This document appears to be a set of technical specifications and details related to a federal contract opportunity for repairs to a paint booth at Building AS518. The key details include:

The solicitation is for a project under the Naval Facilities Engineering Command (NAVFAC) to repair a paint booth, including installation of a new exhaust fan, ductwork, and stack. The work involves roof curb and flashing details, as well as specific requirements for the new exhaust system components. Only contractors listed on the MACC (Multiple Award Construction Contract) are eligible to submit proposals for this project. The solicitation number is N4008524R2728, and the agency is the Department of the Navy.

View the file

Other files

File Type Posted
23-0038 Existing Paint Booth Submittal.pdf PDF
Amend 0004 230038.pdf PDF
Amend 0003 230038.pdf PDF
23-0038 Amendment 0002.pdf PDF
230038 Transmittal Paint Booth.pdf PDF
60040515.pdf PDF
60040513.pdf PDF
23-0038 Upgrade AS518 Paint Booth to NESHAP Stds. Final Specifications 06-19-2024.pdf PDF
Amend 0001 230038.pdf PDF
60040517.pdf PDF
60040520.pdf PDF
23-0038 AS518 MOD Div. 21 Specification.pdf PDF
60040514.pdf PDF
23-0038 AS518 MOD Div. 21 Submittal Register.pdf PDF
60040518.pdf PDF
60040511A.pdf PDF
60040519.pdf PDF
60040521A.pdf PDF
60040521.pdf PDF
60040511.pdf PDF
60040512.pdf PDF
N4008523B0038 Specs.pdf PDF
Mech MACC RFP.pdf PDF
N4008523B0038 Dwgs.pdf PDF
23-0038 APPD.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2246 Yaupon Drive Wilmington, NC 28401

Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2024CBHF Engineers, PLLC

Engineers, PLLC 043801

TROY O. GRADY

SEAL

R

EENI GN

P R

OF E S S I ON

A

E

L

NO

RT H CAROL I NA

NOT TO SCALE1 ROOF CURB DETAIL

NOTES:

1. FOUR (4) CURB WRAP CORNERS WILL COMPLETELY FLASH A MAXIMUM CURB SIZE OF 3'X3'. FOR

LARGER CURBS USE THE TPO CURB WRAP CORNERS IN CONJUNCTION WITH ADDITIONAL SECTIONS

OF TPO MEMBRANE.

2. WHEN MECHANICAL FASTENERS ARE USED TO PENETRATE THE METAL COUNTER-FLASHING, USE

EPDM WASHERS, APPLY WATER CUT-OFF MASTIC UNDER THE COUNTER-FLASHING OR CAULK THE

FASTENER HEADS.

3. APPROXIMATELY 1/8" BEAD OF CUT-EDGE SEALANT IS REQUIRED ON THE CUT EDGES OF THE TPO

FIELD WRAP CORNER.

4. REGARDLESS OF THE FIELD MEMBRANE THICKNESS, THE INTERSECTIONS BETWEEN SPLICES MUST

BE OVERLAID WITH A "T-JOINT" COVER.

USE ONE TPO CURB WRAP CORNER

AT EACH CORNER OF CURB. HOT AIR

WELD ALL SEAMS IN ACCORDANCE

WITH STANDARD SPLICING METHODS.

MAXIMUM 12" O.C. FASTENER SPACING

METAL CAP OR COUNTER-FLASHING

TPO CURB WRAP

HOT AIR WELD 1-1/2" MIN.

CUT-EDGE SEALANT

FASTENER & SEAM FASTENING

PLATE, MAX. 12" o.c.

FASTENER SPACED

AT 12" MAX. O.C.

26 GA. ALUMINUM

CAP.

EXISTING ROOF ASSEMBLY

20 GA. 1-1/2" TYPE B METAL DECK.

3" MINIMUM RIGID INSULATION

SLOPED AT 1/4:12.

8" (M

IN

NOT TO SCALE2 ROOF CURB CAP DETAIL

6' -0

" M

IN

EXISTING PAINT BOOTH NEW FILTER CHAMBER

NEW EXHAUST FAN. LOCATED TO

AVOID STRUCTURAL ROOF

MEMBERS.

NEW EXHAUST DUCTWORK. ROUTED UP

AND THROUGH NEW ROOF PENETRATION.

SEE 1/M-501 FOR CURB INFORMATION.

NOT TO SCALE3 NEW EXHUAST PLENUM, DUCTWORK AND FAN DETAIL

NEW EXHAUST STACK WITH GUY WIRES.

SLOPE