BLDG 915.pdf
PDF 146 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a hood fire suppression system inspection report for Building 915 at Luke Air Force Base in Litchfield Park, AZ, completed by A P Fire Protection on April 11, 2024. The report documents the inspection of a Pyro-Chem dry chemical fire suppression system with a 35 lb ABC cylinder installed in 2016, which passed all required tests per NFPA 17, 17A, and 96 standards.
The inspection details include verification of proper nozzle coverage, fusible links, remote pull stations, pressure gauges, and system operation. The system is monitored by the Emergency Communication Center (623-856-6641) and includes local bell notification. Key equipment specifications include a 16-gram activation cartridge, two 280ML fusible links, and a hydro test date of 2028. The report is related to solicitation FA488725Q0006, which seeks kitchen fire suppression inspection and maintenance services at Luke AFB, with responses due January 24, 2025 at 3 PM MST.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results
Pass
Pass
Pass
N/A
N/A
Pass
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
N/A
Pass
N/A
Pass
Pass
N/A
Pass
Pass
Pass
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 915 LUKE AIR FORCE BASE
Address BLDG 915
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641
Date 4/11/20248
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password
Location of System/Cylinder(s) Left Outside of Connex Inspection Type 6-Month
Manufacturer Pyro-Chem #3 Cylinder Slave Size
Serial Number Size of Activation Cartridge 16 Gram
System Type Dry #1 Cylinder Size #35 ABC Model Number PCI 35 ABC #2 Cylinder Slave Size
Last Recharge Date N/A Number of Fusible Links 2 Best Time to Service 10:00 Type of Fusible Links 280ML
Original System Install Date 2016 Date of Activation Cartridge 2016 Cylinder 12 Year Hydro Test Date 2028 Location of Shut Off/Valves
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Chemical Storage Container
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass
Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A)
Replace System Cover(s)
System Operational & Seals In Place
Slave Cylinder Operational
If System Has Been Discharged, Report Same Pass
Is Pressure Gauge In Proper Range (If Gauged) Pass
Check Cartridge Weight (If Applicable) 2028
Is System Installed Accordance With Manufacturer UL Listing Pass
Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass
Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date N/A
12 Year Regulator Test Date (Ansul) N/A
1/4' Gas Valve Hose Assembly Test Date Pass
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s)
Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed
Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter
Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown
Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass
Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Local Bell Only
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning
Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood
Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) N/A
Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
Mobile User
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Darryel Abraham Location Phone Number 916-893-8045
** Notify Emergency Communication Center at 623-856-6641 prior to test of the system and after test has been accomplished. **
Note: Local Bell Only
Notes/Deficiencies
Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 915 LUKE AIR FORCE BASE
Address BLDG 915
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Date 4/11/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020