Kitchen Fire Suppression Inspection & Maintenance
Solicitation number
FA488725Q0006
Issued by

About this file

This is a Hood Fire Suppression System inspection report for Building 374 at Luke Air Force Base in Litchfield Park, AZ, completed by A P Fire Protection on April 18, 2024. The report documents a 6-month inspection of a Pyro-Chem dry chemical fire suppression system (Model PCI-25S) installed in 2017, with components including a 16-gram activation cartridge (replaced September 2023) and a single 450ML fusible link. The system's next hydro test is due in 2029.

The inspection tested multiple system components with all items receiving passing marks, including proper nozzle positioning, pressure gauge readings, remote pull station operation, gas valve functionality, and puff testing. The system is not monitored by a third party. The report relates to federal contract opportunity FA488725Q0006, which seeks Kitchen Fire Suppression Inspection & Maintenance services at Luke AFB, with responses due by January 24, 2025 at 3:00 PM MST.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results

Pass

Pass

Pass

Pass

N/A

Pass

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Pass

N/A

Pass

N/A

Pass

Pass

N/A

N/A

N/A

Pass

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 374

Address LAFB

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Location Contact Peter Location Phone Number

Monitoring Company Not Monitored Monitoring Company Number

Date 4/18/20248

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password

Location of System/Cylinder(s) Left Connex on the right side Inspection Type 6-Month

Manufacturer Pyro-Chem #3 Cylinder Slave Size

Serial Number Size of Activation Cartridge 16 Gram

System Type Dry #1 Cylinder Size PCI-25S Model Number MCH #2 Cylinder Slave Size

Last Recharge Date N/A Number of Fusible Links 1 Best Time to Service Anytime Type of Fusible Links 450ML

Original System Install Date 2017 Date of Activation Cartridge Sep-23 Cylinder 12 Year Hydro Test Date 2029 Location of Shut Off/Valves

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass

Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A)

Replace System Cover(s)

System Operational & Seals In Place

Slave Cylinder Operational

If System Has Been Discharged, Report Same Pass

Is Pressure Gauge In Proper Range (If Gauged) Pass

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass

Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass

Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date 2029

12 Year Regulator Test Date (Ansul) N/A

1/4' Gas Valve Hose Assembly Test Date N/A

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s)

Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed

Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter

Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown

Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass

Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring N/A

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning

Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood

Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass

Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Location Phone Number

Notes/Deficiencies

Monitoring Company Monitoring Company Number

Account Number Password

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names Bldg 374

Address LAFB

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Date 4/18/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020