FIRE SUPPRESSION TANK FIRE ALARM AS-BUILT SHOP DRAWINGS.pdf
PDF 1 MB Posted
- Attached to
- Tinker AFB MAC BOA - WWYK240176 - Replace Industrial Waste Lift Stations 6N & 6S, B62501
- Solicitation number
- FA813726R0043
About this file
These are As-Built drawings for fire alarm system installations at Tinker Air Force Base, Oklahoma, prepared by Luckinbill Inc. The documents detail system designs for two distinct projects: one covering Buildings 2119 and 2123 for suppression tank and pump monitoring, and another for Building 3202 adding supervisory tank level low monitoring to an existing fire alarm control panel.
The Buildings 2119 and 2123 project specifies installation of a complete fire alarm system with Monaco M2-MAAP+ control panel, 32 addressable monitor modules (Model 729-142-00), one addressable smoke detector (Model 723-353-00), and a Ditek lighting arrestor (Model DTK-2MHLP24BWB). The system monitors four pumps in each building with individual status tracking for pump running, failed to start, A/C failure, trouble, and switch off conditions, plus tank level low and chlorine detector inputs. All devices and circuits comply with NFPA 72 requirements and NFPA 2010 guidelines. Wiring specifications include 18/2 AWG twisted solid wire for signaling line circuits and 18/2 AWG twisted stranded wire for data analog signals. The system transmits alarms and supervisory signals to a monitoring station and includes battery backup calculations and voltage drop analysis. Building 3202 adds a single monitor module for tank level supervision to the existing Monaco fire alarm control panel. Both projects require conduit installation, junction boxes, surge suppressors, and new tank level sensor controllers to integrate with existing building infrastructure.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JLA
2/11/14
AS BUILTS
XXX
NTS
FA1
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
Lu ck in bi ll In c.
W es t C en te nn ia l B lv d E dm on d, O
K
P H
#4
-3
-6
A la rm
L ic
Drawn By
Date
Revision
Revision Date
Scale
Sheet Number
Tinker AFB, OK Suppression Tank and Pumps
Buildings 2119 and 2123SCOPE OF WORK Provide and install a complete fire alarm system as specified here in and according to contract documents. Provide monitoring of pump controller status and tank level.
DRAWING SHEET INDEX
FA1 COVERSHEET,NOTES, SCOPE OF WORK, ALARM MATRIX
FA1.1 ALARM MATRIX CONTINUED
FA2 FIRE ALARM PLAN BLDG 2119, LEGEND
FA2.1 FIRE ALARM PLAN BLDG 2123
FA3 BATTERY CALCULATIONS, VOLTAGE DROPS, WIRING RISER
ALARM MATRIX
Pump 4 bldg 2123 pump running M1-13 NON-LATCHING Pump 4 bldg 2123 pump failed to start M1-14 NON-LATCHING Pump 4 bldg 2123 pump A/C failure M1-15 NON-LATCHING
Pump 4 bldg 2123 pump trouble M1-16 NON-LATCHING Pump 4 bldg 2123 pump switch off M1-17 NON-LATCHING Pump 3 bldg 2123 pump running M1-18 NON-LATCHING
Pump 3 bldg 2123 pump failed to start M1-19 NON-LATCHING Pump 3 bldg 2123 pump A/C failure M1-20 NON-LATCHING
Pump 3 bldg 2123 pump trouble M1-21 NON-LATCHING Pump 3 bldg 2123 pump switch off M1-22 NON-LATCHING Pump 2 bldg 2123 pump running M1-23 NON-LATCHING
Pump 2 bldg 2123 pump failed to start M1-24 NON-LATCHING Pump 2 bldg 2123 pump A/C failure M1-25 NON-LATCHING
Pump 2 bldg 2123 pump trouble M1-26 NON-LATCHING Pump 2 bldg 2123 pump switch off M1-27 NON-LATCHING Pump 1 bldg 2123 pump running M1-28 NON-LATCHING
Pump 1 bldg 2123 pump failed to start M1-29 NON-LATCHING Pump 1 bldg 2123 pump A/C failure M1-30 NON-LATCHING
Pump 1 bldg 2123 pump trouble M1-31 NON-LATCHING Pump 1 bldg 2123 pump switch off M1-32 NON-LATCHING
ACTIV
ATE S
YSTEM LE
VEL A
LA
RM A
T P
ANEL
INPUTS OUTPUTS
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
ACTIV
ATE FIR
E A
LA
RM N
OTIFIC
ATIO
N C
IR
CUITS
TRANSMIT A
LA
RM TO M
ONITORIN
G S
TATIO
N
LO
G A
LA
RM E
VENT IN
S
YSTEM H
IS
TORY B
UFFER
ACTIV
ATE E
XTERIO
R H
ORN/S
TROBE
ACTIV
ATE FIR
E A
LA
RM P
ANEL A
LA
RM LE
D
ALARM
ACTIV
ATE S
YSTEM S
UPERVIS
ORY
LO
G E
VENT IN
S
YSTEM H
IS
TORY B
UFFER
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
TRANSMIT S
UPERVIS
ORY TO M
ONITORIN
G S
TATIO
N
SUPERVISORY
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
UPERVIS
ORY LE
D
TROUBLE
ACTIV
ATE FIR
E A
LA
RM P
ANEL T
ROUBLE
LE
D
ACTIV
ATE S
YSTEM TROUBLE
TRANSMIT TROUBLE
TO M
ONITORIN
G S
TATIO
N
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
SILE
NCE N
OTIFIC
ATIO
N C
IR
CUITS
SILE
NCE FIR
E A
LA
RM P
ANEL S
OUNDER
RESTORE FIR
E P
ANEL T
O N
ORMAL C
ONDITIO
N
MISC.
COMMENTS
2/11/14
XXX
XXX
NTS
FA1.1
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
Lu ck in bi ll In c.
W es t C en te nn ia l B lv d E dm on d, O
K
P H
#4
-3
-6
A la rm
L ic
Drawn By
Date
Revision
Revision Date
Scale
Sheet Number
Tinker AFB, OK Suppression Tank and Pumps
Buildings 2119 and 2123
ALARM MATRIX
Pump 1 bldg 2119 pump running M1-03 NON-LATCHING Pump 1 bldg 2119 pump failed to start M1-04 NON-LATCHING Pump 1 bldg 2119 pump A/C failure M1-05 NON-LATCHING
Pump 1 bldg 2119 pump trouble M1-06 NON-LATCHING Pump 1 bldg 2119 pump switch off M1-07 NON-LATCHING Pump 2 bldg 2119 pump running M1-08 NON-LATCHING
Pump 2 bldg 2119 pump failed to start M1-09 NON-LATCHING Pump 2 bldg 2119 pump A/C failure M1-10 NON-LATCHING
Pump 2 bldg 2119 pump trouble M1-11 NON-LATCHING Pump 2 bldg 2119 pump switch off M1-12 NON-LATCHING
Smoke Detector S1-01 Tank Level Low M1-02 NON-LATCHING
Chlorine Detector M1-01 NON-LATCHING Acknowlegde
Silence Reset Drill
Low Battery FACP A/C Failure
M/ACC COMM FAIL
MAINTENANCE ALERT
SYSTEM TROUBLE
ACTIV
ATE S
YSTEM LE
VEL A
LA
RM A
T P
ANEL
INPUTS OUTPUTS
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
ACTIV
ATE FIR
E A
LA
RM N
OTIFIC
ATIO
N C
IR
CUITS
TRANSMIT A
LA
RM TO M
ONITORIN
G S
TATIO
N
LO
G A
LA
RM E
VENT IN
S
YSTEM H
IS
TORY B
UFFER
ACTIV
ATE E
XTERIO
R H
ORN/S
TROBE
ACTIV
ATE FIR
E A
LA
RM P
ANEL A
LA
RM LE
D
ALARM
ACTIV
ATE S
YSTEM S
UPERVIS
ORY
LO
G E
VENT IN
S
YSTEM H
IS
TORY B
UFFER
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
TRANSMIT S
UPERVIS
ORY TO M
ONITORIN
G S
TATIO
N
SUPERVISORY
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
UPERVIS
ORY LE
D
TROUBLE
ACTIV
ATE FIR
E A
LA
RM P
ANEL T
ROUBLE
LE
D
ACTIV
ATE S
YSTEM TROUBLE
TRANSMIT TROUBLE
TO M
ONITORIN
G S
TATIO
N
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
SILE
NCE N
OTIFIC
ATIO
N C
IR
CUITS
SILE
NCE FIR
E A
LA
RM P
ANEL S
OUNDER
RESTORE FIR
E P
ANEL T
O N
ORMAL C
ONDITIO
N
M1-13 M1-14
M1-15 M1-16
M1-18 M1-19
M1-20 M1-21
M1-23 M1-24
M1-25 M1-26
M1-28 M1-29
M1-30 M1-31M1-17 M1-22 M1-27 M1-32
As Builts
2/17/2015
3/8"=1'
FA2.1
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
Lu ck in bi ll In c.
W es t C en te nn ia l B lv d E dm on d, O
K
P H
#4
-3
-6
A la rm
L ic
Drawn By
Date
Revision
Revision Date
Scale
Sheet Number
2/17/2015
N
PUMPS #4 & #3
PUMPS #2 & #1
PUMP CONTROLLERS #4 & #3
PUMP CONTROLLERS #2 & #1
NEW 1" PIPE FROM BLDG 2119 FOR FIRE ALARM WIRE
MONITOR MODULES
TO BE MOUNTED TO OUTSIDE OF PUMP
CONTROLLERS
NEW 3/4" CONDUIT FOR FIRE
ALARM WIRE
NEW J BOX
NEW NEMA BOX FOR
SURGE SUPPRESSOR
NEW J BOXNEW J BOX
NEW J BOX
NEW J BOX
A2
A2
A2
A2A2
A2 A2 A1
A1
M1-03 M1-04
M1-05 M1-06 M1-07
M1-08 M1-09
M1-10 M1-11 M1-12
M1-01M1-02
A
AS BUILTS
XXX
1/2"=1'
FA2
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
Lu ck in bi ll In c.
W es t C en te nn ia l B lv d E dm on d, O
K
P H
#4
-3
-6
A la rm
L ic
Drawn By
Date
Revision
Revision Date
Scale
Sheet Number
2/17/2015
N
PUMP #2
PUMP #1
PUMP CONTROLLER #2
PUMP CONTROLLER #1
MONITOR MODULES TO BE MOUNTED
TO OUTSIDE OF PUMP CONTROLLERS
EXISTING CHLORINE
DETECTOR SYSTEM
EXISTING ANTENNA
FOR FIRE ALARM SYSTEM
NEW 1" PVC PIPE FOR TANK LEVEL
SENSOR WIRE TO TANK 2120
LEGEND
MODEL # DESCRIPTION MANUFACTURE SYMBOL QUANTITY
M2-MAAP+ FIRE ALARM CONTROL PANEL MONACO 1
729-142-00 ADDRESSABLE MONITOR MODULE MONACO 32
723-353-00 ADDRESSABLE SMOKE DETECTOR MONACO 1
DTK-2MHLP24BWB LIGHTING ARRESTOR DITEK 1
NEW MONACO FIRE ALARM CONTROL PANEL
NEW TANK LEVEL
SENSOR CONTROLLER
NEW 1" PVC PIPE FOR FIRE ALARM WIRE TO
BLDG 2123
BATTERY BACK UP BOX
NEW 3/4" CONDUIT FOR FIRE
ALARM WIRE
NEW 3/4" CONDUIT FOR FIRE
ALARM WIRE
EXISTING 1" CONDUIT
EXISTING J BOX
EXISTING J BOX
EXISTING 1/2" PIPE
WITH ANTENNA WIRE
NEW 3/4" CONDUIT FOR TANK LEVEL
SENSOR WIRE
NEW J BOX
NEW J BOX
NEW J BOX
NEW NEMA BOX FOR
SURGE SUPPRESSOR
NEW J BOX
EXISTING J BOX
NEW J BOXES
MOUNTED TO OUTSIDE
OF PUMP CONTROLLER FOR
MONITOR MODULES
NEW J BOXES
MOUNTED TO OUTSIDE
OF PUMP CONTROLLER FOR
MONITOR MODULES
FIRE ALARM WIRE RUN
BETWEEN DEVICES
IN PUMP CONROLLER PANELS
WIRE CHART
CIRCUIT TYPE DESCRIPTION WIRE SIZE TYPE SYMBOL
SLC SIGNALING LINE CIRCUIT 18/2 AWG TWISTED SOLID A
DAS DATA ANALOG SIGNAL 18/2 AWG TWISTED STRANDED B
X2
NUMBER OF WIRES
TYPE OF CIRCUIT
WIRE TAG
A2
B1
A1
B1
A1
A1
A1
A1
A1A2 A1
M1-01 M1-02 M1-03M1-08 M1-12M1-11M1-10
M1-16M1-15M1-14 M1-24M1-23M1-22
M1-32 M1-31 M1-30
M1-06M1-05M1-04
M1-18 M1-19 M1-20
M1-26M1-27M1-28
M1-09
M1-13 M1-21
M1-29
M1-07
M1-17
M1-25
S1-01
XMT
PANEL
RESET
ALARM
ALM TBL
AC POWER
RCV CD XMTR
DISC
ENT0CE
8 9
5 6
FAULTBATTERY
1 2 3
16 17 18 22 23 2414 15
ENGINE RUNNING SWITCH OFF
PUMPCONTROLLER TROUBLE
115 VAC SUPPLY
NC C NO NC C NO
JLA
AS BUILTS
XXX
NTS
FA3
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
Lu ck in bi ll In c.
W es t C en te nn ia l B lv d E dm on d, O
K
P H
#4
-3
-6
A la rm
L ic
Drawn By
Date
Revision
Revision Date
Scale
2/17/2015
120VAC FROM LOAD CENTER
MOUNTED NEXT TO FACP
CIRCUIT #1
J BOX MOUNTED TO FACP
CABINET FOR POWER CONNECTION
120VAC SURGE SUPPRESSOR
TO BATTERY
BACK UP
ATTENNA CONNECTION
PUMP CONTROLLER 12VDC OFF-NORMAL
BELL NOTIFICATION CIRCUIT
3/14/14
XXX
XXX
NTS
FA1
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
L u c k i n b i l l
I n c
W es t C en te nn ia l B lv d
E dm on d, O K
P
H #4
-3
-6
A la rm L ic
Drawn By
Date
Revision
Revision Date
Scale
Tinker AFB, OK Building 3202
SCOPE OF WORK
ADD SUPERVISORY TANK LEVEL LOW
MONITORING POINT TO EXISTING FACP
DRAWING SHEET INDEX
FA1 COVERSHEET,NOTES, SCOPE OF WORK
FA2 FIRE ALARM PLAN, LEGEND
ALARM MATRIX
TANK LEVEL LOW
ACTIV
ATE S
YSTEM LE
VEL A
LA
RM A
T P
ANEL
INPUTS OUTPUTS
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
ACTIV
ATE FIR
E A
LA
RM N
OTIFIC
ATIO
N C
IR
CUITS
TRANSMIT A
LA
RM TO M
ONITORIN
G S
TATIO
N
LO
G A
LA
RM E
VENT IN
S
YSTEM H
IS
TORY B
UFFER
ACTIV
ATE E
XTERIO
R H
ORN/S
TROBE
ACTIV
ATE FIR
E A
LA
RM P
ANEL A
LA
RM LE
D
ALARM
ACTIV
ATE S
YSTEM S
UPERVIS
ORY
LO
G E
VENT IN
S
YSTEM H
IS
TORY B
UFFER
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
TRANSMIT S
UPERVIS
ORY TO M
ONITORIN
G S
TATIO
N
SUPERVISORY
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
UPERVIS
ORY LE
D
TROUBLE
ACTIV
ATE FIR
E A
LA
RM P
ANEL T
ROUBLE
LE
D
ACTIV
ATE S
YSTEM TROUBLE
TRANSMIT TROUBLE
TO M
ONITORIN
G S
TATIO
N
ACTIV
ATE FIR
E A
LA
RM P
ANEL S
OUNDER
SILE
NCE N
OTIFIC
ATIO
N C
IR
CUITS
SILE
NCE FIR
E A
LA
RM P
ANEL S
OUNDER
RESTORE FIR
E P
ANEL T
O N
ORMAL C
ONDITIO
N
XXX
XXX
1/4"=1'
FA2
Ti nk er A
FB
O kl ah om a
S ys te m
S up pl ie r & In st al le r
Lu ck in bi ll In c.
W es t C en te nn ia l B lv d E dm on d, O
K
P H
#4
-3
-6
A la rm
L ic
Drawn By
Date
Revision
Revision Date
Scale
Sheet Number
3/14/14
N
EXISTING MONACO ANTENNA
EXISTING MONACO FIRE ALARM CONTROL PANEL
NEW 1" PVC CONDUIT TO TANK 3203
LEGEND
MODEL # DESCRIPTION MANUFACTURE SYMBOL QUANTITY
EXISTING FIRE ALARM CONTROL PANEL MONACO 1
729-142-00 ADDRESSABLE MONITOR MODULE MONACO 1
EXISTING MONACO ANTENNA MONACO 1
DTK-2MHLP24BWB LIGHTING ARRESTOR DITEK 1
NEW NEMA BOX FOR
SURGE SUPPRESSOR
NEW J BOX
NEW TANK LEVEL SENSOR CONTROLLER
NEW 3/4" CONDUIT FOR
LEVEL SENSOR WIRE
NEW 3/4" CONDUIT FOR
FIRE ALARM WIRE
| FA1asbuilts |
| pump fire alarm asbuilts-FA1.1 |
| pump fire alarm asbuilts-FA2.1 |
| pump fire alarm asbuilts-FA2 |
| pump fire alarm asbuilts-FA3 |
| Bldg 3202-FA2 4th ASBUILT |
File details come from the government source that posted it. Updated .