The report includes general equipment information, executive summary, recommendations, photographs, personnel qualifications, reference standards, and plans for future inspections. Based on visual inspection, the external condition of the tank was found to be fair with some coating failures and surface rust observed where insulation had been removed. Access was limited by the insulation. Internally, limited inspection was also conducted due to insulation, but no defects or deterioration were observed. Recommendations included replacing the compromised insulation to prevent further corrosion under insulation, and conducting a more thorough inspection for full assessment. Priority 1 and 2 action items were identified.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLIED TECHNICAL SERVICES, INC.
In states where Applied Technical Services, Inc. does not provide engineering services, engineering services will be provided by ATS Engineering, (P)LLC or a licensed contractor.
Professional Engineers and Scientists: Design • Consulting • Testing • Inspection
External Inspection:
Internal Inspection:
Jul 19, 2019 Not in scope of work
Elizabeth Ray
62886
Job Number: 313292
Prepared by:
UT Thickness Inspection: Not in scope of work
636 Waldo Street • Rumford, ME 04276 • 207-364-4200
Inspection Report for
A-102-BLDG72
Consultant III
PSNY - Kittery, ME CCI Construction Services
YES
Approved by:
API-653
YES
Project Manager Chuck Morrisette
451A (01-2019)
Table of Contents313292
Job Number
General Equipment Information
Executive Summary
Recommendations
Photographs
Reference Standards
Future Inspections
Visual Inspection
Personnel Qualifications
S.G. S.G. S.G.
n/aContentsn/aContents
62886
UT Thickness
Yes - while in service
Jacket-Side Service
NoDrawings Available
External Visual
Not in scope Internal Visual
Job Number
AST: Flat Bottom
Construction Standard
Inspection Scope
Equipment Number
Elizabetth Ray
Equipment Identification
A-102-BLDG72Equipment Name
This area intentionally left blank
General Equipment Information
Cert. Cert. #Inspector Name(s) gallons60,000
API 653
N/A Method
Approximate Volume Equipment Type
313292
N/A
EagleManufacturer
API-650
Construction Information
Joint Efficiency of Shell
07-2019YesPrevious External Visual Inspection Guidelines n/a n/a n/a
Operating Temp (°F) Relief Press (psig) Design Temp (°F) Design Vac (psig) n/a Unknown
Atmospheric Unknown n/a n/an/a
Unknown n/a n/a n/a
Yes/No MaineState Where Equipment is Located
Date
06-2018YesPrevious UTT DataNot ApplicableService Category
Not in scope
Unknown
Cert.
06-2018Yes
Mat'l Construction of Shell Unknown CS
Operating Temp (°F) Vent Press (psig) Design Temp (°F)
Shell-Side Service Tube-Side Service
Previous Internal Visual n/a Design Vac (psig)
Operating Temp (°F)
Other Test Methods Performed
Contents No. 2 Fuel Oil
Design Press (psig)
API-653Inspection / Analysis Standard(s)
Historical Documentation
None
0.89
NDT Technician Name(s)
Relief Press (psig) Design Temp (°F) Design Vac (psig) Design Press (psig) Design Press (psig)Atmospheric n/a
Customer PSNY - Kittery, ME
CCI Construction Services City, State
(assumed)
Year of Construction
Executive Summary
External Condition Summary
Job Number
Scope of Work
Equipment Access
Equipment Orientation
Over-Pressure Protection
313292
Internal access gained via:
This report contains the results of the field inspections performed. Inspections and analysis were performed in general accordance with the standards listed in "General Equipment Information". Inspections were limited to areas of accessibility. Prioritized action items and subsequent inspection frequencies have been outlined in this report and should be addressed.
Any non-destructive testing (NDT) performed within this scope of work was completed utilizing trained personnel meeting the requirements of SNT-TC-1A. NDT methods were performed in accordance with the codes, standards, or client specifications agreed upon with the client/owner.
Ground & Ladders
Bottom only
Atmospheric venting was observed on the tank. No visible deterioration or damage was observed at the time of inspection.
External access gained via:
When looking from 'the top down', progression to 360° is:
0° on this equipment is located at: Shell Manway
Clockwise
Analysis
The external inspection was limited due to insulation. The performance of a more thorough external inspection may be considered in order to fully assess the condition of the equipment. This can be accomplished with additional insulation removal during future inspections. No visible deterioration or damage was observed at the time of inspection.
Analysis was performed in general accordance with API-653.
The insulation should be replaced as soon as practicable to prevent further CUI (corrosion under insulation) of tank shell, roof, chime, and nozzles.
2Significant biological growth on/around the tank due to water under insulation.3
313292
Performance of a more thorough inspection may be considered in order to fully assess the condition of the equipment. 2Inspection was limited due to insulation.2
Because process variables can change over time, the Owner should verify the venting capacity for the system meet the requirements of an applicable standard.
(e.g. API 2000, NFPA 30).
As outlined in API 650 (5.8.5), venting should be designed in accordance with applicable standards.
Observation Recommended Action Priority
Priority 1 - High likelihood/consequence of failure (or) Critical code/standard deficiency (or) May not be fit for service without action Priority 2 - Med likelihood/consequence of failure (or) Add'l info needed for evaluation (or) Repair may be considered for continued service Priority 3 - Low likelihood/consequence of failure (or) Non-critical code/standard deficiency (or) Best practice/preventative maintenance
Action items listed in the table below are based upon observations recorded at the time of the on-site inspection and/or as determined during the post-inspection data evaluation. Prioritization has been applied, and is defined as "1", "2", "3":
Job Number Recommendations
❶
❶
❶
❶ Frequency based on API-653.
Internal Visual Inspection UT Thickness Inspection
External Visual Inspection 20 year(s) Jun-2038
Jun-2033
Jul-2024 year(s) year(s)5
Personnel Qualifications
Elizabeth Ray Mechanical Engineer with 7+ years experience with inspection, evaluation, repair, and design in various industries; API 510 / 653 / 570 certified inspector; FTPI certified inspector; STI certified inspector, Pennsylvania DEP IAF and IAM certified inspector.
API 653: Tank Inspection, Repair, Alteration, and Reconstruction1)
Job Number
Date of Next InspectionFrequency
Assuming a continued service of the equipment in its existing service, the recommended frequencies for re-inspection are listed below. These frequencies are based on applicable industry codes, standards, best practices, and the judgement of the inspector/evaluator considering the results of this inspection.
NotesInspection Type
Future Inspections313292
Reference Standards
Yes No NA NI a) b)
d) x
e) x
Yes No NA NI a)
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x
h) x
i) x
j) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) Yes No NA NI
a) b)
Coating failure (peeling, disbond)
Insulation Condition / Comments
Visual limitations (access, insulation, cleanliness) Limited Access
Corrosion, pitting, defects observed
Atmospheric ventAtmospheric vent, Overflow acts as vent, PV breaker, Flame arrestor, Device(s) observed Emergency vent
Location observed None Observed
Attachment defects (brackets, stiffening ring)
Limited visual inspection due to insulation. A small portion of the bare shell could be inspected where insulation was removed around the manway.
Coating failure and surface rust was observed. There is a significant amount of biological growth present due to the insulation being compromised (water under insulation).
Condition / Comments
Insulation damage (wet, staining, missing, CUI) Weld or rivet defects (cracks, leaks, corrosion)
Debris build-up observed Drainage issues (standing water) Defects observed (bulges, dents, holes) Head bolt issues (corrosion, damage, missing) Corrosion or pitting observed Visual limitations (access, insulation, cleanliness)
Defects observed (bulges, dents, holes) Corrosion or pitting observed
InsulationVisual limitations (access, insulation, cleanliness) Shell
Coating failure (peeling, disbond) Insulation damage (wet, staining, missing, CUI) Weld or rivet defects (cracks, leaks, corrosion)
Atmospheric vent cover is dented.
Insulation Condition / Comments
Limited visual inspection due to insulation and access.
There is damaged insulation throughout (cracks, punctures).
Some biological growth present due to the insulation being compromised (water under insulation). Angle ring defects (distortion, corrosion)
Top Head
313292 Job Number External Visual Inspection
Overflow Condition / Comments
NA = Not Applicable NI = Not Inspected
Inspector Name(s): Elizabetth Ray
Venting Condition / Comments Location observed Roof
Indication of pluggage observed
Coating failure (peeling, disbond)
Nozzles
Corrosion or pitting observed Visual limitations (access, insulation, cleanliness)
Limited visual inspection due to insulation.
Coating failure and surface rust was observed.
Anchorage
Floor Chime Condition / Comments Visual limitations (access, insulation, cleanliness) Corrosion or pitting observed
Weld defects (cracks, leaks, corrosion) Repad issues (weep hole leaks, plugged) Flange bolt issues (corrosion, loose, missing)
Limited visual inspection due to insulation. A small portion of the chime could be inspected where insulation was removed around the manway.
Coating failure and surface rust was observed. The seal between the chime and insulation has failed; biological growth is present due to water.
Condition / Comments
Insulation
Type (lugs, chairs, saddles, legs, flange-ring)
2"Min measured projection from toe of weld (inch)
Lugs
Quantity
Coating failure (peeling, disbond) Weld defects (cracks, leaks, corrosion) Defects observed (uplift, gaps, holes) c)
313292 Job Number External Visual Inspection
NA = Not Applicable NI = Not Inspected
Inspector Name(s): Elizabetth Ray c)
d) x
e) x
f) x
g) x
h) x
Yes No NA NI a)
b) x
c) x
d) x
Yes No NA NI a)
b) x
Yes No NA NI a) b)
c) x
d) x
e) x
g) Yes No NA NI x x x x
Miscellaneous Condition / Comments
a) Nameplate - was a nameplate observed
Access ladders have coating failure and surface rust.
Nameplate - was nameplate legible
b) Platforms/Ladders - corrosion Platforms/Ladders - defects (bent, unsupported)
Grounding Cables Condition / Comments
Visual limitations (access, insulation, cleanliness)
Condition / Comments
Limited visual inspection due to insulation.
Scattered coating failure and surface rust on lugs and anchor bolts. Biological growth present at/around support lugs was also noted.Anchor defects (weld cracks, deformation)
Insulation
Coating failure (peeling, disbond) Anchor bolt defects (corrosion, necking, broken)
Type (soil, ring wall, concrete, structural steel) Foundation
Repads observed Corrosion or pitting observed
Scattered concrete deterioration (chipping, stress cracking) was noted throughout.
Concrete
Exposed aggregate, debris, vegetation build-up Drainage issues (standing water) Defects observed (cracks, spalling, settling)
Secondary Containment Condition / Comments
Volume of containment area (gallons) 88,868
No mechanical damage or defects were observed.
Defects observed (broken, frayed, etc.)
Quantity 3
Scattered concrete deterioration (chipping, cracking, spalling) was noted throughout. The containment sump is full of water.
Significant debris was also observed in the contaiment.
Additional Conditions / Comments
The fill gauge is broken and not in use.
Tank is missing all labeling, including a NFPA diamond label.
Sealant defects (degradation, missing, gaps)
Type (berm, concrete, steel, curbing) Concrete Dike
Defects observed (bulges, dents, holes, cracks) Drainage issues (standing water) Visual limitations (access, insulation, cleanliness) No Limitations
f) Dimensions of containment area 66' x 30' x 6'
Job Number
Photographs 322088
451C (01-2020) Proprietary Document. To be reproduced only in full.
Shell, manway, foundation.
Shell.
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
Shell, access stairs, foundation.
Annual AST Inspection reports for 2020. Other requests for
Annual AST Inspection reports for 2020. Other requests for
Broken tank level gauge.
Grounding, support lug, foundation.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Shell, foundation, containment area.
Shell, level gauge, access stairs.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Shell, grounding, support lug, foundation.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Shell, access stairs.
Grounding, support lug, foundation.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Roof, control room fill sensor gauge.
Roof, emergency vent.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Roof.
Roof, atmospheric vent.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Containment area.
Annual AST Inspection reports for 2020. Other requests for this document shall be referred to NAVFAC.
FOR OFFICIAL USE ONLY
DISTRIBUTION STATEMENT D. Distribution authorized to
Department of Defense and U.S. DoD contractors only for
Annual AST Inspection reports for 2020. Other requests for
Annual AST Inspection reports for 2020. Other requests for