This is a Hood Fire Suppression System inspection report conducted at Building 799 Base Chapel at Luke Air Force Base in Litchfield Park, AZ on April 18, 2024. The inspection was performed by A P Fire Protection (ROC #251919/251920) and covered a Range Guard wet-type fire suppression system installed in April 2002.

The report indicates that the system, which protects a 6-burner stove and oven, passed most inspection points including nozzle coverage, fusible links, system operation, and emergency shutoffs. The system uses a RG2.5 cylinder with a 12-gram activation cartridge installed in September 2023, with hydro testing due in 2028. Only minor issues were noted: "light" accumulation of grease in the hood. The system is monitored by "Alarm Guy" and serviced at 9am, with shutdown controls located behind appliances. The inspection was part of a required 6-month maintenance cycle per NFPA 17, 17A, and 96 standards.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass N/A Pass Pass Pass Pass Pass Pass N/A Pass Light Pass

Portable Fire Extinguisher(s) Properly Serviced Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s) Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Pass

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Operated System From Terminal Link Pass Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date 2028 12 Year Regulator Test Date (Ansul) N/A

1/4' Gas Valve Hose Assembly Test Date N/A

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A) Replace System Cover(s)

System Operational & Seals In Place Slave Cylinder Operational

If System Has Been Discharged, Report Same N/A Is Pressure Gauge In Proper Range (If Gauged) Pass

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

6 Burner Stove Oven

Last Recharge Date 2016 Number of Fusible Links 1 Best Time to Service 9am Type of Fusible Links 450ML

Original System Install Date Apr-02 Date of Activation Cartridge Sep-23 Cylinder 12 Year Hydro Test Date 2028 Location of Shut Off/Valves Behind Appliances

Manufacturer Range Guard #3 Cylinder Slave Size Serial Number Size of Activation Cartridge 12 Gram

System Type Wet #1 Cylinder Size RG2.5 Model Number A+ Control Head #2 Cylinder Slave Size

Account Number Password Location of System/Cylinder(s) Right of Hood Inspection Type 6-Month

Location Contact Peter Location Phone Number Monitoring Company Alarm Guy took care of this Monitoring Company Number

Date 4/18/20248

C-16 ROC 251919 CR-67 ROC 251920

Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 799 Base Chapel Address LAFB

City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 799 Base Chapel Address LAFB

City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster

Date 4/18/2024

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Location Phone Number

Notes/Deficiencies

Monitoring Company Monitoring Company Number Account Number Password

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020