.
32. REVIEW SHOP DRAWING SUBMITTALS OF OTHER TRADES FOR DISCREPANCIES BETWEEN THE SUBMITTED ITEM(S) AND THE ELECTRICAL DESIGN INFORMATION. VERIFY AND COORDINATE ALL
CONNECTIONS TO EQUIPMENT WITH SPECIFIC EQUIPMENT FURNISHED.
33. IN MANY CASES THROUGHOUT THE PLANS, EQUIPMENT CONNECTIONS ARE IDENTIFIED ON THE PLANS WITH A LETTER AND A FOUR DIGIT NUMBER. EXAMPLE: R7000 IS A REFRIGERATOR. THE
EQUIPMENT SCHEDULE FOR THESE ITEMS IS SHOWN ON THE ARCHITECTURAL SHEET A-680.
34. THE ELECTRICAL CHARACTERISTICS (SIZE, VOLTAGE, NUMBER OF CONDUCTORS, ETC.) OF ELECTRICAL CONNECTIONS TO MECHANICAL EQUIPMENT, PLUMBING EQUIPMENT, ELEVATOR MOTORS AND
MEDICAL EQUIPMENT ARE BASED ON A PARTICULAR MANUFACTURER. IF THE REQUIRED ELECTRICAL CONNECTIONS TO EQUIPMENT DIFFER FROM THAT SHOWN ON THE DRAWINGS, PROVIDE THE CORRECT CONNECTIONS FOR THE SUBMITTED AND INSTALLED EQUIPMENT. SEE MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES ON MECHANICAL AND PLUMBING DRAWINGS FOR ELECTRICAL REQUIREMENTS. COORDINATE WITH MANUFACTURER'S DATA IN OWNER APPROVED MECHANICAL AND PLUMBING SUBMITTALS SO AS TO ENSURE THAT THE BRANCH CIRCUIT AND OVERCURRENT PROTECTION ARE PROPERLY SIZED FOR THE EQUIPMENT BEING PROVIDED. PROVIDE (AT NO ADDITIONAL COST TO GOVERNMENT) PROPERLY SIZED ELECTRICAL EQUIPMENT AND CIRCUITS BASED ON THE MANUFACTURER'S DATA IN THE APPROVED EQUIPMENT SUBMITTAL. THE CONTRACTING OFFICER MUST APPROVE ANY PROPOSED CHANGES IN THE BRANCH CIRCUIT AND OVERCURRENT
PROTECTION.
35. COORDINATE WITH MANUFACTURER'S DATA IN OWNER APPROVED MEDICAL/DENTAL EQUIPMENT SUBMITTALS SO AS TO ENSURE THAT THE BRANCH CIRCUIT AND OVERCURRENT PROTECTION ARE PROPERLY SIZED. PROVIDE (AT NO ADDITIONAL COST TO THE GOVERNMENT) PROPERLY SIZED ELECTRICAL EQUIPMENT AND CIRCUITS BASED ON THE MANUFACTURER'S DATA IN THE APPROVED SUBMITTALS. THE CONTRACTING OFFICER MUST APPROVE ANY CHANGES IN THE BRANCH CIRCUIT AND OVERCURRENT PROTECTION.
36. VERIFY AND COORDINATE ALL MOUNTING HEIGHTS OF ALL DEVICES MOUNTED IN CASEWORK OR IN OR ABOVE COUNTERS WITH SPECIFIC EQUIPMENT FURNISHED.
37. PROVIDE A UL-LISTED ASSEMBLY FOR PROTECTION AROUND DEVICE BOXES (RECEPTACLES, LIGHT SWITCHES, TELEPHONE, ETC.) OVER 16 SQUARE INCHES IN SMOKE AND FIRE WALLS. WHERE
OUTLET BOXES ARE ON OPPOSITE SIDES OF A FIRE WALL, PROVIDE A 24" HORIZONTAL SEPARATION BETWEEN THEM OR PROVIDE PROTECTION AS DESCRIBED PREVIOUSLY.
38. DO NOT MOUNT DEVICES BACK-TO-BACK.
39. PROVIDE ALL NORMAL RECEPTACLES, SWITCHES, ETC WITH STAINLESS STEEL COVER PLATES. ENGRAVE THE WORD 'EMERGENCY' ON THE DEVICE COVERPLATE FOR RECEPTACLES AND LIGHT
SWITCHES ON 'EMERGENCY' POWER. USE AN APPROVED PERMANENT MEANS TO INDICATE PANELBOARD AND CIRCUIT NUMBER ON EACH RECEPTACLE COVER PLATE. SEES DETAIL ON EP502.
40. PROVIDE BARRIERS BETWEEN ALL 277V SWITCHES MOUNTED UNDER THE SAME COVER PLATE WITH OTHER 277V SWITCHES ON DIFFERENT PHASES OR 120V SWITCHES.
41. PROVIDE WALL MOUNTED DEVICES WITH THE MOUNTING HEIGHTS ABOVE FINISHED FLOOR AS INDICATED IN THE LEGEND AND IN THE FOLLOWING LIST UNLESS NOTED OTHERWISE ON THE PLANS
(MOUNTING HEIGHTS ARE TO CENTERLINE OF DEVICE):
SWITCHES (GENERAL) = 48" RECEPTACLES (GENERAL) = 18"
FOR SPECIAL MOUNTING HEIGHTS OF DEVICES. SEE ELECTRICAL PLANS AND ARCHITECTURAL ELEVATIONS.
42. WHERE AN ELECTRICAL RECEPTACLE IS ADJACENT TO A SINK, LOCATE THE RECEPTACLE LEAST 6" HORIZONTALLY AWAY FROM THE SINK'S TOWEL DISPENSER. DO NOT LOCATE THE RECEPTACLE
UNDER A TOWEL DISPENSER.
43. PROVIDE ALL COMMUNICATION CLOSET RECEPTACLES WHICH ARE CONNECTED TO LIFE SAFETY OR CRITICAL POWER LABELS WITH FACE PLATES HAVING THE WORDS 'LIFE SAFETY' OR 'CRITICAL'
(RESPECTIVELY) ENGRAVED ON THEM.
44. PROVIDE ALL DEVICE BOXES FOR POWER, LIGHTING OR COMMUNICATIONS DEVICES FLUSH MOUNTED UNLESS OTHERWISE NOTED.
45. PROVIDE LEAD LINING FOR ALL WALL MOUNTED, FLUSH ELECTRICAL BOXES AND ENCLOSURES IN RADIOGRAPHIC ROOMS WITH LEAD-LINED WALLS, SO AS TO MAINTAIN INTEGRITY OF LEAD
PROTECTION.
46. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING MOUNTED EQUIPMENT.
47. PROVIDE A COMPLETELY CONCEALED LIGHTNING PROTECTION SYSTEM WITH U.L. MASTER CERTIFICATE .
48. PROVIDE SEISMIC SUPPORTS FOR ALL EQUIPMENT. FOR EQUIPMENT MOUNTED ON HOUSEKEEPING PADS, SEE STRUCTURAL FOR PAD REQUIREMENTS. PROVIDE CABLE TIES TO STRUCTURE FOR ALL
LUMINARIES, AND PROVIDE EARTHQUAKE CLIPS TO TIE LUMINAIRES TO GRID CEILING.
49. PROVIDE STRUCTURAL BACKING AS REQUIRED FOR PROPER SUPPORT OF WALL MOUNTED ELECTRICAL EQUIPMENT. SEE ARCHITECTURAL SHEET A-542, DETAILS D1 AND D2 FOR ADDITIONAL
INFORMATION.
50. IN THE EVENT OF CONFLICTS IN THE DESIGN, PROVIDE A 'REQUEST FOR INFORMATION' (RFI) BEFORE THE START OF INSTALLATION TO AVOID RE-WORK AND ITS ASSOCIATED COSTS.
51. ADHERE TO NFPA 99 CONCERNING RECEPTACLES AND GROUNDING SYSTEM PERFORMANCE AND TESTING. PROVIDE DOCUMENTATION OF SUCCESSFUL TESTING AS A PRE-REQUISITE TO
GOVERNMENT ACCEPTANCE OF RECEPTACLES AND GROUNDING SYSTEMS.
52. WHERE CONDUIT PASSES THROUGH CONCRETE FLOOR AND/OR BEAMS, PROVIDE APPROPRIATE SLEEVE AND COORDINATE EXACT LOCATION WITH STRUCTURAL.
53. DO NOT ROUTE CONDUIT HORIZONTALLY ON ROOFS. ROUTE CONDUIT SERVING ROOF MOUNTED EQUIPMENT FROM ABOVE THE CEILING OF THE LEVEL BELOW THE ROOF. TURN CONDUIT UP THROUGH
THE ROOF AT THE EQUIPMENT SERVED. SEE DETAILS ON ARCHITECTURAL DRAWINGS FOR FLASHING AND/OR SEALING OF CONDUIT PENETRATIONS.
54. PROVIDE RECEPTACLE RETENTION FORCE OF GROUNDING BLADE TEST IN DENTAL TREATMENT ROOMS IN ACCORDANCE WITH NFPA 99, CHAPTER 6 'ELECTRICAL SYSTEMS'.
PHASING NOTES
1. PHASING OF THIS PROJECT WILL FOLLOW THE CONSTRUCTION SEQUENCE GIVEN ON SHEET C-003.
2. NO ELECTRICAL WORK IS ANTICIPATED UNDER PHASE 1.
3. EXISTING ELECTRICAL SERVICES TO BUILDINGS 6002 AND 6008 WILL REMAIN ENERGIZED UNDER PHASES 1, 2 AND 3.
4. EXISTING SITE LIGHTS (CALLED OUT IN CONSTRUCTION LIMITS PHASE 2 AND 3) WILL BE CIRCUIT TRACED AND DOCUMENTED BEFORE ANY POWER IS DISCONNECTED ON THE SITE.
5. EXISTING BUILDING 602 WILL BE DEMOLISHED AFTER THE EXISTING ELECTRIC SERVICE TRANSFORMER HAS BEEN DEMOLISHED.
6. PRIMARY POWER RECONFIGURATION AND SITE LIGHTING WORK ON THE EAST SIDE OF ALASKA STREET WILL BE ACCOMPLISHED DURING PHASE 2.
7. SITE LIGHTING CIRCUITS ON THE WEST SIDE OF ALASKA STREET WILL BE STUBBED OUT DURING PHASE 2.
8. EXISTING BUILDING 674 WILL BE DEMOLISHED AND PARKING LOT CONSTRUCTED DURING PHASE 3.
9. PRIMARY POWER RECONFIGURATION AND SITE LIGHTING WORK ON THE WEST SIDE OF ALASKA STREET WILL BE EXTENDED AND COMPLETED DURING PHASE 3.
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
NOT TO SCALE
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:0
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
E-003
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
N O
T E
S
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909484
MLB RMA MBA
JAS
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
W
WW
W
W
WW
SILTED
AREA
BLDG 674
2 STORY E
E
A
E
M
W
BLD
G
STO
R Y
EX. BLDG 602 TRANSFORMER
TO BE DEMOLISHED (NOTE 1)
T
P
EX
EX
E U
P
EUP
EXISTING
SECTIONALIZING
CABINET TO REMAIN.
SEE NOTE 6.
P
EUP
P
EX
EX
EUP
TEX
P EX
P EXD
EU
P
E U
P
T
T
EX
EX
EUC
EX. BLDG 674
TRANSFORMER TO
BE DEMOLISHED
EUC
NOTE 4
TEXD
NOTE 5
T
EX. BUILDING 6008
TRANSFORMER TO REMAIN
T
NOTE 3
NOTE 3
T
TEUP
EX. BLDG 6002
TRANSFORMER
TO REMAIN
EUP
NOTE 4
CONSTRUCTION
LIMITS PHASE 3
CONSTRUCTION
LIMITS PHASE 2
E U
C
EUS
MH-1
MH-2
MH-3
MH-5
MH-4
NOTE 4
EX
EX
EXD EXD
EXD
EXD
EXD
EXD
EX
EXD
EXD
EXD
EXD
EXD
EXD
EX
EX
EX
ER
EX
EXEX
NOTE 3
NOTE 1
NOTE 2
NOTE 1
NOTE 1
NOTE 1 NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 1
NOTE 7
NOTE:
REFER TO PHASING
NOTES ON SHEET E-003
NOTE 8
NOTE 2NOTE 2
NOTE 2
NOTE 2
BOULEVARD DE FRANCE
BOULEVARD DE FRANCE
A
LA
S K
A S
T R
E E
T
NOTE 2
NOTE 5
E O
CEOC
E O
C
EX. LOAD CENTER TO BE
DEMOLISHED (NOTE 1)
E O
C
E O
C
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
SCALE: 1"=30'-0"
20' 40' 60' 877
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:0
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
1" = 30'-0"
SCALE: 1" = 30'-0"
ES101
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
S
IT
E P
L A
N
D E
M O
L
IT
IO
N
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909485
MLB RMA MBA
ELECTRICAL SITE PLAN - DEMOLITION
JAS
1. DO NOT REMOVE OR DISCONNECT FROM POWER THE EXISTING BLDG 602 TRANSFORMER OR LOAD CENTER UNTIL IT IS DETERMINED WHICH SITE LIGHT CIRCUITS NEED TO BE RE-FED. PROVIDE CIRCUIT TRACING TO DETERMINE WHICH STREET LIGHT POLES ARE AFFECTED BY THE LOAD CENTER REMOVAL. CONTRACTOR MUST IDENTIFY AND LOCATE POINTS IN THE SITE LIGHTING CIRCUITS WHICH WILL REMAIN AFTER DEMOLITION AND BE ACCESSIBLE AFTER CONSTRUCTION. PROVIDE
HANDHOLES AT THESE LOCATIONS FOR CONNECTION TO EXISTING CIRCUITS.
2. REMOVE CABLE AND DUCTBANK IN THEIR ENTIRETY.
3. REMOVE EXISTING PRIMARY LOOP CABLING FROM BLDG 602 TRANSFORMER BACK TO MANHOLE MH-3 AND REMOVE
DUCTBANK IN ITS ENTIRETY. PLUG ALL MANHOLES ENTRANCE WHERE AN OPENING IS LEFT FROM DUCTBANK DEMOLITION.
4. EXISTING DUCTBANK TO REMAIN. REMOVE EXISTING PRIMARY LOOP CABLES CALLED OUT ON SHEET ES601. BLDG 6002
TRANSFORMER WILL REMAIN ENERGIZED THRU THE 2ND LOOP FEEDER.
5. EXISTING DUCTBANK TO REMAIN. REMOVE EXISTING PRIMARY LOOP CABLES CALLED OUT ON SHEET ES601. BLDG 6008
TRANSFORMER WILL REMAIN ENERGIZED THRU THE 2ND LOOP FEEDER.
6. EXISTING SECTIONALIZING CABINET IS MOUNTED DIRECTLY ON TOP OF EXISTING MANHOLE.
7. PROVIDE CIRCUIT TRACING TO CONFIRM EXISTING LIGHT POLES ARE PART OF THE DEMOLITION CIRCUIT AND REPORT
FINDINGS TO ENGINEER OF RECORD.
8. PROVIDE CIRCUIT TRACING TO CONFIRM EXISTING LIGHT POLES ARE NOT PART OF THE DEMOLITION CIRCUIT AND REPORT
FINDINGS TO ENGINEER OF RECORD.
PLAN
NORTH
1. PROVIDE CIRCUIT TRACING TO CONFIRM EXISTING LIGHT POLES ARE PART OF THE DEMOLITION WORK AND
REPORT FINDINGS TO ENGINEER OF RECORD.
2. PROVIDE CIRCUIT TRACING TO CONFIRM EXISTING LIGHT POLES ARE NOT PART OF THE DEMOLITION WORK
AND REPORT FINDINGS TO ENGINEER OF RECORD.
3. REMOVE CABLE AND DUCTBANK IN THEIR ENTIRETY. PLUG ALL MANHOLES ENTRANCE WHERE AN OPENING IS
LEFT FROM DUCTBANK DEMOLITION.
4. SEE SHEET ES601 FOR RE-ESTABLISHMENT OF LOOP CONNECTION.
CONSTRUCTION LIMITS PHASE 3 NOTES: CONSTRUCTION LIMITS PHASE 2 NOTES:
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
PROFESSIONAL
E RN G I N E E
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
W
W
WW
W
WW
SILTED
AREA
CHILLER
CHILLER
ROOF
RECYCLE
TRAILER
T
CLINIC
FFE = 11.50
WM
12" W A
TE
R
M A
IN
12" W A
TE
R
M A
IN
F H
P I0
6" WATER
T
T
P
EX
EX
U P
EXISTING
SECTIONALIZING
CABINET
P
PEX
EX
UP
P
EX
P
EX
T
T
EX
EX
NOTE 1
NOTE 1
PUP
ES401
A1 T
EX. BUILDING 6008
TRANSFORMER TO REMAIN
T
EX
T
EX
UP T
EX. BLDG 6002
TRANSFORMER
EUP
CONSTRUCTION
LIMITS PHASE 3
CONSTRUCTION
LIMITS PHASE 2
G E
N
U S
MH-2
MH-3
MH-1
MH-4
MH-6. SEE DETAILS
ON SHEET ES502
NOTE 2
EX
EX
ER
EX
ES501
A1
ES501
A4 ES501
A2
LOAD BANK
CONNECTION
NOTE 1
UP
WIREWAY AND ECB's
IN RM 1A01A
SC-1
ES503
C3
NOTE:
REFER TO PHASING
NOTES ON SHEET E-003
ES501
A1
FRONT OF
TRANSFORMER
MSWGR IN RM 1A01B
72"
BFG
BOULEVARD DE FRANCE
BOULEVARD DE FRANCE
A
LA
S K
A S
T R
E E
T
VSS EXTENDER
PEDESTAL. SEE
SHEET TS101
GFI
SEE NOTE 1
10's, 1"C.
SEE NOTE 3
ES501
A1
HH
10's, 1"C.
SEE NOTE 4
HH EQ21A:9
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
SCALE: 1"=30'-0"
20' 40' 60' 877
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:1
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
1" = 30'-0"
SCALE: 1" = 30'-0"
ES102
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
S
IT
E P
LA
N
P
O W
E R
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909486
MLB RMA MBA
ELECTRICAL SITE PLAN - POWER
JAS
1. PROVIDE NEW CONDUCTORS IN EXISTING DUCTBANK AS SHOWN ON ES602.
2. EXISTING SECTIONALIZING CABINET IS MOUNTED DIRECTLY ON TOP OF MANHOLE.
3. ROUTE CONDUIT, VIA DIRECTIONAL BORE, IN SAME VICINITY AS SECURITY CAMERA AND
LIGHTING CIRCUIT CONDUITS WHEN CROSSING ALASKA STREET. REFER TO SHEET CU102
FOR ADDITIONAL INFORMATION.
4. SET HANDHOLE IN PLACE UNDER PHASE 2. PROVIDE 30'-0" OF EXTRA CABLE LENGTH FOR
EXTENSION TO VSS EXTENDER PEDESTAL IN PHASE 3.
PLAN
NORTH
1. SURFACE MOUNT RECEPTACLE INSIDE NEMA 4X ENCLOSURE. COORDINATE WITH SECURITY CAMERA
ENCLOSURE MANUFACTURER FOR FINAL LOCATION.
CONSTRUCTION LIMITS PHASE 3 NOTES: CONSTRUCTION LIMITS PHASE 2 NOTES:
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
WW
W
WW
T
CHILLER
CHILLER
G E
N
ROOF
RECYCLE
TRAILER
T
P
CLINIC
FFE = 11.50
M A
T C
H
LI
N E
M A
T C
H
LI
N E
A L
A S
K A
S T
BOULEVARD DE FRANCE
BOULEVARD DE FRANCE
CONSTRUCTION
LIMITS PHASE 3
CONSTRUCTION
LIMITS PHASE 2
EX
EX
EX
EX
EX
EX
EX
EXEX
L4
L4
L4
L3 L4
L4
L4
L4
L4
L4
L3
L1
L1
L2
L1
L1
L1
L1
L1
L1
L2
L1
L1
L2
L4
L3 L4
L1
L1
L2
L1
L1
L2
L2
L1
L1
N41C:13
ELECTRICAL
ROOM 1C
N41C:12,14
THRU LCP-1C
THRU LCP-1C
THRU LCP-1C
THRU LCP-1C
HH
N41C:16,18
THRU LCP-1C
20 22
N41C:20,22
THRU LCP-1C
21 23
HH
THRU LCP-1C
HH
N41C:21,23
THRU LCP-1C
W06
N41C:15
W07
W06
N41C:11
W05 W05 W05
NOTE 5
NOTE 3
HH
HH
HH
HH
1"C, 10's
NOTE 2
1"C, 10's
NOTE 2
1"C, 10's
NOTE 2
HH
1"C, 10's
NOTE 2
HH
1"C, 10's
NOTE 2
NOTE:
REFER TO PHASING
NOTES ON SHEET E-003
1"C, 10's
NOTE 2
EX
W05
N41C:17,19
NOTE 4
NOTE 4
NOTE 2 (TYP)
NOTE 2 (TYP)
W0713
NOTE 1 (TYP)
NOTE 1 (TYP)
NOTE 1 (TYP)
NOTE 1 (TYP)
NOTE 1 (TYP)
NOTE 1 (TYP)
NOTE 1 (TYP)
NOTE 1 (TYP)
10's 10's
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
SCALE: 1"=30'-0"
20' 40' 60' 877
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:1
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
1" = 30'-0"
SCALE: 1" = 30'-0"
ES103
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
S
IT
E P
L A
N
L
IG
H T
IN
G
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909487
MLB AL MBA
ELECTRICAL SITE PLAN - LIGHTING
JAS
1. REFER TO DETAIL A1/ES502 FOR POLE FOUNDATION DETAILS.
2. DIRECT BURY SITE LIGHTING BRANCH CIRCUITING A MINIMUM OF 24" BELOW FINISHED GRADE.
3. ROUTE CONDUIT, VIA DIRECTIONAL BORE, IN SAME VICINITY AS SECURITY CAMERA AND POWER CONDUITS WHEN
CROSSING ALASKA STREET. REFER TO SHEET CU102 FOR ADDITIONAL INFORMATION.
4. SET HANDHOLE IN PLACE UNDER PHASE 2. PROVIDE 5'-0" OF EXTRA CABLE LENGTH AND MAKE SAFE FOR
EXTENSION TO LIGHT POLES IN PHASE 3.
5. ROUTE CONDUIT, VIA DIRECTIONAL BORE, ACROSS ALASKA STREET. REFER TO SHEET CU102 FOR ADDITIONAL
INFORMATION.
PLAN
NORTH
1. REFER TO DETAIL A1/ES502 FOR POLE FOUNDATION DETAILS.
2. DIRECT BURY SITE LIGHTING BRANCH CIRCUITING A MINIMUM OF 24" BELOW FINISHED GRADE.
CONSTRUCTION LIMITS PHASE 3 NOTES: CONSTRUCTION LIMITS PHASE 2 NOTES:
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
J J
EMERGENCY SHUT-
DOWN BUTTON, 48"AFG
CHILLER CH-1
480V, 3PF, 264FLA
CHILLER CH-2
480V, 3PH, 264FLA
RADIATOR END
TRANSFORMER T-1.
SEE DETAIL A3/ES503
GENERATOR SET
AND ENCLOSURE.
SEE DETAIL A1/ES503
U S
CRU-1
480V, 3PH, 9.6FLA
LOAD BANK QUICK CONNECT. SEE
EP601 FOR ADDITIONAL INFORMATION
4HVAC:
14,16,18
NF
NF
LOAD BANK FAN. NEMA 4X,
STAINLESS STEEL
ENCLOSURE. SEE NOTE 3.
(2) 1"C TO ATS's
(CONTROLS). DIRECT
BURY 40" BFG.
(2) 1"C TO REMOTE ANNUNCIATOR
PANEL (RAP) IN RM 1C03. DIRECT
BURY 40" BFG
WP,SS
NOTE 4
T
4HVAC:
19,21,23
WPG
WPG
WPG
WPG
NOTE 5
JACKET HEATER
208V,1PH,22.8A
BATTERY CHARGER
120V,12.5A
1,3
REFER TO SINGLE LINE
DIAGRAM (SHEET
EP601) FOR CONDUIT
AND WIRE SIZE. DIRECT
BURY 40" BFG.
NOTES 1 & 2
LS21A1:
1,3
NOTES 1 & 2
NOTES 1 & 2
LS21A1:6
SLD
WP
U S
U S
U S
LS21A1
LS21A1:510's
SLD.
40" BFG
NEMA 4X, STAINLESS
STEEL ENCLOSURE.
NOTE 6
N21A1:
25,29
8's
NOTE 6
WP,SS
NF
SLD. NOTE 7
MSWGR:3
NF
WP,SS
SLD. NOTE 7
MSWGR:2
SLD
T-1
G E
N E
R A
T O
R S
E T
W08
W08
W08
W08
W08
W08
DP-480-LS:24
WP
NOTE 8 (TYP)
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
4' 8' 16'
SCALE: 1/8"=1'-0"
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:1
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
As indicated
ES401
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E N
LA
R
G E
D S
IT
E
P L A
N S
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909488
MLB RMA MBA
JAS
SCALE: 1/4" = 1'-0"
ENLARGED SITE PLAN - MECH YARD POWER
A1 SCALE: 1/8" = 1'-0"
ENLARGED SITE PLAN - MECH YARD LIGHTING
A4
NOTES:
1. SEE ES102 FOR DUCTBANK CALLOUT.
2. SEE SHEET ES102 FOR CONTINUATION.
3. PROVIDE A 2" DIA IMC NIPPLE, 6" LONG, WITH THREADED CAP ON UNDERSIDE
OF SWITCH FOR CABLE ACCESS DURING LOAD BANK TESTING.
4. PROVIDE CONTROL WIRING AND CONDUIT FOR GENERATOR EMERGENCY
SHUT-OFF SIZED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
5. POWER CONNECTION POINTS FOR BATTERY CHARGER AND JACKET HEATER.
COORDINATE ACTUAL LOCATION WITH MANUFACTURER AND CONCRETE PAD
INSTALLER.
6. 20A-1P, 10KAIC RATED ENCLOSED CIRCUIT BREAKER IN NEMA 4X ENCLOSURE,
MOUNTED 60"AFG AND CONNECTED TO HEAT TRACING CIRCUIT ASSOCIATED
WITH CHILLER UNIT. SEE SHEET M-412 FOR ADDITIONAL INFORMATION.
7. ROUTING OF CHILLER FEEDER IS SHOWN ON SHEET ES102.
8. COORDINATE INSTALLATION OF LUMINAIRE WITH WALL CONSTRUCTION
SHOWN IN DETAIL A1/A-173.
0 2' 4' 8'
SCALE: 1/4"=1'-0"
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
DUCTBANK SCHEDULE
4 - 5" CONDUITS
#1
#2
A1 3 - 1/C #2/0 (15kV) - LOOP IN
SPARE
A2 12 - 4" CONDUITS
#1
#2
#3
#4
#5
#6
#7
#8
#9
#10
4 - 500 KCMIL
4 - 500 KCMIL
4 - 500 KCMIL
4 - 500 KCMIL
4 - 500 KCMIL
4 - 500 KCMIL
4 - 500 KCMIL
4 - 500 KCMIL
#11
#12 SPARE
4 - 500 KCMIL
SPARE
SPARE
#3
#4
3 - 1/C #2/0 (15kV) - LOOP OUT
SPARE
A4 4 - 4" CONDUITS
#1
#2
#3
#4 SPARE
SPARE
4 - 500 KCMIL
4 - 500 KCMIL
NOTES:
1. PROVIDE MINIMUM COVER OF 42" UNLESS OTHERWISE NOTED ON THE
SITE PLANS.
M
IN
4"
3" M
IN
(T Y
P
SEE DUCTBANK SCHEDULE THIS
SHEET
5" 3" MIN.
(TYP.)
21" MIN.
#1 #2
#3 #4
PROVIDE DUCT MARKER MAGNETIC
TAPE AT 12" BELOW GRADE WITH
"ELECTRIC" LOGO
GRADE
SELECT BACKFILL PLACED AND
COMPACTED TO AT LEAST 90% OF
MAXIMUM DENSITY
CONCRETE ENCASEMENT
ANCHORING RODS
@ 60" O.C.
#18 GA. GALV. WIRE (WIRE
FROM TOP TO BOTTOM)
BASE SPACERS @ 60"
O.C.
4"
PROVIDE DUCT MARKER MAGNETIC
TAPE AT 1' BELOW GRADE WITH
"ELECTRIC" LOGO
SELECT BACKFILL PLACED AND
COMPACTED TO AT LEAST 90%
OF MAXIMUM DENSITY
CONCRETE ENCASEMENT
ANCHORING RODS @ 10'
O.C.
#18 GA. GALV. WIRE (WIRE
FROM TOP TO BOTTOM)
BASE SPACERS
@ 60" O.C.
5" 3" MIN.
(TYP.)
4"
3" MIN.
(TYP.)
4"
M
IN
SEE DUCTBANK SCHEDULE FOR
CONDUIT SIZE AND CABLE
GRADE
#1 #2 #3 #4
#5 #6 #7 #8
#9 #12
3" MIN.
(TYP.)
#10 #11
35" MIN.
V A
R
IE
S . S
E E
N O
T E
4"
3" M
IN
(T Y
P
SEE DUCTBANK SCHEDULE THIS
SHEET
5" 3" MIN.
(TYP.)
21" MIN.
#1 #2
#3 #4
PROVIDE DUCT MARKER MAGNETIC
TAPE AT 12" BELOW GRADE WITH
"ELECTRIC" LOGO
GRADE
SELECT BACKFILL PLACED AND
COMPACTED TO AT LEAST 90% OF
MAXIMUM DENSITY
CONCRETE ENCASEMENT
ANCHORING RODS
@ 60" O.C.
#18 GA. GALV. WIRE (WIRE
FROM TOP TO BOTTOM)
BASE SPACERS @ 60"
O.C.
4"
4/0 BARE GROUND. CONNECT TO
GROUND RODS IN MANHOLES
AND AT TRANSFORMER PAD
NOTE: WHERE DUCTBANK ROUTES UNDER PAVED SURFACES, REFER TO CIVIL DETAILS.
A
B
C
D
1 2 3 4
1 2 3 4
A
B
C
D
SCALE:
PROJECT NO:
CONSTR CONTR NO:
NAVFAC DRAWING NO:
SHEET: OF
FIRE PROTECTION
CHIEF ENG/ARCH
BRANCH MGR
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
08/19/2024
P A
R R
IS
I S
L A
N D
S
C M
C R
D
P A
R R
IS
I S
L A
N D
N A
V A
L S
T A
T
IO
N
N O
R F
O L
K V
A
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
M
ID
L A
N T
D C
C O
R E
MT / SVR
EJA
DSN
Approved by Jason J. Root, NAVFAC / MFPO VIA SAT-TO Memo Dated 08/08/2024 Tracey Bond, Defense Health Agency VIA SAT-TO Memo Dated 08/19/2024
/2
/2
:1
:2
P
M
C
U s e rs \r ic k .a n a s ta s io
\D o c u m e n ts
\2
-E ri c k .a n a s ta s io
.r v t
As indicated
ES501
2021-003
D E
N T
A L
C L
IN
IC
R E
P L
A C
E M
E N
T
E
LE
C T
R
IC
A L
S
IT
E D
E T A
IL
S
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A T
L A
N T
IC
12909489
MLB RMA MBA
JAS
SCALE: NOT TO SCALE
GENERATOR FEEDER (2X2) DUCT BANK
A4SCALE: NTS
SECONDARY POWER (3X4) DUCT BANK
A2SCALE: NOT TO SCALE
PRIMARY POWER (2X2) DUCT BANK
A1
M S
O R
G
A N L E E BAR
N E
A AL A B A M
L DI C E N S E
NO. 22474
STYLE
DUCT ENTRANCE
12" x 12" x 10" DEEP
SUMP
6"
A
6"
A
6"
B
6"
PLAN
7/8" ∅ PULLING-IN IRON
FOR MANHOLE FRAME & COVER, SEE FED. SPEC.
A-A-60005 FIG. 4, SIZE 28 AND FIG. 12, SIZE 28
RESPECTIVELY
BRICK COLLAR LINED UP WITH
CEMENT MORTAR
DUCT ENTRANCE
LAP REINF. 24" (TYP.)
WATERSTOP AT ALL
CONSTR. JTS. (TYP.)
7/8" ∅ PULLING-IN IRON
#5 REINF. AT 6" EW TOP,
SIDES & BOTTOM
SLOPE 1:40 TO
SUMP
GROUND ROD & CLAMP
SECTION A-A
NOTES:
1. FOR DETAILS OF CABLE RACKS, DUCT
ENTRANCE AND PULLING-IN IRONS, SEE
PLATE UG-7.
2. MINIMUM CONCRETE COMPRESSIVE
STRENGTH MUST BE 3000 PSI. C (AT HIGH PT.)
6'-6" 6'-6"8'-0"
6'-0"
B
MANHOLE DIMENSIONS
A
6'-0" 6'-0"2
TYPE
STANDARD ELECTRICAL MANHOLE (NONTRAFFIC) TYPES 1 & 2
JUNE 2002SKETCH DATE UG-1
A
1'-0"6"
6"B
C
6"
10"
8"
12" x 12" x 10" DEEP SUMP
8"
A
AA
7/8"∅ PULLING-IN IRON 8"
DUCT ENTRANCE. LOCATION TO BE AS
INDICATED
8"B
8"
PLAN
CONCRETE OR BLACK TOP
ROADWAY
#5 @ 6" EW, T&B
#4 @ 6" EW EF
7/8"∅ PULLING-IN IRON
8"
SLOPE 1:40 TO SUMP
C
B
WATERSTOP AT ALL
CONSTR. JTS. (TYP.)
#4 @ 6" T&B 10"
FOR MANHOLE FRAME & COVER, SEE FED. SPEC.
A-A-60005, FIG. 1, SIZE 30A AND FIG. 8, SIZE 30A,
RESPECTIVELY
BRICK COLLAR LINED UP WITH CEMENT
MORTAR
6" MIN.
DUCT ENTRANCE
LAP REINF. 24" (TYP.)
GROUND ROD & CLAMP
NOTES:
1. MANHOLE AND COVERS ARE DESIGNED FOR
MAXIMUM WHEEL LOAD IN ACCORDANCE WITH
AASHTO HS20-44.
2. FOR DETAILS OF CABLE RACKS, DUCT ENTRANCE
AND PULLING-IN IRONS, SEE PLATE UG-7.
3. MINIMUM CONCRETE COMPRESSIVE STRENGTH
MUST BE 3000 PSI.
SECTION A-A
MANHOLE DIMENSIONS
C (AT HIGH PT.)BATYPE
6'-0" 6'-0" 8'-0"
6'-0" 6'-6" 6'-6"
STANDARD ELECTRICAL MANHOLE (TRAFFIC) TYPES 3 & 4
STYLE UG-2JUNE 2002SKETCH DATE
STAINLESS STEEL
HEX BOLT AND
WASHER
PULL SLOT
SKID
RESISTANT
SURFACE
CONCRETE RING
AROUND BOX
10"
BOX AND
COVER6"
6"
COMPACTED
EARTH
6"
CRUSHED ROCK
SECTIONAL
BOX WHEN
REQUIRED HANDHOLE SIZINGTYPE
12" X 12" X 24" DEEP
12" X 18" X 24" DEEP
12" X 24" X 24" DEEP
24" X 36" X 24" DEEP
30" X 48" X 24" DEEP
HANDHOLE REQUIREMENTS
1. PROVIDE A POLYMER CONCRETE REINFORCED HOUSING WITH A HEAVY WEAVE FIBERGLASS REINFORCING WITH
COMPRESSIVE STRENGTH OF NO LESS THAN 10,000 PSI.
2. COVER AND BOX MUST WITHSTAND A SERVICE LOAD OF NO LESS THAN 15,000 LBS OVER A 10" x 10" AREA.
3. PROVIDE STAINLESS STEEL BOLTS AND INSERTS.
4. PROVIDE WITH (2) 2 1/2" MOUSEHOLES.
5. PROVIDE LABEL "ELECTRICAL" FOR POWER HANDHOLES OR "TELEPHONE" FOR TELEPHONE HANDHOLES, OR AS INDICATED.
STANDARD ELECTRICAL HANDHOLE (NONTRAFFIC)
(COMPOSITE/FIBERGLASS) TYPES 5, 6, 7, 8 & 9
JUNE 2002SKETCH DATE STYLE UG-6
LABEL
ALTERNATE METHOD
L
1"∅ NUT
3" CONCRETE WALL
13/16"
1 1/2" (MIN)
1 1/4"∅ SLEEVE LOCKWASHER
2 1/2"∅ WASHER
6 1/2" X 2 1/2" X 3/16" PLATE
8 3/8"
7/8"∅
9" 3/16"
FILLET WELD
2 1/2" RAD
1"∅ U-BOLT
C
4"
CAST IN PLACE
NOTE
ALL METAL…