Elect 035.pdf
PDF 8 MB Posted
- Attached to
- Y1DA--504-18-119 Replace Boilers and Piping Federal contract opportunity
- Solicitation number
- 36C25722R0010
About this file
This package includes construction documents for replacing boilers and associated piping at the Veterans Affairs Medical Center in Amarillo, Texas. The documents provide details on demolishing existing boilers and controls, installing new 250BHP boilers and controls, connecting equipment to electrical panels, and related scope. An alternate adds installing a new 155KW emergency generator and annunciator panel. Electrical drawings show demolition of existing systems, new connections in panels, and mounting details. A federal contract opportunity notice seeks bids for project 504-18-119 to replace the boilers and piping with a solicitation number of 36C25722R0010 and is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 36C25722R0010 0001.docx | DOCX document | |
| Answers to Questions 36C25722R0010 DB Replace Boilers.pdf | ||
| VA NOTICE OF LIMITATIONS ON SUBCONTRACTING REQUIREMENT.pdf | ||
| Past Performance Questionnaire.pdf | ||
| Mech 035 - Pages 1-3.pdf | ||
| Mech 035 - Pages 4-6.pdf | ||
| OSHA - EMR requirement.pdf | ||
| BP-3-Boiler-steam.pdf | ||
| BP-1-Boiler-fueloil.pdf | ||
| AS ST Series Sheets.pdf | ||
| AD AE Series Sheets.pdf | ||
| G Series Sheets.pdf | ||
| BP-4-Water-Treatment.pdf | ||
| 36C25722R0010_1.docx | DOCX document | |
| Mech 035 - Pages 7-12.pdf | ||
| Phasing sheets.pdf | ||
| Struct 035.pdf | ||
| SELF-PERFORMED CALCULATIONS.pdf | ||
| Mech 035 - Pages 8-19.pdf | ||
| BP-2-Boilers-natgasandpropane.pdf | ||
| 20-09 035 Narrative 02 1r1 Phasing Narrative.pdf | ||
| 20-09 035 Narrative 06 1r1 Civil-LS Design Narrative.pdf | ||
| 20-09 035 Narrative 13 1r1 Specs TOC 000110 035 21-06-30.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UNO UNLESS NOTED OTHERWISE
GFI GROUND FAULT INTERRUPTER
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN
EACH PHASE.
3. LIFE SAFETY, CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS
SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS.
WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING
THE NORMAL BRANCH.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO [27 05 03 AND 28 05 03] [DIVISION 7] [26 05 03]
FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX
CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE A GFI RECEPTACLE LOCATED
DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
8. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS
SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN
GRILLE.
11. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
12. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
14. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF
ANY WELDERS ASSIGNED TO THE JOB.
15. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE
EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES WITH
IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
16. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
17. ELECTRICAL INDENTIFICATION. REFER TO SPECIFICATION SECTION[26 05 53] FOR
COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
SW-1P 26 09 33 SWITCH - SINGLE POLE
SW-COMB 26 09 33 COMBINATION SWITCH AND RECEPTACLE
SW-1P-EM 26 09 33 SWITCH - EMERGENCYE
SW-2P 26 09 33 SWITCH - TWO POLE2
SW-3W 26 09 33 SWITCH - THREE WAY3
SW-3W-EM 26 09 33 SWITCH - THREE WAY - EMERGENCY3E
SW-4W 26 09 33 SWITCH - FOUR WAY4
SW-4W-EM 26 09 33 SWITCH - FOUR WAY - EMERGENCY4E
SW-1P-WP 26 09 33 SWITCH - WEATHERPROOFW
SW-1P-EX 26 09 33 SWITCH - EXPLOSION PROOFX
SW-1P-PL 26 09 33 SWITCH - PILOT LIGHTP
SW-1P-LH 26 09 33 SWITCH - LIGHTED HANDLEL
SW-1P-ADJ 26 09 33 SWITCH - LOCAL TIMER - USER ADJUSTABLET
SW-1P-060 26 09 33 SWITCH - LOCAL TIMER - SPRING WOUND60
SW-A-TPCO 26 09 33 SWITCH - THREE POSITION-CENTER OFFC
SW-1P-M 26 09 33 SWITCH - MOMENTARY CONTACTM
SW-OC-P-O SWITCH - OCCUPANCY SENSOR
WALL SWITCH
O
SW-OC-P-O2 SWITCH - OCCUPANCY SENSOR AND
DUAL SWITCH
O2
OC SW-OC-P-P OCCUPANCY SENSOR - PASSIVE INFRARED
360 DEGREE COVERAGEP
OC SW-OC-P-P2 OCCUPANCY SENSOR - PASSIVE INFRARED
100 DEGREE COVERAGEP2
OC SW-OC-U OCCUPANCY SENSOR - ULTRASONIC 360
DEGREE COVERAGEU
OC SW-OC-U2 OCCUPANCY SENSOR - ULTRASONIC 35'X30'
HAND MOTION COVERAGEU2
OC SW-OC-U-A OCCUPANCY SENSOR - ULTRASONIC TWO
SIDED CORRIDOR COVERAGEA
OC SW-OC-D OCCUPANCY SENSOR - DUAL TECHNOLOGY
D
OC SW-OC-P-HB OCCUPANCY SENSOR - HIGH BAY
HB
OC SW-OC-P-HA OCCUPANCY SENSOR - HIGH BAY AISLE
COVERAGE
HA
ALCR ALCR20 AUTOMATIC LOAD CONTROL RELAY
BCELTS
BCELTS BRANCH CIRCUIT EMERGENCY LIGHTING
TRANSFER SWITCH 20A
LS SW-LS DAYLIGHT LEVEL SENSOR
LS SW-LS-3Z DAYLIGHT LEVEL SENSOR - 3 ZONE
LS SW-LS-D DAYLIGHT LEVEL SENSOR - 1 ZONE DIMMING
D
LS SW-LS-D-3Z DAYLIGHT LEVEL SENSOR - 3 ZONE DIMMING
3D
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
SW-1P-K SWITCH - SINGLE POLE - KEY LOCK 26 09 33
K
SW-2P-K SWITCH - TWO POLE - KEY LOCK
K2
SW-3W-K SWITCH - THREE WAY - KEY LOCK
K3
SW-4W-K SWITCH - FOUR WAY - KEY LOCK
K4
SW-D-6 DIMMER - 600 WATT
SW-D3-6 DIMMER - 600 WATT - 3 WAY
SW-D-10 DIMMER - 1000 WATT
SW-D3-10 DIMMER - 1000 WATT - 3 WAY
SW-D-15 DIMMER - 1500 WATT
SW-D3-15 DIMMER - 1500 WATT - 3 WAY
SW-D-20 DIMMER - 2000 WATT
SW-D3-20 DIMMER - 2000 WATT - 3 WAY
SW-D-LVM DIMMER - MAGNETIC BALLAST
L
SW-D-LVE DIMMER - ELECTRONIC BALLAST
E
SW-D-FL DIMMER - FLUORESCENT BALLAST
F
SW-LS-PC PHOTOCELL26 09 33PC
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
26 09 33
MD-SD-# 26 28 16 MOBILE DIAGNOSTICS SERVICE DISCONNECT.
REFER TO DISC/STA SCHEDULE
CB-# 26 28 16 CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
CB-# 26 28 16 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
DS-#/FDS-#/DSS-# 26 28 16 DISCONNECT. REFER TO DISC/STA SCHEDULE
SW-OC-D-W OCCUPANCY SENSOR - DUAL
TECHNOLOGY - WALL MOUNTED
D
26 09 33OC
SW-OC-P-W OCCUPANCY SENSOR - PASSIVE INFRARED -
WALL MOUNTED
P
26 09 33OC
SW-OC-U-W OCCUPANCY SENSOR - ULTRASONIC - WALL
MOUNTED
U
26 09 33OC
26 09 33
26 09 33
26 09 33
26 09 33
SW-D-LED DIMMER - LED
D
26 09 33
SW-D3-LED DIMMER - LED - 3-WAY
D3
26 09 33
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
FA-LA 26 09 16 LAMP ANNUNCIATORLA
SW-DCS DIMMER CONTROL STATION26 09 33#B
SW-LCS DIMMER CONTROL STATION WITH FADERS26 09 33
TC-# TIME SWITCH 26 09 33TC
RI-TV 26 05 33 TV ANTENNA OUTLET ROUGH-INTV
FB-# 26 27 26 FLOOR BOX - DUAL COMPARTMENT
FB-# 26 27 26 FLOOR BOX - MULTI SERVICE
FB-# 26 27 26 FLOOR BOX - DUPLEX RECEPTACLE
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
WW-# 26 05 35 ELECTRICAL WIREWAY w/ DEVICES SHOWN
WM-# 26 05 35 MULTI OUTLET SYSTEM
RI-TECH-C 26 05 33 TECHNOLOGY ROUGH-IN, CEILING
RI
RI-TECH-W 26 05 33 TECHNOLOGY ROUGH-IN, WALL PHONE
DPM 26 09 13/
26 24 13
DIGITAL POWER METERDPM
PANEL '###' 26 24 16 PANELBOARD - SURFACE MOUNT
PANEL '###' 26 24 16 PANELBOARD - RECESS MOUNT
IPC-# 26 24 22 INTEGRATED POWER CENTER
IPP-# 26 24 21 ISOLATED POWER PANEL
RIM 26 24 21 REMOTE LINE ISOLATION MONITORRIM
MG 26 24 21 MASTER GROUND STATION MODULEMG
PM 26 24 21 OPERATING ROOM POWER MODULEPM
GB 26 05 26 GROUND BUSGB
IBT 26 05 26 INTERSYSTEM BONDING TERMINATIONIBT
PB PB 26 09 16 MOMENTARY PUSHBUTTON OPERATOR
ES ES 26 09 16 EMERGENCY STOP, N.C. CONTACT
EPO 26 09 16 EMERGENCY STOP, N.O. CONTACTEPO
CPC 26 09 16 CONTROL POWER CABINETCPC
MX-#/MS-#
/CB-#/CS-#
26 24 19 MANUAL SWITCH / STARTER / COMBINATION
STARTER/ CIRCUIT BREAKER. REFER TO
DISC/STA SCHEDULE
LCS-# 26 09 33 LIGHTING CONTROL STATION
#B#F
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
MPC-# 26 24 23 PACKAGED POWER CENTER
DEM DEM ENERGY METER26 09 13
EEM EEM EXTERNAL ENERGY METER26 09 13
PQM PQM POWER QUALITY METER26 09 13
TR-#/DTR-# 26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
FB-# 26 27 26 FLOOR - SERVICE FITTING
SV
SW-1P-DJ 26 09 33 SWITCH - DOOR JAMBJ
SW-OD DIMMER - WALL DIMMER
OCCUPANCY SENSORO
26 09 33
SW WALL CONTROL STATION26 09 33SW
SW-LV 26 09 33 CENTRAL CONTROL - STATIONLV
LCD SW-LCD LIGHTING CONTROL LCD STATION26 09 33
BD-# 26 25 00 BUSWAYB B B B
BP-# 26 25 00 BUSS PLUG - CIRCUIT BREAKER.
REFER TO DISC/STA SCHEDULE
BFP-# 26 25 00 BUSS PLUG - FUSIBLE DISCONNECT.
REFER TO DISC/STA SCHEDULE
BCS-# 26 25 00 BUSS PLUG - COMBINATION STARTER.
REFER TO DISC/STA SCHEDULE
BD-REC-# 26 25 00 BUSSWAY RECEPTACLE UNIT.
REFER TO DISC/STA SCHEDULE
R #
NLC SW-NLC NURSE CALL LIGHTING CONTOLLER26 09 33
ITDM ITDM IMPULSE-TOTALIZING DEMAND26 24 13
RAS 26 24 21 REMOTE ANNUNCIATOR STATIONRAS
26 32 13
LINEAR LUMINAIRES
TROFFER
WALL SCONCE LUMINAIRE
DOWNLIGHT LUMINAIRE
AIMABLE OR WALL WASH LUMINAIRE
INDUSTRIAL LUMINAIRE
POLE MOUNTED LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
EMERGENCY UNIT
WALL BRACKET LUMINAIRE
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
WALL/CEILING EMERGENCY EXIT SIGN
REC-DUP-GFI-R 26 27 26 GROUND FAULT DEVICEG
REC-TAMP 26 27 26 DUPLEX RECEPTACLE, TAMPER RESISTANT, 125V
REC-SIM-L1630R 26 27 26 RECEPTACLE, L16-30R, 480V, 3PH
REC-FB-# 26 27 26 FLOOR BOX - POKE THRU, 125V
REC-TAMP-GFI 26 27 26 GFI DUPLEX RECEPTACLE,
TAMPER RESISTANT, 125V
REC-TAMP-QUAD 26 27 26 QUAD RECEPTACLE, TAMPER RESISTANT, 125V
REC-SIM-L2120R 26 27 26 RECEPTACLE, LOCKING L21-20R, 120/208V, 3PH
REC-SIM-L2130R 26 27 26 RECEPTACLE, LOCKING L21-30R, 120/208V, 3PH
REC-ISO-
SUR-QUAD
26 27 26 ISOLATED GROUND QUAD RECEPTACLE WITH
SURGE SUPPRESSION, 125V
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
REC-DUP-XP 26 27 26 DUPLEX RECEPTACLE, EXPLOSION PROOF, 125V
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
REC-DUP-WP 26 27 26 DUPLEX GFI WEATHERPROOF RECEPTACLE 125V
W
REC-ISO 26 27 26 ISOLATED GROUND RECEPTACLE, 125V
REC-ISO-SUR 26 27 26 ISOLATED GROUND RECEPTACLE WITH SURGE
SUPPRESSION, 125V
REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V
REC-QUAD-GFI 26 27 26 QUAD GFI RECEPTACLE, 125V
REC-SIM-520R 26 27 26 SIMPLEX RECEPTACLE, 125V
REC-SIM-530R 26 27 26 RECEPTACLE, 125V
REC-SIM-620R 26 27 26 RECEPTACLE, 6-20R, 250V
REC-SIM-630R 26 27 26 RECEPTACLE, 6-30R, 250V
REC-SIM-650R 26 27 26 RECEPTACLE, 6-50R, 250V
REC-SIM-720R 26 27 26 RECEPTACLE, 7-20R, 277V
REC-SIM-730R 26 27 26 RECEPTACLE, 7-30R, 277V
REC-SIM-750R 26 27 26 RECEPTACLE, 7-50R, 277V
REC-SIM-1420R 26 27 26 RECEPTACLE, 14-20R, 125/250V
REC-SIM-1430R 26 27 26 RECEPTACLE, 14-30R, 125/250V
REC-SIM-1450R 26 27 26 RECEPTACLE, 14-50R, 125/250V
REC-SIM-1460R 26 27 26 RECEPTACLE, 14-60R, 125/250V
REC-SIM-1520R 26 27 26 RECEPTACLE, 15-20R, 250V, 3PH
REC-SIM-1530R 26 27 26 RECEPTACLE, 15-30R, 250V, 3PH
REC-SIM-1550R 26 27 26 RECEPTACLE, 15-50R, 250V, 3PH
REC-SIM-XP 26 27 26 RECEPTACLE, EXPLOSION PROOF, 125V
REC-SIM-L520R 26 27 26 RECEPTACLE, LOCKING TYPE, L5-20R, 125V
REC-SIM-L530R 26 27 26 RECEPTACLE, LOCKING TYPE, L5-30R, 125V
REC-SIM-L620R 26 27 26 RECEPTACLE, LOCKING L6-20R, 250V
REC-SIM-L630R 26 27 26 RECEPTACLE, LOCKING L6-30R, 250V
REC-SIM-L720R 26 27 26 RECEPTACLE, LOCKING L7-20R, 277V
REC-SIM-L730R 26 27 26 RECEPTACLE, LOCKING L7-30R, 277V
REC-SIM-L1420R 26 27 26 RECEPTACLE, LOCKING L14-20R, 125/250V
REC-SIM-L1430R 26 27 26 RECEPTACLE, LOCKING L14-30R, 125/250V
REC-SIM-L1520R 26 27 26 RECEPTACLE, LOCKING L15-20R, 250V, 3PH
REC-SIM-L1530R 26 27 26 RECEPTACLE, LOCKING L15-30R, 250V, 3PH
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
REC-USB 26 27 26 DUPLEX RECEPTACLE, USB CHARGING
X
S
S
U
X
DUPLEX RECEPTACLE CONTROLLED BY
OCCUPANCY
O REC-DUP-O 26 27 26
REC-PED-QUAD 26 05 33 RECEPTACLE - PEDESTAL STYLE
REC-DUP-PED 26 05 33 RECEPTACLE - PEDESTAL STYLE
REC-ARC 26 27 26 ARC FAULT CIRCUIT INTERRUPTER RECEPT 125V
REC-SIM-550R 26 27 26 RECEPTACLE 125V, 50A, 125V
REC-SIM-1560R 26 27 26 RECEPTACLE, 15-60R, 250V, 3PH
REC-SIM-L1620R 26 27 26 RECEPTACLE, L16-20R, 480V, 3PH
REC-QUAD-USB 26 27 26 QUAD RECEPTACLE, USB 125V
U
REC-QUAD-WP 26 27 26 QUAD GFI WEATHERPROOF RECEPTACLE, 125V
W
REC-Z# 26 27 26 IEC PIN AND SLEEVE RECEPTACLE, 600V
PP# 26 27 23 POWER POLE
QUAD RECEPTACLE CONTROLLED BY
OCCUPANCY
O REC-QUAD-O 26 27 26
REFER TO LUMINAIRE
SCHEDULE
W/RI
RI
RI-TECH 26 05 33 TECHNOLOGY OUTLET ROUGH-IN
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS
4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO [ARCHITECTURAL] DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER
TO [CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S] INSTRUCTIONS
FOR MORE DETAILS, PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL,
ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE
MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND
METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
T101
SIM
DETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
SIM
INDICATES SIMILAR DETAIL
REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR
(DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN
(LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR
(DARK SHORT DASHED LINE)
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TEXT INDICATES ADDITIONAL INFORMATION CAN BE FOUND
ELSEWHERE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
LINE TYPE AND TAG KEY:
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
NL = SUBSCRIPT (IF APPLICABLE)
Z = ZONE DESIGNATION
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL SHEET INDEX
11-E-100 FIRST FLOOR PLAN ELECTRICAL - BUILDINGS 11, 16, & 19
11-ED-100 FIRST FLOOR PLAN ELECTRICAL - DEMOLITION - BUILDINGS 11, 16, & 19
E-100 ELECTRICAL COVERSHEET
E-300 ELECTRICAL DETAILS
GRAND TOTAL: 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo
B o ile r
R e p la c e m e n t_ C
S c o tt .R
.K o c ia n .r v t
/1 /2
:4
:0
P M
E-100
ELECTRICAL COVERSHEET
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL -
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
Revisions: Date:
FOR REFERENCE
ONLY NOT FOR
CONSTRUCTION
B-2 B-3B-1
1 1 1
2.2
C K M N
4A
A
2.7
B
GD E F
3.5
L
2.2
H
1A
JC1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo
B o ile r
R e p la c e m e n t_ C
S c o tt .R
.K o c ia n .r v t
/1 /2
:4
:0
P M
11-ED-100
FIRST FLOOR PLAN ELECTRICAL -
DEMOLITION - BUILDINGS 11, 16, & 19
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL -
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
N O R
HT
1/8" = 1'-0"
FIRST FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
GENERAL NOTES:
1. THE INFORMATION ON THE DEMOLITION
DRAWINGS ARE FROM DOCUMENTS PROVIDED
TO THE ENGINEER. CONTRACTOR WILL BE
RESPONSIBLE FOR VISITING THE SITE PRIOR
TO SUBMITTING A BID TO DETERMINE THE
AMOUNT OF DEMOLITION THAT WILL BE
REQUIRED. CONTRACTOR SHALL EXAMINE THE
EXISTING BUILDING AND GENERALLY VERIFY
THE LOCATION OF ALL EXISTING WORK AND
BECOME INFORMED AS TO THE RELATION TO
AND EFFECT ON, THE WORK REQUIRED
BEFORE SUBMITTING A BID. SUBMISSION OF A
BID WILL CONSTITUTE EVIDENCE THAT THE
CONTRACTOR HAS INSPECTED THE SITE OF
THE PROPOSED WORK. DEVICES ON EXISTING
WALLS TO REMAIN OR TO BE REMOVED MAY
NOT APPEAR ON DRAWINGS DUE TO EXISTING
FURNITURE, BOOKCASES, EQUIPMENT, ETC.
BLOCKING VIEW DURING SITE VISIT.
2. CONTRACTOR SHALL STUDY ALL PLANS AND
UNDERSTAND THE FULL SCOPE OF
CONSTRUCTION PRIOR TO BIDS AND
BEGINNING ANY WORK. CONTRACTOR SHALL
UNDERSTAND THAT THE BUILDING WILL BE
RENOVATED IN PHASES AND THAT
ELECTRICAL EQUIPMENT SERVING THOSE
ARES THAT WILL BE RENOVATED IN LATER
PHASES SHALL BE RECONNECTED AND RE-
ENERGIZED TO MAINTAIN POWER TO THOSE
AREAS IF DISRUPTED DURING PHASED
CONSTRUCTION. CONTRACTOR SHALL
UNDERSTAND THAT THE ELECTRICAL
EQUIPMENT SERVING PORTIONS OF THE
BUILDING THAT ARE OUTSIDE OF THIS
PROJECT’S SCOPE SHALL REMAIN AND BE
RECONNECTED AND RE-ENERGIZED TO
MAINTAIN POWER TO HOSE AREAS IF
DISRUPTED DURING PHASED CONSTRUCTION.
3. COORDINATE DEMOLITION WORK WITH THE
BUILDING MAINTENANCE PERSONNEL AND
OTHER TRADES PERFORMING WORK IN THE
BUILDING PRIOR TO THE REMOVAL OF ANY
ITEMS OF EQUIPMENT OR SYSTEMS THAT WILL
AFFECT OTHER SYSTEMS WITHIN THE LIMIT OF
NEW CONSTRUCTION OR OTHER AREAS OF
THE BUILDING. CONTRACTOR SHALL VERIFY
WITH THE OWNER IF THE BUILDING WILL BE
OCCUPIED DURING CONSTRUCTION, AND
THEREFORE UTILITIES MUST REMAIN IN
OPERATION AT ALL TIMES. ANY REQUIRED
OUTAGES MUST BE COORDINATED WITH THE
OWNER.
4. PRIOR TO THE REMOVAL OF ANY EQUIPMENT,
CONTRACTOR MUST VERIFY THE ORIGIN AND
TERMINATION OF THOSE SYSTEMS AND
CONFIRM THAT THE ITEMS BEING REMOVED
DO NOT SERVE ANY ITEMS THAT ARE TO
REMAIN DOWN/UP STREAM (INCLUDING THOSE
IN AREAS OUTSIDE THE CONTRACTOR LIMITS).
IF REMOVAL OF ANY ITEMS DOES DISRUPT
OTHER SYSTEMS DOWN/UP STREAM,
CONTRACTOR SHALL EXTEND, RECONNECT TO
NEW OR RELOCATED EQUIPMENT, AND
MAINTAIN FULL FUNCTIONALITY OF SYSTEM.
5. REFER TO HVAC & PLUMBING DRAWINGS FOR
OTHER DEMOLITION INFORMATION.
DISCONNECT AND REMOVE ALL WIRE,
CONDUIT, AND DISCONNECT SWITCHES
SERVING EQUIPMENT TO BE REMOVED AND
LABEL CIRCUIT BREAKER ‘SPARE’
KEYNOTES:
1. EXISTING BOILER AND BOILER CONTROLS TO
BE DEMOLISHED. DISCONNECT AND REMOVE
ALL ASSOCIATED WIRE AND CONDUIT BACK TO
MOTOR CONTROL PANEL.
2. ADD ALTERNATE : EXISTING 155KW
GENERATOR, ASSOCIATED WIRE AND CONDUIT
TO BE DISCONNECTED AND REMOVED.
3. ADD ALTERNATE : EXISTING GENERATOR
ANNUNCIATOR PANEL, ALL ASSOCIATED
WIRING AND CONDUIT TO BE DISCONNECTED
AND REMOVED.
4. ADD ALTERNATE : EXISTING GENERATOR
CIRCUIT BREAKER TO BE DISCONNECTED AND
REMOVED.
Revisions: Date:
FOR REFERENCE
B-02 B-01B-03
1 1 1
BOILER HOUSE MCC
EXISTING ATS
2 2 2
2.2
C K M N
4A
A
2.7
B
GD E F
3.5
L
2.2
H
1A
JC1
NO SCALE2
EXISTING BOILER HOUSE MCC
NO SCALE3
PANEL 'L12' SPARE BREAKERS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo
B o ile r
R e p la c e m e n t_ C
S c o tt .R
.K o c ia n .r v t
/1 /2
:3
:1
P M
11-E-100
FIRST FLOOR PLAN ELECTRICAL -
BUILDINGS 11, 16, & 19
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL -
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
N O R
HT
1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
KEYNOTES:
1. NEW 250BHP BOILER. CONNECT NEW BOILER
TO NEW OVERCURRENT PROTECTION DEVICE
(MATCH EXISTING) IN EXISTING BOILER HOUSE
MOTOR CONTROL CENTER IN SPACE MADE
AVAILABLE THROUGH DEMOLITION OF
EXISTING BOILER.
2. NEW BOILER CONTROLS. CONNECT EACH
BOILER CONTROL PANEL TO DEDICATED
SPARE 20A/1P CIRCUIT BREAKER IN PANEL
'LIGHTING PANELBOARD L12' LOCATED INSIDE
BOILER HOUSE MCC. VERIFY EXACT LOCATION
PRIOR TO ROUGH IN. REFER TO DETAIL 1/E300
FOR MOUNTING INFORMATION.
3. ADD ALTERNATE : NEW 155KW GENERATOR.
CONNECT TO EXISTING AUTOMATIC TRANSFER
SWITCH.
4. ADD ALTERNATE : NEW GENERATOR
ANNUNCIATOR PANEL.
Revisions: Date:
FOR REFERENCE
ONLY NOT FOR
CONTROL PANEL
UNI STRUT SUPPORT
EMBEDDED
CONCRETE BASE
4" CONCRETE BASE
FINISHED FLOOR
TO BUILDING 4 SWITCHBOARD
EXISTING 400A MLO PANEL 'M'
100 300
TO PANEL 'H-19'
BOILER HOUSE METER
M
EXISTING ATS
EXISTING BOILER HOUSE MCC
EXISTING 250A GENERATOR
CIRCUIT BREAKER
EXISTING 155KW GENERATOR
MAIN BREAKER
BOILER 1
BOILER 3
BOILER 2
PANELBOARD L11
PANELBOARD L12
PANELBOARD H11
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Shaffer & Stevens 9910 North 48th Street
Omaha, Nebraska68152
Phone: 402.455.7698 Fax: 402.455.7597
504-18-119
AMI Environmental Inc
8802 S 135th Street
Omaha, NE 68138
Phone:(402) 397-5001
IMEG Corp.
14755 Preston Rd., Suite 845
Dallas, TX 75254
Phone:(972) 239-6100
15% Design Submission 07/14/2020
20% Design Submission
30% Design Submission
35%/SD1 Schematic Design Submission
09/08/2020
08/14/2020
11/17/2020
C R e v it L o c a l F ile s \M
E
.0
A m a ri llo
B o ile r
R e p la c e m e n t_ C
S c o tt .R
.K o c ia n .r v t
/1 /2
:4
:0
P M
E-300
ELECTRICAL DETAILS
November 17, 2020
Replace Boilers and PipingSD-1 35% SUBMITTAL -
REQUEST FOR PROPOSAL
Thomas E. Creek VAMC-Amarillo, TX
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS
DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE
THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG CORP. © 2020 IMEG CORP.
14755 PRESTON ROAD, SUITE 845
DALLAS, TX 75254
972.239.6100 FAX: 972.239.6102
www.imegcorp.com
TBPE# F-18632
20001967.00
NO SCALE
CONTROL PANEL MOUNTING DETAIL
NO SCALE
PARTIAL EXISTING ELECTRICAL ONE LINE DIAGRAM
Revisions: Date:
FOR REFERENCE