Lamanda_Park_Branch_Library-public_RFP.pdf

PDF 22 MB Posted

Attached to
Design-Build Services for Solar and Energy Storage Installations at Category 1 City-Owned Properties
Solicitation number
2026-RFP-0189
Issued by
Los Angeles County, California

About this file

This is a conceptual design document and request for proposal issued by the City of Pasadena through Pasadena Water and Power (PWP) for design-build services to install solar and energy storage systems at the Lamanda Park Branch Library, a Category 1 city-owned property. The project requires the contractor to design and install solar canopies with a minimum height of 14 feet 6 inches, rooftop solar arrays, an energy storage battery system with a minimum capacity of 60 kilowatts and 4-hour duration, EV charging infrastructure designed for future installation of four Level 2 chargers, and associated electrical equipment including switchgear, buried transformer enclosures, conduits, and lighting compliant with Illuminating Engineering Society standards. The design must maximize solar and battery installations while maintaining all applicable federal, state, and local code compliance, enabling automatic microgrid operation and backup power capability during outages. The contractor is responsible for conducting field surveys to verify existing conditions, procuring and installing all specified equipment, coordinating with PWP's Electric Service Planning Group, repairing any damaged utilities or property, managing parking lot striping and ADA compliance, and ensuring no existing parking spaces are eliminated except as marked on the conceptual plot plan.

The project scope emphasizes that the conceptual design is not final and may be modified provided solar and batteries do not offset the building meter and can operate as a microgrid with backup power functionality. The contractor must protect vertical support structures from vehicular traffic, install protective measures for battery systems including CMU block walls for ground-mounted units or protective cages for wall-mounted systems, and provide two 1-inch spare conduits to each vertical support structure along with conduits for surveillance cameras. PWP will provide transformers, high-voltage cables, and service entrance conductors, while the contractor assumes full responsibility for all other service equipment procurement and installation. All new electrical installations must comply with City of Pasadena Water and Power Department Regulation 21, and the contractor must submit preliminary service equipment information to PWP for approved electrical service design prior to construction commencement.

View the file

Other files

File Type Posted
Design-Build_Services_for_Solar_and_Energy_Storage_Installations_at_Category_1_City-Owned_Properties_(Addendum_#4_Revision).pdf PDF
Solar_and_Energy_Storage_-_09.29.2026.pdf PDF
Design-Build_Services_for_Solar_and_Energy_Storage_Installations_at_Category_1_City-Owned_Properties_(Addendum_#2_Revision).pdf PDF
Design-Build_Services_for_Solar_and_Energy_Storage_Installations_at_Category_1_City-Owned_Properties.pdf PDF
City's_Standard_Form_(Traditional)_Design-Build_Agreement_Place_Holder.pdf PDF
CONFLICT_OF_INTEREST_(5).pdf PDF
PWP_Rooftop_Solar_Design_Build_Project.pdf PDF
REQUIRED_FORMS_-_AAs_-_SIG-LEGAL-STATUS_-_DECLARATION_OF_NONCOLUSION_08022024_v2.pdf PDF
Pasadena_Taxpayer_Protection_Amendment_Disclosure_(2).pdf PDF
DISQUALIFICATION_DISCLOSURE_(4).pdf PDF
DESIGNATED_REPRESENTATIVESdocx.pdf PDF
FAITHFUL_PERFORMANCE_BOND_FORM_(2).pdf PDF
Allendale_Branch_Library_RFP.pdf PDF
Madison_Parking_Lot_RFP.pdf PDF
Glenarm_Power_Plant-RFP.pdf PDF
Central_Library_RFP.pdf PDF
Washington_Park-public_RFP.pdf PDF
Victory_Park_South_RFP.pdf PDF
San_Rafael_Branch_Library_RFP.pdf PDF
Robinson_Park_and_Recreation_Center_RFP.pdf PDF
Linda_Vista_Branch_Library_RFP.pdf PDF
La_Pintoresca_Branch_Library-public_RFP.pdf PDF
Jackie_Robinson_Community_Center_RFP.pdf PDF
Hamilton_Park-public_RFP.pdf PDF
Emergency_FEMA_TC.pdf PDF
DoIT_Technical_Questionnaire.xlsx XLSX spreadsheet
AR_4.pdf PDF
Unique_Entity_ID_(SAM).pdf PDF
Disclosure_of_Lobbying_Activities.pdf PDF
Federal_Required_Certification_(4).pdf PDF
Exclusive_Negotiation_Agreement__TEMPLATE.pdf PDF
RELEVANT_EXPERIENCE_FORM.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(N) SOLAR CANOPY FOR

SEATING AREA

(N) SOLAR CARPORTS

(N) ROOFTOP SOLAR

(N) LOCATION FOR

BATTERIES

(N) SWITCHGEAR

(N) BURIED

TRANSFORMER

ENCLOSURE

(N) CONDUIT

(N) EV / AUX PANEL

(E) ELECTRICAL ROOM

AND PANELS

(F) EV CHARGERS

(N) CURB CUT FOR

FUTURE EV ADA PATH

OF TRAVEL

(E) UNDERGROUND VAULT

M M M MM

RE

VIS

ION

S

CIT

Y O

F P

AS

AD

EN

A -

DE

PA

RT

ME

NT

OF

W

AT

ER

AN

D P

OW

ER

LA

M

AN

D

A

PA

R K

BR

AN

C H

L

IB

R

AR

Y

S

AL

TA

D

EN

A

D R

PA

SA

D

EN

A, C

A

SEAL:

CONCEPTUAL

DESIGN

PLOT PLAN

SCALE: NONE

LAMANDA PARK BRANCH LIBRARY

CONCEPTUAL SINGLE LINE DIAGRAM

SCALE: NONE

NOTES:

1. LAYOUT IS CONCEPTUAL. CONTRACTOR SHALL SUBMIT PROPOSAL TO MAXIMIZE SOLAR AND

BATTERIES AT THE SITE WHILE MAINTAINING COMPLIANCE WITH ALL APPLICABLE FEDERAL,

STATE, AND LOCAL CODES.

2. PROPOSED DESIGN MAY DEVIATE FROM CONCEPTUAL DESIGN PROVIDED IT MEETS THE

FOLLOWING REQUIREMENTS:

2.1. SOLAR AND BATTERIES SHALL NOT OFFSET BUILDING METER

2.2. SOLAR AND BATTERIES SHALL BE CAPABLE OF AUTOMATIC MICROGRID OPERATION

AND PROVIDE BACKUP POWER TO THE BUILDING IN CASES OF A POWER OUTAGE

3. THE CONTRACTOR IS FULLY RESPONSIBLE FOR REPAIRING OR REPLACING ANY EXISTING

PROPERTY OR UTILITIES DAMAGED DURING CONSTRUCTION. ALL REPAIRS SHALL BE

EXECUTED TO A CONDITION EQUAL OR BETTER THAN THE PRE-CONSTRUCTION CONDITION

4. CONTRACTOR SHALL PERFORM ON-SITE FIELD SURVEY TO VERIFY ALL EXISTING CONDITIONS

AND DIMENSIONS PRIOR TO PROCEEDING WITH DESIGN

5. SOLAR CANOPIES

5.1. MINIMUM HEIGHT OF CARPORT CANOPY SHALL BE 14'-6"

5.2. THERE SHALL BE 2-1" CONDUITS FROM THE SWITCHGEAR TO EACH SOLAR CANOPY

FOR CAMERAS (TOTAL OF 6) - EXACT CAMERA LOCATIONS TO BE DETERMINED

DURING DESIGN PHASE

5.3. CONTRACTOR TO PROVIDE LIGHTING WHICH COMPLIES WITH THE ILLUMINATING

ENGINEERING SOCIETY (IES) - CHAPTER 17 PARKING LOTS AND PARKING GARAGES

5.4. VERTICAL SUPPORT STRUCTURES SHALL BE PROTECTED FROM VEHICULAR TRAFFIC

5.5. SOLAR CANOPY AND EQUIPMENT (UNLESS MARKED IN THE CONCEPTUAL PLOT PLAN)

SHALL NOT CAUSE ANY PARKING SPACES TO BE LOST

5.6. 2-1" SPARE CONDUIT SHALL BE RAN TO EACH VERTICAL SUPPORT

6. BATTERY

6.1. DIMENSIONS TO BE PROVIDED BY CONTRACTOR AND SITING TO BE DETERMINED AT A

FUTURE POINT

6.2. PREFERABLE TO HAVE BATTERIES MOUNTED ON SOLAR STRUCTURE

6.3. OTHERWISE PROPOSAL SHALL SPECIFY A BATTERY SYSTEM AT A MINIMUM OF 60KW,

4 HR

6.4. GROUND MOUNTED BATTERIES SHALL BE PROTECTED WITH A CMU BLOCK WALL.

WALL MOUNTED BATTERIES SHALL HAVE A PROTECTIVE CAGE INSTALLED

7. CONTRACTOR TO PROCURE AND INSTALL COMMUNICATIONS CABINET, PAD, CONDUITS, AND

POWER FOR TELECOM

8. PARKING LOT

8.1. CONTRACTOR SHALL ENSURE PARKING SPACES AND PATH OF TRAVEL ARE

COMPLIANT WITH ADA REQUIREMENTS

8.2. CONTRACTOR SHALL ENSURE FUTURE EV CHARGING ADA SPACES AND PATH OF

TRAVEL ARE COMPLIANT WITH ADA REQUIREMENTS

8.3. CONTRACTOR IS RESPONSIBLE FOR PARKING STRIPING

9. EV CHARGERS

9.1. SWITCHGEAR SHALL BE DESIGNED FOR FUTURE (4) LEVEL 2 EV CHARGERS

9.2. CONTRACTOR TO DESIGN AND INSTALL EV CHARGER PANEL, CONDUITS, PULLBOXES,

AND CONCRETE PADS TO ALLOW FOR FUTURE EV CHARGER INSTALLATION WITHOUT

ANY ADDITIONAL CIVIL WORK

10.ELECTRIC SERVICE NOTES

10.2. ALL NEW ELECTRICAL SERVICE INSTALLATIONS SHALL COMPLY WITH THE CITY OF

PASADENA WATER AND POWER DEPARTMENT'S ELECTRICAL SERVICE

REQUIREMENTS (REGULATION 21). ONCE AWARDED, THE CONTRACTOR SHALL

SUBMIT PRELIMINARY SERVICE EQUIPMENT INFORMATION TO PWP FOR ELECTRICAL

SERVICE DESIGN. ELECTRICAL SERVICE INFORMATION ON THIS PAGE IS CONCEPTUAL

ONLY AND MAY CHANGE DEPENDENT ON THE CONTRACTOR EQUIPMENT AND SIZING.

10.2.1. EQUIPMENT LOCATIONS AND DESIGN ARE CONCEPTUAL. CONTRACTOR

SHALL BE RESPONSIBLE FOR COORDINATING WITH PWP'S ELECTRIC SERVICE

PLANNING GROUP TO OBTAIN AN APPROVED SERVICE DESIGN

10.2.2. CONTRACTOR IS RESPONSIBLE FOR FOLLOWING ALL REQUIREMENTS STATED

ON THE PWP SERVICE DESIGN

10.3. CONTRACTOR IS RESPONSIBLE FOR THE PROCUREMENT AND INSTALLATION OF THE

FOLLOWING SERVICE EQUIPMENT

10.3.1. BURIED TRANSFORMER ENCLOSURE 4-6"X8'6" JENSEN PRECAST

K4686-TE78-20 OR EQUIVALENT

10.3.2. PRIMARY CONDUITS ON PRIVATE PROPERTY

10.3.3. SECONDARY CONDUITS ON PRIVATE PROPERTY

10.3.4. SWITCHGEAR AND ELECTRICAL PANELS

10.3.4.1. NEW MAIN SWITCHGEAR SHALL INCLUDE CONTROLS, MOTORIZED

MAIN BREAKER, AND RELAYING CAPABLE OF AUTOMATICALLY

ISLANDING AND SYNCHRONIZING THE SITE TO SUPPORT MICROGRID

OPERATIONS

10.4. PWP SHALL PROVIDE THE FOLLOWING:

10.4.1. TRANSFORMERS LOCATED INSIDE THE UNDERGROUND VAULT

10.4.2. HIGH VOLTAGE CABLES FROM PWP SYSTEM TO TRANSFORMER

10.4.3. SERVICE ENTRANCE CONDUCTORS FROM THE TRANSFORMER TO

SWITCHGEAR

CONCEPTUAL

DESIGN NOT FOR

CONSTRUCTION

AutoCAD SHX Text

(N) SWITCHGEAR

AutoCAD SHX Text

120/208V 3PH 4W

AutoCAD SHX Text

TO PWP

AutoCAD SHX Text

(N) BURIED BURIED TRANSFORMER ENCLOSURE

AutoCAD SHX Text P/L

AutoCAD SHX Text

(E) ELECTRICAL PANEL 1PH

AutoCAD SHX Text

(N) SOLAR AND BATTERIES

AutoCAD SHX Text

(E) ELECTRICAL PANEL 3PH

AutoCAD SHX Text

(N) EV / AUX PANEL

AutoCAD SHX Text

(F) EV CHARGERS

AutoCAD SHX Text

(N) AUX (LIGHTS, CAMERAS, ETC)

AutoCAD SHX Text

(E) BUILDING LOAD

AutoCAD SHX Text

(E) BUILDING LOAD

AutoCAD SHX Text

(N) CONDUITS

AutoCAD SHX Text

(N) CONDUITS AND CABLES

AutoCAD SHX Text

(N) CONDUITS AND CABLES

AutoCAD SHX Text

(N) CONDUITS AND CABLES

AutoCAD SHX Text

AS BUILT

AutoCAD SHX Text

MARK

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

CHKD.

AutoCAD SHX Text

ADDRESS:

AutoCAD SHX Text

PROJECT:

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

CIP:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PJO:

Lamanda Park Branch Library-public
Sheets and Views
public
PXL_20251218_151405668
PXL_20251218_151430463
PXL_20251218_153742215
A-1 Existing Site Plan
A-2 Site and Roof Plan
A-4 Reflected Ceiling Plan
E-1 Plot Plan, single Line diagram, Symbols & Schedules
E-2 Lighting, Receptacle & Tele. Plans

File details come from the government source that posted it. Updated .