Bldg 799 Base Chapel.pdf
PDF 169 KB Posted
- Solicitation number
- FA488725Q0006
About this file
This is a Hood Fire Suppression System inspection report conducted at Building 799 Base Chapel at Luke Air Force Base in Litchfield Park, AZ on April 18, 2024. The inspection was performed by A P Fire Protection (ROC #251919/251920) and covered a Range Guard wet-type fire suppression system installed in April 2002.
The report indicates that the system, which protects a 6-burner stove and oven, passed most inspection points including nozzle coverage, fusible links, system operation, and emergency shutoffs. The system uses a RG2.5 cylinder with a 12-gram activation cartridge installed in September 2023, with hydro testing due in 2028. Only minor issues were noted: "light" accumulation of grease in the hood. The system is monitored by "Alarm Guy" and serviced at 9am, with shutdown controls located behind appliances. The inspection was part of a required 6-month maintenance cycle per NFPA 17, 17A, and 96 standards.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Results Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass N/A Pass Pass Pass Pass Pass Pass N/A Pass Light Pass
Portable Fire Extinguisher(s) Properly Serviced Certification Tag Place On System & Remote
System Equipped With Water Mist/Water Wash
Check Operation of Gas Valve(s) Pass Proper Nozzle Covers/Caps/Seals In Place Pass
Puff Test Completed Pass Is Suppression System Compliant
Clean Cylinders/Wall Mount Brackets
Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass
Replaced Fusible Link(s) Check Travel of Cable Nut/S-Hooks
All Piping Conduit Securely Bracketed Proper Separation/Fryer & Flames (N.F.P.A. 90A)
Proper Clearance of Flames To Filter Exhaust Fan in Operating Order
When System Activated Did Make-Up Air Shutdown Fuel Shut Off In Position
Wipe Grease Off Nozzles (Surface Cleaning Only) Pass Visually Check All Fusible Links Pass
Did System Report to Fire Alarm Panel/Monitoring Pass
Check Operation of Micro-Switch(s) Pass
Date of The Last Hood/Duct/Plenum Cleaning Accumulation of Grease In Hood
Exhaust Fan Warning Sign On Hood Personnel Instructed In Operation Of System
K-Class Extinguisher(s) Properly Serviced
Operated System From Terminal Link Pass Test for Proper Operation From Remote Pull Station Pass
12 Year Hydro Cylinder Test Date 2028 12 Year Regulator Test Date (Ansul) N/A
1/4' Gas Valve Hose Assembly Test Date N/A
Remote Pull 42"-48" From Floor (N.F.P.A. 17A)
All Appliances Properly Covered With Correct Nozzles Pass Duct and Plenum Covered With Correct Nozzles Pass
Check Positioning/Condition of All Nozzles Pass
Results
Inspect Cylinder/Wall Mount Bracket(s) Pass
Remote Station(s) Have Signage (N.F.P.A. 17A) Replace System Cover(s)
System Operational & Seals In Place Slave Cylinder Operational
If System Has Been Discharged, Report Same N/A Is Pressure Gauge In Proper Range (If Gauged) Pass
Check Cartridge Weight (If Applicable) Pass
Is System Installed Accordance With Manufacturer UL Listing Pass Hood & Duct Penetrations Sealed With Weld or UL Device Pass
Check If Seals Intact, Evidence of Tampering Pass
Item(s) CheckedItem(s) Checked
Duct and Plenum Nozzle Protection (List Model/Type/Position)
Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)
6 Burner Stove Oven
Last Recharge Date 2016 Number of Fusible Links 1 Best Time to Service 9am Type of Fusible Links 450ML
Original System Install Date Apr-02 Date of Activation Cartridge Sep-23 Cylinder 12 Year Hydro Test Date 2028 Location of Shut Off/Valves Behind Appliances
Manufacturer Range Guard #3 Cylinder Slave Size Serial Number Size of Activation Cartridge 12 Gram
System Type Wet #1 Cylinder Size RG2.5 Model Number A+ Control Head #2 Cylinder Slave Size
Account Number Password Location of System/Cylinder(s) Right of Hood Inspection Type 6-Month
Location Contact Peter Location Phone Number Monitoring Company Alarm Guy took care of this Monitoring Company Number
Date 4/18/20248
C-16 ROC 251919 CR-67 ROC 251920
Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names Bldg 799 Base Chapel Address LAFB
City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384
Page 1 of 2 REV 04-2020
Hood Fire Suppression System Report (Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)
Location Names Bldg 799 Base Chapel Address LAFB
City, State, Zip Litchfield Park, AZ Technician Cody Buckmaster
Date 4/18/2024
C-16 ROC 251919 CR-67 ROC 251920
Location Contact Location Phone Number
Notes/Deficiencies
Monitoring Company Monitoring Company Number Account Number Password
A P Fire Protection www.apfireprotection.com
7612 N 71st Ave, Glendale, AZ 85303 Phone: (623) 772-5344 Fax: (623) 772-5384
Page 2 of 2 REV 04-2020