About this file

This document package includes a federal solicitation and related project files for construction services. The solicitation seeks pricing for Hurricane Florence recovery and applied instruction facilities at Marine Corps Base Camp Lejeune, including seven projects. Offerors must provide pricing for demolition, abatement, and construction of new structures such as fire stations, a mess hall, and a Provost Marshal's office. Electronic pricing is due by June 16, 2020 with hard copy submissions due June 24, 2020. The Navy Facilities Engineering Command will administer the contract and conduct evaluations. The project files provide requirements for hazardous materials abatement, geotechnical work, landscaping, and mechanical, electrical and plumbing systems. Responses to questions seek clarification on demolition scope, occupancy loads, and other technical requirements.

View the file

Other files

File Type Posted
19R9255 0016.pdf PDF
N4008519R9255-0015 combined.pdf PDF
19R9255 0013.pdf PDF
19R9255 0012.pdf PDF
P1519_PART 6_AV Requirements.pdf PDF
19R9255 0011.pdf PDF
19R9255 0010.pdf PDF
P1312_4.1_Space Tabulation.pdf PDF
Food Service Equipment Schedule 100 percent.pdf PDF
Part 6 - TFF 5 - Site Bubble Diagram-P1312.pdf PDF
19R9255 0009.pdf PDF
P883_PKG 5_Room Requirements.pdf PDF
Part 6 - TFF 5 - Site Bubble Diagram-P1533.pdf PDF
Haz Test Part 1 of 2.zip ZIP file
19R9255 0008.pdf PDF
Navfac_Fact_Sheet-Vapor Intrusion.pdf PDF
Haz Test Part 2 of 2.zip ZIP file
Pak5_B (1).zip ZIP file
Pak5_A.1.zip ZIP file
19R9255 0007.pdf PDF
Pak5_A.2 (1).zip ZIP file
PDFs.zip ZIP file
19R9255 0006.pdf PDF
19R9255 Amendment 0005.pdf PDF
TFF Package 5 Price Proposal.pdf PDF
TFF 5 RFP RTA PART6 CHAPTER Ca_16MAR2020 (3 of 5) REV.pdf PDF
TFF 5 RFP RTA PART6 CHAPTER A-B_16MAR2020 (2 of 5).pdf PDF
TFF 5 RFP RTA PART1 - PART5_16MAR2020 (1 of 5).pdf PDF
TFF 5 RFP RTA PART6 CHAPTER Ca_16MAR2020 (3 of 5).pdf PDF
19R9255 PKG 5 Am 0004 PH II.pdf PDF
TFF 5 RFP RTA PART6 CHAPTER D-K_16MAR2020 (5 of 5).pdf PDF
TFF 5 RFP RTA PART6 CHAPTER Cb_16MAR2020 (4 of 5).pdf PDF
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
Attachment B SECNAV 5512.pdf PDF
N40085-19-R-9255 HFRM PKG 5.pdf PDF
Attachment I One Day Pass Request.xls XLS spreadsheet
ATTACHMENT F - PPQ.pdf PDF
ATTACHMENT D- SB SUBCONTRACTING RECORD.pdf PDF
ATTACHMENT H- PROPOSED PROJ DURATIONS.pdf PDF
ATTACHMENT C - CON DES EXP DATA SHEET.pdf PDF
ATTACHMENT G - SB SUBCONTRACTING PLAN.pdf PDF
ATTACHMENT E - SB PART AND COMMIT STRAT.pdf PDF
Attachment A - PPI Inquiry Log.xls XLS spreadsheet
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

See Continuation Sheet.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 20

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 03-Jun-2020

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N4008519R9255

X 9B. DATED (SEE ITEM 11)

19-Dec-2019

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

03-Jun-2020

CODE

NAVFAC MID ATLANTIC

ACQUISITION CORE

9324 VIRGINIA AVENUE

NORFOLK VA 23511-3095

N40085 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

N4008519R9255

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)

The following have been added by full text:

AMENDMENT 0014

This amendment hereby incorporates the following:

1. Provide PPI responses to PPIs # 127, 129-133, 135-140, 145, 160, 185-196, 199-202, 205-208, 212-214, 224, 227-229, 231-237.

2. Delete reference to the demolishing of Building BB293A as listed in Part 3- Chapter 3.1.2.1, fifth paragraph and Chapter 6- F2010 eighth paragraph.

3. Replace all Part 3.1 to 3.7, Chapter 6, ESR D303001 and D304006 with the Attached “TFF MILCON D303001 and D304006 REV 6”.

4. Delete Attachment F- Price Proposal Form, as conveyed in Amendment 0005. Replace with attachment revised version that incorporates in red numerical corrections gained from PPI’s. Section 1.4.e has new added text for clarification. See Attachment F- Price Proposal Form Revision 1.

5. Add to P1533 PMO- the occupant load for hurricane shelter shall be 248, as discussed in PPI# 160 of this Amendment.

6. Add the following text to Part 3.7 P1533, Chapter 6 G101002.

G101002 TREE REMOVAL

Per G101001 CLEARING, remove and dispose of all trees as required for project construction.

To reduce the incidental take of migratory birds and their nests, trees with active nests should not be cleared. If tree clearing is proposed between April and July, contact the LWRS Biologist for additional guidance. Contractor must engage the installation arborist and preserve trees per the arborist’s direction.

Attachments:

1. Attachment F – Price Proposal Form Revision 1.pdf

2. TFF MILCON D303001 and D304006 REV 6.pdf

The proposal due date remains unchanged.

All other terms and conditions remain unchanged.

PPIs Responses # 127, 129-133, 135-140, 145, 160, 185-196, 199-202, 205-208, 212-214, 224, 227-229, 231-237:

Question No.

REFERENCE QUESTION Response

Page Section Para.

127 Attachment F Section 1.1 Description of CLIN 0001 through CLIN 0005 states the base bids are from CLINs 0001 through 0005.

Whereas section 1.4 states CLINs 0001 through 0007 are base bids. Hence please confirm the

Base Bids are CLINs 0001 through 0007. See revised

Price Proposal Form in Amendment 0014.

base bid CLINs are 0001 through 0007 and provide the updated CLIN schedule.

129 Attachment F Section 1.1 Sub CLIN 0001B is provided for abatement of buildings#510,512 & 514 but there was no CLIN provided for the demolition of these buildings. Can a separate CLIN for Demolition be added.

See PPI #7, Demolition of buildings 510,514, 512 are included as Base Bid and would fall under CLIN 0001.

130 Attachment F Section 1.1 Sub CLIN 0004B is provided for abatement of building# H32 but there was no CLIN provided for the demolition of this building. Can a separate CLIN be added for demolition?

Demolition of building H32 is included as Base Bid and would fall under CLIN 0004.

131 Attachment F Section 1.1 and 1.2

In section 1.1, CLIN 0027 states the list of buildings to be demolished are 18,18D, 159 and 1400 whereas in section 1.2 the number of buildings to be demolished under this CLIN are only two (18 & 1400). Hence please clarify the list of buildings to be demolished

See Amendment 0014 with revised Price Proposal Form.

There are four buildings being demolished under

CLIN 0027.

132 Attachment F Section 1.2 Section 1.2, description of CLINs 0013,0014, 0018, 0019, 0022, 0023, 0025, 0026, 0030, 0031, 0034 & 0035 states the cost of design, design submittals, pathways and electrical powered required for these CLINs to be included in CLIN

See Amendment 0014 with revised Price Proposal Form.

0001A. Kindly confirm whether this cost allocation is correct.

133 Attachment F Section 1.3 (f), 1.4 (e)

Please clarify the maximum timeline for the Government to award the optional CLINs 0008 through 0036 since there is a conflict between sections 1.3 (f ) and

1.4 (e )

There is a distinction between Planned

Modifications and options on the timelines. See

Amendment 0014 with revised Price Proposal Form for corrected CLIN numbering.

135 Attachment F Section 1.1 Clarify the list of buildings to be demolished under CLIN 0011 since it is not clear whether one of the buildings references is 411C or

FC411?.

FC411 is being deleted and the correct Bldg. is 411C.

See Amendment 0014 with revised Price Proposal Form.

136 Attachment F Section 1.4 (g)

Please provide separate CLINs for base bids and optional bids in order to account the cost properly.

CLIN's are separated by type.

Note 1.4 (g) refers to Options and Planned Modifications.

137 Attachment F Section 1.1 All the optional items listed from CLINs 0011 through 0036 are mentioned as ‘Option 1’. Hence please provide the correct option reference numbers

Corrected, see Amendment 0014 for revised Price

Proposal Form

138 Attachment F Section 1.1 CLIN 0001 & CLIN 0011 are for the demolition/ abatement of buildings related building P883. Under which CLIN external works demolition required for P883 will be considered?

Presuming "external works" is referring to utilities and site infrastructure around the building, all would be included as the associated CLIN to the building referenced. Ex. CLIN 001 includes bldgs. 510,512,514 and related site.

139 Attachment F Section 1.1 Please confirm up to what extend the cost related to the parking structure has to be included in CLIN

0001AE?

Include building plus associated site, like entry access, landscaping, sidewalk at garage.

140 Attachment F Section 1.1 Reference to the CLINs 0016 & 0028, please clarify, whether the full cost of bi-fold doors to be included in these CLINs or the difference in cost between the original base scope door and upgraded bi-fold door to be included?

CLINs 16 & 28 would be the difference of original doors from costs of bi-folds.

145 Solicitation section 00 73

00 – Supplementary

Conditions

Reference to the phased construction schedule requirement, please confirm the Government intended phasing arrangement.

See RFP, Part 2, 01 14 00, Part 1.2 Special Scheduling

Requirements

160 Per response to PPI #29 included as part of Amendment No. 9, required occupant load to be supported for P1533 PMO is 348 occupants. Per

ICC 500

requirements, community shelters for hurricanes require a space for 20 sq.ft.

per occupant. For the PMO facility, accommodations for 348 occupants would then require a minimum usable floor area of 6,960 sq.

ft. (with no increase included for use or furniture type). This designated area comprises a significant portion of the overall facility. Our understanding of the 348 occupancy load for this building is that it would also include transient visitors and personnel who are present for

Occupant load for hurricane shelter shall be 248 persons.

training. During a hurricane event, it is presumed that visitors will not be allowed, training will not continue, thus such spaces to shelter these occupants would not apply. It may also be logical to assume a substantial reduction in permanent staff members for the duration of a hurricane. As a comparison, the occupant loads associated with the two fire stations that are part of Package 5 seem logical and reasonable and reflect a fraction of the total occupancy. Please confirm if it is the government’s intent to provide a shelter for such a high number of occupants for the P1533 PMO facility.

185 Amendment 0005 Bid Form

All CLIN 0005AC, 0006AC & 0007AC all say complete work for the facility inside the 5' line. This is the same description as

CLIN 0005AB,

0006AB & 0007AB.

Please confirm CLIN

0005AC, 0006AC &

0007AC should all say complete work for the facility outside the 5' line.

5AC, 6AC and 7AC should read "outside". See

Amendment 0014 for revised Price Proposal Form.

186 Amendment 0005 Bid Form

All The bid form requires soil samplings for Total Petroleum Hydrocarbons (TPH) diesel range and gasoline range organics (DRO & GRO), and Benzene, Toluene, Bid per RFP.

Methylbenzene, and Xylenes (BTEX), plus other analytes required by the treatment/disposal facility. Are there any other contaminents the soil samples need to be analyzed for?

187 Part 6 Attachment B.9

P1203 & P1518

Attachment B.9 states that there was a suspected PFAS release and recommends a site invistigation at Building 18 (Hadnot Point Fire Station) and Building BB8 (Courthouse Bay Fire Station). Plese confirm that only a site investigation is required as part of the construction contract and that if PFAS is present and requires remediation it will be considered a changed condition. Please provide the required criteria for a site investigation (what contamanents should be tested for, # of samples, etc...).

Yes, bid per RFP.

188 Part 6 - Attachment B.8

P1312 Scope indicates a full archaeological report would be submitted (following current OSA reporting requirements). Would a full archaeological report be required if no cultural features are recorded or can an executive summary suffice?

Per current OSA reporting requirements, a full report will be required. If no features are found, there would be less info to report, but standard report format needs to be adhered to.

189 Part 6 - Attachment B.8

P1312 Can you please confirm that monitoring is for the purposes of recording intact archaeological features and human remains, not general artifact collection from the site (Section IIB: “…archaeologist shall record and be authorized to collect archaeological material as warranted for analysis”)?

If intact features are located within areas that would be disturbed during demolition, feature excavation and collection of artifacts for analysis from the features would be required. General artifact collection should be limited to minimum required by OSA reporting requirements. Sample size to be determined by archaeological field director based on OSA requirements. If human remains are encountered, all work in vicinity stops and OSA must be notified for consulting on treatment/recovery plan. Human remains may require excavation for standard analysis if avoidance is not feasible.

190 Part 6 - Attachment B.8

P1312 Under Section IIA:

“archaeologist shall be present…until it is determined that project construction activities could have no effects on significant archaeological resources.”

Determined by whom? The archaeological monitor? The base archaeologist?

Determined by archaeological project manager, Base Archaeologist, and the demolition contract manager through review of demo plans detailing level and extent of ground disturbance.

191 Part 6 - Attachment B.8

P1312 For intact non-burial features: “…the archaeologist shall, after making a reasonable effort to assess the identity, integrity, and significance of the encountered archaeological resource, present the findings of this assessment to PWD and ECON”. In this case, what constitutes

Burial features may not be evident from surface stain or artifact/shell concentrations on the surface until a feature is bisected. For intact non-posthole features- present findings to Base Archaeologist, record, map and bisect all non-posthole features; record and map all posthole features, but bisect only a representative sample of post-like features. If human remains are discovered during feature reasonable? Bisect each feature?

Although unlikely (given the previous disturbance in the area) what if multiple posthole features are recorded? Can a representative sample be recorded/excavated?

bisection excavations or noted at feature surface, stop work and consult with Base

Archaeologist and OSA.

192 Part 6 - Attachment B.8

P1312 The scope indicates that the archaeologist must be Secretary of Interior (SOI) qualified. If human remains and/or larger cultural features are encountered that need to be recorded and excavated, can we bring in additional archaeologists to assist? Can the scope be amended to “It is mandated that the supervising archaeologist hired meets the standards of the Secretary of the Interior…”?

Yes, and yes.

193 Part 6 - Attachment B.8

P1312 Can you please confirm that the scope of work does not include costs associated with the excavation of human remains (would need to scope separately/issue a change order) and that no skeletal analysis is included as part of this project (recovery only)?

The scope of work does not include costs associated with the excavation of human remains and no skeletal analysis is included as part of this project.

194 Part 6 - Attachment B.8

P1312 Can we put a limit to the number/types of materials collected and the level of analysis? For example: no collection of cultural materials from the general surface or disturbed soils and analysis limited to a representative sample of culturally diagnostic artifacts from excavated features.

No collection of cultural materials from the general surface or disturbed soils and analysis limited to a representative sample of culturally diagnostic artifacts from excavated features.

195 Attachment F All The bid form has individual CLINs for each project to Undercut of Geotechnically Unsuitable Subgrade Soils and Replacement with Imported Structural Fill material. Part

3.1.3.1 there are criteria for bidding that include removal of uncontrolled fill, over excavation at the parking lots, etc...

Please clarify if the Contractors are to include removal and replacement of unsuitable material in their proposal in addition to the unit prices required or are the unit prices intended to cover all removal and replacement of unsuitable material.

The removal and replacement of the uncontrolled fill materials noted in the Criteria for Bidding is included in the quantity provided in the Price

Proposal Form Line 0001C for Removal & Replacement of Geotechnically Unsuitable

Subgrade Soils.

196 Amendment

The Hurricane Florence Relief Packages 05 (Thursday, JUNE 4

2020, 1600 EST)

and 07 (Tuesday, June 9, 2020, 2:00 pm Eastern Time) are currently scheduled to have price proposals due within five business days between submissions.

To provide a better opportunity for subcontractors and vendors to participate in both pricing efforts, can the price proposal due date for HFRM Package 05 be rescheduled one week later? (Tuesday, June 16, 2020, 2:00 pm Eastern Time)

Additionally, the successor price submissions would need to change. See below for the proposed revised submission dates:

• Electronic Price Proposal Tuesday, June 16, 2020, 2:00 pm Eastern Time.

• Electronic Factor 6 Proposal Wednesday, June 17, 2020, 2:00 pm Eastern Time.

• Hard Copy Price and Factor 6 Proposal Wednesday, June 24, 2020, 2:00 pm Eastern Time

Duplicate PPI 182 - see 182.

199 Section 01 30

00.05 20 - 1.5

All Section 01 30 00.05 20 - 1.5 requires at least one (1) qualified Project Manager and one (1) on-site Project Superintendent per construction site (not including demolition only sites)capable of reading, writing, and conversing fluently in English. Please confirm that each of the 7 project number requires a PM and Superintendent.

See Amendment 0012, item 2.

200 Section 01 35

26.05 20

All Section 01 35 26.05 20 requires the Contractor to provide a safety oversight team that includes a minimum of one (1) person at each project site to function as the Site Safety and Health Officer (SSHO). Please confirm that each of the 7 project numbers require a dedicated no other duties

SSHO.

See Amendment 0012, item 2b.

201 Section 01 50

00.05 20 - 1.6.2

Section 01 50 00.05 20 - 1.6.2 states that reasonable amounts of utilities will be made available to the Contractor at the prevailing Government rates.

Please provide rates for all utilities so Contractors can include in their proposals.

Confirmed: Prevailing rates are as follows:

- Electricity:

$70.92/MWh

- Potable Water: $2.53/kgal

- Wastewater:

$2.24/kgal

202 Part 5 - 02 82 16 - 3.3.1

All Part 5 - 02 82 16 -

3.3.1 states that furniture and equipment will be removed from the area of work by either the Government or the contractor before asbestos work begins.

Please confirm all furniture and equipment will be removed by the Government prior to any abatement or demolition activities.

If the Contractor is required to remove all furniture and equipment please provide a list that includes dimensions, wieght , pictures, etc... so that the Contractor's are able to quantify and price.

The contractor shall anticipate moving furniture and equipment for some hazardous abatement. See

Site photos for interior pictures.

205 Part 3.6 - C102001

P1519 All interior doors must be 3’-0” wide X 7’-0” high doors, unless noted otherwise. All interior doors must be wood flush and/or stile and rail paneled.

All interior doors must be wood, except where hollow metal doors are required to meet fire rating. All interior door frames must be hollow metal.

Bid per RFP.

206 Part 3.1, 3.2, 3.3, 3.4, 3.5,

3.6 &

3.7 - C30

All SSPC QP 1 Certification is required in C30 for all of the projects.

SSPC QP 1

Certification is meant to attest to an industrial painter’s ability to apply coatings to complex industrial and marine coatings. This requirement is not applicable based on the type of project that is. This requirement will greatly reduce the number of painters who can price this job which will negatively affect the Government from a budget stand point.

Please consider removing this requirement.

207 Part 3.2 & Part 3.5 E101004

P1203 & P1518

The engineering system requirements require the contrcator to furnish and install the industrial laundy equipment per the Room Requirements.

The room requirements for P1203 & P1518 say they are part of the FF&E Package.

Please clarify if the washers and dryers are in the construction scope or part of the FF&E Package.

Bid per RFP.

208 Part 3.2 & Part 3.5 E101004

P1203 & P1518

Please clarify if the industrial extractors and dryers are in the construction scope or part of the FF&E Package.

Bid per RFP.

212 Part 3.1, 3.2, 3.3, 3.4, 3.5,

3.6 - G101002

All Part 3.1, 3.2, 3.3, 3.4, 3.5, 3.6 - G101002 To reduce the incidental take of migratory birds and their nests, trees with active nests should not be cleared. If tree clearing is proposed between April and July, contact the LWRS Biologist for additional guidance.

This is required for all projects except P1533 Provist Marhsall Office.

Yes, see Amendment 0014.

This does apply to P1533.

Please confirm if this is correct or should this be added to Part 3.7?

213 Part 3.1, Chapter 3, 3.1.3.1

P883 Criteria for Bidding states "Anticipate removal of approximately 3 feet of uncontrolled fill materials in the vicinity of borings 19B-14 and 19B-15 replacement with imported structural fill." Price Proposal Form Line 0001C includes 1200 CY of Removal & Replacement of Geotechnically Unsuitable Subrade Soils. Is the removal of the uncontrolled fill materials noted in Criteria for Bidding included in the quantity provided on the Price Proposal Form? If no, please provide an area (length x width) that is to be included in the vacinity of borings 19B-14 and 19B-15.

The removal and replacement of the uncontrolled fill materials noted in the Criteria for Bidding is included in the quantity provided in the Price

Proposal Form Line 0001C for Removal & Replacement of Geotechnically Unsuitable

Subgrade Soils.

214 Amendment #12

RFI #161 The response of "Bid per RFP, no additional information is available" was provided in the previous amendment.

With all due respect and since we cannot properly bid per the RFP because it is not clear; based on bidder low price assumption (and probably not what the government would prefer), please review attached exhibit A and re-issue the response. If we were to bid it this way and other offers do not, we are at a significant price disadvantage. The original RFI is as follows; P1203, CHB Fire Station - Please provide a LOD Demolition Layout or LOD of any hardscapes, utilities and other site features that are to be addressed as part of the bid option demolition for BB8, Part 3, Chapters 3 & 6 as well as Part 6 do not address the demolition extent or LODs of the utility scope and hardscapes in F2010 1.1 General Demolition and F2010 1.2 Utilities.

RFP discusses utility & pavement demolition in the respective Part 3, Section

3.1.2.1 along with in Chapter 6, F20, Section F2010. The Government has provided all inormation available.

224 Part 3, Chapter 2 (Pg 3) & Part 3, Chapter 4 (Pg 2)

Are the bleachers for the (5) covered bleachers to be included in the base bid or are these part of the FFE package?

If base bid please provide req's for these locations. The RFP does not provide

Bleachers are part of the Base Bid and are consisted real property, not collateral equipment or FF&E.

who is responsible for these.

227 P1519 LSSS

Facility Replacement Part 3, Chapter

ESR D30:

General System Requirements

RFP section ESR D30: General System Requirements, calls for 78 F indoor space cooling temperature setpoint and 68 F indoor heating temperature setpoint.

The USCDG calls for 75 F and 72 F respectively. Please clarify desired setpoints.

78/68 for cooling/heating setpoints.

228 P1519 LSSS

Facility Replacement Part 3, Chapter

ESR D30:

General System Requirements

RFP section ESR D30: General System Requirements, calls for ventilation in compliance with ASHRAE 62.1. The USCDG requires 20 cfm per person ventilation, which appears to be drawn from an obsolete version of ASHRAE

62.1. Please clarify if

ventilation should be based on RFP referenced ASHRAE

62.1 standard.

Yes, ventilation should be based off of ASHRAE 62.1

229 P1519 LSSS

Facility Replacement Part 3, Chapter

ESR

D304001: Air Distribution, Heating and Cooling

USCDG requires 6 to 10 air changes per hour in various types of courtrooms. The RFP calls for a variable air volume distribution system and specifically waives the UFC requirement for a minimum of 4 air changes per hour when cooling loads do not require that much supply air.

Please clarify if design intent was to provide the high levels of air changes in the courtrooms as required in the USCDG or follow RFP intent waiving air change requirements.

231 P1519 LSSS

Facility Replacement Part 3, Chapter

ESR D30:

General System Requirements

USCDG requires economizer for all systems over 3,000 cfm. RFP section ESR D30: General System Requirements, states that “Economizer cycles must not be used”. Please confirm economizers are not permitted.

Bid per RFP.

232 P1519 LSSS

Facility Replacement Part 3, Chapter

ESR

D309090:

Other Special Mechanical Systems

USCDG has requirements for humidity throughout courtrooms, but indicates that humidification may be omitted in moderate southern climates. RFP section ESR D309090 only requires a humidifier in the telecom rooms.

Please confirm humidification of courtroom spaces is not required.

Humidification is not required in Courtrooms. Bid per RFP.

233 P1519 LSSS

Facility Replacement Part 3, Chapter

ESR

D304001: Air Distribution, Heating and Cooling

USCDG requires that jury deliberation rooms should be on same system as the courtroom. USCDG also requires that the system serving the judge’s chambers must be sized to include conference room law clerk offices, reception, and secretarial space to facilitate off hour operation. Please

Bid per RFP. The DOR is responsible for design means and methods.

confirm a single AHU per floor, serving VAV terminal units zoned as required in the RFP, meets the RFP intent. A VAV AHU can modulate down during low load periods and terminals serving unoccupied spaces can be closed during off hours.

234 P883 Mess Hall, Part 3.1 Chapter 5 “Room Requirements”

Per Amendment #10, Item #4 (page 6 of

13) states to install ductile iron hub and spigot pipe with high temperature silicone gaskets for the sanitary drain line serving the “Utensil Wash” and the “Dish Wash/Tray Cleanup” rooms. However, Durion piping is no longer being manufactured.

Previously completed Camp Lejeune projects have utilized PVC or “Blucher” stainless steel piping due to the unavailability of ductile iron. Local vendors have suggested to use “Blucher” stainless steel piping in lieu of ductile iron. Please confirm this is acceptable.

Use stainless steel.

235 Page 3 Part 3, Chapter

6, ESR E10

P1203 CHB

Firestation & P1518 Hadnot Point Firestation

Please provide basis of design and/or intended use for E1090 Other Equipment, Containment Fill Station. The description provided is pretty vague for each firestation.

This is for extinguishing agent, also see UFC 4-730-

10.

236 Page 14 Part 3, Chapter 4, Room Datat Sheet for Fire Extinguisher Maintenance & Storage

P1518 Hadnot Point Firestation

The room data sheet lists to provide cylindar for extinguishing agent recovery and is listed under E109090.

There is no E109090.

Is this FF&E? If in base contract provide details of what is required.

See Chapter 6, E1090 for cylinder requirements, plus

UFC 4-730-10. This is Built-in equipment and part of the

Base Bid.

237 Part 6 of the RFP states all domestic water to be type K copper. Design guide states type L above and type K below ground. Please confirm which direction for domestic water shall be used for this project.

(End of Summary of Changes)