ST101.pdf

PDF 485 KB Posted

Attached to
P303, DESIGN-BID-BUILD, MARINE CORPS RESERVE CENTER, CAMP FRETTERD MD
Solicitation number
N4008021R6986
Issued by

About this file

This solicitation package outlines requirements for a design-build construction project for the Marine Corps Reserve Center in Camp Fretterd, Maryland. The project scope includes constructing a new 35,130 square foot single-story reserve center facility with an armory, drill hall, locker rooms, classrooms, fitness center, offices and covered weapons cleaning area. Additional construction includes a 10,968 square foot single-story vehicle maintenance facility with vehicle bays, offices and carpentry shop, and a 4,000 square foot single-story organic storage shed. The solicitation is issued by the Naval Facilities Engineering Command for the Department of the Navy, with responses due by the date specified in the solicitation package. Interested contractors should review submission requirements and specifications contained therein to understand what products and services are being solicited and ensure any response complies with terms of the solicitation.

View the file

Other files

File Type Posted
P303 AMENDMENT 0007.pdf PDF
10 51 13.pdf PDF
P303 AMENDMENT 0006.pdf PDF
P303 Amendment 0005.pdf PDF
BLDG-P303-1624797_C_A-002.pdf PDF
P303 Revised Price Schedule 1NOV2021.doc DOC document
BLDG-P303-1624797_C_A-200.pdf PDF
1624807Amendment4SPECS.pdf PDF
08 71 00.pdf PDF
BLDG-P303-1624797_A_A-601 Revised.pdf PDF
BLDG-P303-1624797_A_A-303.pdf PDF
32 31 13.pdf PDF
1624807Amendment4DWG.pdf PDF
1624807Amendment4.docx DOCX document
BLDG-P303-1624797_A_A-631.pdf PDF
07 05 23.pdf PDF
08 71 00C.pdf PDF
Revision Description (10-26-2021).docx DOCX document
P303 Amendment 0004.pdf PDF
P303-AMENDMENT 0003.pdf PDF
FFE FINAL - Building A.pdf PDF
SID Package - Building B.pdf PDF
SID Package - Building A.pdf PDF
BLDG-P303-1624797_A_A-601.pdf PDF
P303 Amendment 0002.pdf PDF
P303 Site Visit Sign-In Sheet.pdf PDF
C-508.pdf PDF
C-501.pdf PDF
E-601.pdf PDF
CS400.pdf PDF
26 20 00.pdf PDF
32 15 00.pdf PDF
P303 Amendment 0001.pdf PDF
40 95 00.pdf PDF
CS410.pdf PDF
COMBINED CIVIL DRAWINGS 2 of 2.pdf PDF
COMBINED CIVIL DRAWINGS 1 of 2.pdf PDF
ATTACHMENT E - SAFETY DATA SHEET.docx DOCX document
BLDG A COMBINED DRAWING.pdf PDF
P303 Final Volume 3 Specs.pdf PDF
1624807DWGBLDGC1of1.pdf PDF
SF1442 - N40080-21-R-6986.pdf PDF
ATTACHMENT D - CONSTRUCTION EXPERIENCE PROJECT DATA SHEET.docx DOCX document
Visitor Access Request List.xlsx XLSX spreadsheet
Small Business Subcontracting Plan.doc DOC document
P303 Final Volume 1 Specs.pdf PDF
BLDG B Combined Drawings.pdf PDF
SITE-VISIT PARKING AREA.png PNG image
ATTACHMENT F - SMALL BUSINESS PAST PERFORMANCE.docx DOCX document
P303 Final Volume 2 Specs.pdf PDF
Show 40 more

Latest 50 of 55 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEAL

DRAWFORM REVISION: 10 MARCH 2009

1100 NORTH GLEBE ROAD

SUITE 500

ARLINGTON, VIRGINIA 22201

571.218.1000

FAX: 571.218.1600

1624807

M A

R

IN

E C

O R

P S

R E

S E

R V

E C

E N

TE

R

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D , W

A S

H

IN

G

TO

N

DES DRW CHK

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

04/16/2021

3/16" = 1'-0"

TANK ELEVATION

1'-6" DIAMETER TANK VENT,

SEE GENERAL NOTE 2 AND

LADDER SHIELD

SEE

3/4

LADDER AND

SAFETY CAGE

SEE

30" DIA

MANWAY

CONCRETE RINGWALL

GENERAL NOTES:

FULL CAPACITY

HEIGHT

RADIUS A - TANK WALL

221,757 GAL

32'-0"

17'-7"

DESIGN CRITERIA

1. TANK DESIGN CRITERIA:

AWWA D100-11 AND AS MODIFIED BELOW:

DESIGN METAL TEMPERATURE (DMT) 17 DEG F

IMPACT (CHARPY) TEST IN ACCORDANCE WITH

AWWA D100, SECTION 14.2. ACCEPTANCE

CRITERIA: 15 FT - LB AT DMT.

FABRICATE TANK FROM ASTM A36

MINIMUM PLATE THICKNESS 1/4"

RISK CATEGORY IV

GROUND SNOW LOAD

WIND LOAD:

BASIC WIND SPEED (3-SECOND GUST)

EXPOSURE

IMPORTANCE FACTOR

2. LOCATE TANK VENT AS NEAR TO ROOF APEX AS PRACTICABLE.

3. PROVIDE INSULATION SYSTEM (WITH AN R-VALUE NOT LESS THAN 13 AND MINIMUM THICKNESS OF 2") ON THE EXTERIOR TANK

SHELL AND ROOF. INSULATION SYSTEM SHALL HAVE AN INTEGRAL PREFINISHED ALUMINUM OUTER FACE. THE FACTORY

FINISHED PANELS SHALL BE SECURED IN PLACE WITH MANUFACTURER'S METAL STRAP SYSTEM, SEE SPEC SECTION 33 16 13.

6 GAUGE MINIMUM THICKNESS. REFER TO SPECIFICATIONS FOR DESIGN AND COATING REQUIREMENTS.

4. PROVIDE SAFETY CHAINS WITH SNAP HOOK AT LADDER OPENING TO ROOF PLATFORM.

PROVIDE GALVANIZED STEEL PLATE SIGN WITH WARNING "DO NOT CLIMB OVER

RAILING" ATTACHED TO RAILING. SIGN DIMENSIONS: 12" HIGH x 18" WIDE.

5. COAT STEEL SURFACE UNDER CENTER COLUMN PRIOR TO SETTING COLUMN.

25 PSF

113 MPH

C

1.15

TANK PLAN

3/16" = 1'-0"

TANK REFERENCE LINE

MANWAY

TYP OF 2

SEE

NOTES:

1. ALL PIPING TO BE ASTM A53, GRADE B, TYPE E

OR S, SCH 80 UNLESS NOTED OTHERWISE.

COMPLY WITH ASME B31.3 NORMAL FLUID

SERVICE CATEGORY.

2. SHOP COAT ANCHOR BOLTS (NOT THREADS)

WITH ONE COAT EPOXY. FIELD FINISH EXPOSED

PORTIONS OF ANCHOR BOLTS DURING FIELD

COATING OF TANK.

3.

COLUMN BASE

PLATE BY TANK

MANUFACTURER

ROOF LIVE LOAD 40 PSF

GUST FACTOR: 1.0

SEISMIC LOADS: S

= 0.044g

S

S

= 0.145g

S

MS

= 0.232g

S

M1

= 0.104g

S

DS

= 0.155g

S

D1

= 0.07g

Risk Category IV

Site Class = C

R

A

D

I

U

S

A

5'-0" DIA

FLAT AREA

ROOF HATCH,

SEE

ASTM F1554, GRADE 36,

1 1/4" DIA ANCHOR BOLTS

AND ANCHOR CHAIRS,

TYP 11 PLACES, SEE

PROVIDE 11 ANCHOR

CHAIRS & BOLTS,

EQUALLY SPACED

AROUND TANK

PERIMETER

PROVIDE CONICAL SURFACE WITH

2"/10' SLOPE DOWN FROM CENTER

TOP OF TANK

FLOOR PLATE

TOP OF

TANK

BOTTOM

PLATE

TOP OF

RINGWALL

N

OVERFLOW

PIPE, SEE

ROOF VENT, SEE

SEE

A

ST501

ST101

N/A

T A

N K

P

L A

N

E

L E

V A

T I O

N

A

D

O T

E S

FD

RB

TT

02/18/21

MIN 3/8" SHELL

THICKNESS

MIN 1/4" SHELL

THICKNESS

4°

10" SUCTION PIPE

8" RETURN PIPE

3" POTABLE

WATER INLET PIPE,

SEE

4" WATER TRUCK FILL PIPE, SEE

HEATER

HEATER TYP,

SEE

OVERFLOW

EL 730.30'

3" POTABLE WATER

INLET EL 730.50'

4" WATER TRUCK FILL

PIPE EL 730.50'

4" TANK DRAIN

COORDINATE PIPE LOCATIONS NEAR TOP OF

TANK SHELL TO CLEAR ROOF RAFTERS.

VORTEX

BREAKER,

SEE

ST502

ST502

ST501

ST501

ST301

ST501

ST502

ST503

ST503

ST501

ST102

ST503

ST102

HEATER

45° ELBOW

'-1

TOP OF SOIL EL= 699.70'

AT CENTER OF TANK

ST504

PUMP SHED

3-INCH FLANGE FOR

LEVEL/TEMPERATURE

ELEMENT

13133705

1-1/2-INCH FLANGE FOR FLOAT

AND BOARD LEVEL GAUGE,

SEE GENERAL NOTE #7.

BOARD LEVEL GAUGE,

SEE GENERAL NOTE #6.

ATTACH LEVEL BOARD

SUPPORT BRACKETS TO

TANK LADDER.

SEE GENERAL NOTE #6.

NOTCH LADDER SHIELD AS NEEDED TO

ACCOMMODATE TANK LEVEL BOARD

MOUNTING BRACKETS

6. COORDINATE WITH TANK LEVEL GAUGE SUPPLIER FOR SST BRACKET LOCATIONS, SIZE

AND MOUNTING REQUIREMENTS. CUSTOM BRACKETS WILL BE REQUIRED TO MOUNT THE

LEVEL BOARD TO THE LADDER. BRACKETS WILL NEED TO BE LOCATED SO THAT THEY

DO NOT INTERFERE WITH THE TANK INSULATION OR LADDER GUARD.

7. GENERAL CONTRACTOR TO COORDINATE WITH TANK FABRICATOR, LEVEL GAUGE

SUPPLIER, AND INSULATION MANUFACTURER TO DETERMINE THE LOCATION, NUMBER

AND TYPE OF ROOF PENETRATIONS AND METHODS OF LEVEL BOARD ATTACHMENT.

A

D

E

X T

E R

N A

L

T

A N

K

L E

V E

L

G

A U

G

ST101 - TANK PLAN, ELEVATION, AND NOTES

2021-06-10T09:25:39-0400
Terri Tovey