BLDG 1143 Youth Center.pdf
PDF 144 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System inspection report for Building 1143 Youth Center at Luke Air Force Base, completed on April 11, 2024, by A P Fire Protection. The inspection covered an Ansul R-102 wet system with a 3-gallon cylinder installed in 2010, servicing a 4-burner stove setup. The system passed all major inspection points including fusible links, nozzle positioning, remote pull stations, gas valve operation, and fire alarm panel connectivity.
The report indicates the system is compliant with NFPA standards 17, 17A, and 96, with key maintenance dates including a January 2022 recharge and future hydro testing due in 2034. One deficiency was noted regarding a ground fault on the fire alarm panel and a missing tamper bar holder requiring replacement. The system is monitored by the Emergency Communication Center (623-856-6641), with Darryel Abraham listed as the location contact.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Light
Pass
Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass
Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s)
Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed
Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter
Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown
Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass
Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning
Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood
Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Operated System From Terminal Link Pass
Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2034
12 Year Regulator Test Date (Ansul) 2034
1/4' Gas Valve Hose Assembly Test Date 2034
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass
Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A)
Replace System Cover(s)
System Operational & Seals In Place
Slave Cylinder Operational
If System Has Been Discharged, Report Same Pass
Is Pressure Gauge In Proper Range (If Gauged) N/A
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass
Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
4 Burner Stove (1F, 2F)
Last Recharge Date 2022 Number of Fusible Links 3 Best Time to Service 11:00 Type of Fusible Links 450ml
Original System Install Date 2010 Date of Activation Cartridge Jan-22 Cylinder 12 Year Hydro Test Date 2034 Location of Shut Off/Valves Behind appliances
Manufacturer Ansul #3 Cylinder Slave Size
Serial Number R100258 Size of Activation Cartridge LT-30-R
System Type Wet #1 Cylinder Size 3 Gallon Model Number R-102 #2 Cylinder Slave Size
Account Number Password
Location of System/Cylinder(s) Kitchen Left of Hood Inspection Type 6-Month
Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641
Date 4/11/20248
C-16 ROC 251919 CR-67 ROC 251920
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 1143 Youth Center LUKE AIR FORCE BASE
Address BLDG 1143
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 1143 Youth Center LUKE AIR FORCE BASE
Address BLDG 1143
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Date 4/11/2024
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Darryel Abraham Location Phone Number 916-893-8045
** Notify Emergency Communication Center at 623-856-6641 prior to test of the system and after test has been accomplished. **
Note: There was a ground fault on the FA panel upon arrival.
There is a missing tamper bar holder that needs to be replaced.
Notes/Deficiencies
Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020