BLDG 915.pdf

PDF 146 KB Posted

Attached to
Kitchen Fire Suppression Inspection & Maintenance
Solicitation number
FA488725Q0006
Issued by

About this file

This is a hood fire suppression system inspection report for Building 915 at Luke Air Force Base in Litchfield Park, AZ, completed by A P Fire Protection on April 11, 2024. The report documents the inspection of a Pyro-Chem dry chemical fire suppression system with a 35 lb ABC cylinder installed in 2016, which passed all required tests per NFPA 17, 17A, and 96 standards.

The inspection details include verification of proper nozzle coverage, fusible links, remote pull stations, pressure gauges, and system operation. The system is monitored by the Emergency Communication Center (623-856-6641) and includes local bell notification. Key equipment specifications include a 16-gram activation cartridge, two 280ML fusible links, and a hydro test date of 2028. The report is related to solicitation FA488725Q0006, which seeks kitchen fire suppression inspection and maintenance services at Luke AFB, with responses due January 24, 2025 at 3 PM MST.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results

Pass

Pass

Pass

N/A

N/A

Pass

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Pass

N/A

Pass

N/A

Pass

Pass

N/A

Pass

Pass

Pass

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 915 LUKE AIR FORCE BASE

Address BLDG 915

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641

Date 4/11/20248

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password

Location of System/Cylinder(s) Left Outside of Connex Inspection Type 6-Month

Manufacturer Pyro-Chem #3 Cylinder Slave Size

Serial Number Size of Activation Cartridge 16 Gram

System Type Dry #1 Cylinder Size #35 ABC Model Number PCI 35 ABC #2 Cylinder Slave Size

Last Recharge Date N/A Number of Fusible Links 2 Best Time to Service 10:00 Type of Fusible Links 280ML

Original System Install Date 2016 Date of Activation Cartridge 2016 Cylinder 12 Year Hydro Test Date 2028 Location of Shut Off/Valves

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Chemical Storage Container

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass

Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A)

Replace System Cover(s)

System Operational & Seals In Place

Slave Cylinder Operational

If System Has Been Discharged, Report Same Pass

Is Pressure Gauge In Proper Range (If Gauged) Pass

Check Cartridge Weight (If Applicable) 2028

Is System Installed Accordance With Manufacturer UL Listing Pass

Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass

Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date N/A

12 Year Regulator Test Date (Ansul) N/A

1/4' Gas Valve Hose Assembly Test Date Pass

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s)

Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed

Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter

Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown

Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass

Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Local Bell Only

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning

Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood

Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) N/A

Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

Mobile User

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Darryel Abraham Location Phone Number 916-893-8045

** Notify Emergency Communication Center at 623-856-6641 prior to test of the system and after test has been accomplished. **

Note: Local Bell Only

Notes/Deficiencies

Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 915 LUKE AIR FORCE BASE

Address BLDG 915

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Date 4/11/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020