Bldg. AS518 Paint Booth Repairs
Solicitation number
N4008524R2728
Issued by

About this file

This document appears to be an electrical drawing addendum for a federal construction project. The key details are:

The electrical drawing addendum provides additional requirements and specifications for electrical work on the project, including general notes, demolition notes, and a legend of electrical symbols and abbreviations. It covers requirements for items such as lighting fixtures, electrical panels, conduit, wiring, and grounding. The drawings indicate that this is a renovation project, with some demolition and modification of existing electrical systems required. Specific information is provided about maintaining existing systems during construction and coordinating with other trades.

The related federal contract opportunity is for repairs to a paint booth in Building AS518, limited to contractors on the General Requirements cover page. The solicitation is being issued by the Department of the Navy Naval Facilities Engineering Command.

View the file

Other files

File Type Posted
23-0038 Existing Paint Booth Submittal.pdf PDF
Amend 0004 230038.pdf PDF
Amend 0003 230038.pdf PDF
23-0038 Amendment 0002.pdf PDF
230038 Transmittal Paint Booth.pdf PDF
60040515.pdf PDF
60040513.pdf PDF
23-0038 Upgrade AS518 Paint Booth to NESHAP Stds. Final Specifications 06-19-2024.pdf PDF
Amend 0001 230038.pdf PDF
60040516.pdf PDF
60040520.pdf PDF
23-0038 AS518 MOD Div. 21 Specification.pdf PDF
60040514.pdf PDF
23-0038 AS518 MOD Div. 21 Submittal Register.pdf PDF
60040518.pdf PDF
60040511A.pdf PDF
60040519.pdf PDF
60040521A.pdf PDF
60040521.pdf PDF
60040511.pdf PDF
60040512.pdf PDF
N4008523B0038 Specs.pdf PDF
Mech MACC RFP.pdf PDF
N4008523B0038 Dwgs.pdf PDF
23-0038 APPD.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2246 Yaupon Drive Wilmington, NC 28401

Phone: 910.791.4000 Fax: 910.791.5266 www.cbhfengineers.com NC# P-0506c Copyright 2024CBHF Engineers, PLLC

Engineers, PLLC 35230

SEAL

R

EENI GN

P R

OF E S S I ON

A

E

L

NO

RT H CAROL I NA

JA

S

O N

P . FAM I GL

I E T

T I

ADDENDUM: ADDED TWO SHEETS 06/19/24

DESCRIPTIONSYMBOL

2x4 LIGHT FIXTURE SURFACE MOUNTED

ELECTRICAL LEGEND

MANUAL MOTOR STARTER, ELECTRICAL CONTRACTOR SHALL COORDINATE POLES

AND SIZE WITH EQUIPMENT

## = AMPERAGE RATING WHEN INDICATED ON DRAWING

DISCONNECT SWITCH, FUSED, HEAVY DUTY, SIZE AS INDICATED ON DRAWINGS

##A = DISCONNECT SIZE / # = NUMBER OF POLES / # = NEMA RATING,

/##AF = FUSE SIZE

30A/3/3R, W/ 30AF

PANELBOARD, SURFACE OR RECESSED MOUNTED AS SHOWN. SIZE, RATINGS, AND

MOUNTING AS INDICATED ON PANEL SCHEDULE. CONTRACTOR IS RESPONSIBLE FOR

REQUIRED CLEARANCE IN FRONT OF ELECTRICAL PANEL. SEE NEC TABLE 110.26

WORKING SPACES FOR ADDITIONAL CLEARANCE CONDITIONS.

208/120V

CONDUIT, HOME RUN TO PANEL BOARD

HATCHING INDICATES ITEMS TO BE DEMOLISHED. REMOVE DEVICE, EQUIPMENT, FIXTURE

INDICATED, CIRCUIT, AND CONDUIT BACK TO SOURCE UNLESS OTHERWISE NOTED.

POWER & SWITCH LEG

EX

E-XXX

DETAIL, SECTION OR

PLAN NUMBER

DRAWING SHEET PLAN,

DETAIL OR SECTION

APPEARS ON

EX

E-XXX

ENLARGED PLAN ELEVATION

SM ##

GENERAL NOTES

1. ALL ELECTRICAL WORK SHALL BE IN FULL COMPLIANCE WITH NFPA 70, THE INTERNATIONAL BUILDING

CODE, ALL LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE

LOCAL AUTHORITY HAVING JURISDICTION.

2. THE ELECTRICAL CONTRACTOR SHALL HAVE A VALID NORTH CAROLINA PUBLIC UTILITY - ELECTRICAL

CONTRACTORS LICENSE AND SHALL BE INSURED TO DO SUCH WORK IN THE STATE OF NORTH

CAROLINA.

3. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED AND LABELED BY A

NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL MATERIAL, EQUIPMENT AND DEVICES SHALL BE NEW

CURRENT PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH

PRODUCTS. EQUIPMENT SHALL BE SUITABLE FOR ITS APPLICATION (E.G. WHEN INSTALLED OUTDOORS, IT SHALL BE WEATHERPROOF, ETC.)

4. THE CONTRACTOR SHALL REVIEW THE ARCHITECTURAL AND MECHANICAL DRAWINGS AND

SPECIFICATIONS FOR WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL

EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER.

5. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THOROUGHLY FAMILIARIZING HIMSELF WITH ANY CONTRACTUAL REQUIREMENTS AS MAY BE SET FORTH IN THE OTHER DIVISIONS OF THE PROJECT

SPECIFICATIONS.

6. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY THE CONTRACTOR SHALL BE COMPLETE AND FULLY-FUNCTIONING AFTER INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS

WORK, BUT REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM, SHALL BE

PROVIDED AT NO ADDITIONAL COST TO THE GOVERNMENT. ADDITIONAL CIRCUITS SHALL BE INSTALLED

WHEREVER NEEDED TO CONFORM TO THE SPECIFIC REQUIREMENTS OF EQUIPMENT.

7. TEMPORARY POWER CONNECTIONS AS REQUIRED SHALL BE PROVIDED BY THE CONTRACTOR AT NO

ADDITIONAL EXPENSE TO THE GOVERNMENT. ALL TEMPORARY EQUIPMENT WIRING SHALL BE IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE CONTRACTOR SHALL PROVIDE DETAILS, METHODS, MATERIALS, ETC. TO THE CONTRACTING OFFICER PRIOR TO MAKING TEMPORARY

CONNECTIONS. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS INCLUDING CONTROL

EQUIPMENT, MOTOR STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS,

TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE ELECTRICAL UTILITY AS

REQUIRED.

8. THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR ADJUSTMENTS NECESSARY FOR THE PROPER

FUNCTIONING OF THE SYSTEM AND EQUIPMENT.

9. ALL EQUIPMENT SHOWN DOTTED OR DASHED IS BY OTHERS OR IS EXISTING, AS NOTED.

10. ALL ELECTRICAL EQUIPMENT SHALL, AT ALL TIMES DURING CONSTRUCTION, BE ADEQUATELY

PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER AND/OR THE ELEMENTS.

ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUT OF DOORS, BUT SHALL BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR THE ELEMENTS, SUCH DAMAGE SHALL BE REPLACED AT NO ADDITIONAL COST TO

THE GOVERNMENT.

11. DO NOT SCALE ELECTRICAL DRAWINGS. REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONS

OF NEW CONSTRUCTION. FIELD VERIFY ALL EXISTING CONDITION DIMENSIONS.

12. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR OTHER INSTALLATION

DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING OF FEEDER AND BRANCH CIRCUIT

RACEWAYS AND CABLES IS THE RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT

ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE CONTRACTOR SHALL

ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION.

13. UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. EXACT DEVICE LOCATIONS SHALL BE AS INDICATED ON THE ARCHITECTURAL DRAWINGS OR AS DIMENSIONED. IF NOT SHOWN ON THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL DRAWINGS, VERIFY EXACT LOCATION WITH THE CONTRACTING

OFFICER PRIOR TO ROUGH-IN.

14. CONDUIT TERMINATING IN PRESSED STEEL BOXES SHALL HAVE DOUBLE LOCKNUTS AND INSULATED

BUSHINGS. CONDUITS TERMINATING IN GASKETED ENCLOSURES SHALL BE TERMINATED WITH

GROUNDING TYPE CONDUIT HUBS.

15. THE DRAWINGS INDICATE THE NUMBER OF BRANCH CIRCUIT HOMERUN PHASE CONDUCTORS VIA

ARROWHEADS. PROVIDE NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED. ADDITIONAL

CONDUCTORS REQUIRED FOR CONTROL SHALL BE INCLUDED EVEN IF NOT EXPLICITLY SHOWN.

16. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS WATERTIGHT.

17. ALL EXTERIOR WIRING DEVICES, BOXES, ETC. SHALL BE WEATHERPROOF. LIGHTING FIXTURES SHALL

BE APPROPRIATELY RATED AND LISTED FOR THE ENVIRONMENT.

18. ALL RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE.

19. ALL SURFACE MOUNTED RACEWAY MOUNTED ON THE INTERIOR OF THE BUILDING SHALL BE EMT. RGS

SHALL BE USED WHERE THE POSSIBILITY EXISTS FOR PHYSICAL DAMAGE.

20. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS SHALL BE RUN STRAIGHT AND TRUE. RUN PARALLEL OR

BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE PRACTICAL. MAKE BENDS IN

PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL.

21. PROVIDE AND PLACE ALL SLEEVES FOR CONDUITS PENETRATING WALLS, FLOORS, PARTITIONS, ETC.

LOCATE ALL NECESSARY SLOTS FOR ELECTRICAL WORK AND FORM BEFORE CONCRETE IS POURED.

22. PATCHING OF WATERPROOFED SURFACES SHALL RENDER THE AREA OF THE PATCHING COMPLETELY

WATERPROOF.

23. ALL MOTORS AND OTHER VIBRATING EQUIPMENT SHALL BE CONNECTED TO THE CONDUIT SYSTEM BY

MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF FLEXIBLE CONDUIT UNLESS OTHERWISE

INDICATED. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED INSIDE THE FLEXIBLE

CONDUIT AND TERMINATE AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.

24. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES, RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR WALLS SHALL BE SUPPORTED BY SPACERS TO

PROVIDE A 1/4" MINIMUM CLEARANCE BETWEEN THE WALL AND EQUIPMENT.

25. FINAL TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR POCKET SHALL

INCLUDE THE GENERAL DESCRIPTION SHOWN ON THE PANEL SCHEDULES ON THE DRAWINGS.

26. CONDUCTOR SIZING IS BASED ON 75 DEGREE C. COPPER NEC RATINGS, UNLESS NOTED OTHERWISE.

THE CONTRACTOR SHALL VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR

SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY FOR EVALUATION/CORRECTION.

27. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL ROUGH PLASTERING OR MASONRY HAS BEEN

COMPLETED.

28. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS SHALL CONSIST OF #12 OR #10 AWG

MINIMUM PHASE, NEUTRAL AND EQUIPMENT GROUND CONDUCTORS IN 3/4" MINIMUM RACEWAY.

29. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH

(INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.

30. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN CONDUCTORS BEING SPLICED.

USE SPLICE AND TAP CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS AT EACH OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND COMPONENTS TO

WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY THE MANUFACTURER.

31. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE CONTRACTING

OFFICER. HOMERUNS SHALL BE CONTINUOUS FROM THE LAST OUTLET BOX TO THE SERVING

PANELBOARD.

32. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.

33. TROUGH TAPS SHALL BE AT SWITCH AMPACITY, UNLESS NOTED OTHERWISE.

34. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS. ALSO COORDINATE MOUNTING HEIGHTS WITH THE ARCHITECTURAL DRAWINGS. IF CONFLICTING, ARCHITECTURAL DRAWINGS AND

DETAILS SHALL GOVERN.

35. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IN ACCORDANCE WITH THE NEC INCLUDING ALL EXTERIOR RECEPTACLES AND RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS. ALL RECEPTACLES INSTALLED WITHIN 6 FEET OF A SINK SHALL BE GFI PROTECTED.

36. CONNECT BATTERY PACK TYPE EMERGENCY AND EXIT LIGHTING FIXTURES AND FLUORESCENT EMERGENCY BATTERY (BODINE TYPE) BALLASTS TO THE UNSWITCHED LIGHTING CIRCUIT SERVING THE SPACE LIGHTED BY THE EMERGENCY AND EXIT FIXTURES. THESE CONNECTIONS ARE INTENTIONALLY

NOT SHOWN TO MAINTAIN DRAWING FOR CLARITY.

37. ADJACENT SWITCHES SHALL BE GANGED. INSTALL BARRIERS BETWEEN UNLIKE VOLTAGE SECTIONS.

38. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR SHALL COORDINATE WITH

OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL EQUIPMENT (MOTORS, HEATERS,

COMPRESSORS, ETC.) AND ADJUST THE RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT.

39. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE CONTRACTOR PROVIDING THE

EQUIPMENT.

40. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS. VERIFY THE TYPE OF FINAL CONNECTION

AND PROVIDE APPROPRIATE WIRING METHOD. THE CONTRACTOR SHALL COORDINATE WITH THE

MECHANICAL AND PLUMBING EQUIPMENT, PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY MECHANICAL AND PLUMBING EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE

ELECTRICAL DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR COSTS ASSOCIATED WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION EQUIPMENT, EVEN IF THE ELECTRICAL

WORK IS INSTALLED PER THE ELECTRICAL DRAWINGS.

41. THE CONTRACTORS SHALL FURNISH ALL STARTERS AND CONTROLS FOR THEIR EQUIPMENT. THE CONTRACTOR SHALL PROVIDE ALL SAFETY SWITCHES, SHALL MOUNT STARTERS AND PROVIDE WIRING AND CONNECTIONS TO LINE SIDE OF STARTERS. THE CONTRACTOR SHALL PROVIDE LOAD SIDE WIRING

AND CONNECTIONS TO MECHANICAL AND PLUMBING EQUIPMENT. FOR RESISTANCE TYPE LOADS

WHERE STARTERS OR CONTACTORS ARE NOT REQUIRED, THE CONTRACTOR SHALL PROVIDE ALL

POWER WIRING AND CONNECTIONS COMPLETE TO EQUIPMENT. THE MECHANICAL AND PLUMBING

CONTRACTORS SHALL PROVIDE ALL CONTROL WIRING AND CONNECTIONS AND DEVICES FOR THEIR

EQUIPMENT.

42. THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS AND CORDSETS WITH

VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS FOR SPECIALITY EQUIPMENT WITH

CASEWORK PRIOR TO ROUGH-IN.

43. THE LAYOUT AND PLACEMENT OF ELECTRICAL DISTRIBUTION EQUIPMENT IN ELECTRICAL AND

MECHANICAL EQUIPMENT ROOMS IS BASED ON PUBLISHED EQUIPMENT SIZES AND SHALL BE

FOLLOWED AS CLOSELY AS POSSIBLE. DEVIATIONS FROM CONFIGURATIONS SHOWN IS THE

RESPONSIBILITY OF THE CONTRACTOR. PROVIDE NATIONAL ELECTRIC CODE REQUIRED CLEARANCES

FOR ALL ELECTRICAL EQUIPMENT, PANELBOARDS, TRANSFORMERS, SAFETY SWITCHES,

SWITCHBOARDS, ETC. COORDINATE RESOLUTION OF CONFLICTS WITH OTHER TRADES. ADVISE THE

CONTRACTING OFFICER OF CONFLICTS BEFORE ROUGH-IN.

44. INSTALLATION INFORMATION PACKED WITH LIGHTING FIXTURES, DEVICES AND EQUIPMENT SHALL BE

RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.

45. THE CONTRACTOR SHALL PERFORM ALL CUTTING IN STRAIGHT LINES USING 90 DEGREE ANGLES AS MUCH AS POSSIBLE TO INSTALL ALL EQUIPMENT AS REQUIRED. CONTRACTOR SHALL REESTABLISH ALL FINISHES TO THEIR ORIGINAL CONDITION WHERE CUTTING AND PATCHING OCCUR. ALL CUTTING AND

PATCHING SHALL BE DONE IN A THOROUGHLY WORKMANSHIP MANNER. SAW CUT CONCRETE AND

MASONRY PRIOR TO BREAKING OUT SECTIONS. ALL PATCHING MATERIALS AND WORKMANSHIP SHALL BE PERFORMED BY TRADESMEN EXPERIENCED IN THAT WORK. ALL WORK SHALL BE SUBJECT TO THE

APPROVAL OF THE CONTRACTING OFFICER.

46. INSTALL WORK AT SUCH TIME AS TO REQUIRE THE MINIMUM AMOUNT TO CUTTING AND PATCHING.

47. SAFETY: COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.

48. CONTRACTOR IS RESPONSIBLE FOR PROVIDING OVERLOADS FOR EACH MOTOR RELOCATED OR

INSTALLED DURING THIS PROJECT. OVERLOADS SHALL BE SIZED PER NAMEPLATE DATA OF

EQUIPMENT.

GENERAL DEMOLITION NOTES

1. SELECTIVE ELECTRICAL DEMOLITION SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR AS

DESCRIBED HEREIN AND AS SHOWN ON THE CONTRACT DRAWINGS. GROSS DEMOLITION WILL BE

PROVIDED BY THE GENERAL CONTRACTOR. IDENTIFY ACTIVE UTILITIES, AND AT THE APPROPRIATE TIME, DISCONNECT AND CAP OFF SUCH UTILITIES AND PROVIDE EXPERIENCED PERSONNEL ON SITE

DURING GENERAL CONTRACTOR DEMOLITION OPERATIONS TO PERFORM SUCH OPERATIONS AND

RESOLVE ISSUES. REMOVE MATERIALS NOTED FOR SALVAGE AND REUSE. IDENTIFY AND MARK

WIRING AND DEVICES TO REMAIN FOR THE GENERAL CONTRACTOR.

2. THE ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR DEMOLITION REQUIREMENTS AND CARRY OUT HIS

WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER. REMOVE ALL WIRING DEVICES, BOXES,

FIXTURES, EXPOSED ABANDONED RACEWAYS, HANGARS, ETC., AND THOSE MADE OBSOLETE BY THESE

ALTERATIONS AND AS SHOWN ON THE ELECTRICAL DRAWINGS. ALL ITEMS TO BE REMOVED OR

MODIFIED MAY NOT BE SHOWN, HOWEVER, THIS CONTRACTOR SHALL REMOVE ANY ELECTRICAL WORK

AS REQUIRED BY THE CONSTRUCTION OR AS DIRECTED BY THE GOVERNMENT OR

ARCHITECT/ENGINEER. SURVEY THE AFFECTED AREAS BEFORE SUBMITTING A BID AS ALL EXISTING CONDITIONS CANNOT BE COMPLETELY DEPICTED ON THE DRAWINGS AND SOME UNUSUAL CONDITIONS

MAY EXIST.

3. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION.

4. ALL EXISTING ELECTRICAL EQUIPMENT AND DEVICES SHALL REMAIN UNLESS SPECIFICALLY NOTED TO

BE REMOVED.

5. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS ARE AS SHOWN ON DRAWINGS.

6. VERIFY THAT ABANDONED WIRING AND EQUIPMENT SERVE ONLY ABANDONED FACILITIES.

7. DISCONNECT AND/OR DE-ENERGIZE ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS

SCHEDULED FOR REMOVAL.

8. PROVIDE TEMPORARY AND/OR PERMANENT WIRING AND CONNECTIONS AS SHOWN AND/OR AS

REQUIRED BY CONDITIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION.

WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR CIRCUITS, AND WHEN SUCH WORK IS SPECIFICALLY APPROVED BY THE GOVERNMENT AND PERMITTED BY REGULATORY AUTHORITIES, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS.

9. EXISTING ELECTRICAL SERVICE: COORDINATE POWER OUTAGES WITH THE GOVERNMENT AND UTILITY

COMPANY. MAINTAIN EXISTING SYSTEMS IN SERVICE. DISABLE SYSTEMS ONLY TO MAKE

SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM THE GOVERNMENT AT LEAST 24 HOURS

BEFORE PARTIALLY OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION. MAKE

TEMPORARY CONNECTIONS TO MAINTAIN SERVICE IN AREAS ADJACENT TO WORK AREA.

10. CONTINUOUS SERVICE IS REQUIRED ON ALL CIRCUITS AND OUTLETS AFFECTED BY THESE CHANGES, EXCEPT WHERE THE GOVERNMENT WILL PERMIT AN OUTAGE FOR A SPECIFIC TIME. OBTAIN

GOVERNMENT'S CONSENT BEFORE REMOVING ANY CIRCUIT FROM CONTINUOUS SERVICE.

11. PROTECT ALL EXISTING TELEPHONE, DATA, LIFE SAFETY SYSTEMS, FIRE ALARM, SECURITY, ACCESS

CONTROL AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION THROUGHOUT THE

PROGRESS OF THE WORK. NOTIFY THE GOVERNMENT AND ARCHITECT/ENGINEER IN WRITING IF

SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE DURATION OF A

PROPOSED OUTAGE CANNOT BE TOLERATED BY THE GOVERNMENT, PROVIDE TEMPORARY

CONNECTIONS AS REQUIRED TO MAINTAIN SERVICE.

12. WHERE ELECTRICAL SYSTEMS PASS THROUGH THE DEMOLITION AREAS TO SERVE OTHER PORTIONS

OF THE PREMISES, THEY SHALL BE PROTECTED FROM DAMAGE AND REMAIN OR BE SUITABLY

RELOCATED UTILIZING MATCHING SIZE AND TYPE MATERIALS AND THE SYSTEM RESTORED TO NORMAL OPERATION. ADVISE THE ARCHITECT/ENGINEER IMMEDIATELY IF SUCH CONDITIONS ARE UNCOVERED

BEFORE PROCEEDING WITH ADDITIONAL WORK.

13. EXISTING FIRE ALARM SYSTEM: COORDINATE WORK WITH THE GOVERNMENT'S FIRE ALARM SYSTEM VENDOR AND MAINTAIN THE EXISTING SYSTEM IN SERVICE UNTIL THE NEW SYSTEM IS ACCEPTED.

DISABLE SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. NOTIFY THE GOVERNMENT AND LOCAL FIRE SERVICE AT LEAST 24 HOURS BEFORE PARTIALLY OR COMPLETELY DISABLING SYSTEM.

LIMIT OUTAGES TO NORMAL BUSINESS HOURS ONLY AND MINIMIZE OUTAGE DURATION. MAKE

TEMPORARY CONNECTIONS TO MAINTAIN SERVICE IN AREAS ADJACENT TO WORK AREA.

14. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN ACTIVE. MODIFY

INSTALLATION OR PROVIDE ACCESS PANEL AS APPROPRIATE.

15. ENDS OF ALL CONDUITS TO REMAIN SHALL BE TIGHTLY PLUGGED TO EXCLUDE DUST AND MOISTURE

WHILE THE BUILDING IS UNDER RENOVATION.

16. PROTECT EXISTING CIRCUITS TO REMAIN AND EXTEND AS REQUIRED UTILIZING MATCHING

CONDUCTORS AND CONDUIT SIZE AND TYPE.

17. SECURE ALL CIRCUITS, RACEWAYS, CABLE AND CONDUCTORS THAT, AS A RESULT FROM THIS

CONSTRUCTION, ARE ABANDONED OR UNUSED. REMOVE UNUSED EXPOSED CONDUIT AND WIRING

BACK TO POINT OF CONCEALMENT INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILINGS.

REMOVE UNUSED WIRING IN CONCEALED CONDUITS BACK TO SOURCE OR NEAREST POINT OF USAGE.

BLANK ABANDONED KNOCKOUTS IN REMAINING BOXES. INSTALL BLANK PLATES FOR ALL UNUSED OUTLETS THAT WILL REMAIN AS A RESULT OF THIS CONSTRUCTION. ALL SUCH WORK SHALL BE IN

STRICT ACCORDANCE WITH ALL APPLICABLE CODES AND ORDINANCES.

18. TRACE OUT EXISTING WIRING THAT IS TO BE RELOCATED OR REMOVED AND PERFORM THE

RELOCATION OR REMOVAL WORK AS REQUIRED FOR A COMPLETE OPERATING AND SAFE SYSTEM.

19. RECONNECT EXISTING CIRCUITS SEPARATED AS A RESULT OF THIS CONSTRUCTION.

20. DELIVER ALL REMOVED AND SALVAGED LIGHTING FIXTURES, WIRING DEVICES, FIRE ALARM DEVICES, SPEAKERS, ETC., TO THE GOVERNMENT, OR AT THE GOVERNMENT'S OPTION, DISPOSE OF PROPERLY OFF SITE IN ACCORDANCE WITH LOCAL, STATE AND FEDERAL ENVIRONMENTAL REGULATIONS. FEES

ASSOCIATED WITH DISPOSAL SHALL BE INCLUDED IN THE CONTRACTOR'S BASE BID.

21. PROTECT EXISTING CIRCUITS FEEDING LIGHTING FIXTURES FOR EXTENSION TO NEW AND RELOCATED

LIGHTING FIXTURES.

22. ALL FLUSH MOUNTED WIRING DEVICES SHALL REMAIN UNLESS SPECIFICALLY NOTED TO BE REMOVED.

IT IS THE INTENTION OF THE THIS CONTRACT TO REMOVE ALL FLUSH MOUNTED DEVICES THAT

CONFLICT WITH NEW CONSTRUCTION AND SECURE THEIR ASSOCIATED BRANCH CIRCUITS.

23. COORDINATE WITH THE OTHER TRADES, PRIOR TO BID, AND INCLUDE IN THE BASE BID THE ELECTRICAL DISCONNECTION OF ANY EQUIPMENT BEING DEMOLISHED, EVEN IF NOT EXPLICITLY SHOWN. UNLESS NOTED OTHERWISE, REMOVE ALL DEMOLISHED EQUIPMENT FROM THE PROPERTY AND IDENTIFIED IN

THE ELECTRICAL DRAWINGS.

24. THESE DRAWINGS ARE COMPILED BY THE ARCHITECT/ENGINEER FROM THE GOVERNMENT'S RECORD DRAWINGS AND LIMITED FIELD VERIFICATION OF EXISTING CONDITIONS FOR THE PURPOSE OF INDICATING THE WORK REQUIRED AND ARE BELIEVED TO BE CORRECT. NOTWITHSTANDING, THE CONTRACTOR SHALL VERIFY ALL CIRCUITS, WIRING, CONDUIT, DIMENSIONS, POINTS OF ACCESS AND ALL FIELD CONDITIONS AFFECTING HIS WORK. BEGINNING OF DEMOLITION MEANS THE CONTRACTOR

ACCEPTS EXISTING CONDITIONS.

25. THE CONTRACTOR IS RESPONSIBLE FOR DISPOSAL OF ALL LAMPS CONTAINING MERCURY IN A LINED

LANDFILL IN ACCORDANCE WITH NC GEN STATUTE 309.10M.

26. SEE GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.

A, AMP

AFF

AFG

AHU

AIC

ATS

AWG

BOF

BRKR

C, CND

CAB

CAT

CL

CB

CCTV

CKT

CLG

CP

CR

CS

CV

CT

CU

EF

EMER

EMT

ENCL

EQUIP

EWC

EWH

EPRF

FA

FAAP

FACP

FBO

FLA

FLUOR

FLR

FWE

GEN

G, GND

GFCI

HH

HID

HOA

HP

HPF

HPS

HTR

HV

Hz

IMC

INCAND

JB

K

KCMIL

KVA

KW

KWH

LP

LTG

MCB

MCC

MCP

MDP

MFR

MH

MLO

MTD

MTG

MTS

MV

N, NEUT

NA

NC

NEC

NIC

NL

NO

NTS

P

PA

PB

PF

PH,ɸ

PLC

PNL

PP

PT

PWR

RECPT, RCP

REQ'D

RGS

RM

RTU

SCR

SH

SPEC

SS

SST

SW

SWBD

SWGR

TEL

TPS

TVSS

TYP

UGND

UH

UON

UTIL

V

VFD

W

WH

WP

XFMR

AMPERE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BOTTOM OF FIXTURE

BREAKER

CONDUIT

CABINET

CATALOG

CHLORINE

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CEILING

CONTROL PANEL

CONTROL RELAY, CORROSION RESISTANT

CONTROL SWITCH

CONTROL VALVE

CURRENT TRANSFORMER

COPPER

EXHAUST FAN

EMERGENCY

ELECTRICAL METALLIC TUBING

ENCLOSURE

EQUIPMENT

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXPLOSION PROOF

FIRE ALARM

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FURNISHED BY OTHERS

FULL LOAD AMPS

FLUORESCENT

FLOOR

FURNISHED WITH EQUIPMENT

GENERATOR

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

HANDHOLE

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO

HORSE POWER

HIGH POWER FACTOR

HIGH PRESSURE SODIUM

HEATER

HIGH VOLTAGE

HERTZ

INTERMEDIATE METALLIC CONDUIT

INCANDESCENT

JUNCTION BOX

THOUSAND

THOUSAND CIRCULAR MILLS

KILOVOLT AMPERE

KILOWATTS

KILOWATT-HOURS

LIGHTING PANEL, LIGHT POLE

LIGHTING

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTOR

MAIN DISTRIBUTION PANEL

MANUFACTURER

MANHOLE

MAIN LUGS ONLY

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

MEDIUM VOLTAGE

NEUTRAL

NOT APPLICABLE

NORMALLY CLOSED

NATIONAL ELECTRIC CODE

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE

PUBLIC ADDRESS

PULL BOX, PUSH-BUTTON

POWER FACTOR

PHASE

PROGRAMMABLE LOGIC CONTROLLER

PANEL

POWER PANEL, POWER POLE

POTENTIAL TRANSFORMER

POWER

RECEPTACLE

REQUIRED

RIGID GALVANIZED STEEL CONDUIT

ROOM

REMOTE TELEMETRY UNIT

DC MOTOR DRIVE

SHEET

SPECIFICATION

SELECTOR SWITCH

STAINLESS STEEL

SWITCH

SWITCHBOARD

SWITCH GEAR

TELEPHONE

TWISTED PAIR SHIELDED

TRANSIENT VOLTAGE SURGE SUPPRESSER

TYPICAL

UNDERGROUND

UNIT HEATER

UNLESS OTHERWISE NOTED

UTILITY

VOLTS

VARIABLE FREQUENCY DRIVE

WIRE, WATT

WATT-HOUR

WEATHERPROOF

TRANSFORMER

TYPICAL ABBREVIATIONS:

RECEPTACLE, DUPLEX, 120VAC, 20A, MOUNTED 16" AFF, UNLESS OTHERWISE NOTED. (SEE

ELECTRICAL MOUNTING HEIGHT DETAIL)

WP - LISTED WEATHER-RESISTANT TYPE DEVICE WITH WEATHERPROOF IN USE COVER

GFI - GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A, MOUNTED 6" ABOVE

COUNTER OR BACK SPLASH LOCATE GFI TEST SWITCH IN A READILY ACCESSIBLE

LOCATION

TR - TAMPER RESISTANT

2 HOUR RATED FIRE WALLuu uuu u u 1 HOUR RATED FIRE WALL

3 HOUR RATED FIRE WALL

SMOKE PARTITIONSP

EXISTING 2x4 LIGHT FIXTURE SURFACE MOUNTED

EXISTING LIGHT FIXTURE TO BE REMOVED

(X)

EXISTING(X)

JFamiglietti Date 06/19/2024

2024-06-19T09:55:38-0400
Jason P Famiglietti
I am the author of this document.