This is a Hood Fire Suppression System inspection report for Building 954 Flight Line at Luke Air Force Base in Litchfield Park, AZ, dated April 18, 2024. The report documents the inspection of an Ansul R-102 wet fire suppression system with two 3-gallon cylinders (one main and one slave), installed in 2018. The system includes 4 fusible links (450ML), covers mixers and flat-top fryers, and has passed all required inspection points according to NFPA 17, 17A, and 96 standards.

The related contract opportunity (FA488725Q0006) is a Request for Quote from the Department of the Air Force Air Education and Training Command for Kitchen Fire Suppression Inspection and Maintenance services at Luke AFB. The solicitation seeks to establish a Firm-Fixed Price Service contract, with responses due by January 24, 2025, at 3 PM MST. Questions must be submitted by January 5, 2025, and site visit requests must be submitted by January 5, 2025, at 0800 MST.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Pass

Light

Pass

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 954 Flight Line

Address LAFB

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Location Contact Peter Location Phone Number

Monitoring Company Emergency Services Monitoring Company Number

Date 4/18/20248

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password

Location of System/Cylinder(s) Mechanical Room Inspection Type 6-Month

Manufacturer Ansul #3 Cylinder Slave Size

Serial Number S4077013 Size of Activation Cartridge Double Tank

System Type Wet #1 Cylinder Size 3 Gallon Model Number R-102 #2 Cylinder Slave Size 3 Gallon

Last Recharge Date N/A Number of Fusible Links 4 Best Time to Service 7:30am Type of Fusible Links 450ML

Original System Install Date 2018 Date of Activation Cartridge Oct-17 Cylinder 12 Year Hydro Test Date 2030 Location of Shut Off/Valves Behind Appliances

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Mixers Flat Top FryerFlat Top

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass

Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A)

Replace System Cover(s)

System Operational & Seals In Place

Slave Cylinder Operational

If System Has Been Discharged, Report Same N/A

Is Pressure Gauge In Proper Range (If Gauged) N/A

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass

Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass

Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date 2030

12 Year Regulator Test Date (Ansul) 2030

1/4' Gas Valve Hose Assembly Test Date 2030

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s)

Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed

Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter

Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown

Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass

Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Pass

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning

Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood

Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass

Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Location Phone Number

Notes/Deficiencies

Monitoring Company Monitoring Company Number

Account Number Password

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 954 Flight Line

Address LAFB

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Date 4/18/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020