Mech 035 - Pages 7-12.pdf
PDF 26 MB Posted
- Attached to
- Y1DA--504-18-119 Replace Boilers and Piping Federal contract opportunity
- Solicitation number
- 36C25722R0010
About this file
This document provides details on a federal contract solicitation. The solicitation number is 36C25722R0010 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17 for replacing boilers and piping at VA-22-00004245. The opportunity type is listed as a solicitation. No further details are provided on products or services required, response dates, pricing terms, set asides, or other salient information needed to fully understand the requirements of this contracting opportunity.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 36C25722R0010 0001.docx | DOCX document | |
| Answers to Questions 36C25722R0010 DB Replace Boilers.pdf | ||
| VA NOTICE OF LIMITATIONS ON SUBCONTRACTING REQUIREMENT.pdf | ||
| Past Performance Questionnaire.pdf | ||
| Mech 035 - Pages 1-3.pdf | ||
| Mech 035 - Pages 4-6.pdf | ||
| OSHA - EMR requirement.pdf | ||
| BP-3-Boiler-steam.pdf | ||
| BP-1-Boiler-fueloil.pdf | ||
| AS ST Series Sheets.pdf | ||
| AD AE Series Sheets.pdf | ||
| Elect 035.pdf | ||
| G Series Sheets.pdf | ||
| BP-4-Water-Treatment.pdf | ||
| 36C25722R0010_1.docx | DOCX document | |
| Phasing sheets.pdf | ||
| Struct 035.pdf | ||
| SELF-PERFORMED CALCULATIONS.pdf | ||
| Mech 035 - Pages 8-19.pdf | ||
| BP-2-Boilers-natgasandpropane.pdf | ||
| 20-09 035 Narrative 02 1r1 Phasing Narrative.pdf | ||
| 20-09 035 Narrative 06 1r1 Civil-LS Design Narrative.pdf | ||
| 20-09 035 Narrative 13 1r1 Specs TOC 000110 035 21-06-30.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11-EF-1
NEW
EXHAUST
FAN
EXISTING PACKAGED
ROOFTOP UNIT
TO REMAIN
EXISTING SHOWER /
LOCKER EXHAUST
FAN TO REMAIN
1 11
EXISTING PRESS.
REDUCING STATION
SAFETY RELIEF VENT
TO REMAIN
2.2
C K M N
4A
A
2.7
B
GD E F
3.5
L
2.2
H
1A
JC1
EXISTING ROOF
ACCESS HATCH
EXISTING BOILER
#4 BREECHING TO
REMAIN
EXISTING BOILER
STEAM SAFETY
VALVE VENT TO
REMAIN
11-EF-2
EXISTING SURGE
VENT THROUGH
ROOF TO REMAIN
6 11-EF-3
2.2
C K M N
4A
A
2.7
B
GD E F
3.5
L
2.2
H
1A
JC1
5 3
4 4
11 1
EXISTING
EXHAUST
FAN TO BE REMOVED
EXISTING PACKAGED
ROOFTOP UNIT
TO REMAIN
EXISTING SHOWER /
LOCKER ROOM EXHAUST
FAN TO REMAIN
EXISTING PRESS.
REDUCING STATION
SAFETY RELIEF VENT
TO REMAIN
EXISTING BOILER
#4 BREECHING TO
REMAIN
EXISTING ROOF
ACCESS HATCH
EXISTING BOILER
STEAM SAFETY
VALVE VENT TO
REMAIN
EXISTING SURGE
VENT THROUGH
ROOF TO REMAIN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo B o ile r R e p la c e m e n t_ C d e ta c h e d
P a u l.
W
.L ic h te n h a n .r v t
/1 /2
:5
:0
P M
11-M-102
ROOF PLAN - MECHANICAL- BLDG. 11
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
KEYNOTES:
1. NEW 2" BOILER SAFETY RELIEF VENT
THROUGH ROOF AND EXTEND 7'-0" ABOVE
ROOF LEVEL.
2. NEW 8" STEAM BOILER TEST HEADER VENT
THROUGH ROOF AND EXTEND 7'-0" ABOVE
ROOF LEVEL.
3. NEW 2" DEAERATOR STEAM RELIEF VENT
THROUGH ROOF AND EXTEND 7'-0" ABOVE
ROOF LEVEL.
4. NEW BOILER BREECHING WITH WEATHER CAP.
EXTEND 7'-0" ABOVE ROOF LEVEL. UTILIZE
EXISTING ROOF PENETRATION AND PROVIDE
OFFSETS AS REQUIRED. PROVIDE FLASHING
AND COUNTER FLASHING AT NEW BOILER
STACK THROUGH ROOF.
5. NEW 6" BOILER BLOW DOWN SEPARATOR
RELIEF VENT THROUGH ROOF. EXTEND 7'-0"
ABOVE ROOF LEVEL.
6. NEW EXHAUST FANS FOR BOILER PLAN
VENTILATION.
7. NEW GENERATOR EXHAUST. (ADD ALTERNATE)
N O R
HT
1/8" = 1'-0"
ROOF PLAN - BLDG. 11 - MECHANICAL
N O R
HT
1/8" = 1'-0"
ROOF PLAN - BLDG. 11 DEMOLITION - MECHANICAL
DEMOLITION KEYNOTES:
1. DEMOLISH 2" BOILER SAFETY RELIEF VENT
THROUGH ROOF.
2. DEMOLISH 8" STEAM BOILER TEST HEADER
VENT THROUGH ROOF.
3. DEMOLISH BOILER HOUSE EXHAUST FANS AND
ROOF CURBS.
4. DEMOLISH BOILER BREECHING AND WEATHER
CAP.
5. DEMOLISH 6" BOILER BLOW DOWN SEPARATOR
RELIEF VENT.
6. DEMOLISH EXISTING GENERATOR EXHAUST.
Revisions: Date:
T U N N E L
S T A
IR
S
EXISTING
PRESS. RED.
STATION TO
REMAIN
MPS UP
EXISTING
HOT WATER HEAT
EXCHANGERS
TO REMAIN
REPLACE EXISTING
DOMESTIC HOT WATER
HEATING HEAT
EXCHANGER
EXISTING
CONDENSATE
PUMP TO REMAIN
REMOVE EXISTING
ABANDONED STEAM
DROP
EXIST. PRESSURE
REDUCING VALVE
EXIST. STEAM
PRESS.SAFETY
VALVE
MPS
EXISTING FLASH
TANK TO REMAIN
EXISTING
HOT WATER
PUMPS TO
REMAIN
NO SCALE2
PIPE DROP TO BE REMOVED
NO SCALE3
POOR INSULATION
NO SCALE4
WATER HEATER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo B o ile r R e p la c e m e n t_ C d e ta c h e d
P a u l.
W
.L ic h te n h a n .r v t
/1 /2
:4
:4
P M
28-M-100
EXISTING CONDITIONS PLAN AND
PHOTOS - MECH ROOM - BLDG 28
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
N O R
HT
1/8" = 1'-0"
BASEMENT FLOOR PLAN - BLDG. 28 - MECHANICAL ROOM 1158
RECEPTION
RECOVERY
STORAGE
MED
GAS
SOILED
DECON
RAT SUPPLY
NURSE
STATION
ENDO
ROOM
MECHANICAL
ROOM
144 127
PRESS. RED.
STATION
CONDENSATE
PUMP TO REMAIN
REPLACE AND RECONFIGURE
CONDENSATE PIPING TO FLASH
TANK. REPLACE FLASH TANK
REPLACE EXISTING
DOM. HOT WATER
HEAT EXCHANGERS
6" HPS
FROM
TUNNEL
2" PUMPED
CONDENSATE
RETURN
4" MPS
HEAT EXCHANGER
W/COND. PUMP
4" MPS
HIGH
PRESSURE
RETURN
STEAM
VENT
MEDIUM
PRESSURE
RETURN
AIR SEPARATOR
INSULATE
CONDENSATE PIPING
EXISTING HOT
WATER HEATING
HEAT EXCHANGERS
TO REMAIN
29-FT-1
NO SCALE2
REINSULATE CONDENSATE PIPING
NO SCALE3
FLASH TANK AND PIPING
NO SCALE4
CONDENSATE PUMP
NO SCALE5
FLASH TANK AND CONDENSATE PIPING
NO SCALE6
REINSULATE CONDENSATE PIPING
NO SCALE7
FLASH TANK TO CONDENSATE PIPING
NO SCALE8
DOMESTIC WATER HEATER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo B o ile r R e p la c e m e n t_ C d e ta c h e d
P a u l.
W
.L ic h te n h a n .r v t
/1 /2
:4
:5
P M
29-M-100
EXISTING CONDITIONS PLAN AND
PHOTOS - MECH ROOM - BLDG 29
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
N O R
HT
1/8" = 1'-0"
BASEMENT FLOOR PLAN - BLDG. 29 - MECHANICAL ROOM 0528
GENERAL NOTES:
1. REINSULATE CONDENSATE PIPING FROM PRV
AND HEAT EXCHANGERS TO FLASH TANK.
KEYNOTES:
1. REROUTE ALL MEDIUM PRESSURE
CONDENSATE RETURN BACK TO
DEARERATOR, IN BOILER PLANT, SEPERATE
FROM LOW PRESSURE OR PUMPED
CONDENSATE PIPING.
ELEVATION
CONCRETE BASE BOILER ROOM
FINISHED FLOOR
BURNER
SIGHTFLOW INDICATOR
WITH ROTOR (ORIENT
WINDOWS TO FACE UP
AND DOWN)
20mm [3/4"]
TO BLOWOFF LINE
15mm [1/2"]
STEAM PRESSURE GAGE
(0-2000kPa [0-300 PSIG])
HIGH PRESSURE
CUTOUTS
FEEDWATER LEVEL CONTROL
UNIT LOW WATER CUTOFF
BOILER
PLUGGED CROSS
(TYPICAL)
AUXILIARY LOW
WATER CUTOFF LOW
WATER ALARM HIGH
WATER ALARM
AUXILIARY LOW WATER
CUTOFF SHUNT SWITCH
(LOCATE WITHIN 900mm [3'] OF
ALWCO DRAIN VALVE)
20mm [3/4"]
TO BLOWOFF
LINE
SIGHTFLOW INDICATOR
WITH ROTOR (ORIENT
WINDOWS TO FACE UP
AND DOWN)
32mm [1 1/4"]
GAGE GLASS
LOW WATER CUTOFF SHUNT
SWITCH (LOCATE WITHIN 3'
[900mm] OF LWCO AND GAGE
GLASS DRAIN VALVES)
BALL VALVES PROHIBITED
(TYP)
STEAM NOZZLE
m m
32mm [1 1/4"] m m
32mm [1 1/4"]
600mm [2'] MAX.
LADDER HANDRAIL
BOILER
ACCESS PANEL
STACK
ECONOMIZER
SAFETY VALVE
VENT THRU ROOF
VENT
MANWAY
NON-RETURN
STOP-CHECK VALVE
BURNER
PLAN VIEW
HANDRAIL
PLATFORM
TOP OF BOILER
CASING
LADDER
STEAM LEAD
NON-RETURN
STOP-CHECK VALVE
BOILER
CONCRETE PAD
BOILER ROOM FLOOR
BURNER
ELEVATIONNOTE:
SUPPORT PLATFORM FROM FINISHED
FLOOR OR FROM BOILER IF BOILER
MANUFACTURER PROVIDES BOILER
ATTACHMENTS AND APPROVES
INSTALLATION. COORDINATE WITH
STRUCTURAL
HANDLE FOR VALVE TO BE
ACCESSED FROM PLATFORM
LC
762mm [2'-6"]
PLATFORM
300mm [12"]
25mm [1"]
D
S W
F W
S
B W
S
B W
S
B W
S
15mm [1/2"]
FROM EACH
BOILER
8mm [1/4"]
FROM
DEAERATOR
20mm [3/4"]
COOLING
WATER
8mm [1/4"]
SAMPLE
OUTLET
20mm [3/4"]
ANTI-SYPHON
VACUUM BREAKER
0-83°C [30-180°F]
SAMPLE COOLER
PROVIDE SEPARATE COOLERS FOR BWS
AND FWS. MOUNT BWS COOLER 1.2M [4']
ABOVE FINISHED FLOOR ON WALL OR
COLUMN. MOUNT FWS COOLER 0.6M [2'] ±
ABOVE MEZZANINE FLOOR AT DEAERATOR.
15mm [1/2"]
ELEVATION
FD
S W
PROVIDE SAME WATER SAMPLE AS
COOLER'S PIPING ARRANGEMENT
AND EQUIPMENT FOR THE BOILER
WATER AS SHOWN FOR THE
FEEDWATER SAMPLE COOLER.
127mm [5"] THICK
CONCRETE HOUSEKEEPING
PAD
FLOOR
20mm [3/4"] DRAIN, DISCHARGE INTO NEAREST
FLOOR DRAIN, NC.
THERMOMETER
GRAVITY RETURN
FROM FLASH TANK
IF SHOWN ON
FLOOR PLAN
SCHEDULE 80
PUMP DISCHARGE
TO PLANT
CONTROL CABINET
VENT
RECEIVER
WATER LEVEL
GAUGE
THERMOMETER
FLUSHING
CONNECTION
SCHEDULE 80
STEEL PIPE
SCHEDULE 80
STEEL PIPE
LPR
R
F W
P S
FROM FEEDWATER DEAERATOR
TO FEEDWATER DEAERATOR
WITH BYPASS TO CONDENSATE
STORAGE TANK
R
FWPS
[30" VAC-30PSI]
0-2000kPa
[0-300PSI]
0-150°C [30-300°F]
F W
P D
-1
F W
P D
-2
BOILER FEEDWATER
PUMP NO. 1
(TYPICAL)
F W
P S
R
F W
P D
-1
F W
P D
-2
BOILER FEEDWATER
PUMP NO. 2
F W
P S
R
F W
P D
-1
F W
P D
-2
BOILER FEEDWATER
PUMP NO. 3
FWPD-1
FWPD-2
TO BOILERS
AND ECONOMIZERS
NOTE:
CAPACITY OF EACH PUMP
APPROX. 125% OF ONE BOILER
FLEX
CONNECTION
RECIRCULATION
ORIFICE SEE DETAIL
THIS SHEET
XXS PIPE
2000kPA
[300 PSI]
FITTINGS
PLUG
TO TANK
COUPLING
UNION
COUPLING
ORIFICE
PUMP DISCHARGE
DETAIL - PUMP RECIRCULATION
ORIFICE ASSEMBLY
EMERGENCY BOILER
CONNECTION TO
OUTSIDE OF BUILDING
762mm VAC-207kPa m m
[3
M
BO
CF
C B
D
BOILER
(TYPICAL)
ECONOMIZER
(TYPICAL)
V
D
OSD
V T
R
D
CV-6,7,8
10-260°C [50-500°F]
F W
P D
FWPD
F W
P D
FWPD
SRV-1
F W
P D
-2
F W
P D
-1 F
R O
M F
E E
D W
A T
E R
P U
M P
S
20mm [3/4"]
VENT INTO
BOILER ROOM
20mm [3/4"]
STACK
B W
S
BO
51mm [2"]
T O
S A
M P
L E
C O
O L E
R
20mm 3/4" FROM
CHEMICALFEEDER
TO BO TANK
OR, IF SPECIFIED, TO
BLOWDOWN HEAT
RECOVERY
BO
2ND BO LINE
REQUIRED IF BOILER
HAS TWO BO
CONNECTIONS
FWPD
CONTROLLER
BOILER WATER LEVEL CONTROL SCHEMATIC
(SEE SPECS FOR TYPE OF SYSTEM)
CV-6,7,8
BOILER WATER LEVEL
TRANSMITTER
BOILER STEAM FLOW
TRANSMITTER
BOILER FEEDWATER
PRESSURE TRANSMITTER
S
IN
G L E
E L E
M E
N T
S Y
S T
E M
D U
A L
E L E
M E
N T
S Y
S T
E M
T H
R E
E E
L E
M E
N T
S Y
S T
E M
0-150°C [30-300°F]
0-2000kPa
[0-300PSIG]
C V
-9 ,1
,1
DESIGNER'S NOTE:
SEE SD232111-04 BASIC FLOW DIAGRAM -
CONDENSATE AND BOILER FEEDWATER FOR
COMPLETE SYSTEM.
PROVIDE CONTROL VALVES HERE
THAT WOULD MODULATE IN
UNISON (ONE OPENS, THE OTHER
ONE CLOSES) TO PREVENT TOO
LOW A FLUE GAS TEMPERATURE
OUT OF THE ECONOMIZER.
PROVIDE
TEMPERATURE
TRANSMITTERS
HERE
0-2000kPa
[0-300PSIG]
20mm [3/4"]
DESIGNER'S NOTE:
SEE SD232111-04 BASIC FLOW DIAGRAM -
CONDENSATE AND BOILER FEEDWATER FOR
COMPLETE SYSTEM.
SW
CTPD
CONTROLLER
WATER LEVEL
TRANSMITTER
WATER LEVEL CONTROL SCHEMATIC
LPS
HPR/MPR
F W
P S
O F
L
FROM PRV STATION
(FOR DETAIL SEE
SD232213-01)
FEEDWATER DEAERATOR
AND STORAGE TANK
TO CONDENSATE STORAGE
TANK. TANK TO BE ASME
STAMPED FOR THE DESIGN
PRESSURE AND TEMPERATURE
OF THE APPLICATION.
EMERGENCY MAKE-UP
NORMAL
MAKE-UP
CTPD
CV-3
CV-4
NC
40mm [1 1/2"]
NCNCNCNC
25mm [1"]
LEVEL
TRANSMITTER
LOW LEVEL
ALARM SW
GAGE GLASS
HIGH LEVEL
ALARM SW
OFL CONTROL
SWITCH
D
OSD
NC
51mm [2"]
F W
S
C F
P
6mm [1/4"]
TO
SAMPLE
COOLER
TO
BOILER
FEEDER
PUMPS
FROM
CHEMICAL
PUMP
VALVE LOCKED OPEN
OFL PIPE IN TANK-INLET
150mm [6"] BELOW LOW LEVEL
ALARM SET POINT
CV-5
SW
R
FROM BOILER FEED
WATER PUMPS SEE SD
232111-07
0-150°C [30-300°F]
TOP OF TANK
OFL LINE
HIGH LEVEL ALARM
LOW LEVEL ALARM
EMERGENCY MAKE-UP
NORMAL WATER LEVEL
CV-3
CV-4
OFL
OFL
CONTROLLER
OFL CONTROL
SWITCH
OVERFLOW CONTROL SCHEMATIC
CV-5
SAFETY DEVICE MANUAL
CAN BE 1/3 OF TANK
PROVIDE STEAM CONTROL
VALVE MODULATED TO
CONTROL TEMPERATURE AT
THE SCRUBBING SECTION OF
THE DEARERATOR.
0-150°C [30-300°F]
[30" VAC-30PSI]
762mm VAC-207kPa
25mm [1"]
B Y
D A
M F
G R m m m m m m
C OF TANKL
[4
[4
[4
D
PROVIDE UNION UNLESS
SAFETY VALVE HAS
FLANGED OUTLET
SAFETY VALVE
OPEN DRAIN (NOTE 3)
CONNECTION TO
PRESSURE VESSEL
OR PIPE
VENT PIPE THROUGH ROOF
SUPPORT AS INDICATED ON
DWGS. (NOTES 1, 2)
PIPE THREADED INTO ELBOW
(SAME SIZE AS ELBOW)
DRIP PAN ELBOW
(SECTIONAL VIEW)
20mm [3/4"] DRAIN TO
FLOOR DRAIN OR OPEN
SIGHT DRAIN (NOTE 4)ELEVATION
NOTES:
1. UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS
NOT BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD
CONTAINED IN ANSI B31.1. POWER PIPING CODE, APPENDIX II. THE VENT PIPE SHOULD GO
VERTICAL THRU THE ROOF WITH NO TURNS OR ANGLES. WHERE REQUIRED THERE SHALL
BE NO MORE THEN A TOTAL OR 180 DEGREES IN DIRECTIONAL CHANGES MADE WITH 45
DEG. ELBOWS.
2. VENT PIPE SHALL TERMINATE 1829mm [6'] MIN. ABOVE FINISHED ROOF.
3. DISCHARGE OF DRAIN SHALL BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS
WHERE PERSONNEL MAY OCCUPY.
4. DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
5. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
FLEXIBLE
CONNECTOR
m m [1
M
IN
610mm
[24" MAX]
76mm [3"]
TT
PT
PRESSURE
TRANSMITTER
TEMPERATURE
TRANSMITTER
FLOW METER
INTERFACE WITH
BACNET SYSTEM
DIFFERENTIAL
PRESSURE (DP)
CELL STEAM FLOW
MEASUREMENT
SHUTOFF VALVE
TO METERING
SYSTEM
BUILDING INCOMING
MAIN STEAM
NOTE:
MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY
METER MANUFACTURERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo B o ile r R e p la c e m e n t_ C d e ta c h e d
P a u l.
W
.L ic h te n h a n .r v t
/1 /2
:0
:1
P M
M-300
MECHANICAL DETAILS
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
NO SCALE
FIRE TUBE BOILER AUXILIARY WATER LEVEL SAFETY PIPING
1 NO SCALE
ACCESS PLATFORM ARRANGEMENT
2 NO SCALE
WATER SAMPLE COOLERS BOILER WATER AND FEED WATER
NO SCALE
CONDENSATE PUMPS PIPING CONNECTIONS
4 NO SCALE
BOILER FEEDWATER PUMPS FLOW DIAGRAM
5 NO SCALE
BOILER FLOW DIAGRAM
NO SCALE
FEEDWATER DEAERATOR FLOW DIAGRAM
7 NO SCALE
STEAM SAFETY VALVE
NO SCALE
STEAM METER DETAIL
m m
M A
X
SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000 LB.] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
mm
[IN]
mm
[FT]
mm
[FT]
THRU 20
[THRU 3/4]
[7]
[5]
[1]
[7]
[6]
[11/4]
[7]
[7]
[11/2]
[9]
[8]
[2]
[10]
[8]
[21/2]
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
PROVIDE INSULATION
SHIELD & INSERT FOR ALL
PIPING (200mm [8"] MIN.)
43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm [2"X2"X1/4"] ANGLE
15mm [1/2"] DIA. HANGER RODS WITH 900mm [36"] MAX. SPACING
ON EACH CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTE:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
BAND
A
A
BB
SECTION A-A (BASE NOT POURED WITH SLAB)
SECTION A-A (BASE POURED WITH FLOOR SLAB)
PLAN
TYPICAL ANCHOR
BOLT NUT & WASHER
SECTION B-B
EQUIPMENT BASE PLATE
PROVIDE #3 BARS 12" [300mm] O.C.
EACH WAY IN THE BASE & DOWEL
BASE TO FLOOR
EQUIPMENT BASE PLATE
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
WELD HEAD TO PLATE OR
BEND OVER END 5D
FLOOR
PIPE SLEEVE (5D, 3"
[75mm] MIN.)
ANCHOR
BOLT (TYP)
CONCRETE BASE
NOTE:
L & W DIMENSIONS SHALL
BE 6" [150mm] GREATER
THAN THE EQUIPMENT
BASE PLATE.
[400mm]
M
IN
[1 m m
M
IN
[1 m m
TYPICAL ANCHOR
BOLT NUT & WASHER
[2 m m
L /1
L
/1
D 1
16"
2D
L
W
D
5D
CW
TEMPERATURE REGULATOR,
CHECK VALVE, STRAINER,
AND THERMOMETER
CONNECT TO
DRAIN
FROM BOILER
BLOWDOWN
STEAM VENT
THRU ROOF
FLOOR
102mm [4"]
HEIGHT DEPENDING
ON INLET OR PUMP
TO BE INSTALLED.
PROVIDE PIPE
SUPPORT
AND SADDLES.
0-2000kPa [30°-300°F]
FLASH TANK DIELECTRIC FITTING
(WHEN RETURN IS COPPER)
RETURN
H.P. DRIP RETURNS.
(SEE FLOOR PLANS)
51mm [2"] VENT TO
OUTSIDE OF BUILDING
FLOOR
GRAVITY RETURN TO
CONDENSATE PUMP
PIPE WITH 6mm [1/4"] PERFORATIONS
SHALL EXTEND FULL LENGTH OF
TANK AND SHALL BE SAME
DIAMETER OF CONDENSATE
RETURN CONNECTION TO TANK.
TOTAL AREA OF ALL 6mm [1/4"]
PERFORATIONS SHALL BE
EQUIVALENT TO THE TRANSVERSE
AREA OF THE PIPE.
CONDENSATE
PUMP CAP. - L/S
(GPM)
APPROX. CAP. OF
FLASH TANK - L
(GALLONS)
SIZE OF FLASH
TANK - mm (in)
0 THRU 237
[0 THRU 15]
253THRU 349
[16 THRU 22]
364 THRU 475
[23 THRU 30]
491 THRU 586
[31 THRU 37]
602 THRU 713
[38 THRU 45]
729 THRU 951
[46 THRU 60]
967 THRU 1189
[61 THRU 75]
1205 THRU 1537
[76 THRU 97]
1553 THRU 2377
[98 THRU 150]
61 [16]
91[24]
117[31]
140[37]
159[42]
231[61]
284[75]
360[95]
587[155]
356mm DIA X 610mm LONG
[14 DIA. X 24 LONG]
365mm DIA X 914mm LONG
[14 DIA. X 36 LONG]
406mm DIA X 914mm LONG
[16 DIA. X 36 LONG]
406mm DIA X 1067mm LONG
[16 DIA. X 42 LONG]
406mm DIA X 1219mm LONG
[16 DIA. X 48 LONG]
457mm DIA X 1372mm LONG
[18 DIA. X 54 LONG]
457mm DIA X 1676mm LONG
[18 DIA. X 66 LONG]
610mm DIA X 1372mm LONG
[24 DIA. X 54 LONG]
610mm DIA X 1981mm LONG
[24 DIA. X 78 LONG]
FLASH TANK SCHEDULE
NOTES:
1. SEE FLOOR PLANS FOR PIPE SIZES.
2. SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2. INSTALL VALVES AS
RECOMMENDED BY MANUFACTURER.
3. MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE LARGEST PRV.
4. PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED CONNECTIONS.
5. SLOPE PILOT CONTROL LINE FROM PRESSURE REDUCING VALVE TO DOWN STREAM STEAM PIPING. MIMIMUM
SLOPE SHALL BE 25'/100', 25mm/300mm [1"/12"]
SIPHON (TYP.)
VENT TO ATMOSPHERE
PILOT CONTROL LINE
REDUCER
(TYP.) IF
REQUIRED
NOTE 1
D1
N.C.
D2
D2
NOTE 1
NOTE 3
INVERTER
BUCKET TRAP
ASSEMBLY TYP.
PSV
V
4XD2 MIN.
20XD2 MIN.10XD1 MIN.
NOTES:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH
DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"]
SCALE POCKET BELOW TRAP INLET.
2. PROVIDE BYPASS PIPING.
SEE DRAWINGS
FOR PIPE SIZES
TO RETURN MAIN
SCHEDULE 80 STEEL
PIPE
PIPE SIZE SHALL
BE SAME SIZE
AS TRAP
INVERTED BUCKET TRAP.
SEE PLANS, AND
SCHEDULES
DIELECTRIC FITTING
WHERE RETURN IS
COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL
PLANE LEVEL WITH TRAP OR IN
VERTICAL PLANE & BELOW TRAP
DRIP LEG OR EQUIPMENT CONNECTION.
MAKE THE SAME SIZE AS THE SUPPLY
MAIN OR EQUIPMENT CONNECTION.
SEE NOTE 1
1" GATE VALVE
USE 4-BOLT RAISED FACE
FLANGES
m m m m
[1
M
IN
[6
M
IN
NOTE:
ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH
DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"]
SCALE POCKET BELOW TRAP INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME
SIZE AS TRAP
FLOAT AND THERMOSTATIC
TRAP. SEE PLANS, AND
SCHEDULES
DIELECTRIC FITTING
WHERE RETURN IS
COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
BYPASS-INSTALL IN HORIZONTAL PLANE
LEVEL WITH TRAP OR IN VERTICAL
PLANE & BELOW TRAP PROVIDE BYPASS
PIPING FOR ALL TRAPS 25mm [1"] AND
LARGER.
DRIP LEG OR EQUIPMENT
CONNECTION. MAKE THE SAME
SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE
NOTE 1
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE
SIZES
25mm [1"]
GATE VALVE
USE 4-BOLT RAISED FACE
FLANGES
m m m m
[1
M
IN
[6
M
IN
NOTE:
1. ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 300mm [12"] MINIMUM HIGH DRIP LEG
FROM BOTTOM OF
STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 150mm [6"] SCALE POCKET BELOW TRAP INLET.
TO RETURN MAIN
PIPE SIZE SHALL BE SAME SIZE AS
TRAP
THERMOSTATIC TRAP. SEE
OTHER STEAM DETAILS,
PLANS, AND SCHEDULES
DIELECTRIC FITTING
WHERE RETURN IS
COPPER PIPE
FLOW
SCHEDULE 80
STEEL PIPE
DRIP LEG OR EQUIPMENT
CONNECTION. MAKE THE SAME
SIZE AS THE SUPPLY MAIN OR
EQUIPMENT CONNECTION. SEE
NOTE 1
SCHEDULE 80 STEEL PIPE
SEE DRAWINGS FOR PIPE
SIZES
25mm [1"]
GATE VALVE
USE 4-BOLT RAISED FACE FLANGES
m m m m
[1
M
IN
[6
M
IN
TO DRAIN
MV
MANUAL
AIR VENT
TO BUILDING
LOAD
INVERTED
BUCKET
TRAP ASSEMBLYWELDED TEE
SCHEDULE 80 STEEL
PIPE
25mm [1"] GATE VALVE
WELDED TEE
CONDENSATE
STEAM PIPE
300mm[12"]
150mm[6"]
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo B o ile r R e p la c e m e n t_ C d e ta c h e d
P a u l.
W
.L ic h te n h a n .r v t
/1 /2
:0
:1
P M
M-301
MECHANICAL DETAILS
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
NO SCALE
PIPE HANGERS DETAIL
1 NO SCALE
CONCRETE EQUIPMENT BASES
NO SCALE
BOILER BLOW DOWN SEPARATOR
NO SCALE
TYP. CONNECTIONS TO FLASH TANK
NO SCALE
STEAM PRESS. RED. STATION DOUBLE VALVE 1/3 & 2/3
5 NO SCALE
INVERTED BUCKET STEAM TRAP ASSY.
6 NO SCALE
FLOAT & THERMOSTATIC STEAM TRAP ASSY.
NO SCALE
THERMOSTATIC STEAM TRAP ASSY.
8 NO SCALE
END OF LINE STEAM TRAP
STEAM TRAP ASSEMBLY
STEAM LINE DRIP POCKET
DRIP LEG (TYP.)
20mm [3/4"] DRAIN
(ALTERNATE LOCATIONS)
(TYPICAL)
STEAM LINE
(TYPICAL)
CAP (TYPICAL)
PIPE T0 STEAM
TRAP (TYPICAL)
NOTE:
DRIP POCKET PIPE SIZE SAME AS
STEAM MAIN UNLESS OTHERWISE
NOTED.
20mm [3/4"] MIN.
FROM DRIP
CONNECTION
DRIP
RETURN
10mm [3/8"] TEST
CONNECTION
m m [6
M
IN
m m
[1 m m [6
M
IN
[1
M
IN
m m
V T
R
BO
HPR
CW
CW
32mm [1 1/4"]
OFL
FULL
CIRCUMFERENCE
WEAR PLATE
PLAN VIEW
LEG (4 REQD.)
HPR
BO
C W
50mm [2"]
PLUGGED
COUPLING
(TYP)
WEAR PLATE
TEMPERATURE
CONTROL
VALVE (TCV-1)
32mm [1 1/4"]
20mm [3/4"]
THERMAL BULB
50mm [2"]
PIPE SIZE IN
AREA OF
THERMAL
BULB
0-150°C
[30-300°F] (TYP)
WELL
CROSS
OFL
FROM STEAM ATOMIZING
BURNER AND OIL HEATER
TRAPS
0-200 kPa [0-30 PSIG]
FROM BOILERS
GAUGE GLASS (25mm [1/2"] MIN.DIA)
INTERNAL OFL PIPE (WATER SEAL)
STEEL
ANGLES GROUT
PLUGS
ELEVATION
NOTE:
TANK SHALL BE MANUFACTURED AND
FURNISHED IN ACCORDANCE WITH
THE ASME BOILER AND PRESSURE
VESSEL CODE AND AMERICAN
NATIONAL STANDARD ANSI/ASME BPV
VIII-1. INSPECTION AND
REGISTRATION ARE WITH THE
NATIONAL BOARD OF BOILER AND
PRESSURE VESSEL INSPECTORS
20mm [3/4"]
OPENING
(SYPHON
BREAKER)
50mm [2"] DRAIN
FINISHED
FLOOR
PLATE
OPEN SIGHT DRAIN
MANHOLE 305x406mm [12"x16"]
32mm [1 1/4"]
NC
C
305mm [12"]
ALIGN WITH CENTER OF WEAR
PLATE
L TANK (NORMAL WATER LEVEL)
152mm [6"]
152mm [6"]
152mm [6"] m
1/2" ALL AROUND
1" X 1/8" X LENTH OF
SLEEVE (4 REQ'D)
PIPE SLEEVE 2"
LARGER I.D.
THAN PIPE O.D.
AS REQUIRED
FOR DIFFERENT
PIPE SIZES
6 GA. SHEET
METAL (GALV.)
FLASHING COLLAR
FLASHING &
COUNTER FLASHING
ROOF
WELD (TYP)
WELD TO VENT
INSULATION
WHERE REQUIRED
FLASHING AND COUNTER
VENT STORM COLLAR
RAIN CAP
7'-0" ABOVE ROOF
DOUBLE WALL POSITIVE
PRESSURE TYPE
SMOKE STACK
19-1/4" INSIDE DIA. STACK
FROM BOILERS.
SPRING VIBRATION
ISOLATORS
YOKE END FORGED
STEEL CLEVIS HANGER
FORGED STEEL
THREADED TURNBUCKEL
WITH ALL THREAD ROD
ROOF SUPPORT
ASSEMBLY
PRIME AND PAINT. REFER TO SPECIFICATION
SECTION. NTS: EDIT SECTION BASED ON
WHICH CONTRACTOR IS RESPONSIBLE FOR
EXHAUST PIPING.
PROVIDE GAP FOR VERTICAL
EXPANSION OF PIPE.
18 GA. RADIANT
DEFLECTOR NOTE 1
PERFORATE RADIANT
DEFLECTOR SUPPORT RING
TO ALLOW AIR FLOW PAST.
RAIN HOOD
(18 GA. GALV. STEEL)
PREFABRICATED CURB WITH
WOOD NAILER.
FASTEN COUNTER
FLASHING TO CURB WITH
CADMIUM PLATED SCREWS.
CARRY ROOFING UP UNDER
COUNTER FLASHING.
INSULATION
CONCRETE ROOF DECK
PIPE ANCHORS BY H.C. AT 120̊ SPACING.
CONTINUOUS WELD TO PIPE SLEEVE.
LONG SWEEP ELBOW
3/4" DRAIN LINE WITH NORMALLY CLOSED
DRAIN VALVE - PIPE TO FLOOR DRAIN
EXHAUST PIPE TO SILENCER
PIPE SUPPORT
METAL
ROOF DECK
CAP HEIGHT 12"
ABOVE ROOF DECK
6”
A P
P R
O X
STAINLESS STEEL BIRD
SCREEN WELDED TO PIPE
OPENING.
CUT END AT 45°
WELD RAIN HOOD CAP TO
STACK (CONTINUAL WELD
TO MAKE WATER TIGHT)
3" HIGH TEMPERATURE
FIBERBOARD INSULATION.
BIRD SCREEN (NOT
ATTACHED TO ROOF
CURB).
6”3”
NOTES:
1. RADIANT DEFLECTOR RING SHALL BE EXTENDED 6" ABOVE
INSULATED ROOF CURB AND 6" BELOW ROOF DECK.
OUTSIDE WALL
PIPE TO FLOOR DRAIN.
FLEX CONNECTION
BYPASS MOTORIZED
DAMPER (NEW)
MOTORIZED
DAMPER (NEW)
EXISTING EXHAUST AIR
LOUVER
DUCTWORK
FLEX CONNECTION AND
ISOLATION VALVE REQUIRED ON
FUEL PIPING
EMERGENCY GENERATOR
3/4"
LONG SWEEP ELBOW
LABELED DRAIN VALVE
(NORMALLY CLOSED).
RADIATOR WITH GEN SET
VIBRATION ISOLATORS BY M.C. (TYPICAL)
FURNISH AND INSTALL SADDLE TYPE
SUPPORTS TRAPEZE HANGERS, AND
STRUCTURAL STEEL ROOF
ATTACHMENT (I.E. BEAM CLAMPS).
(TYPICAL)
FURNISH AND PROVIDE NEW
SILENCERPIPE SUPPORTS 5' O.C. AND AT
CHANGE OF DIRECTION (TYP.)
EXHAUST PIPE PITCHED AWAY
FROM ENGINE
EXHAUST PIPING
FLEXIBLE PIPE CONNECTION
VIBRATION ISOLATION BASE
EXISTING
INTAKE HOOD
NEW MOTORIZED
DAMPER
REFER TO DETAIL 5/M302 FOR
EXHAUST PIPE INSTALLATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo B o ile r R e p la c e m e n t_ C d e ta c h e d
P a u l.
W
.L ic h te n h a n .r v t
/1 /2
:5
:0
P M
M-302
MECHANICAL DETAILS
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
NO SCALE
STEAM DRIP POCKET AND TRAP ASSEMBLY
2 NO SCALE
BOILER BLOWDOWN SEPARATOR TANK
3 NO SCALE
HOT VENT THROUGH ROOF
4NO SCALE
BOILER STACK DETAIL
NO SCALE
GENERATOR EXHAUST PIPE ROOF PENETRATION
5 NO SCALE
GENERATOR INSTALLATION DETAIL - ADD ALTERNATE