Bldg. AS518 Paint Booth Repairs
Solicitation number
N4008524R2728
Issued by

About this file

This document appears to be an engineering drawing and specifications related to a federal contract opportunity for repairs to a paint booth at Building AS518 on the Camp Lejeune military installation.

The key details are: The contract is for the modification of an existing paint booth to meet NESHAP (National Emission Standards for Hazardous Air Pollutants) requirements. This includes installing a new 3-stage filter chamber, a new 25HP exhaust fan, air solenoid valve, and roof penetration for the exhaust stack. The work must be completed by factory authorized technicians. The solicitation number is N4008524R2728, the opportunity type is a Solicitation, and the contracting agency is the Department of the Navy Naval Facilities Engineering Command. Only pre-qualified MACC (Multiple Award Construction Contract) mechanical contractors are eligible to submit a proposal for this project.

View the file

Other files

File Type Posted
23-0038 Existing Paint Booth Submittal.pdf PDF
Amend 0004 230038.pdf PDF
Amend 0003 230038.pdf PDF
23-0038 Amendment 0002.pdf PDF
230038 Transmittal Paint Booth.pdf PDF
60040513.pdf PDF
23-0038 Upgrade AS518 Paint Booth to NESHAP Stds. Final Specifications 06-19-2024.pdf PDF
Amend 0001 230038.pdf PDF
60040517.pdf PDF
60040516.pdf PDF
60040520.pdf PDF
23-0038 AS518 MOD Div. 21 Specification.pdf PDF
60040514.pdf PDF
23-0038 AS518 MOD Div. 21 Submittal Register.pdf PDF
60040518.pdf PDF
60040511A.pdf PDF
60040519.pdf PDF
60040521A.pdf PDF
60040521.pdf PDF
60040511.pdf PDF
60040512.pdf PDF
N4008523B0038 Specs.pdf PDF
Mech MACC RFP.pdf PDF
N4008523B0038 Dwgs.pdf PDF
23-0038 APPD.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(X) GUH5-1

(X)MAU1

44x44

2246 Yaupon Drive Wilmington, NC 28401

Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2024CBHF Engineers, PLLC

Engineers, PLLC 043801

TROY O. GRADY

SEAL

R

EENI GN

P R

OF E S S I ON

A

E

L

NO

RT H CAROL I NA

ADDENDUM: ADDED TWO SHEETS 06/19/24

1/4" = 1'-0" 0 4' 8'2'1 PARTIAL FLOOR PLAN

PLAN

NORTH

INSTALL NEW FILTER CHAMBER WHILE MAINTAINING ALL OF THE MANUFACTURER'S

RECOMMENDED CLEARANCES.

INSTALL NEW EXHAUST FAN WHILE MAINTAINING ALL OF THE MANUFACTURER'S

RECOMMENDED CLEARANCES.

INSTALL VERTICAL EXHAUST DUCTWORK UP THROUGH NEW ROOF PENETRATION.

PROVIDE DUCT OFFSETS AS NEEDED. INSTALL NEW CURB, SEE 1/M-501 AND

3/M-501 FOR FURTHER INFORMATION.

CONSTRUCTION KEYED NOTES

WORK THIS AREA

GENERAL NOTES

1. EXISTING PAINT BOOTH IS BY ROHNER FINISHING SYSTEMS OUT OF VANCOUVER

WASHINGTON.

2. MODIFICATIONS AND START-UP OF THE PAINT BOOTH MUST BE COMPLETED BY

FACTORY AUTHORIZED TECHNICIANS.

3. MODIFY THE EXISTING PAINT BOOTH TO MEET APPLICABLE NESHAP REQUIREMENTS.

4. PROVIDE NEW NESHAP 3-STAGE FILTER CHAMBER. FILTER SYSTEM MUST MEET OR

EXCEED NATIONAL EMISSION TEST STANDARD 319. PROVIDE MANOMETER TO

MONITOR OVER SPRAY BUILDUP ON FILTERS.

5. PROVIDE NEW 25 HP 460 VOLT 3 PHASE MIXED FLOW CENTRIFUGAL FAN WITH SPARK

RESISTANT CONSTRUCTION AND VFD. FAN MUST BE CAPABLE OF 22,000 CFM WITH

THE ADDITIONAL PRESSURE DROP RESULTING FROM ADDITIONAL FILTRATION. FAN

TO BE INTEGRATED INTO THE EXISTING PAINT BOOTH CONTROL SYSTEM

6. INSTALL AIR SOLENOID VALVE INTERLOCKED WITH SPRAY APPARATUS TO ONLY

ALLOW SPRAY WHILE THE EXHAUST SYSTEM IS OPERATIONAL.

7. ROOF PENETRATION FOR EXHAUST STACK AND GUY WIRES TO BE MADE WEATHER

TIGHT.

ROOF MEMBERS ABOVE (TYPICAL).

NOT TO SCALE0 KEY PLAN