Bldg 954 Flight Line.pdf
PDF 116 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System inspection report for Building 954 Flight Line at Luke Air Force Base in Litchfield Park, AZ, dated April 18, 2024. The report documents the inspection of an Ansul R-102 wet fire suppression system with two 3-gallon cylinders (one main and one slave), installed in 2018. The system includes 4 fusible links (450ML), covers mixers and flat-top fryers, and has passed all required inspection points according to NFPA 17, 17A, and 96 standards.
The related contract opportunity (FA488725Q0006) is a Request for Quote from the Department of the Air Force Air Education and Training Command for Kitchen Fire Suppression Inspection and Maintenance services at Luke AFB. The solicitation seeks to establish a Firm-Fixed Price Service contract, with responses due by January 24, 2025, at 3 PM MST. Questions must be submitted by January 5, 2025, and site visit requests must be submitted by January 5, 2025, at 0800 MST.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Light
Pass
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names Bldg 954 Flight Line
Address LAFB
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Location Contact Peter Location Phone Number
Monitoring Company Emergency Services Monitoring Company Number
Date 4/18/20248
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password
Location of System/Cylinder(s) Mechanical Room Inspection Type 6-Month
Manufacturer Ansul #3 Cylinder Slave Size
Serial Number S4077013 Size of Activation Cartridge Double Tank
System Type Wet #1 Cylinder Size 3 Gallon Model Number R-102 #2 Cylinder Slave Size 3 Gallon
Last Recharge Date N/A Number of Fusible Links 4 Best Time to Service 7:30am Type of Fusible Links 450ML
Original System Install Date 2018 Date of Activation Cartridge Oct-17 Cylinder 12 Year Hydro Test Date 2030 Location of Shut Off/Valves Behind Appliances
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Mixers Flat Top FryerFlat Top
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass
Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A)
Replace System Cover(s)
System Operational & Seals In Place
Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A
Is Pressure Gauge In Proper Range (If Gauged) N/A
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass
Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass
Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2030
12 Year Regulator Test Date (Ansul) 2030
1/4' Gas Valve Hose Assembly Test Date 2030
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s)
Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed
Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter
Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown
Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass
Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning
Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood
Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass
Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Location Phone Number
Notes/Deficiencies
Monitoring Company Monitoring Company Number
Account Number Password
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names Bldg 954 Flight Line
Address LAFB
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Date 4/18/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020