This document contains details regarding a federal solicitation for a multiple award construction contract. The solicitation seeks contractors to perform design-build and design-bid-build construction projects for the Public Works Department Maine under an indefinite delivery, indefinite quantity contract. Work will include new construction, demolition, repair, renovation and alteration of buildings, systems and infrastructure such as administrative facilities, industrial facilities, maintenance facilities, warehouses, communications facilities, personnel support facilities, recreational facilities, lodging facilities, medical facilities, training facilities, ranges and roads. Lead and asbestos abatement may be required. Selected contractors will be responsible for all labor, supervision, engineering, design, materials, equipment and transportation to complete individual task orders. Work may involve explosive facilities. All work will support the Public Works Department Maine area of responsibility managed by the Naval Facilities Engineering Command Mid-Atlantic. The period of performance is not specified.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B72 Repair Fuel Oil Storage Tanks
PPI Attachment - Equipment list
EQUIP.
ID
EQUIPMENT
DESCRIPTION
MOTOR/INPUT NOTES
DB-2 HRSG-2 Duct Burner
42.5 mmbtu/hr (gas/oil)
Deltak Corp.
Dino 4LF-2219-SE Oil Firing:
Heat Input: 42.5 mmbtu/hr Max Firing: 1747 oF Turndown: 4 to 1 Pressure at burner: 150 psig
DG-1 &
Diesel/Generator 147.6 gph (Lf) Fuel Oil Day Tank / Pump Manufacturer: Phillips Pump Tank capacity: 500 gallons Pump: 15 gpm @ 150 psi FOC-1 Fuel Oil Return Cooler Young F-301-HY-2P 15 gpm CW
CTG-2 Combustion Turbine Generator #2
69.86 mmbtu/hr (gas/oil)
Solar Turbines Taurus 60 Gas Firing:
Gas Line pressure: 275 psig Heat Input: 69.86 mmbtu/hr (HHV)
Flow: 69,860 scfh or 3,050 lbs/hr
B-3 & B-4
Boiler #3, & 4 83.2 mmbtu/hr
(LF)
Nebraska Boiler Company
NS-E-61 SH (MR,ST)
Oil Firing:
Heat input: 83.2 mmbtu/hr Turndown: 8 to 1 Pressure @ burner: 150 psig Excess air @ MCR: 15% Flue gas rate @ MCR: 15% Atomizing steam pressure @ burner: 100 psig
FOP 1
& 2
Fuel Oil Pump 1, 20 HP - 480V/3ph/ 60Hz Motor Model R877, 4 in. Suction 3 in. discharge