BLDG 1124 Burger King report .pdf

PDF 132 KB Posted

Attached to
Kitchen Fire Suppression Inspection & Maintenance
Solicitation number
FA488725Q0006
Issued by

About this file

This is a Hood Fire Suppression System inspection report for Building 1124 Burger King at Luke Air Force Base in Litchfield Park, AZ, conducted on May 2, 2024 by A P Fire Protection. The inspection was performed according to NFPA 17, 17A, and 96 standards.

The system is an Amerex wet-chemical system installed in 2009, consisting of two 2.72 gallon KP275 cylinders with N2 actuation, protecting four fryers. The inspection revealed that most system components passed testing requirements, including nozzle positioning, fusible links, gas valve operation, and fire alarm panel monitoring. Key deficiencies noted include both cylinders being due for their 12-year hydrostatic testing. The hood has light grease accumulation, and the last hood/duct/plenum cleaning was performed in April 2024. The system is monitored by the Emergency Communication Center and includes proper signage, remote pull stations, and K-class fire extinguishers.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Results

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

N/A

Apr-24

Light

See Notes

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 1124 Burger King

Address Luke Air Force Base

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Location Contact Darryel Abraham Location Phone Number 916-893-8045 Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641

Date 5/2/20248

C-16 ROC 251919 CR-67 ROC 251920

Account Number Password

Location of System/Cylinder(s) Right of hood on wall Inspection Type 6-Month

Manufacturer Amerex #3 Cylinder Slave Size

Serial Number Size of Activation Cartridge N2 Actuation Cylinder

System Type Wet #1 Cylinder Size 2.72 Gallon KP275 Model Number KP #2 Cylinder Slave Size 2.72 Gallon KP275

Last Recharge Date Due Number of Fusible Links 4 Best Time to Service 7:30am Type of Fusible Links 450ML

Original System Install Date 2009 Date of Activation Cartridge 2017 Cylinder 12 Year Hydro Test Date Due Location of Shut Off/Valves Above hood in ceiling

Check If Seals Intact, Evidence of Tampering Pass

Item(s) CheckedItem(s) Checked

Duct and Plenum Nozzle Protection (List Model/Type/Position)

Appliance Line Up Left To Right (Size of Hazards/Nozzle Coverage Description)

Fryer x 4

Remote Pull 42"-48" From Floor (N.F.P.A. 17A)

All Appliances Properly Covered With Correct Nozzles Pass

Duct and Plenum Covered With Correct Nozzles Pass

Check Positioning/Condition of All Nozzles Pass

Results

Inspect Cylinder/Wall Mount Bracket(s) Pass

Remote Station(s) Have Signage (N.F.P.A. 17A)

Replace System Cover(s)

System Operational & Seals In Place

Slave Cylinder Operational

If System Has Been Discharged, Report Same N/A

Is Pressure Gauge In Proper Range (If Gauged) Pass

Check Cartridge Weight (If Applicable) Pass

Is System Installed Accordance With Manufacturer UL Listing Pass

Hood & Duct Penetrations Sealed With Weld or UL Device Pass

Operated System From Terminal Link Pass

Test for Proper Operation From Remote Pull Station Pass

12 Year Hydro Cylinder Test Date Due

12 Year Regulator Test Date (Ansul) Due

1/4' Gas Valve Hose Assembly Test Date Due

Clean Cylinders/Wall Mount Brackets

Grease Filters Aluminum/Stainless Steel (N.F.P.A. 96) Pass

Replaced Fusible Link(s)

Check Travel of Cable Nut/S-Hooks

All Piping Conduit Securely Bracketed

Proper Separation/Fryer & Flames (N.F.P.A. 90A)

Proper Clearance of Flames To Filter

Exhaust Fan in Operating Order

When System Activated Did Make-Up Air Shutdown

Fuel Shut Off In Position

Wipe Grease Off Nozzles (Surface Cleaning Only) Pass

Visually Check All Fusible Links Pass

Did System Report to Fire Alarm Panel/Monitoring Pass

Check Operation of Micro-Switch(s) Pass

Date of The Last Hood/Duct/Plenum Cleaning

Accumulation of Grease In Hood

Exhaust Fan Warning Sign On Hood

Personnel Instructed In Operation Of System

K-Class Extinguisher(s) Properly Serviced

Portable Fire Extinguisher(s) Properly Serviced

Certification Tag Place On System & Remote

System Equipped With Water Mist/Water Wash

Check Operation of Gas Valve(s) Pass

Proper Nozzle Covers/Caps/Seals In Place Pass

Puff Test Completed Pass Is Suppression System Compliant

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 1 of 2 REV 04-2020

C-16 ROC 251919 CR-67 ROC 251920

Location Contact Darryel Abraham Location Phone Number 916-893-8045

Both Cylinders are due for Hydro.

Notes/Deficiencies

Monitoring Company Emergency Communication Center Monitoring Company Number 623-856-6641 Account Number Password

Hood Fire Suppression System Report

(Tested Per N.F.P.A. 17, 17A, 96 Standards & Manufacturer Requirements)

Location Names BLDG 1124 Burger King

Address Luke Air Force Base

City, State, Zip Litchfield Park, AZ

Technician Cody Buckmaster

Date 5/2/2024

A P Fire Protection www.apfireprotection.com

7612 N 71st Ave, Glendale, AZ 85303

Phone: (623) 772-5344 Fax: (623) 772-5384

Page 2 of 2 REV 04-2020