La_Pintoresca_Branch_Library-public_RFP.pdf

PDF 793 KB Posted

Attached to
Design-Build Services for Solar and Energy Storage Installations at Category 1 City-Owned Properties
Solicitation number
2026-RFP-0189
Issued by
Los Angeles County, California

About this file

La Pintoresca Branch Library Solar Installation

This is a conceptual design document and Request for Proposals issued by the City of Pasadena, Department of Water and Power (PWP), for design-build services to implement a solar and energy storage installation at the La Pintoresca Branch Library/Park located at 1355 N. Raymond Avenue, Pasadena, California 91103. The project requires the selected contractor to design, procure, construct, install, interconnect, and commission solar canopies, battery energy storage systems, electrical infrastructure, and associated site improvements while maximizing solar generation and battery capacity within code compliance and site constraints. The project is categorized as a Category 1 priority site intended for completion by June 2028. Key design specifications include solar carport canopies with a minimum height of 14 feet 6 inches, a battery system with a minimum capacity of 20 kilowatts over 4 hours (preferably mounted on the solar structure), lighting compliant with Illuminating Engineering Society standards for parking facilities, protection of vertical support structures from vehicular traffic, and preservation of existing parking spaces. The contractor is responsible for conducting on-site field surveys to verify existing conditions, coordinating with PWP's Electric Service Planning Group for meter spot approval, procuring and installing secondary conduits, switchgear, and electrical panels, ensuring Americans with Disabilities Act compliance for parking and pedestrian pathways, parking lot striping, and repairing or replacing any damaged existing property or utilities to pre-construction condition or better.

The City of Pasadena reserves the right to award one contract, multiple contracts by individual site, by combination of sites, or in whole as determined in the City's best interest. All electrical service installations must comply with PWP's Electrical Service Requirements (Regulation 21), with equipment locations and service design subject to change based on contractor equipment specifications and sizing. PWP will provide service entrance conductors from the transformer to the switchgear, while the contractor assumes full responsibility for all other electrical infrastructure procurement and installation. The contractor must submit preliminary service equipment information to PWP for electrical service design review and obtain required approvals before construction. The conceptual design presented is for planning purposes only and not for construction, with the contractor obligated to submit a final proposal that optimizes solar and battery placement while maintaining full compliance with all applicable federal, state, and local codes.

View the file

Other files

File Type Posted
Design-Build_Services_for_Solar_and_Energy_Storage_Installations_at_Category_1_City-Owned_Properties_(Addendum_#4_Revision).pdf PDF
Solar_and_Energy_Storage_-_09.29.2026.pdf PDF
Design-Build_Services_for_Solar_and_Energy_Storage_Installations_at_Category_1_City-Owned_Properties_(Addendum_#2_Revision).pdf PDF
Design-Build_Services_for_Solar_and_Energy_Storage_Installations_at_Category_1_City-Owned_Properties.pdf PDF
City's_Standard_Form_(Traditional)_Design-Build_Agreement_Place_Holder.pdf PDF
CONFLICT_OF_INTEREST_(5).pdf PDF
PWP_Rooftop_Solar_Design_Build_Project.pdf PDF
REQUIRED_FORMS_-_AAs_-_SIG-LEGAL-STATUS_-_DECLARATION_OF_NONCOLUSION_08022024_v2.pdf PDF
Pasadena_Taxpayer_Protection_Amendment_Disclosure_(2).pdf PDF
DISQUALIFICATION_DISCLOSURE_(4).pdf PDF
DESIGNATED_REPRESENTATIVESdocx.pdf PDF
FAITHFUL_PERFORMANCE_BOND_FORM_(2).pdf PDF
Allendale_Branch_Library_RFP.pdf PDF
Madison_Parking_Lot_RFP.pdf PDF
Glenarm_Power_Plant-RFP.pdf PDF
Central_Library_RFP.pdf PDF
Washington_Park-public_RFP.pdf PDF
Victory_Park_South_RFP.pdf PDF
San_Rafael_Branch_Library_RFP.pdf PDF
Robinson_Park_and_Recreation_Center_RFP.pdf PDF
Linda_Vista_Branch_Library_RFP.pdf PDF
Lamanda_Park_Branch_Library-public_RFP.pdf PDF
Jackie_Robinson_Community_Center_RFP.pdf PDF
Hamilton_Park-public_RFP.pdf PDF
Emergency_FEMA_TC.pdf PDF
DoIT_Technical_Questionnaire.xlsx XLSX spreadsheet
AR_4.pdf PDF
Unique_Entity_ID_(SAM).pdf PDF
Disclosure_of_Lobbying_Activities.pdf PDF
Federal_Required_Certification_(4).pdf PDF
Exclusive_Negotiation_Agreement__TEMPLATE.pdf PDF
RELEVANT_EXPERIENCE_FORM.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(N) SOLAR ON OPEN PERGOLA

(N) SOLAR

CARPORT

(N) ELECTRICAL

PANEL

(N) CONDUIT

(E) TRANSFORMER

ENCLOSURE

M

RE

VIS

ION

S

CIT

Y O

F P

AS

AD

EN

A -

DE

PA

RT

ME

NT

OF

W

AT

ER

AN

D P

OW

ER

LA

P

IN

TO

R

ES

C A

LI

BR

AR

Y/

PA

R

K

SO

LA

R

IN

ST

AL

LA

TI

O

N

N . R

AY

M

O N

D A

VE

PA

SA

D

EN

A, C

A

SEAL:

CONCEPTUAL

DESIGN

PLOT PLAN

SCALE: NONE

CONCEPTUAL SINGLE LINE DIAGRAM

SCALE: NONE

LA PINTORESCA BRANCH LIBRARY

NOTES:

1. LAYOUT IS CONCEPTUAL. CONTRACTOR SHALL SUBMIT PROPOSAL TO MAXIMIZE SOLAR AND

BATTERIES AT THE SITE WHILE MAINTAINING COMPLIANCE WITH ALL APPLICABLE FEDERAL,

STATE, AND LOCAL CODES.

2. THE CONTRACTOR IS FULLY RESPONSIBLE FOR REPAIRING OR REPLACING ANY EXISTING

PROPERTY OR UTILITIES DAMAGED DURING CONSTRUCTION. ALL REPAIRS SHALL BE EXECUTED

TO A CONDITION EQUAL OR BETTER THAN THE PRE-CONSTRUCTION CONDITION

3. CONTRACTOR SHALL PERFORM ON-SITE FIELD SURVEY TO VERIFY ALL EXISTING CONDITIONS

AND DIMENSIONS PRIOR TO PROCEEDING WITH DESIGN

4. SOLAR CANOPIES

4.1. MINIMUM HEIGHT OF CARPORT CANOPY SHALL BE 14'-6"

4.2. THERE SHALL BE 2-1" CONDUIT FROM THE SWITCHGEAR TO EACH SOLAR CANOPY FOR

CAMERAS (TOTAL OF 6) - EXACT CAMERA LOCATIONS TO BE DETERMINED DURING

DESIGN PHASE

4.3. CONTRACTOR TO PROVIDE LIGHTING WHICH COMPLIES WITH THE ILLUMINATING

ENGINEERING SOCIETY (IES) - CHAPTER 17 PARKING LOTS AND PARKING GARAGES

4.4. VERTICAL SUPPORT STRUCTURES SHALL BE PROTECTED FROM VEHICULAR TRAFFIC

4.5. SOLAR CANOPY AND EQUIPMENT (UNLESS MARKED IN THE CONCEPTUAL PLOT PLAN)

SHALL NOT CAUSE ANY PARKING SPACES TO BE LOST

4.6. 2-1" SPARE CONDUIT SHALL BE RAN TO EACH VERTICAL SUPPORT

5. BATTERY

5.1. DIMENSIONS TO BE PROVIDED BY CONTRACTOR AND SITING TO BE DETERMINED AT A

FUTURE POINT

5.2. PREFERABLE TO HAVE BATTERIES MOUNTED ON SOLAR STRUCTURE

5.3. OTHERWISE PROPOSAL SHALL SPECIFY A BATTERY SYSTEM AT A MINIMUM OF 20KW, 4

HR

5.4. GROUND MOUNTED BATTERIES SHALL BE PROTECTED WITH A CMU BLOCK WALL, WALL

MOUNTED UNITS SHALL HAVE A PROTECTIVE CAGE INSTALLED

6. CONTRACTOR TO PROCURE AND INSTALL COMMUNICATIONS CABINET, PAD, CONDUITS, AND

POWER FOR TELECOM

7. PARKING LOT

7.1. CONTRACTOR SHALL ENSURE PARKING SPACES AND PATH OF TRAVEL ARE COMPLIANT

WITH ADA REQUIREMENTS

7.2. CONTRACTOR IS RESPONSIBLE FOR PARKING STRIPING

8. ELECTRIC SERVICE NOTES

8.2. ALL NEW ELECTRICAL SERVICE INSTALLATIONS SHALL COMPLY WITH THE CITY OF

PASADENA WATER AND POWER DEPARTMENT'S ELECTRICAL SERVICE REQUIREMENTS

(REGULATION 21). ONCE AWARDED, THE CONTRACTOR SHALL SUBMIT PRELIMINARY

SERVICE EQUIPMENT INFORMATION TO PWP FOR ELECTRICAL SERVICE DESIGN.

ELECTRICAL SERVICE INFORMATION ON THIS PAGE IS CONCEPTUAL ONLY AND MAY

CHANGE DEPENDENT ON THE CONTRACTOR EQUIPMENT AND SIZING.

8.2.1. EQUIPMENT LOCATIONS AND DESIGN ARE CONCEPTUAL. CONTRACTOR SHALL

BE RESPONSIBLE FOR COORDINATING WITH PWP'S ELECTRIC SERVICE

PLANNING GROUP TO OBTAIN A METER SPOT

8.2.2. CONTRACTOR IS RESPONSIBLE FOR FOLLOWING ALL REQUIREMENTS STATED

ON THE PWP METER SPOT

8.3. CONTRACTOR IS RESPONSIBLE FOR THE PROCUREMENT AND INSTALLATION OF THE

FOLLOWING SERVICE EQUIPMENT

8.3.1. SECONDARY CONDUITS ON PRIVATE PROPERTY

8.3.2. SWITCHGEAR AND ELECTRICAL PANELS

8.4. PWP SHALL PROVIDE THE FOLLOWING:

8.4.1. SERVICE ENTRANCE CONDUCTORS FROM THE TRANSFORMER TO SWITCHGEAR

CONCEPTUAL

DESIGN NOT FOR

CONSTRUCTION

AutoCAD SHX Text

TO PWP

AutoCAD SHX Text

(N) SOLAR AND BATTERIES

AutoCAD SHX Text

(E) TRANSFORMER ENCLOSURE

AutoCAD SHX Text P/L

AutoCAD SHX Text

AUX POWER

AutoCAD SHX Text

(N) ELECTRICAL PANEL 120/208V 3PH 4W

AutoCAD SHX Text

AS BUILT

AutoCAD SHX Text

MARK

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text

CHKD.

AutoCAD SHX Text

ADDRESS:

AutoCAD SHX Text

PROJECT:

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

SHEET TITLE

AutoCAD SHX Text

CIP:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PJO:

Sheets and Views
public

File details come from the government source that posted it. Updated .