BLDG 1540 Charlies - 2.pdf

PDF 60 KB Posted

Attached to
Kitchen Fire Suppression Inspection & Maintenance
Solicitation number
FA488725Q0006
Issued by

About this file

This is a Hood Fire Suppression System Report for Building 1540 Charlies #2 at Luke Air Force Base in Litchfield Park, AZ, conducted by A P Fire Protection on May 3, 2024. The inspection was performed on an Ansul R-102 wet system with a 3-gallon cylinder installed in 2017, which includes protection for two fryers and a 4x2 flat top grill.

The report indicates that the system passed most inspection points, including proper nozzle coverage, fusible link testing, gas valve operation, fire alarm panel monitoring, and puff testing. The system uses 450 ML fusible links and an LT-30-R activation cartridge. One notable item is that the accumulation of grease in the hood was rated as "Medium." The system's next required hydro test date is 2029. The system is monitored by the Emergency Communication Center (623-856-6641) and complies with N.F.P.A. 17, 17A, and 96 standards and manufacturer requirements.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass N/A Pass Pass Pass Pass Pass Pass N/A Pass

Medium Pass

Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 1540 Charlies #2 Address Luke Air Force Base

City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster

Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641

Date 5/3/2024

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password Location of System/Cylinder(s) In the back on the wall Inspection Type 6-Month

Manufacturer Ansul #3 Cylinder Slave Size Serial Number S102742 Size of Activation Cartridge LT-30-R

System Type wet #1 Cylinder Size 3 Gallon Model Number R-102 #2 Cylinder Slave Size

Last Recharge Date N/A Number of Fusible Links 2 Best Time to Service 7am Type of Fusible Links 450 ML

Original System Install Date 2017 Date of Activation Cartridge 2017 Cylinder 12 Year Hydro Test Date 2029 Location of Shut Off/Valves Above Ceiling

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Fryer x 2 4x2 Flat top

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A) Replace System Cover(s)

System Operational & Seals In Place Slave Cylinder Operational

If System Has Been Discharged, Report Same N/A Is Pressure Gauge In Proper Range (If Gauged) N/A

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date 2029 12 Year Regulator Test Date (Ansul) 2029

1/4' Gas Valve Hose Assembly Test Date 2029

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s) Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Pass

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Darryel Abraham Location Phone Number 916-893-8045

Notes/Deficiencies

Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password

Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 1540 Popeye's & Charlies Address Luke Air Force Base

City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster

Date 5/3/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020

Sheet1

File details come from the government source that posted it. Updated .