BLDG 545 Hensman Dining 2.pdf
PDF 117 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System Report for Building 545 Hensman Dining at Luke Air Force Base in Litchfield Park, AZ, completed by A P Fire Protection on May 2, 2024. The report documents a 6-month inspection of a Buckeye wet-chemical fire suppression system (Model SRM-D) with BFR-10 and BFR-12 cylinders installed in 2014.
The inspection covered all major system components including nozzles, cylinders, fusible links, gas valves, and monitoring connections. Nearly all inspection items passed, with only two notable findings: a "Light" accumulation of grease in the hood and one "N/A" rating for the water mist/water wash system. The system includes 4 fusible links rated at 450ML, a 16-gram activation cartridge (dated September 2021), and is monitored by the Emergency Communication Center. The system's cylinder requires hydrostatic testing by 2026. All fire safety components were verified operational, including proper fuel shutoff, fire alarm panel monitoring, and remote pull stations.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
N/A
Pass
Light
Pass
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 545 Hensman Dining
Address Luke Air Force Base
City, State, Zip Litchfield Park, AZ
Technician Cody Buckmaster
Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641
Date 5/2/20248
C-16 ROC 251919 CR-67 ROC 251920
Account Number Password
Location of System/Cylinder(s) On wall Inspection Type 6-Month
Manufacturer Buckeye #3 Cylinder Slave Size
Serial Number Size of Activation Cartridge 16 gram
System Type Wet #1 Cylinder Size BFR-10 Model Number SRM-D #2 Cylinder Slave Size BFR-12
Last Recharge Date N/A Number of Fusible Links 4 Best Time to Service 8:50am Type of Fusible Links 450ML
Original System Install Date 2014 Date of Activation Cartridge Sep-21 Cylinder 12 Year Hydro Test Date 2026 Location of Shut Off/Valves Behind Appliances
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
Oven
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass
Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A)
Replace System Cover(s)
System Operational & Seals In Place
Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A
Is Pressure Gauge In Proper Range (If Gauged) Pass
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass
Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Operated System From Terminal Link Pass
Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date Pass
12 Year Regulator Test Date (Ansul) Pass
1/4' Gas Valve Hose Assembly Test Date Pass
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s)
Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed
Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter
Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown
Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass
Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning
Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood
Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Portable Fire Extinguisher(s) Properly Serviced
Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass
Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Darryel Abraham Location Phone Number 916-893-8045
Notes/Deficiencies
Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password
Hood Fire Suppression System Report
(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names BLDG 545 Hensman Dining
Address Luke Air Force Base
City, State, Zip Litchfield Park, AZ
Technician 5/2/2024
Date 5/2/2024
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303
Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020