60040521.pdf
PDF 452 KB Posted
- Attached to
- Bldg. AS518 Paint Booth Repairs
- Solicitation number
- N4008524R2728
About this file
This document appears to be a set of technical specifications and drawings for a federal contract opportunity related to renovations and repairs to Building AS518 at Camp Lejeune. The key details are:
The federal contract opportunity is for a project to repair the paint booth in Building AS518 at Camp Lejeune. The solicitation number is N4008524R2728, and it is being issued by the Department of the Navy Naval Facilities Engineering Command. Only contractors listed on the General Requirements cover page may submit a proposal for this project within the ROICC Camp Lejeune area of responsibility. The document provides details on the existing electrical panel, loads, and proposed changes to accommodate the paint booth repairs. It includes a detailed equipment nameplate specification, a load summary, and schematic diagrams. No specific pricing terms, set asides, award dates, or incumbents are provided in this document.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2246 Yaupon Drive Wilmington, NC 28401
Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2024CBHF Engineers, PLLC
Engineers, PLLC 35230
SEAL
R
EENI GN
P R
OF E S S I ON
A
E
L
NO
RT H CAROL I NA
JA
S
O N
P . FAM I GL
I E T
T I
ADDENDUM: ADDED TWO SHEETS 06/19/24
"EQUIPMENT NAME"
SOURCE: PANEL "###"
SOURCE LOCATION "###"
RATING: ### AMPS
VOLTAGE: 480/277V, 3Ø, 4WRATING DESIGNATION 1/4"
WHITE ENGRAVED LETTERS
SOURCE DESIGNATION 1/4"
WHITE ENGRAVED LETTERS
3/
4"
LENGTH AS REQUIRED
EQUIPMENT DESIGNATION 3/8"
WHITE ENGRAVED LETTERS
VOLTAGE & PHASE DESIGNATION
1/4" WHITE ENGRAVED LETTERS
MACHINE SCREW WITH ACORN
NUT AND LOCKWASHER, TYP.
SOURCE LOCATION DESIGNATION
1/4" WHITE ENGRAVED LETTERS
NOTE: SEE SPECS. SECTION 260553 FOR NAMEPLATE
MATERIAL AND ENGRAVING COLORS.
NOT TO SCALE1 TYPICAL EQUIPMENT NAMEPLATE DETAIL
EXISTING PANEL P2B (BUILDING AS518)
TYPE: NEMA 1 480 277 V, 3 PH, 4 WIRE MANUFACTURER: GENERAL ELECTRIC
BOLT-ON MOUNT: SURFACE SERIES: CCB
LOAD CKT CKT LOAD VA CKT CKT LOAD
LOAD SERVED VA BKR # A B C # BKR VA LOAD SERVED
PAINT BOOTH (NOTE 1) 17,044 100/3 17,044 (X) SPACE
" 17,044 | 1 17,044 2 " " 17,044 | 17,044 "
(X) UNIT HEATER 19 30/3 70/3 (X) PANEL 2B
" | 3 4 | "
(X) COLUMN 18 BUS DUCT (NOT USED) 125/3 (X) SPACE
" | 5 6 "
(X) COLUMN 18 BUS DUCT (NOT USED) 125/3 125/3 (X) COLUMN 13 BUS DUCT (NOT USED )
" | 7 8 | "
NOTES: 17,044 17,044 17,044 TOTAL V. AMPS 600 A. BUS (COPPER)
1. PROVIDE AND INSTALL NEW CIRCUIT BREAKER IN 62 62 62 CONN. AMPS 600 A. MAIN LUGS
EXISTING PANELBOARD SPACE.
LOAD SUMMARY (BUILDING AS518)
VOLTAGE PHASE
480 3 1.732
EXISTING DEMAND LOAD
(DETERMINED BY 1 YEAR POWER BILLS) 554,000 WATTS
ASSUMED POWER FACTOR OF .8 692,500 VA
EXISTING DEMAND AMPS 833 AMPS
x 125% ( PER NEC 220.87) 1,041 AMPS
LOAD ADDED THIS PROJECT
LARGEST MOTOR APPROX. AMPS 34 AMPS
LARGEST MOTOR APPROX. AMPS X .25 9 AMPS
EXISTING HVAC (FROM PREVIOUS PROJECTS)
AHU01 6,917 VA
HP01 5,986 VA
CH01 24,610 VA
FC01 2,062 VA
SUB-TOTAL HVAC DEMAND 39,575 VA
SUB-TOTAL HVAC DEMAND 48 AMPS
EXISTING EQUIPMENT (FROM PREVIOUS PROJECTS)
HYDRAULIC TEST STAND 187,056 VA
HVAC CONTROL PANEL 300 VA
HEAT TRACE & HOT BOX HEATER 500 VA
SUB-TOTAL EQUIPMENT DEMAND 187,856 VA
TOTAL EQUIPMENT DEMAND 226 AMPS
EXISTING RECEPTACLES (FROM PREVIOUS PROJECTS) 180 VA
TOTAL DEMAND FOR RECEPTACLE 180 VA
TOTAL DEMAND FOR RECEPTACLE 0 AMPS
HVAC (ADDED THIS PROJECT)
PAINT BOOTH 51,131 VA
SUB-TOTAL HVAC DEMAND 51,131 VA
SUB-TOTAL HVAC DEMAND 62 AMPS
ADD FOR LARGEST MOTOR 226 AMPS
TOTAL EQUIPMENT DEMAND 287 AMPS
TOTAL LOAD ADDED THIS PROJECT 335 AMPS
TOTAL LOAD ADDED THIS PROJECT 278,742 VA
TOTAL DEMAND BUILDING AMPS 1,377 AMPS
TOTAL DEMAND BUILDING LOAD 1,144,367 VA
JFamiglietti Date 06/19/2024
| 2024-06-19T09:55:37-0400 | |
| Jason P Famiglietti | |
| I am the author of this document. |
File details come from the government source that posted it. Updated .