Wastewater - System Description
| WASTEWATER SYSTEMS DECSRIPTION |
| Collection System Description: |
| NAVFAC’s Sanitary Sewer Systems collect wastewater from buildings to either the centralized wastewater treatment plant on the installations or to the municipal wastewater treatment facility. The system contains laterals that connect buildings to a main sewer pipeline. The sewer system is a conveying system that includes pump stations, force mains, manholes, storage facilities and other components. Most of the systems are designed to take advantage of gravity flow; however, in areas lacking adequate depths, pump or lift stations move wastewater into a new pipe section (force main) to continue the transfer. The collection piping systems may include combinations of differing materials and sizes. |
| Wastewater Teatment Plant (WWTP) Description: |
| The NAS Sigonella wastewater treatment plants are composed as follows: |
• Pre-treatment
• Equalization
• Biological plant + MBR plant
• Disinfection The wastewater produced by the activities carried out within the base is pre-treated with the removal of big and fine solids by means of existing pre-treatment. The wastewater are collected into equalization tank and mixed by two submersible mixers. From the equalization basin, three submersible pumps transfer the mixed wastewater to the biological treatment. The biological process takes place in the bioreactor tank and into membrane tank for the degradation of pollutants. The treated effluent is finally disinfected and discharged.
NAS I
| ATTACHMENT J-1604000-03 | | | | | | | | |
| WASTEWATER SYSTEMS DESCRIPTION AND INVENTORY | | | | | | | | |
| (*) Reference Section C, Annex 0200000 Management and Administration, Spec Item 2.6.2 Dissemination of Information | | | | | | | | |
| NAS I - Lift Stations Inventory | | | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION (*) | MANUFACTURER | MODEL NO. | Level Sensor | REMARKS | CLEANING FREQUENCY | LEVEL SENSOR CALIBRATION FREQUENCY |
| NAS I | 231 | | DAB | VS 1000T-NA | Float switch | 2 pumps; 1 electrical panel; 1 level sensor | Not required | 1 time per year |
| NAS I | 157 | | Wilo | Rexa UNIV06/T15-540 | Wilo-Control EC-L | 2 pumps; 2 | Not required | |
| | | | | | check valves; 2 | | |
| | | | | | gate valves; 1 electrical panel; 1 level sensor | | |
| NAS I | 234 | | KSB | Amarex N F65- 170/042 ULG-152 | AquaRanger 5L | 2 pumps; 2 | 2 times per year | |
| | | | | | check valves; 2 | | |
| | | | | | gate valves; 1 electrical panel; 1 level sensor | | |
| NAS I | 229 | | Flygt | NP 3085.160 | AquaRanger 5L | 2 pumps; 2 | 1 time per year | |
| | | | | | check valves; 2 | | |
| | | | | | gate valves; 1 electrical panel; 1 level sensor | | |
| NAS I - WWTP Inventory | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION | MANUFACTURER | MODEL NO. | REMARKS | CLEANING FREQUENCY |
| NAS I | 229 | Pre-treatment | NA | NA | Inlet channel cleaning and sludge disposal + 3 Bins solid sludge disposal | 1 time per year |
| NAS I | 229 | EQ pit pumps | Flygt | NP 3085.160 | 3 pumps; 1 electrical panel; 1 sensor level | 1 time per year |
| NAS I | 229 | Equalization Tank | Flygt | SR 4640 | tank with 2 mixers; 1 electrical panel | 1 time per year |
| NAS I | 229 | MBR Tank | NA | NA | tank | 1 time per year |
| NAS I | 229 | MBR | Sulzer | XFP100C-CB1.4-PE22/4-D14*10 | 2 pumps; 1 electrical panel | NA |
| NAS I | 229 | MBR Tank | Sulzer | XRW 3031 PA29/6-EC-10-BO | 2 mixer; 1 electrical panel | NA |
| NAS I | 229 | 4 Dry beds | NA | NA | NA | 2 times per year - each dry bed |
| NAS I - WWTP Tools Inventory | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION | MANUFACTURER | MODEL NO. | Asset | CALIBRATION FREQUENCY |
| NAS I | 229 | Influent channel | Endress+Hauser | Prosonic S FDU91 | 1 flow meter | 1 time per year |
| NAS I | 229 | Equalization Tank | Siemens | Sitrans LUT420 | 1 level transmitter | |
| NAS I | 229 | MBR Tank | Endress+Hauser | controller probes CM444-13R1/0 | 1 pH sensor; 1 suspended solid sensor; 1 oxygen sensor; 1 Redox sensor |
| | | | 2 controllers level transmitter RIA46-13L9/0 | 1 level transmitter MBR tank ; 1 level transmitter permeate tank |
| | | | PMC51-JT20/295 | 2 pressure meter blower; 1 pressure meter permeate pump |
| | | | 6BABL1-7J27/115 | 2 flow transmitters blower |
| | | | 10L1Z-16C0/101 | 1 flow meter permeate pump; 1 flow meter backwash pump |
| NAS I | 229 | Effluent Channel | Hach Lange | SC200 Universal Controller | 1 pH sensor; 1 suspended solid sensor; 1 conducibility sensor; 1 Chlorine sensor |
| | | Endress+Hauser | Prosonic S FDU91 | 1 flow meter |
NAS II
| ATTACHMENT J-1604000-03 | | | | | | | | |
| WASTEWATER SYSTEMS DESCRIPTION AND INVENTORY | | | | | | | | |
| (*) Reference Section C, Annex 0200000 Management and Administration, Spec Item 2.6.2 Dissemination of Information | | | | | | | | |
| NAS II - Lift stations inventory | | | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION (*) | MANUFACTURER PUMPS | MODEL PUMPS | LEVEL SENSOR | REMARKS | CLEANING FREQUENCY LIFT STATION | LEVEL SENSOR CALIBRATION FREQUENCY |
| NAS II | 402.1 | | Flygt | NP 3085.160 | 4 Float switches | 3 pumps; 3 | 3 times per year | 1 time per year |
| | | | | | check valves; 3 gate valves | | |
| NAS II | 431 | | Flygt | NP 3069 | AquaRanger 3 | 2 pumps; 2 | 2times per year | |
| | | | | | check valves; 2 | | |
| | | | | | gate valves; 1 electrical panel | | |
| NAS II | 565 | | KBS | AMAREX N F80-220/034 | Ultra Ranger MUR 1 | 2 pumps; 2 | 2 ctimes per year | |
| | | | | | check valves; 2 | | |
| | | | | | gate valves; 1 electrical panel | | |
| NAS II | 820 | | Faggiolati | G409J6V1- M64AA0 | AquaRanger 5 | 2 pumps; 2 | NA | |
| | | | | | check valves; 2 | | |
| | | | | | gate valves; 1 electrical panel | | |
| NAS II | 1023 | | Lowara | 1320H- | AquaRanger 5 | 2 pumps; 2 | NA | |
| | | | 80x.253.V92 | | check valves; 1 electrical panel | | |
| NAS II - WWTP inventory | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION | MANUFACTURER | MODEL NO. | REMARKS | CLEANING FREQUENCY |
| NAS I | 402 | Pre-treatment | NA | NA | Inlet channel cleaning and sludge disposal + 5 Bins solid sludge disposal | 1 time per year |
| NAS II | 402 | EQ pit pumps | Flygt | CP3085MT | 3 pumps; 3 | 1 time per year |
| | | | | check valves; 3 gate valves | |
| NAS II | 402 | Equalization Basin | Flygt | SR-4640 | tank with 2 mixers | 1 time per year |
| NAS II | 402 | AST Tank | Flygt | NP 3085.160 | 1 sludge recycle pump | NA |
| NAS II | 402 | AST Tank | Flygt | SR-4640 | 2 mixers | NA |
| NAS II | 402 | MBR Tank | NA | NA | Tank | 1 time per year |
| NAS II | 402 | MBR Tank | Sulzer | XFP100C-CB1.4-PE22/4-D14*10 | 2 pumps; 1 electrical panel | NA |
| NAS II | 402 | MBR Tank | Sulzer | XRW 3031 PA29/6-EC-10-BO | 2 mixer; 1 electrical panel | NA |
| NAS II | 402 | UV System | Prominent | 2 Dulcodes 4 x 350 LP | 1 UV disinfection electrical panel, 8 UV lamps | NA |
| NAS II | 402 | 1 Dry beds | NA | NA | NA | 3 times per year |
| NAS II - WWTP tools inventory | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION | MANUFACTURER | MODEL NO. | Asset | CALIBRATION FREQUENCY |
| NAS II | 402 | Influent channel | Endress+Hauser | Prosonic flow 91 | 1 flow meter | 1 time per year |
| NAS II | 402 | Equalization Tank | Endress+Hauser | controllers level transmitter prosonic FMU 860 | 1 level transmitter | |
| NAS II | 402 | MBR Plant | Endress+Hauser | controller probes CM444-13R1/0 | 1 pH sensor; 1 suspended solid sensor; 1 oxygen sensor; 1 Redox sensor |
| | | | 2 controllers level transmitter RIA46-13L9/0 | 1 level transmitter MBR tank ; 1 level transmitter permeate tank |
| | | | PMC51-JT20/295 | 2 pressure meter blower; 1 pressure meter permeate pump |
| | | | 6BABL1-7J27/115 | 2 flow transmitters blower |
| | | | 10L1Z-16C0/101 | 1 flow meter permeate pump; 1 flow meter backwash pump |
| NAS II | 402 | AST Tank | Hach Lange | SC1000 Universal Controller | 1 pH sensor; 1 oxygen sensor; 1 Redox sensor |
| NAS II | 402 | Effluent Channel | Hach Lange | SC200 Universal Controller | 1 pH sensor; 1 suspended solid sensor; 1 conducibility sensor; 1 Chlorine sensor |
| | | Endress+Hauser | Promag 400 | 1 flow meter |
Irrigation Systems - NAS I
| ATTACHMENT J-1604000-03 | | | | | |
| WASTEWATER SYSTEMS DESCRIPTION AND INVENTORY | | | | | |
| (*) Reference Section C, Annex 0200000 Management and Administration, Spec Item 2.6.2 Dissemination of Information | | | | | |
| Irrigation Plant Inventory | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION (*) | Asset Name / Manufacturer | REMARKS | PM Frequency |
| NAS I | TDB | Irrigation tank | Tank / NA | NA | 3 times per year |
| NAS I | TDB | Irrigation tank | FM-1, FM-2 / Hach lange | 2 flow meters | 1 time per year (calibration) |
| Irrigation System Inventory | | | | | | |
| SITE | Zone / Description (*) | Delivery Point | Area (m2) | Delivery point details | Motorized Valve Code | PM frequency |
| NAS I | CP4 / Manhole | 16000 | manholes including: valves, water meter, filter, programming irrigation controller, irrigation zone controller valves, type connection, piping, motorized valves, control wire to zone controller, and all component not specified | MV 4.1 | Daily |
| Tank cleaning, transport and disposal of waste produced in compliance with environmental regulations. | | | | | |
| The Contractor shall perform calibration to ensure proper operation, to minimize breakdowns, and to maximize useful life. | | | | | |
| The tools need maintenance by qualified and certified personnel in order to carry out proper functioning and/or calibration checks of the equipment. |
| Instrument calibration, instrument calibration certification and measurement certification of the instrument and related reports are required as per manufacturer |
Irrigation Systems - NAS II
| ATTACHMENT J-1604000-03 |
| WASTEWATER SYSTEMS DESCRIPTION AND INVENTORY |
| (*) Reference Section C, Annex 0200000 Management and Administration, Spec Item 2.6.2 Dissemination of Information |
| Irrigation Plant Inventory | | | | | | |
| SITE | BLDG NO | FACILITY DESCRIPTION (*) | Asset name / Manufacturer | REMARKS | PM frequency | |
| NAS II | TDB | Irrigation tan | Tank / NA | NA | 3 times per year | |
| NAS II | TDB | Irrigation tan | FM-1, FM-2 / Hach Lange | 2 flow meters | 1 time per year (calibration) | |
| Irrigation system inventory | | | | | | |
| SITE | Zone / Description | Delivery Point | Area Irrigated (m2) | Delivery Point Details | Motorized Valve Code | PM frequency |
| NAS II | N2C-104 | CP1 | 3609 | manholes including: valves, water meter, filter, programming irrigation controller, irrigation zone controller valves, type connection, piping, motorized valves, control wire to zone controller, and all component not specified | MV.1.1 | Daily |
| N2C-106 | CP5 | 5695 | | MV 5.1 | |
| N2C-101 / New Entry Control Point | CP6 | 6882 | | MV 6.1 | |
| N2C-105 / New Entry Control Point | CP7 | 1652 | | MV 7.1 | |
| NA / New Entry Control Point | CP8 | 5470 | | MV 8.1 | |
| Tank cleaning, transport and disposal of waste produced in compliance with environmental regulations. | | | | | | |
| The Contractor shall perform calibration to ensure proper operation, to minimize breakdowns, and to maximize useful life. | | | | | | |
| The tools need maintenance by qualified and certified personnel in order to carry out proper functioning and/or calibration checks of the equipment. |
| Instrument calibration, instrument calibration certification and measurement certification of the instrument and related reports are required as per manufacturer |