AMD 02 CU-127-AST-01.pdf
PDF 2 MB Posted
- Attached to
- Results - Demolish Bulk Fuel Facility Cutler Federal contract opportunity
- Solicitation number
- N4008524B2507
About this file
This document is an Inspection Report for a diesel tank (CU-127-AST-01) located in Cutler, Maine. The report was prepared by Applied Technical Services (ATS) and provides a condition assessment of the external and internal components of the tank. Key findings include:
The tank's exterior shows scattered coating failure, surface rust, and biological growth. Access to some components was limited, so a more thorough external inspection may be needed. The concrete foundation shows deterioration. The report recommends coating repairs, verifying adequate overpressure protection, and scheduling future inspections per API-653 guidelines. No UT thickness data was collected, as it was not part of the inspection scope. Overall, the report identifies several priority action items to address the equipment's condition.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLIED TECHNICAL SERVICES
Job Number: 399868
Inspected by:
Project Manager
Chuck Morissette
Reviewed by:
Senior Engineer
East Syracuse, NY • 315-487-4390
Inspection Report
Diesel Tank for
CU-127-AST-01
Cutler, ME
CCI Construction Services
In states where Applied Technical Services does not provide engineering services, engineering services will be provided by ATS Engineering, (P)LLC or a licensed contractor.
Professional Engineers and Scientists: Design • Consulting • Testing • Inspection
External Inspection:
Internal Inspection:
May 30, 2023 Not in scope
Elizabeth Ray
62886
UT Thickness Testing: Not in scope
API-653
451A (03-2023) Proprietary Document. To be reproduced only in full.
Reinspection Frequency
Visual Inspection
Personnel Qualifications
Photographs
Executive Summary
Action Items
Table of Contents 399868
Job Number
General Equipment Information ft in ft in This area intentionally left blank
Long: Circ:
n/a
UnknownSerial Number
Other Test Methods Performed
Jurisdiction and RAGAGEP*
Shell-Side
Service Category
Previous Internal Visual
Previous UTT Data -
Unknown
Unknown
Unknown
Construction Information
Construction Standard
Material Type
05-2022
While out of service
Not in scope
Not in scope
+ pressure - vacuum temperature
External Visual
Internal Visual
UT Thickness
Contents Diesel
State Equipment is Located
Not Applicable
Inspection Scope
Unknown
None
Joint Efficiency
YesPrevious External Visual
No
Historical Documentation
Inspection & Analysis API-653
New York
Date
NoDrawings Available
No
Approximate Volume
Outer Diameter 36
N/A
NDT Technician(s)
315,000
Elizabeth Ray gallons
Inspector(s)
API 653 (62886)
Training
Training
N/A
Equipment Identification
Diesel TankEquipment Name
General Equipment Information 399868
Job Number
Shell Height / Length
Owner
Cutler, ME
CCI Construction Services
Location
Equipment Location
In tank farm across from building 103.
Equipment Number
40 0
CU-127-AST-01
Unknown n/a n/a temperature n/aField Observed
Design
Field Observed
Design
Unknown AmbientUnknown
UnknownUnknown vent pressure vent vacuum temperature n/a n/an/a vent pressure vent vacuum
Jacket-Side
Contents n/a
+ pressure - vacuum temperature
UnknownManufacturer
Year of Construction
Carbon Steel
Yes/No
API-650
451A (03-2023)
* Recognized and Generally Accepted Good Engineering Practices
Proprietary Document. To be reproduced only in full.
An earthen berm was observed. No visible deterioration or damage observed.
The tank's nameplate has been painted over. Coating failure and surface rust observed on access ladder and platform.
None was observed on this equipment.
Roof
Inspection of this component was limited due to accessibility. Scattered coating failure and surface rust observed. Biological growth
(mold/moss) observed throughout.
Floor Chime
This was observed on the roof. No visible deterioration or damage observed.
Overflow
Scattered coating failure and surface rust observed. Heavy biological growth was observed throughout.
Anchorage
No anchors observed.
Foundation
This report identifies the over-pressure protection that was readily obvious during inspection. No determination of relief capacity was made by ATS. The owner should verify properly sized protection is provided for the system.
Normal Venting
Shell
Inspection of this component was limited due to accessibility. Scattered coating failure and surface rust observed.
Nozzles
Inspection of this component was limited due to accessibility. Scattered coating failure and surface rust observed.
Nameplate/Platforms/Ladders/Labels
A concrete support pad is the foundation for this equipment. Concrete deterioration observed throughout.
Secondary Containment
Executive Summary
External Condition
Job Number
Scope of Work
Over-Pressure Protection
399868
ATS performed inspections in general accordance with API-653. This report lists the results of inspection and provides a condition assessment of the equipment based upon the information gathered.
External inspections were performed from the ground and available ladders/platforms. External inspections were limited due to a lack of access (or height restrictions).
Grounding Cables
More than 3 grounding cables were observed. No visible deterioration or damage observed.
Executive Summary Job Number
399868
Analysis
This equipment was visually assessed in general accordance with API-653. The results listed in this report are based upon the visual inspection performed, and does not include UT thickness data analysis (as UTT was not part of the inspection scope).
3 Coating deterioration was observed.
Coat areas as necessary. Refer to coating provider for best surface preparation and coating application.
External inspection was limited due to access.
The performance of a more thorough (i.e. not limited) external inspection may be considered to better assess the condition of the equipment.
Venting was observed. No determination of venting capacity was made by ATS.
Owner should verify venting capacity satisfies the requirements of an applicable standard for the system operating parameters (e.g.
API-2000, NFPA-30, UL-142).
Observation / Finding Action Item Priority
Priority 1 - High likelihood/consequence of failure (or) Critical code/standard deficiency (or) May not be fit for service without action
Priority 2 - Med likelihood/consequence of failure (or) Add'l info needed for evaluation (or) Action may be considered for continued service
Priority 3 - Low likelihood/consequence of failure (or) Non-critical code/standard deficiency (or) Best practice/preventative maintenance
Action items listed below are based on observations recorded at the time of inspection and/or findings determined during the post-inspection analysis. Priority "1", "2", "3" has been applied and is defined as:
Job Number
Action Items 399868
❶
❶
❶
Date of Next InspectionMax. Frequency NotesFormal Inspections
Maximum frequencies are based on applicable industry codes, standards, best practices, and judgement of ATS at the time of this evaluation. Formal inspections should be performed by qualified personnel experienced with inspection practices.
Reinspection Frequency 399868
Job Number
Internal Visual
UT Thickness
External Visual
20 year(s) Unknown prior inspection
Unknown prior inspection
Elizabeth Ray NY registered Engineer-in-Training; degreed Mechanical Engineer. 10+ years experience with inspection, evaluation, repair, and design within various industries. API 510 / 653 / 570 certified inspector; FTPI certified fiberglass inspector; STI certified inspector; Pennsylvania DEP IAF and IAM certified inspector.
May-2028 year(s) year(s)5
Frequency based on API-653. [RPB's and other safeguards have not been assessed in this analysis.]
Per API-653, Owner/Operator inspections should be performed monthly.
❶
Personnel Qualifications
2 Yes No NA NI
- X
- X
2 Yes No NA NI
- X
- X
9 Yes No NA NI
- X
- X
- X
- X
- X
- X
- X
- X
- X
6 Yes No NA NI
- X
- X
- X
- X
- X
- X
5 Yes No NA NI
- X
- X
- X
- X
- X
Attachment defects (brackets, stiffening ring)
Corrosion or pitting observed
Visual limitations (access, insulation, cleanliness)
Condition / Comments
Scattered coating failure and surface rust observed. Biological growth
(mold/moss) observed throughout.
Coating failure (peeling, disbond)
Weld defects (cracks, leaks, corrosion)
Repad issues (weep hole leaks, plugged)
Flange bolt issues (corrosion, loose, missing)
Angle ring defects (distortion, corrosion)
Roof
Weld or rivet defects (cracks, leaks, corrosion)
Access
Debris build-up observed
Defects observed (bulges, dents, holes)
Head bolt issues (corrosion, damage, missing)
Drainage issues (standing water)
Corrosion or pitting observed
Visual limitations (access, insulation, cleanliness)
Coating failure (peeling, disbond)
Scattered coating failure and surface rust observed.
Coating failure (peeling, disbond)
Nozzles
Shell
Insulation damage (wet, staining, missing, CUI)
Weld or rivet defects (cracks, leaks, corrosion)
Defects observed (bulges, dents, holes)
Corrosion or pitting observed
AccessVisual limitations (access, insulation, cleanliness)
399868
Job Number
External Visual Inspection
NA = Not Applicable
NI = Not Inspected
Inspector Name(s): Elizabeth Ray
Normal Venting
Indication of pluggage observed
Location observed (roof, shell, not observed) Observed on roof
Condition / Comments
Condition / Comments
Access
Condition / Comments
Insulation damage (wet, staining, missing, CUI)
Atmos vent, Vacuum breaker, Flame arrestor, Weighted plate, Conservation vent
Overflow Condition / Comments
Location observed (roof, shell, not observed) None observed
Visual limitations (access, insulation, cleanliness)
Corrosion, pitting, defects observed
Indication of pluggage observed
Visual limitations (access, insulation, cleanliness) No limitations No visible deterioration or damage observed.
Nominal Vent Diameter (inches) no access no access
Type
Vacuum breaker
Corrosion, pitting, defects observed
Atmospheric vent
Device type(s)
Scattered coating failure and surface rust observed.
Flame arrestor
Vacuum breaker no access
Job Number
External Visual Inspection
NA = Not Applicable
NI = Not Inspected
Inspector Name(s): Elizabeth Ray
5 Yes No NA NI
- X
- X
- X
- X
- X
4 Yes No NA NI
- X
- X
- X
- X
5 Yes No NA NI
- X
- X
- X
- X
- X
1 Yes No NA NI
- X
4 Yes No NA NI
- X
- X
- X
- X
6 Yes No NA NI
X
X
X
X
X
X
Corrosion or pitting observed
Visual limitations (access, insulation, cleanliness)
Condition / Comments
Type (skirt, saddles, lugs, chairs, legs, none)
Concrete pad
Corrosion or pitting observed
Condition / Comments
Uneven settling or frost heaving observed
Weld defects (cracks, leaks, corrosion)
Defects observed (uplift, gaps, holes)
Min measured projection from toe of weld (inch) 2.000
Coating failure (peeling, disbond)
Condition / Comments
Visual limitations (access, insulation, cleanliness)
Defects observed (cracks, spalling, etc.)
Anchorage
Corrosion or pitting observed
No visible deterioration or damage observed.
Miscellaneous Condition / Comments
The tank's nameplate has been painted over.
Coating failure and surface rust observed on access ladder and platform.
Nameplate
- nameplate missing
- corroded or illegible
Labels
- labels damaged or torn
- labels illegible
- corrosion observed
- defects (bent, unsupported) Platforms/Ladders
Drainage issues (standing water)
Areas observed buried or covered
None observed
Concrete deterioration observed throughout.
Exposed aggregate, debris, vegetation build-up
Floor Chime
Condition / Comments
Type (soil, ring-wall, concrete pad, structural steel)
Coating failure (peeling, disbond)
Anchor bolt defects (corrosion, necking, broken)
Structure defects (bending, cracking, broken)
No visible deterioration or damage observed.
Defects observed (broken, frayed, corroded)
Quantity observed (none, 1, 2, 3, 3+) 3+
Foundation
Secondary Containment Condition / Comments
Grounding Cables
Sealant defects (degradation, missing, gaps)
Type (none, earth berm, dike wall, curbing) Earthen berm
Defects observed (bulges, dents, holes, cracks)
Drainage issues (standing water)
Areas breached or structurally unstable
No limitations
Scattered coating failure and surface rust observed. Heavy biological growth was observed throughout.
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 1'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 2'
399868
Overall view.
Photo 1
Job Number
Photographs
Photo 2
Top head, venting, nozzles.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 3'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 4'
Photo 3
Top head, venting, nozzles.
Photo 4
Shell.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 5'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 6'
Photo 5
Shell.
Photo 6
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 7'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 8'
Shell, access ladder.
Photo 8
Photo 7
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 9'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 10'
Photo 9
Shell.
Photo 10
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 11'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 12'
Nozzle.
Photo 11
Shell, access ladder.
Photo 12
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 13'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 14'
Photo 13
Shell, manway, nameplate.
Photo 14
Shell, manway.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 15'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 16'
Photo 15
Shell, manway, foundation.
Photo 16
Shell, chime, foundation, grounding.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 17'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 18'
Photo 17
Shell, chime, foundation, grounding.
Photo 18
Shell, chime, foundation, grounding.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 19'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 20'
Photo 19
Shell, chime, foundation.
Photo 20
Shell, chime, foundation.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 21'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 22'
Photo 21
Shell, chime, foundation.
Photo 22
Shell, chime, foundation.
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 23'
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 24'
Shell, chime, foundation, grounding.
Photo 24
Secondary containment.
Photo 23
Job Number
Photographs
DELETE THE CAPTION
BELOW BEFORE ADDING
NEW PHOTO.
DO NOT DELETE: 'Photo 25'
Photo 25
Secondary containment.