J-1502000-9 STI 6th AST Annual.pdf

PDF 63 KB Posted

Attached to
AST/UST/Cathodic Protection Maintenance and Repair
Solicitation number
N40085-20-R-3006
Issued by

About this file

This document contains an aboveground storage tank inspection form and details of a related federal contract opportunity. The inspection form provides a checklist for annually inspecting storage tanks and includes items such as verifying strainers and filters are clean, insulation is free of moisture, tank valves are free of leaks, and release detection is being performed and documented.

The federal contract opportunity is a solicitation from the Naval Facilities Engineering Command to provide all materials, services, labor, equipment, transportation and management to test, calibrate, adjust and repair cathodic protection, automatic tank gauging and fuel management systems on aboveground and underground tanks, piers and quay walls at the Naval Submarine Base New London in Groton, Connecticut. The work includes testing and repair of associated equipment.

View the file

Other files

File Type Posted
N4008520R3006 002.pdf PDF
J-1502000-10 UNDERGRD STORAGE TANK INSP FORM MONTHLY-ANNUAL.pdf PDF
Amendment 1_site_visit.pdf PDF
J-150200-12 ELINS cathodic 2020.xls XLS spreadsheet
J-0200000-09 Charc Meter Reading.xlsx XLSX spreadsheet
1502000 F Facility Investment CATHODIC.pdf PDF
J-0200000-08 Specification Information.xlsx XLSX spreadsheet
20R3006_Cathodic Protection.pdf PDF
J-0200000-07 Asset Information.xlsx XLSX spreadsheet
J-0200000-11 SPCC Plan.pdf PDF
J-020000-05A Quality Inspection and Surveillance report.xlsx XLSX spreadsheet
1502000 C Facility Investment CATHODIC.pdf PDF
0200000 F Management and Administration v2.8.pdf PDF
J-1502000-06 Service Order Summary Report.xlsx XLSX spreadsheet
J-020000-05B On site Labor Summary Report (1).xlsx XLSX spreadsheet
0200000 C Management and Administration v2.9.pdf PDF
J-1502000-05 CATHODIC INVENTORY.xlsx XLSX spreadsheet
1502000 J Facility Investment CATHODIC.pdf PDF
0100000 C General Information Cathodic Protection.pdf PDF
J-1502000-03 BASE MAP 2019.pdf PDF
J-1502000-08 ABOVEGROUND STORAGE TANK INSP FORM MONTHLY.pdf PDF
J-0200000-04 Invoice Form.pdf PDF
NEPA_AST_UST_Cathodic2020_signed.pdf PDF
J-1502000-07 Maintenance Summary Report - Copy.xlsx XLSX spreadsheet
J-0200000-06 - Ser Provider Info.xlsx XLSX spreadsheet
1502000 FAP Facility Investment CATHODIC.pdf PDF
0200000 J Management and Administration v2.6.pdf PDF
J-1502000-10 STI 6th AST Monthly.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABOVEGROUND STORAGE TANK INSPECTION FORM ‐ ANNUAL

Inspector:

Tank Location: Date and Time:

NO N/A COMMENTS

Are strainers and filters clean and in good condition?

Insulation free of noticeable areas of moisture?

Solenoid valve Fire valve

Is the emergency vent in good working condition and functional as required by manufacturer? Consult manufacturer's requirement. Verify components are moving freely (including long‐bolt manways).

Check valve Gate valve Pressure regulator valve

Shear valve

Expansion relief valve

Anti‐siphon valve

Normal vent on tanks storing gasoline equipped with pressure / vacuum vent?

Are all valves free of leaks, corrosion, and other damage? Follow the manufacturer's instructions for regular maintenance of these items. Check the following and verify functionality as applicable:

Is interstitial leak detection equipment functioning and in good condition?

Are windows on sight gauges clear? Are wire connections intact? If equipment had a "test" function, does it activate to confirm activation?

Are flame arrestors free of corrosion and are air passages free of blockage?

Additional Information:

Tank / Piping Release Detection

Is release detection being performed and documented?

Other Equipment

Has the cathodic protection system on the tank been tested as required by the designing engineer?

If "NO" is marked for any item above, immediate corrective action may be required.

Is inventory control being performed and documented if required?

Are electrical wiring and boxes in good condition?

Free of visible signs of coating failure?

Free of missing insulation? Insulation free of visible signs of damage?

Insulation adequately protected from water intrusion?

Insulated Tanks

Insulation free of mold?

Is the grounding strap between the tank and foundation / supports in good condition?

Tank Equipment Normal and emergency vents free of obstructions?

Are all labels and tags intact and legible?

Tank shell, Heads, and Roof Free of visible signs of coating failure?

Free of standing water on roof?

Free of noticeable distortions, buckling, denting, or bulging?

Tank Manways, Piping, and Equipment Flanged connection bolts tight and fully engaged with no sign of wear or corrosion?

Tank ID #:

YES

Tank supports in satisfactory condition?

Is water able to drain away from tank if tank is resting on a foundation or on the ground?

Tank Foundation and Supports Free of tank settlement or foundation washout?

Concrete pad or ring wall free of cracking and spalling?