BLDG 1540 Charlies - 2.pdf
PDF 60 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System Report for Building 1540 Charlies #2 at Luke Air Force Base in Litchfield Park, AZ, conducted by A P Fire Protection on May 3, 2024. The inspection was performed on an Ansul R-102 wet system with a 3-gallon cylinder installed in 2017, which includes protection for two fryers and a 4x2 flat top grill.
The report indicates that the system passed most inspection points, including proper nozzle coverage, fusible link testing, gas valve operation, fire alarm panel monitoring, and puff testing. The system uses 450 ML fusible links and an LT-30-R activation cartridge. One notable item is that the accumulation of grease in the hood was rated as "Medium." The system's next required hydro test date is 2029. The system is monitored by the Emergency Communication Center (623-856-6641) and complies with N.F.P.A. 17, 17A, and 96 standards and manufacturer requirements.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass N/A Pass Pass Pass Pass Pass Pass N/A Pass
Medium Pass
Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 1540 Charlies #2 Address Luke Air Force Base
City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster
Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641
Date 5/3/2024
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password Location of System/Cylinder(s) In the back on the wall Inspection Type 6-Month
Manufacturer Ansul #3 Cylinder Slave Size Serial Number S102742 Size of Activation Cartridge LT-30-R
System Type wet #1 Cylinder Size 3 Gallon Model Number R-102 #2 Cylinder Slave Size
Last Recharge Date N/A Number of Fusible Links 2 Best Time to Service 7am Type of Fusible Links 450 ML
Original System Install Date 2017 Date of Activation Cartridge 2017 Cylinder 12 Year Hydro Test Date 2029 Location of Shut Off/Valves Above Ceiling
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Fryer x 2 4x2 Flat top
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A) Replace System Cover(s)
System Operational & Seals In Place Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A Is Pressure Gauge In Proper Range (If Gauged) N/A
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2029 12 Year Regulator Test Date (Ansul) 2029
1/4' Gas Valve Hose Assembly Test Date 2029
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s) Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Darryel Abraham Location Phone Number 916-893-8045
Notes/Deficiencies
Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password
Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 1540 Popeye's & Charlies Address Luke Air Force Base
City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster
Date 5/3/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020
Sheet1